BS5839 PART 1: 2017: A Guide To Fire Alarm Systems Design
BS5839 PART 1: 2017: A Guide To Fire Alarm Systems Design
BS5839 PART 1: 2017: A Guide To Fire Alarm Systems Design
2
CATEGORIES
Fire Alarm and Fire Detection systems are categorised in the
following way:
3
SMOKE DETECTORS
It should be noted that large smoke particles will have a similar particle size to
small particle contaminates including some types of dust and aerosols. As such
care should be taken when siting smoke detectors to limit subjection to this
phenomenon.
HEAT DETECTORS
The minimum static response of heat devices should not be less than 29°C
above the average ambient temperature, or less than 4°C above the highest
temperature the device can be expected to experience.
4
FIRE DETECTOR COVERAGE & POSITIONING
5
In corridors less than 2m wide the horizontal spacing of detectors may be
increased, the areas of coverage need not overlap as in the case of a room. Any
corridor over 2m wide is deemed a room and device spacing should follow the
standard for rooms (see page 5).
6
Detectors must not be sited less than 1m from air inlets or air conditioning units.
A device should not be mounted within 500mm of any obstruction. If the top of a
solid partition is less than 300mm from the ceiling then treat it as a wall. Similarly,
ceiling obstructions such as beams should be treated as walls if deeper than 10%
of the ceiling height.
7
Never mount devices closer than twice the depth of light fittings.
Voids less than 800mm in height need not have independent coverage, unless
fire or smoke is able to spread from one area to another through the void or risk
assessment shows AFD (Automatic Fire Detection) to be necessary.
8
For ceilings that feature an apex: as long as the height of the apex from the
rest of the ceiling is less than 150mm for heat detectors or less than 600mm
for smoke detectors then these can be treated the same as flat ceilings. For
higher apexes, a device should be installed at the highest point. The distance to
adjacent devices can be increased by 1% per degree of angle of the roof up to a
maximum of 25%.
9
Vertical shafts like lifts and stairways should have a device mounted within 1.5m
of any opening.
10
DETECTOR SPECIFICATION
The sensing element of a heat detection device (thermistor) should not be less
than 25mm below ceiling, and not greater than 150mm below ceiling.
11
SEARCH DISTANCE
A person searching a zone for a fire should not have to travel more than 60m
from the entrance of a zone to identify the source of a fire. Particular attention is
required when siting the detectors LED to minimise the search.
SECOND
FIRST
GROUND
Less than 300m2 can be covered by a single zone. When the total floor area
exceeds 300m2, each floor would require a zone (or zones if the floor area
exceeds 2000m2 ). Stairwells, liftwells or similar should be separate zones.
12
MANUAL CALL POINTS (MCP)
1.4m
(+/- 200mm)
The centre of the element of the manual callpoint should be positioned 1.4m
(+/-200mm) from floor level (unless a wheelchair user is likely to be the first
person to raise the alarm, when this is applicable it should be noted on any
certification). All manual call points should be fitted with a protective cover, which
is moved to gain access to the frangible element.
A person should not have to travel more than 45m along an escape route
to reach a manual call point (25m if disabled person to operate, or rapid fire
development is likely). Manual call points should be sited at all stairwells and
exits from the building.
13
SOUNDERS
Sounder device cabling should be arranged so that in the event of a fault at least
one sounder will remain operational during a fire condition.
14
75
For areas where people are sleeping, sounder devices should produce a
minimum of 75dB(A) at the bed-head with all doors shut.
-30
FIRE DOOR
15
VISUAL INDICATION DEVICES
Visual indication devices (VIDs), such as strobes, can be ceiling or wall mounted.
For wall mounting they should always be mounted 2.1m above floor level. Visual
alarm devices should conform to BS EN 54-23.
Unless MICC cable is used, all cabling should be mechanically protected from
floor level up to a height of 2m.
16
VISUAL ALARM DEVICE CATEGORIES
EN54-23 specifies that the VAD produces an illumination of 0.4 lux on surfaces
perpendicular to the direction of the light emitted from the device. They are
not designed to wake people that are asleep and can be red or white light.
VADs are classified into three categories based on their application:
W - Wall-mounted
C - Ceiling-mounted
O - Open Category
Wall and Ceiling mounting categories are specified at specific installation heights
and particular patterns of coverage - see diagrams. For W and C categories,
the shape of the volume covered is fixed by the standard. The dimensions of
this coverage volume are specified by the manufacturer. For all categories, the
volume covered can be used to determine VAD spacing within the building.
Open category allows manufacturers to specify the coverage shape and volume
and does not put any restriction on mounting height.
Wall-Mounted - Coverage Volume Ceiling-Mounted - Coverage Volume
17
CABLING
Fire resistant cabling is now required within the whole fire alarm system
including the main supply cables. The use of non-fire resisting cables, whether
mechanically protected by fire-resisting construction or not, will no longer comply
with BS5839.
18
FIRE DETECTION & ALARM SYSTEMS
®
TWINFLEXpro2
Smart 2-Wire Fire Alarm System
A conventional 2-wire fire alarm
system is often the natural choice for
smaller applications or where budget
constraints exist.
Building on those strengths and designed for ease of use and state-of-the-art
monitoring, the LPCB-Approved TWINFLEXpro2 is the next generation in 2-wire
fire alarm reliability.
19
FIRE DETECTION & ALARM SYSTEMS
DUONET®& QUADNET®
Multi- Loop Intelligent Addressable Systems
The Duonet & Quadnet intelligent fire
alarm systems offer both cost-effective
and reliable solutions for a wide
variety of fire detection applications.
The innovative technology built into
the Duonet and Quadnet panels is
designed to significantly reduce false
alarms. The systems can support up to
200 Multipoint ASD combined detector/
sounders on a single loop.
20
MULTI-SENSOR DETECTORS
Using the Multipoint ASD detector as part of a Fike system means that when a
detector is wired to the system, a sounder and strobe can also be connected
without extra installation time or cost. This greatly reduces the number of points
that need to be installed and the time it takes to install.
• 7/15 modes of fire detection including combined smoke/heat
• Optional built-in sounder and/or strobe in a single device
• Self-calibrates every 6 hours
• Continuously monitors for dust contamination
• Easily removable for maintenance at height
• LED to report status of detector ( normal / fault / fire )
21
FIKE TRAINING
22
CPD Accredited Presentations
23
Sabre Fire and Security Ltd are an authorised Fike supply and service centre.
We are listed in the LPCB (Loss Prevention Certification Board) and The National
Landlords Association Recommended Supplier List. We are also members of the
UKFA (UK Fire Association) and FSB (Federation of Small Business).
Sabre Fire and Security Ltd are the sole UK and European distributors of StoveTop
FireStop® an automatic domestic pan fire suppression system – details can be
found on our website.
SERVICES PROVIDED
WWW.SABRE-FIRE.CO.UK