Consultants Guide Fire Alarm Systems PDF
Consultants Guide Fire Alarm Systems PDF
Consultants Guide Fire Alarm Systems PDF
No part of this guide may be reproduced or transmitted in any form, or by any means,
electronic or mechanical, including photocopying, scanning, recording, or other
information storage and retrieval systems, for any purpose other than personal use,
without the express written permission of Thorn Security Limited.
The text of the specification contained in Part 2 of this guide is not covered by the
copyright and may be copied and edited as required.
Thorn Security Limited accept no liability whatsoever with respect to the use of the
information contained in this guide. While every effort has been taken to ensure that
the information in this publication is correct, Thorn Security Limited assumes no
responsibility for errors or omissions. Furthermore, Thorn Security Limited shall not
be responsible for any claim, proceedings, damages, loss or expense resulting from
the use of the information contained herein.
Publication Circulation
Reference Number: ...........................................................................................................................................
Address: ..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
..................................................................................................................................................
Please return copy of this completed form to: Tyco Electronic Products Group
Product Management Department
Security House
Hanworth Road
Sunbury-on-Thames
Middlesex, TW16 5DB
CONTENTS
About This Manual ................................................................................................................... Page iv
Purpose .......................................................................................................................................... iv
Readership ..................................................................................................................................... v
The Diskette ................................................................................................................................... v
Acknowledgments .......................................................................................................................... v
Appendix 2 Features and Benefits of Analogue Addressable Fire Controller Systems ......... 60
Purpose
=
The code of practice for fire detection and alarm systems for commercial buildings (BS 5839: Pt 1:
1988) is a detailed and comprehensive document which requires considerable study before it can be
fully understood. Even when it is understood, many users still find it difficult to understand why certain
clauses, relating to the recommendations and options offered, are included in the code.
The purpose of this manual is to provide a step-by-step approach to the necessary guidelines
described in BS 5839: Pt1: 1988 so that users can achieve maximum benefit from the
recommendations. This should assist in the task of choosing the best options, help in preparing the
specification of the fire protection system, and assist architects, designers and electrical engineers in
providing the most cost effective system that meets the needs of the user.
This manual is a consultants guide to the contents and usage of the British Standard code for the
design, installation and servicing of fire detection and alarm systems for commercial buildings,
BS 5839: Pt 1: 1988. Throughout the manual where it was necessary to reference this long title, we
will simply refer to it as the code.
The code is divided into four sections. The first section is intended to be of general interest to all
users, the second is intended to be of interest to the system designer, architect or electrical engineer,
the third section is for the installer and the fourth is for the user. Because the code is sectionalised in
this way, it has resulted in much duplication and cross-referencing of information within. This makes it
quite difficult to follow because you have to constantly go back and forth in order to interpret its full
meaning.
In practice one organisation or company is usually responsible for both the design of the system and
its installation. Furthermore, the code recognises that, in most cases, the user is unlikely to go out and
buy a copy of the code in order to learn about his responsibilities. In fact, the code recommends that
the installer should instruct the user on his responsibilities.
Considering the points described above, its clear that the organisation (often one person) needs to be
familiar with all aspects of the code. In this manual therefore we basically follow through the design
phase, the installation phase and use of the system phase without strictly following the code as
sectionalised.
This manual is a guideline to the code only, and as such it is important therefore to read this
manual in conjunction with the code so that all aspects can be fully understood. This manual
is not a replacement for the code.
The manual consists of two parts.
Part 1 Guide to design of Fire Systems
This part contains information taken from the planning and design guidelines described in BS 5839:
Pt1: 1988. It also contains extracts from the publication titled Fire Detection and Alarm Systems by
Peter Bury (published by Paramount Publishing Ltd.). Peter Burry was a member of the Technical
Committee responsible for producing the code of practice. He was also an active member of the
Working Party in which many technical discussions took place.
Part 2 Specification for an Analogue Addressable Fire System
This part contains a sample specification for an Analogue Addressable Fire System. The information
in the specification may be edited and used in specifications for Fire System designs as appropriate.
A file containing the text of the specification is provided on the diskette included with this manual (see
The Diskette section below for further details). By using the sample specification included on the
diskette, you can save yourself a considerable amount of time and effort because much of what is
contained in the sample specification is applicable to almost all fire protection system designs.
=
The code of practice for fire detection and alarm systems for dwellings, i.e. domestic buildings, is covered in BS 5839: Pt 6.
Readership
This manual has been prepared for use by architects, designers and electrical engineers responsible
for the design, specification and installation of fire protection and alarm systems intended for use in
medium to large size buildings, for example, schools, hotels, hospitals, office complexes, shopping
precincts, super market stores, airports, warehouses, etc.
The information provided herein is intended specifically for the use of appropriately qualified and
experienced persons as stipulated in the Foreword to BS 5839: Pt 1: 1988.
The Diskette
Included with this manual you will find a 3.5 floppy disk. This disk contains the text of the sample
specification for an Analogue Addressable Fire System printed in Part 2 of this manual. To satisfy the
requirements of most PC users, the file has been saved to the disk in seven word-processing formats,
as follows:
Filename Word-processing Format
FAS-MSW6.DOC Microsoft Word 6/7 for Windows
FAS-WP50.DOC WordPerfect 5.0
FAS-WP51.DOC WordPerfect 5.1 for DOS
FAS-WP5X.DOC WordPerfect 5.x for Windows
FAS-WS70.WS7 WordStar 7.0
FAS-WMAC.MCW Word 5.1 for Macintosh
FAS-ASCI.TXT ASCII Text (with line breaks)
If you decide to use one of the files containing the text of the sample specification, we recommend you
first make a copy of the file and work with the copy rather than the original file. By adopting this
procedure, should your copy of the file become corrupt or damaged in any way, then you will always
have the original file to fall back on.
Note: Throughout this manual, references in square brackets, for example [12.2.11], refer to
the relevant section of the BS 5839: Pt 1: 1988 code of practice which describes the
associated topic in greater detail.
Acknowledgments
Thorn Security Limited gratefully acknowledge the use of extracts taken from Peter Burrys publication
titled Fire Detection and Alarm Systems (ISBN 0 947665 11 0) published by Paramount Publishing
Limited, Paramount House, 17/21 Shenley Road, Borehamwood, Herts. WD6 1RT.
Company Background
Thorn Security is one of the longest established names within the fire detection and emergency
lighting industry. By investing millions of pounds on research and development, Thorn Security are at
the forefront of fire detection and emergency lighting technology.
With an increasing local office network, Thorn Fire & Security has an unprecedented reputation for
quality, reliability and service. A comprehensive range of products, built up over a number of years,
has positioned the company as the leader of the fire and security market. Thousands of customers
all over the world have chosen the company for their fire detection, security and building management
systems
Following Thorn Securitys successful management buyout from Thorn EMI Plc, the company has
increased its turnover from that predicted, to approaching 200 million. With its headquarters at
Sunbury near London, the company operates from 30 offices in the UK and from nine other major
centres around the world including Cleveland Ohio, Kuala Lumpur, Hong Kong and Singapore. In
addition, it has manufacturing facilities in Walthamstow in the UK and Ohio in the USA; R&D in the
UK and USA; alarm monitoring facilities in the UK, USA and Singapore, and employs over 3,300
people world-wide.
The Company has exceptional capabilities in systems integrating fire protection, security,
environmental control and energy management technologies as well as providing stand-alone
products and services in all of its core business areas.
Fire Protection
Thorn Security designs, installs and services fire protection systems for every type and size of
building or installation. Systems can incorporate automatic detectors, manual call points, control
panels, alarm sounders and extinguishing systems.
Security
The Company provides security systems to cover a wide variety of risks. These include the following:
Intruder detection and alarm systems
Closed-circuit television (CCTV) and slow-scan TV for remote central surveillance of multiple sites
High security systems for banks and other high risk buildings
A versatile range of access control systems and manned guarding services.
Alarm Communications
A network of manned central stations provides around-the-clock monitoring of customers premises
ensuring that all alarm signals are immediately actioned and recorded. Central station staff ensure
that the relevant emergency services are informed and, if necessary, arrange for a duty service
engineer to call.
BS EN ISO 9001
Assessing Body:
British Standards Institute - Quality Assurance (BSI)
Scope of Cover:
The Design, Manufacture and Supply of Products used to
configure Fire Detection and Alarm Systems, Security and
Surveillance Systems, associated Signalling and
Communications Systems and Building Management
Systems.
Walthamstow FM 967
Richmond FM 967
BS EN ISO 9002
Assessing Body:
Loss Prevention Certification Board (LPCB)
Scope of Cover:
Installation and Servicing of Fire Detection Systems and
Fixed Gaseous Fire Extinguishing Systems.
Newcastle 168-8
BS EN ISO 9002
Assessing Body:
Loss Prevention Certification Board (LPCB)
Scope of Cover:
The Design, Manufacture and Supply of Products
used to configure Fire Detection and Alarm
Systems, Security and Surveillance /systems,
associated Signalling and Communications
Systems and Building management Systems.
BS EN ISO 9002
Assessing Body:
National Approval Council for Security Systems
(NACOSS)
Scope of Cover:
Installation and Servicing of Fire Detection
Systems and Fixed Gaseous Fire Extinguishing
Systems.
LPS 1014
Assessing Body:
Loss Prevention Certification Board (LPCB)
Scope of Cover:
System Design, Installation, Commissioning and
Servicing of Fire Detection and Alarm Systems.
Position: ............................................................................................................................................
Address: ............................................................................................................................................
............................................................................................................................................
............................................................................................................................................
DETAILS OF ENQUIRY
(Please provide details of your enquiry so that the necessary action can be carried out as quickly as possible.)
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
.........................................................................................................................................................................
To enable THORN Security to keep your file up-to-date and provide new or updated literature in the future, we
would appreciate you using this form to notify us of any change of address or personnel responsible for the
up-keep of this publication.
Name: ................................................................................................................................................
Company: ................................................................................................................................................
Address: ................................................................................................................................................
................................................................................................................................................
................................................................................................................................................
Date: ................................................................................................................................................
Please return copy of this completed form to: Tyco Electronic Product Group
Product Management Department
Security House
Hanworth Road
Sunbury-on-Thames
Middlesex, TW16 5DB
Name: ................................................................................................................................................
Company: ................................................................................................................................................
Address: ................................................................................................................................................
................................................................................................................................................
................................................................................................................................................
Date: ................................................................................................................................................
Please return copy of this completed form to: Tyco Electronic Products Group
Product Management Department
Security House
Hanworth Road
Sunbury-on-Thames
Middlesex, TW16 5DB
1. Introduction
Fire detection and alarm systems are designed to provide warning of the outbreak of fire and
allow appropriate fire fighting action to be taken before the situation gets out of control. As all
systems are designed primarily to protect life and property, this places a great responsibility on
the designer because each building will present a different set of problems in relation to the
risk of fire and fire spread. Each fire detection and alarm system therefore must be
specifically designed to meet the requirements for each building.
In designing a system, particular consideration must be given to the type of building, its
construction and the purpose for which it is being used, so that in the event of a fire, the fire
detection system, combined with appropriate fire prevention procedures, will keep risk to both
personnel and property to a minimum.
With Thorn Security being at the forefront in planning and designing fire detection and alarm
systems for many years, the techniques and procedures described in this manual are based
on knowledge and experience gained over that time.
The information provided herein is intended to help and enable appropriately qualified
designers to plan and design fire systems suitable for use in any type of building or
installation.
As mentioned above, the designer of fire detection and alarm systems bears a great
responsibility because the safety of personnel and property rests with him. Occasionally,
particular problems may occur which are not covered in this manual. In such cases it is most
important that you seek specialist advice at an early stage. Should you need help in resolving
a system design problem, you can always contact our design specialists for assistance by
calling our HELPLINE on 01932 74 3333.
When designing a fire detection and alarm system, in addition to deciding the type of
controller, detectors, call points and sounders to be used etc., there are also other aspects
which need to be considered, for example, method of installation, materials required during
installation, operator training, routine maintenance procedures, and service agreement. For
any system to function reliably and provide problem free service throughout the life of the
system, all of these aspects must be considered in the overall system design and plan.
As Thorn Security is an LPS 1014 Certificated company, you can be sure that any fire
detection and alarm systems we design, install, commission, service and maintain not only
complies with the requirements of BS 5389: Pt 1: 1988 but also fully complies with the
requirements of LPS 1014.
=
The LPCB is an internationally recognised and independent certification body accredited by the Department of Trade and
Industrys National Accreditation Council for Certification Bodies (NACCB) and has an independent board made up from
representatives from industry, insurers, trade associations and CACFOA (Chief and Assistant Chief Fire Officers
Association), with observers from the Department of the Environment, the Home Office and the Health and Safety
Executive.
By specifying a company which is certificated to LPS 1014, you can be confident that your fire
detection and alarm system will be installed competently to the codes of practice that you
specify (e.g. BS 5839: Pt 1: 1988) and that the company can provide the necessary
maintenance service required to maintain a valid LPS 1014 Certificate of Conformity.
For a company to be LPS 1014 Certificated it must fulfil the following requirements:
have a several years experience in design, installation, commissioning and servicing of
systems.
have randomly selected installations inspected by the LPCB every six months against the
specified contract requirements. Certificates must reliably identify any deviations from the
Installation Rules applied.
have the resources to support systems in case of a break down with 8-hour emergency call
out service.
be competently capable of performing the planned servicing of installations.
have suitably trained and experienced staff.
operate a BS EN ISO 9000 quality system.
When an LPS 1014 approved company completes each installation contract, the client is
issued with a Certificate of Conformity. Copies of these certificates are also forwarded to the
LPCB. The LPCB use their copies of the certificates to randomly choose which installations to
inspect.
To be sure that the company you employ to install, service and maintain your fire alarm
system is competent, and that the installation will be likely to meet the statutory requirements
of the fire brigade and satisfy your insurance company, you should use a company which is
LPCB Certificated to LPS 1014.
Servicing Arrangements
Servicing arrangements are important because they represent a hidden cost to the user.
Some systems may require regular attendance by a service engineer in order to maintain the
system at a high efficiency level. Not only does the engineer have to be paid for, but his
presence may also cause disruption to the day-to-day operation of the business. The latter
element may actually be much more important to the end user than the service cost.
[Clause 29] of the code in fact specifies a routine for servicing. This can vary from daily
through weekly, monthly, quarterly and annually to a special wiring check every five years. It
also states [29.2.1], if some of the functions are tested automatically then the manufacturer
can specify an increased interval between manual testing of those functions. This can pay off
in servicing requirements [clause 5, h] since the end user can see the financial advantages of
such a system. It should be noted that if servicing requirements is included, it means that the
quotation should also include the costs of the recommended system maintenance.
Manual (Type M)
Type M A system which provides manual alarm only.
[Section 6] of the code further divides the level of protection required for Life (Type L) and
Property (Type P) systems in terms of the extent of coverage. The question to be asked is;
what degree of coverage should be provided?
This classification provides for the protection of life, that is the safety of the occupants. It
caters for the detection of a fire, initiates an alarm of fire, and provides sufficient time for
the occupants to escape from the building.
Type L3 Covers escape routes and adjoining rooms (detectors should be situated
adjacent to the door onto the escape route).
Type L2 Covers escape routes, adjacent rooms and any other areas where it is
considered the occupants are vulnerable.
Type L1 Total Coverage,
This classification provides for the protection of property and its contents. It caters for the
automatic detection of a fire, initiates an alarm of fire, and indicates the location of the fire
within the premises.
Type P2 Covers all high risk areas.
Type P1 Total Coverage.
The philosophy behind protecting escape routes and all areas adjacent to the escape routes is
that people are unwilling to travel through a corridor if their visibility is impaired by smoke. The
reasoning behind the protection of adjacent rooms is that smoke moving through a door crack
from a rapidly burning fire may be cool and dense. Thus the escape corridor could become
smoke-logged at low levels before reaching the corridor smoke detectors [13.5].
If a person in an enclosed office has to travel through another area in order to reach an
escape route corridor then that area adjacent to the corridor shall be considered as part of the
escape route for the enclosed office and therefore should be protected by a smoke detector.
This may not be the case in hospitals or day-care centres with infants, handicapped
persons or senior citizens.
Are the premises residential where many people are asleep at varying times of the
day?
If they are spread over the whole building then it can be argued that detection (by sight, or
smell) would be quicker.
These people could be at risk from fire breaking out in unoccupied areas.
What are the costs of extending the system protection to all parts?
The answers to these questions will determine whether a particular area within a premises is
to be protected or not, since the code does not give exact guidelines.
The fundamental fire engineering principle of the danger of fire is whether there is an
expectation of damage, and whether the contents are combustible.
With regard to life and property, if there can be no significant damage incurred in the event of
a fire then there is no need for protection. Likewise, in respect to contents, no matter what the
value, if there is no possibility of ignition then there is no need for protection. These two
extreme cases rarely occur and in real life situations there is usually some degree of damage
incurred and no site contains completely fire proof contents. The dividing line is difficult to
draw and a balance has to be struck.
Having, in consultation with interest parties, agreed the type of protection and coverage
required for the building, the next step in the design process is to configure the zone
arrangement within the premises, see section 3 (How to Configure Zones within Premises).
4. If the total floor area of a building is 300m or less then the building need only be one zone,
regardless of the number of floors [7.2].
5. If the total floor area of a building is greater than 300m, then each floor should be a
separate zone (or set of zones, if the floor area is large enough). There are however two
exceptions to this rule:
a) If communication (via interconnecting doors) between two adjacent vertical
compartments is at the lowest level, only then can each vertical compartment still be
considered to be separate multi-storied zones. See Figure 3.
b) Structures such as stairwells extending to more than one floor but remaining within the
same vertical compartment can be considered as taken as multi-storey zones. See
Figure 4.
The justification of exception b) is in case of manual call points. People escaping via a
staircase from a fire on the ninth floor for example, may not feel confident enough to stop
and operate a break glass call point unit until they reach the fourth floor, the information on
the fire system control panel would then be misleading if it indicated that the fire was on the
fourth floor when it was actually on the ninth. If the call points are connected in a staircase
zone, then misleading information becomes less likely.
3. For multi-occupancy buildings, zone boundaries should not cross occupancy boundaries,
hence a zone should contain only one occupancy. This ruling may be relaxed for manual
(Type M) systems.
Fig. 2
Consider two adjacent areas with one of the
offices containing three separately
compartmented store rooms. The zoning may
be as shown in this diagram (provided the
maximum area and search distance limitations
are not exceeded).
Fig. 3
Fig. 4
disadvantages of having individual spurred wiring for each zone and having a complete loop
(See Figures 5, 6 and 7).
One main problem concerning the choice of system which should be used in a building is that
of fault monitoring. The code therefore makes a number of recommendations concerning how
faults are monitored:
1. A fault occurring on one zone should not affect the operation of other zones [6.6.2].
In conventional systems this will always be achieved since an open or short circuit
condition will only affect the individual zone circuit concerned (See Figure 5).
In addressable systems where a number of zones share the same ring circuit or loop (See
Figure 6), an open circuit is not too much of a problem (just so long as the fault is reported)
since the loop can be driven in both directions. The case of a short circuit however is far
more serious since this condition could prejudice every device (up to 99) on the circuit.
Short circuit protection is therefore required in all loop circuits. This is achieved by placing
zone/line isolator devices in the loop circuit at zone boundaries.
For example, with reference to the circuit shown in Figure 6, if a short circuit were to occur
in zone 2, the two line isolators X and Y would operate and create two breaks in the
circuit at points X and Y. The loop would then drive in both directions, that is, zone 1 in
one direction and zones 5, 4 and 3 in the other direction. The zone/line isolators would
again automatically become passive after the short circuit has been repaired.
In addressable systems where two or more zones can share the same circuit and the
circuit is not connected in a loop (See Figure 7), to comply with the recommendation of the
code then only one zone of detectors and call points may be connected to each
addressable spur.
2. A single fault should not remove protection from an area greater than that allowed
for a single zone [6.6.2].
In conventional systems this will always be achieved (See Figure 5) and providing zone/line
isolator modules are employed, as in the case of addressable loop systems, then this will
also comply with the recommendation of the code.
3. Two faults should not remove protection from an area greater than 10,000 square
metres.
This recommendation imposes a maximum area of coverage for a single loop in an
addressable loop system (See Figure 6). No loop in the system therefore should ever
service a area of coverage greater than 10,000 square metres. If the area to be protected
exceeds this maximum limit, then an additional loop(s) should be used.
4. Short circuit faults should be reported by the control panel within 100 seconds of
occurrence and open circuit faults should be reported within 60 minutes of
occurrence.
These limitations should not be exceeded and in either case a false indication (due to the
fault) should occur first.
The 60 minute limitation on open circuit faults is only applicable to loop configured systems
which continue to operate under this condition.
If the system is radially or spur wired, or for any other reason is not able to operate under
an open circuit condition, then this fault should be indicated within 100 seconds.
When you have established the zone arrangement for the building, the next step in the design
process is to decide which type of fire alarm system should be used, see section 4 (Which
Type of Fire Alarm Detection System?).
4.1.1 Zoning
If zoning was to be is extended to the limit, each circuit would have only one detector
connected, and the exact location of the fire could be established at the fire controller without
the need to physically search the zone. To do this with conventional detectors and a
conventional control panel would be prohibitively expensive because of the number of zones
required on the fire controller and the large amount of installation work involved.
In conventional systems all the detectors on a zone circuit continuously communicate with the
control panel. When one detector goes into the fire alarm state, the voltage on the circuit
drops and all other detectors on that zone become disabled. During this period no further
information about the zone can be obtained.
In addition, flame, heat and smoke detectors designed for use in hazardous areas must
comply with the requirements of BS 5345 (EN50020) and be certified with suitable BASEEFA
or equivalent approval.
Manual Break Glass call points which can share the same circuit as the detectors must
comply with the requirements of BS 5839: Pt 2: 1988.
The code states that the removal of a detector on a circuit shall not prevent the operation of
any Break Glass call point. This can be achieved by having an addressable system where
call points are connected in a ring, or by installing all call points first on one spur and then
connecting the detectors. It can also be achieved by using some newer conventional
equipment which provides this facility automatically by use of special equipment.
The control panel then sends out the next address, and so on until all devices have been
addressed, and then it repeats the whole cycle again. Each device in the system should be
interrogated at least 30 times a minute.
Clearly it is possible for many detectors on the same circuit to be in alarm at the same time
and for the control panel to recognise this. This means that much more information about the
spread of fire within a zone can be obtained. Because of the communication techniques
involved, the detectors do not have to be arranged on the circuit in address order, hence
circuit wiring can take the most economical route. This method obviates the necessity of
accurate installation drawings.
For the system to raise a pre-alarm in the event of a smouldering fire, the analogue value
output by the detector must be in the pre-alarm condition (or band) for a period equal to the
time taken to complete 10 successive address scans (or 20 seconds). The pre-alarm facility
provides sufficient time to check the control panel for an indication of a smouldering fire. It
does not provide sufficient time to visually check for the presence of a fire.
As the output from each detector is an analogue value, the alarm threshold level can be
controlled (or set) by software within the analogue addressable fire controller. This software is
usually stored in non-volatile memory (EEPROM).when the system is being configured during
installation.
The option of being able to change the sensitivity settings of detectors can be useful in many
situations. For example, at certain times of the day when the building is occupied you might
want to reduce the sensitivity level of detectors in selected zones, this feature allows the
settings to be manually switched to low sensitivity for those zones and then switched back to
normal sensitivity when the premises are again unoccupied (see Figure 13 below). There may
be many reasons why you might want to do this, one being that you want to reduce the
possibility of a false alarm occurring during the working day, but you want full protection at all
other times.
The choice of alarm level sensitivities, plus any time delay which may be deliberately
introduced, determine the overall system response to fire conditions. The alarm level and
time delay can in theory be allocated any value, but in practice it is sufficient to select those
levels which respond the same as conventional (two-state) detectors.
When you have determined the type of fire alarm detection system to use in the building, that
is, conventional, addressable or analogue addressable, the next step in the design process is
to decide which type of detectors should be used in the different areas (zones) to be
protected, see section 5 (Detector Suitability).
5. Detector Suitability
Once you have decided upon the type of fire protection and alarm system to use in the
building, that is conventional, addressable or analogue addressable, you now need to choose
which type of detectors are to be used to protect the different areas (zones) within the
premises.
There are several types of detector spread across the range, each of which responds to a
different product of combustion (smoke, heat, etc.). Manual call points are used for the
human initiation of the fire alarm.
The different detector types available are as follows:
High Performance Optical Smoke Detector (point type)
Ion Chamber Smoke Detector (point type)
Photo-Optical Smoke Detector (point type)
Heat Detector (point type)
Infra-Red Flame Detector (point type)
Split Optical Beam Detector (beam type)
Aspirating Detector (specialised)
Linear Heat Detector (line type)
Duct Probe Unit (specialised)
The Duct Probe Unit has been designed for use in situations where the smoke, heat and
flame type detectors cannot be used. It is primarily used for detecting the presence of smoke
or combustion products in ventilation ducting systems. The detector operates much the same
as the Aspirating detector in that it contains a small tube which draws air from the duct into a
sampling chamber. For further information also see subsection 5.2.6.
ENVIRONMENT TYPE
The operation of each detector type is briefly described in the following subsections.
The sensitivity response classifications awarded to smoke detectors are A, B and C, where A
is the highest sensitivity, B is the mid-range value and C is a pass. N means not classified.
It should be noted that test fire 6 (TF6) designated smoke detectors are not expected to pass
this test since no smoke is developed and only a rate of rise in temperature can be detected.
In situations where there a mixed risk of fire, a class A response smoke detector should be
regarded as too sensitive for practical purposes as it would be prone to give false alarms.
As infra-red flame detectors cannot respond until there is flame, it is considered practical to
also use smoke detectors in conjunction with flame detectors in areas where the contents are
likely to smoulder in the event of fire. In the case of smouldering fires, smoke is very often
produced long before flaming occurs, consequently, the smoke detectors should cause the
system to go into alarm before flaming can start. Conversely, if the contents are highly
flammable then the flame detectors should cause the system to go into alarm long before the
smoke detectors can detect the presence of smoke.
Each detector is capable of protecting an area 7 metres each side of the beam centre line for
a distance of up to 100 metres, thus providing a total coverage of up to 1400 square metres
(see Figure 16 below).
The detector provides a number of outputs, each of which relate to a different density of
smoke contained in the air being sampled. It is normal practice to monitor at least two outputs
from each detector, one can indicate that smoke is present in the air (30% density), and the
other that fire is present (60% density). These outputs can be reported on separate zones of
a conventional fire system control panel but it is more appropriate for the outputs to be
connected to two address points in an addressable fire system.
These detectors are particularly useful for protecting computer suites, clean rooms or historic
buildings where point or line-type detectors would look out of place.
6. Detector Coverage
Clauses 12 and 13 of the code describe where detectors should be sited and what spacing
should be used. Clause 12 deals with property protection and clause 13 with life protection,
but in fact the two are very similar; clause 13 really deals with the small changes specific to life
fire detection systems.
When calculating smoke detector coverage for corridors, the information given in Table 5
should be used. This table shows the allowable radius of detector coverage for several
corridor widths and also provides details of the maximum spacing which may be used
between the smoke detectors.
6.4 Obstructions
If the passage of smoke or hot gas from a fire to a detector is likely to be disturbed by a ceiling
obstruction (such as a beam) which has a depth greater than 150mm but less than 10% of the
height of the ceiling, then the normal coverage distance allowed for the detector (5.3m for a
heat and 7.5m for a smoke) should be decreased by twice the depth of the obstruction
[12.2.10]. Furthermore, detectors should not be mounted within 500mm of any such
obstruction, wall or partition [12.2.9, 12.2.10].
Walls, partitions or dividers reaching within 300mm of the ceiling, or ceiling obstructions (such
as beams) deeper than 10% of the ceiling height will obstruct the flow of fire gases to
detectors, therefore the areas on either side of such walls, partitions, beams, etc. should be
treated as separate rooms [12.2.9, 12.2.10].
If the sections are to be protected by point-type heat detectors, their heights must not
exceed 10.5m if the General Limits are applicable, or 15m if the Rapid Attendance
Limits apply.
If the sections are to be protected by point-type smoke detectors, their heights must not
exceed 12.5m for the General Limits or 18m for Rapid Attendance Limits [12.2.5,
12.2.6].
6.7 Voids
Ceiling and under-floor voids 800mm or more in height should also be zoned and protected by
detectors. Any void less than 800mm in height need not be protected unless extensive spread
of fire or its products, particularly between rooms or compartments, can take place within it
before detection [12.2.11].
Where it is considered necessary to install detectors in shallow voids having poor ventilation,
for example under-floor service voids, special care should be taken with the positioning of the
detectors. As the initial smoke layer in a fire usually takes up the top 10% of the void height,
in shallow voids this may be small compared with the dimensions of the detector. Care should
therefore be taken to ensure that the sensing element of the detector lies within the top 10%
of the voids height.
6.8 Ventilation
Ventilation systems in buildings should also be taken into account when designing fire
systems because air movements in a space protected by heat or smoke detectors can have a
number of effects on the operation of the devices.
Extraction systems can draw the fire products away from normally sited detectors, and fresh
air inlets can keep clean air passing over detectors even when the room air is smoky.
Increased air turbulence can give increased dilution of the smoke, and in some detectors
clean air can cause a false alarm if it moving fast enough.
All heat and smoke detectors depend on the movement of fire products from the fire to the
detector. Movement of air in the building may be due to many causes, all of which can have
an effect on the movement of the fire gases. As the fire gets bigger its convective effects
gradually overpower all other causes of air movement. This, however, is not of much use to
us as we need to detect fires when they are small.
Computer Suites A case of special importance lies in the protection of computer suites.
These usually combine a high financial value with high ventilation rates; just when we need to
detect fires particularly quickly, the ventilation makes things especially difficult! The code
recommends that BS 6266 (Code of practice for fire protection of electronic data processing
installations) should be consulted here.
Ventilated Rooms The code does provide useful advice on installation of detectors in
ventilated rooms [12.2.16]. Detectors should not be mounted directly in the fresh air input
from air conditioning systems. In general, a spacing of not less than 1m between the detector
and the air inlet should be maintained. Where the air inlet is through a perforated ceiling, the
ceiling should imperforate for a radius of at least 600mm round each detector.
Smoke Tests The use of exploratory smoke tests to identify the optimum positions for
detectors in ventilated areas is recommended. Consideration should also be given to the
detection of fires which might occur when the ventilation is turned off.
If the smoke is going to be drawn out of the room by the ventilation system, then duct probe
units (detectors) should also be installed in the ventilation system extract duct(s).
6 Bell 91 85 79 73 67
8 Bell 95 89 83 77 71
Bedhead Sounder 96 90 84 78 72
Squashni Sounder 85 79 73 67 -
Discrimination The type, number and location of fire alarm sounders should be such that
the alarm sound is distinct from all the background noise. The note of the fire alarm sounders
should also be distinct from any other that are likely to be heard, and in particular it should be
distinct from the audible fault warning signal given by the control equipment.
All fire alarm sounders within the building should have similar sound characteristics, unless
particular conditions such as an area of high background noise makes this impracticable. In
this case other types of fire alarm may also be used, for example flashing coloured beacons
[9.4.2].
Frequency Young persons are most sensitive to sounds at frequencies between 500 Hz and
8000 Hz. Age and hearing damage reduce the sensitivity of the ear, particularly to
frequencies above 2000 Hz.
Partitions, dividing walls and doors attenuate sound; in general, the higher the frequency of
the sound, the greater the attenuation. Because of this, fire alarm sounders should therefore
ideally lie in the range 500 Hz to 1000 Hz [9.4.3].
If a two-tone alarm is used, at least one of the major frequencies should lie within the 500 Hz
to 1000 Hz range. Where the frequency range of background noise is such that it masks the
range, then the use of frequencies outside this range may be acceptable
Where fire alarm sounders are grouped, the control equipment should have facilities both for
controlling each group individually and for sounding an alarm (either alert or evacuate) in all
groups simultaneously.
The wiring should be so arranged that failure of a sounder or of sounder wiring in one group
will not cause a failure in any other group.
9. Controller Equipment
The control equipment used in all fire systems should comply with BS 5839: Pt 4: 1988 and be
approved by the Loss Prevention Certification Board. The complete range of fire control
equipment, detectors, sounders, call points and ancillary modules available from Thorn all
comply with these requirements.
Although we described the features and operation of the different types of fire detection
systems in section 4, there are also other factors which should also be considered when
designing a system, namely Siting of Control Equipment, Location of Origin of the Alarm and
Security of Control Equipment. Each of these topics are described below.
((Maximum Unsupervised Time + 24 Hours) x Operating Current) + (Alarm Current x Alarm Duration)
i.e. (86 x 0.35) + (2.0 x 0.5)
= 31.1 Ah capacity batteries (minimum)
In order that some spare capacity is provided, 36 Ah batteries should be used for the standby
supply in this case.
To cater for longer unsupervised periods, such as extended holiday weekends, etc., the code
allows for batteries to be manually connected if required. For example, a set of fully charged
batteries could be manually switched in mid-point during the unsupervised period so as to
provide sufficient power for the system to continue normal operation throughout the whole
period [16.5.1.3]
Type 1 cables are those which must continue to function in a fire for at least 30 minutes. Two
cable types that satisfy these requirements without further protection [17.4.2] are as follows:
1. Mineral-insulated copper-sheathed cables (MICC) complying with BS 6207, with or without
an overall PVC sheath.
2. Cables complying with BS 6387 and meeting at least the requirements for categorisation
as AWX or SWX.
Cables other than these two types may be used where prolonged operation during a fire is
required provided they are protected against exposure to the fire by either:
a) Burial in the structure of the building and protection by the equivalent of at least 12 mm of
plaster; or
b) Separation from any significant fire risk by a wall, partition or floor having at least 30
minutes resistance to fire in accordance with the appropriate British Standards and
Building Legislation [17.4.2].
Type 2 cables are those which having served their purpose in a fire can then fail. The cable
types that satisfy these requirements are as follows:
a) Mineral-insulated copper-sheathed cables (MICC) complying with BS 6207, with or without
an overall PVC sheath (see Note 1).
b) Cables complying with BS 6387 and meeting at least the requirements for categorisation
as AWX or SWX (see Note 1).
c) Cables complying with BS 6387 and meeting at least the requirements for categorisation
as A or S.
d) PVC-insulated and sheathed cables complying with BS 6004.
e) PVC-insulated and non-sheathed cables complying with BS 6004.
f) General purpose elastomer-insulated textile-braided and compounded cables complying
with BS 6007.
g) PVC-insulated cables of types BK, BR and BU complying with BS 6346.
h) Sheathed steel-wire-armoured cables with cross-linked polyethylene or hard ethylene
propylene rubber insulation complying with BS 5467.
i) Polyethylene-insulated PVC-sheathed coaxial cable with a central conductor of not less
than 16 strands/0.2 mm in diameter, but otherwise complying with the dimensional
requirements BS 2316: Part 3 for Uniradio Sheet M210 (see Note 2).
j) Cables designed for the detection of heat (see Note 2).
Notes: 1. Cables used in applications requiring prolonged operation during exposure to fire
should be either as described in a) or b) above [17.4.2].
2. The code states that coaxial cable or cables designed for the detection of heat
(see I) and j) above) may be used for the inter-connection of detectors within a
zone, provided that the system is such as to give a fire alarm in response to the
occurrence of fire at such a cable [17.4.1].
3. Cables other than those listed in a), h) and I) above are not sufficiently robust
to withstand the mechanical hazards which they may experience in practice, such
as impact, abrasion or attack by rodents. PVC-insulated non-sheathed cable, as
described in e) should always have mechanical protection. Cables other than
those described in a), e), h) and I) should be given mechanical protection if
they are not monitored or they are less than 2.25 m above the floor, or if physical
damage or rodent attack is likely. Mechanical protection can be provided by
installing the cables in conduit, ducting or trunking, or by laying them in a channel
[17.5.2].
11.4 Segregation
The code states that conductors carrying fire alarm power or signals should be separated
from conductors used for other systems in the building [17.10]. The reason for this
requirement is twofold. First, the possibility that other conductors nearby might produce
interference on the fire alarm system, and second, that electric cabling is a known cause of
fires.
The methods used to separate fire alarm system cables from other cables in the building may
be any one of the following:
1. Installation in conduit, ducting, trunking or a channel reserved for fire alarm conductors.
2. Installation in multi-compartment trunking consisting of a mechanically strong, rigid and
continuous partition manufactured in a non-combustible material.
3. Mounting the cables at a distance of at least 300mm from conductors of other systems.
4. Wiring with cables having BASEC certificates of compliance with BS 6387 and assessed
under any scheme (such as the BASEC scheme) as suitable for use without segregation.
5. Wiring with mineral-insulated copper-sheathed cable with an insulating sheath or barrier.
The exposed-to-touch rating defined in BS 7671 (Requirements for Electrical Installations -
IEE Wiring Regulations, Sixteenth Edition) should not be exceeded
The mains supply cables on the supply side of the fire alarm system isolating switch-fuse
device need not be segregated. Cables carrying power in excess of extra-low voltage should
always be kept separated from other fire alarm system cables. In particular, the mains supply
cable should NOT be brought through the same cable entry as cables carrying extra-low
voltage power or signals.
1. Care should be taken in planning the accommodation for the equipment to ensure that the
structure can accept the necessary loading, and that heavy or bulky equipment can be
readily transported to or from its installed position [23.1].
2. Easy access to the equipment should be provided to allow for cleaning and maintenance
[23.1].
3. Provision should be made at the control equipment for the following:
4. All metallic parts of the system, including conduit, trunking, ducting, cabling and
enclosures, should be well separated from any metalwork forming part of any lightning
protective system [23.2].
5. Siting of the control equipment and the routing of cables should take account of any
hazards that might exist in the area when the building is occupied.
Precautions against Fire Spread In order to keep fire spread to a minimum, ensure that the
fire alarm system does not breach the fire separation between compartments. To achieve this
use suitable fire stopping materials to fill holes or gaps round the cables or the cable conduit.
Fire stopping should also be used inside ducts or trunking wherever they pass through
compartment walls or floors unless the duct or trunking has at least the same resistance to fire
as the wall or floor through which it is passing [24.3].
Cabling and Wiring The installation of cabling and wiring should be undertaken generally in
accordance with the requirements of BS 7671 (Requirements for Electrical Installations - IEE
Wiring Regulations, Sixteenth Edition) [24.4].
For further details of the different cable types, etc. which should be used in fire system
installations (see Section 11, Cabling Considerations).
12.4 Certification
Upon successful completion of all inspections, testing and commissioning, the installer should
certify that the installation complies with the recommendations outlined in Part 1 of the code,
or if deviations have been agreed [4.3] then a statement of these deviations should be given
by the installer [Appendix B].
4. Record drawings showing the positions of the systems components and wiring, particularly
where routine maintenance requires access to components.
5. The system log book [28.2.2 and Appendix D].
6. Certificates of installation and commissioning [26.6 and Appendix B].
If one detector or a group of detectors is responsible for more than one false alarm every two
years, or the system produces more than one false alarm per year for each ten detectors then
a special investigation should be undertaken by the maintenance company to resolve the
cause.
Addressable system A system in which signals from each detector and/ or call
point are individually identified at the control panel.
Analogue system A fire alarm system in which the detectors and sensors give
output signals that represent the value of the sensed
phenomena. The detectors and sensors themselves do not
determine if there is a fire, this is decided by the control
equipment. This type of system uses both radial and loop
circuits, and in the event of a fire, the actual location of the
fire within a zone can determined and indicated by the control
equipment.
Control and indicating equipment Equipment, which on receipt of a fire signal, controls the
initiation of a fire alarm by activating one or more sounders,
alarm indicating equipment, or transmitting a signal to other
fire alarm control equipment such as a fire alarm
transmission link.
Conventional system A fire alarm system in which all detectors give the same
output signal that represents an alarm of fire. This type of
system uses radial circuits in which each spur monitors just
one zone. An alarm of fire is given by the control equipment
whenever it receives a signal from any detector. In this type
of system, only the zone in which a fire occurs can be
indicated by the control equipment; the actual location of the
fire within the zone cannot be determined.
EOL End of line device used for open and short circuit monitoring
of detector and sounder circuits.
Final voltage of a battery The voltage at which the cell manufacturer considers the
cells to be fully discharged at the specified current.
Fire alarm transmission link An electrical circuit for transmitting fire alarm signals and fault
warnings to a central station or control room.
Mimic diagram Plan of a protected premises showing the layout of the fire
alarm system in relation to the compartments or subdivisions
of the building.
Monitored wiring Failure of wiring, whether to open circuit or to short circuit, will
result in a fault warning and not an alarm indication.
Normal supply The supply from which the fire alarm system is expected to
obtain its power. The normal supply is usually derived from
the public electricity supply system.
Staged alarm system An alarm system in which two or more stages of alarm can
be given within a given area.
Two-stage alarm system A fire alarm system in which the initial alarm is given only in a
restricted part of the premises, with an alert signal being
given in the remainder of the premises.
Features Benefits
Output to printer
Hard copy of historical data
Multi-isolation facility
By circuit, zone, point, device or function
Fault monitoring
Open and short circuit
Signalling
Software
Mains supply
Battery condition
Sounder outputs
Alarm and fault relays
Graphics link
May be linked to the ThornGraph graphical user
interface
CONTENTS
1 GENERAL REQUIREMENTS
1.1 The Fire Alarm contractor shall be responsible for the design, supply, installation,
commissioning and servicing of an analogue addressable fire detection and alarm system.
1.2 The Fire Alarm contractor shall be capable of providing a remote alarm monitoring service
with a direct communications link to the Fire Brigade Service.
1.3 The Fire Alarm contractor shall have an adequate number of staff trained and experienced in
the design, installation, commissioning and servicing of analogue addressable fire detection
and alarm systems.
1.4 The Fire Alarm contractor shall have a minimum of 10 years experience in designing,
installing, commissioning and servicing fire detection and alarm systems, at least 5 years of
which must be with analogue addressable systems.
1.6 All equipment central to the operation of the analogue addressable fire alarm system shall be
designed and manufactured by the company installing and commissioning the system. As a
minimum requirement, this clause covers the following:
1.7 The supplier shall be approved to ISO 9002 Quality system standard for the design and
manufacture of the equipment referred to in clause 1.6.
1.8 The main equipment proposed for use in the in the analogue addressable fire detection and
alarm system shall be approved by at least one of the following UK or international
organisations:
1.9 The Fire Alarm contractor shall have available a complete set of technical manuals for all
equipment installed. This must cover technical specification, system design
recommendations and guidelines for installation, commissioning, operating and servicing the
proposed equipment.
1.10 The Fire Alarm contractor, given reasonable notice, shall permit the buyer, or its nominated
agent, to conduct a quality audit at the premises where the proposed equipment is
manufactured.
1.11 All deviations from this specification that the contractor proposes to make shall be clearly
indicated in writing, making reference to the relevant paragraph(s) of this specification.
2.2.1 BS5839: Pt.1: 1988 Code of practice for system design, installation and servicing.
2.2.3 BS5839: Pt.3: 1988 Specification for automatic release mechanisms for certain fire protection
equipment.
2.2.4 BS5839: Pt.4: 1988 Specification for control and indicating equipment.
2.2.5 BS5839: Pt.5: 1988 Specification for optical beam smoke detectors.
2.3 BS4678: Pt.4: 1988 Specification for cable trunking made of insulating material.
2.4 BS5345 Code of practice for selection, installation and maintenance of electrical apparatus
for use in potentially explosive atmospheres (other than mining applications or explosives
processing and manufacture).
2.4.3 BS5345: Pt.3: 1990 Installation and maintenance requirements for electrical apparatus with
type of protection 'd'. Flameproof enclosure.
2.4.4 BS5345: Pt.4: 1977 Installation and maintenance requirements for electrical apparatus with
type of protection 'i'. Intrinsically safe electrical apparatus and systems.
2.4.5 BS5345: Pt.6: 1990 Recommendations for type of protection 'e'. Increased safety.
2.4.6 BS5345: Pt.7: 1990 Installation and maintenance requirements for electrical apparatus with
type of protection N.
2.5.2 BS5445: Pt.5: 1977 (EN 54: Pt.5: 1976) Heat sensitive detectors - point detectors containing
a static element.
2.5.3 BS5445: Pt.7: 1984 (EN 54: Pt.7: 1982) Specification for point-type smoke detectors using
scattered light, transmitted light or ionization.
2.5.4 BS5445: Pt.8: 1984 (EN 54: Pt.8: 1982) Specification for high temperature heat detectors.
2.6 BS5446: Pt.1: 1990 Specification for self-contained smoke alarms and point-type smoke
detectors.
2.7.2 BS5501: Pt.5: 1977 (EN 50018: 1977) Flameproof enclosure 'd'.
2.7.3 BS5501: Pt.6: 1977 (EN 50019: 1977) Increased safety 'e'.
2.7.4 BS5501: Pt.7: 1977 (EN 50020: 1977) Intrinsic safety 'i'.
2.7.5 BS5501: Pt.9: 1982 (EN 50039: 1980) Specification for intrinsically safe electrical
systems 'i'.
2.8 BS6207: 1991 Specification for mineral-insulated copper sheathed cables with copper
conductors.
2.9 BS6266: 1992 Code of practice for fire protection for electronic data processing installations.
2.10 BS6387: 1994 Specification for performance requirements for cables required to maintain
circuit integrity under fire conditions.
2.11 BS6724: 1990 Specification for armoured cables for electricity supply having thermosetting
insulation with low emission of smoke and corrosive gases when affected by fire.
2.12 BS7273: Pt.1: 1990 Code of practice for the operation of fire protection measures. Electrical
actuation of gaseous total flooding extinguishing systems.
2.13 BS7671: 1992 Requirements for electrical installations. IEE Wiring regulations. Sixteenth
Edition.
2.14 HTM82 Fire safety in health care premises. Fire alarm and detection systems.
2.16 Draft British Standard code of practice for the design, installation and servicing of voice
systems associated with fire detection systems (BS5839: Pt.8).
3.1 General
3.1.1 The control and indicating equipment shall form the central processing unit of the system,
receiving and analysing signals from fire sensors, providing audible and visual information to
the user, initiating automatic alarm response sequences and providing the means by which
the user interacts with the system.
3.1.2 The control and indicating equipment shall be modular in construction to allow for future
extension of the system.
3.1.3 The control and indicating equipment shall be easily configurable so as to meet the exact
detection zone and output mapping requirements of the building.
3.1.4 The control and indicating equipment shall be microprocessor based and operate under a
multitasking software program. Operating programs and configuration data must be
contained in easily up-datable non-volatile memory (EEPROM).
3.1.5 The control and indicating equipment shall incorporate a real-time clock to enable events to be
referenced against time and date. This clock shall be accurate to within 1 minute per year
under normal operating conditions.
3.1.6 It shall be possible for an engineer to perform configuration updates on site by plugging a
portable personal computer into the control and indicating equipment. Configuration data shall
be retained on a micro-floppy disk.
3.1.7 The company responsible for the installation shall operate an approved document control
system for the retention of configuration data.
3.1.8 The control and indicating equipment shall meet the requirements of BS5839 Part 4 and shall
be approved, together with associated ancillary equipment, by the Loss Prevention Council
Board (LPCB).
3.1.9 The control and indicating equipment shall comprise separate processors, cross-monitoring
each others correct operation, for the major functions of the systems. In particular, different
processors must be used for the main control function, the detection input and alarm output
functions, and the display and control function.
3.1.10 No more than 200 addressable input or output points shall be controlled by a single processor.
3.1.11 To ensure continuous stability of the system, the setting of the address code in each
addressable device shall be by either a DIL switch in the detector base or smart card
technology.
3.1.12 In the case of plug-in analogue addressable detectors, the address code shall be set in the
base to prevent unauthorised and potentially dangerous reconfiguration of the system.
3.1.13 The control and indicating equipment shall incorporate a keyswitch with three positions
Normal, Trapped Normal and Enable to prevent unauthorised use of the manual controls.
conventional detectors
addressable two-state detectors
analogue addressable detectors
3.2.2. The control and indicating equipment shall be capable of operating with intrinsically safe
conventional detectors and analogue addressable detectors suitable for installation in
hazardous areas.
3.2.3. Addressable input and output devices shall be connected to addressable loops capable of
accepting up to 99 devices.
3.2.4. The control and indicating equipment shall have a minimum capacity for operating 1 fully
loaded addressable loop. This shall be extendible up to a maximum capacity of 10
addressable loops.
3.2.5. Provision shall be made for each addressable loop to be sub-divided into a maximum of 8
geographical zones. The section of wiring corresponding to each zone circuit shall be
protected from faults in other sections by line isolator modules.
3.2.6. It shall be possible to allocate all 99 addressable devices on the loop to a single zone.
3.2.7. In order to facilitate re-configuration and system extension, the allocation of addresses to
devices shall be independent of their physical arrangement on the loops.
3.2.8. The control and indicating equipment shall have provision to drive and monitor up to 20
repeater panels providing a repeat of the indications on the control and indicating equipment
display and up to a further 3 repeater panels also incorporating the full set of system manual
user controls.
3.2.9. The control and indicating equipment shall have provision to house the AC Main power supply
and batteries required to power systems of up to 16 zones.
3.2.10. The control and indicating equipment shall have provision for the connection of external power
supplies, either local to the control and indicating equipment or distributed throughout the
system, to supply power in excess of that stated in clause 3.2.9.
3.2.11. The control and indicating equipment shall have provision for the connection of an 80
character line printer, either locally via a parallel port or remotely via a serial port.
3.2.12. The control and indicating equipment shall be capable of interfacing directly to an electronic
radio paging system.
3.2.13. The control and indicating equipment shall be capable of being interfaced with other similar
control and indicating equipment without locking up or being affected by feedback signals.
3.2.14. It shall be possible to connect a VDU monitor to the control and indicating equipment to
display the information that would otherwise appear on the printer referred to in clause 3.2.11.
3.2.15 The control and indicating equipment shall have the facility to enable an on board
communications module to be added to allow local area networking to other controllers.
3.3.2 The housings shall be capable of being surface or semi-recessed mounted and shall come
complete with cable entries, fixings, knock-outs and covers.
3.3.3 The display component of the control and indicating equipment shall be mounted on an hinged
front cover that must not open at an angle greater than 90 degrees to prevent cover damage.
3.3.5 It shall not be possible to open the control and indicating equipment without the use of a
special tool.
3.3.6 The control and indicating equipment shall be of a neutral light grey colour.
3.4.2 The control and indicating equipment shall monitor the status of all internal connection and
interfaces, including charger, battery and remote signalling functions.
3.4.3 The control and indicating equipment shall provide the following discrete visual indications:
3.4.4 In addition to the indications provided in clause 3.4.3, the control and indicating equipment
shall also have an integral 80 character LCD alphanumeric display. In order that an easy
identification of different information is provided, the LCD display shall be arranged as follows:
3.4.5 The control and indicating equipment shall provide a set of push button controls to enable an
authorised operator to perform the following:
3.4.6 The control and indicating equipment shall provide a facility to manually check all the discrete
LED indicators. This shall be clearly marked LAMP TEST and be accessible at all time.
3.4.7 The control and indicating equipment shall provide a simple to operate keypad to enable a
user to access the various built-in functions, and interact with the information displayed on the
LCD. For security reasons, the control and indicating equipment shall provide a customer
configurable password code facility for the following levels of access:
User Operator
User Manager
User Engineer
Specialist Engineer
Specialist Engineer Supervisor
Alarm Company Engineer
3.4.8 The control and indicating equipment shall provide facilities to drive visual indication LED
mimic displays for each of the following zonal status:
Alarm
Fault
Isolated
3.4.9 The control and indicating equipment shall provide facilities for signalling the following system
conditions to a remote (Central Station) and/or an on-site monitoring centre:
Alarm
Pre-alarm
Fault
Zone Isolated
3.4.10 The control and indicating equipment shall be capable of monitoring and controlling remote
site devices, such as door release units and relays for the control of plants and dampers,
directly from the addressable loops.
3.4.11 The control and indicating equipment shall be capable of monitoring fire doors such that, in
the event of a fire alarm condition, an event is generated to warn of the failure of a fire door to
close.
3.4.12 The control and indicating equipment shall provide programmable outputs to activate
emergency lighting in the event of a mains supply failure.
3.5.2 The control and indicating equipment shall incorporate fire decision algorithms specifically
adapted to the response characteristics of the analogue addressable detectors employed.
3.5.3 The algorithms mentioned in clause 3.5.2 shall perform a trend analysis of the signal received
from the analogue addressable detectors in order that non-fire events may be differentiated.
3.5.4 The control and indicating equipment shall be designed so that, for each type of analogue
addressable detector, the overall response time, including that for the sensor, the signal
transmission system and the fire decision algorithm, meets the requirement of the relevant
part of BS5445 (EN54).
3.5.5 The response time of the control and indicating equipment to two-state addressable detectors
and conventional detectors shall not exceed 10 seconds.
3.5.6 The control and indicating equipment shall have a special scanning sequence so that
designated manual call points provide alarm indication and warning within 1 second of
operation.
3.5.7 The control and indicating equipment shall have a facility to automatically adjust the sensitivity
of analogue detectors to a higher level for periods of time when the building is unoccupied.
3.5.8 The control and indicating equipment shall have, as an optional software enhancement, the
ability to annunciate a pre-alarm condition designed to give the earliest possible warning of a
potential fire condition without raising the full alarm condition.
3.5.9 The control and indicating equipment shall have, as an optional software enhancement, the
ability to automatically adjust the alarm and pre-alarm threshold levels to compensate for
changes in detector sensitivity due to contamination over a period of time.
3.5.10 The control and indicating equipment shall have, as an optional software enhancement, the
ability to provide automatic warning that a detector has reached a level of contamination which
requires that it be replaced or serviced.
3.6.2 The control and indicating equipment shall be able to monitor and control the integrity of zonal
sounder circuits, via a suitable addressable module.
3.6.3 The control and indicating equipment shall be capable of providing a two-stage alarm sounder
facility that can be programmed, either on a zonal basis or common system basis, to meet the
requirements of the fire authority. Three possible sound output signals shall be available as
follows:
3.6.4 The control and indicating equipment shall have the facility to change, on a per sounder zone
basis, the sound output dependent upon whether the source of alarm is:
3.6.5 The control and indicating equipment shall be capable of generating customer definable time
delay sequences to upgrade alarm sounder responses, without the need for external timers,
as follows:
Silent to Alert
Alert to Evacuate
Silent to user defined tone.
3.6.6 The control and indicating equipment shall be capable of operating addressable voice alarm
units and monitoring the integrity of the wiring connection to individual loudspeakers.
3.6.7 The control and indicating equipment shall provide an interface to drive a public address
system as described in section 9.2 of BS5839: Pt.1: 1988. The system shall be arranged such
that, in the event of a failure of the public address system, back-up sounders are available to
alert or evacuate the relevant areas of the protected premises.
3.6.8 The control and indicating equipment shall have the ability to delay the transmission to the Fire
Brigade of fire alarm signals from automatic detectors in pre-determined detection zones. The
time delay shall be configurable up to a maximum time of 2 minutes.
3.6.9 The control and indicating equipment shall provide the facility to automatically inhibit the delay
function described in clause 3.6.8 when the building is unoccupied.
3.6.10 The facility described in clause 3.6.8 shall not apply to alarms generated by manual call points
which shall always be transmitted immediately.
3.7.2 The following faults shall be reported in the manner described in clause 3.7.1:
3.7.3 To help rapid fault finding and repair, the control and indicating equipment shall provide text
messages to indicate the precise location of where a fault has occurred in the system.
3.7.4 The control and indicating equipment shall be capable of monitoring and indicating the status
of auxiliary units, such as a remote signalling transmitter. This shall be achieved using a
suitable addressable contact monitor module.
3.7.5 With respect to clause 3.7.4, the control and indicating equipment shall have the facility to
delay the generation of an event to confirm operation of the monitored device. This shall be
either 6 seconds for normal de-bounced contacts, or 40 seconds for fluctuating contacts, e.g.
sprinkler flow valve switches.
3.8.2 Access to the facilities described in clause 3.8.1 shall be restricted to User Engineer level or
above.
3.8.3 The control and indicating equipment shall have an event log capable of storing up to the last
500 events that have occurred. It shall be possible to view the content of the log via the
alphanumeric display. Events shall be displayed in chronological order in any of the following
three options:
3.8.4 The control and indicating equipment shall be capable of providing audible and visual warning
when a weekly system test, as defined in BS5839: Pt.1: 1988, is required.
3.8.5 The control and indicating equipment shall be capable, via a suitable timer unit, of isolating a
group of selected detectors in areas of the building where maintenance work is carried out.
The detectors shall be automatically re-instated after a pre-determined time.
3.8.6 The control and indicating equipment shall have a facility to enable the user to easily change
the time and date settings of the system real-time clock.
Height : 320 mm
Width : 440 mm
Depth : 140 mm
3.9.2 The overall weight of the control and indicating equipment, standard power supply unit and
standard repeater unit shall not exceed 7 Kg (weight of batteries excluded).
3.9.3 The control and indicating equipment shall operate on a mains power supply of:
or
3.9.4 The control and indicating equipment, standard power supply unit and standard repeater unit
shall comply with the following environmental conditions:
3.9.5 The control and indicating equipment, standard power supply unit and standard repeater unit
shall comply with, at least, the EMC test requirements described in BS5839: Pt.4: 1988 and
the EEC requirements for the EMC Directive 89/336/EU and subsequent amendments
92/31/EU.
4.1.2 The Fire Alarm contractor shall be capable of offering both an analogue addressable and a
two-state addressable version of the following type of automatic fire detectors:
4.1.3 The Fire Alarm contractor shall have available the following types of conventional automatic
detectors, manual call points and ancillary units for connection to the system via suitable
interfaces:
4.1.4 The automatic fire detectors shall be fixed to the installation by mean of plug-in detector
bases. Both an addressable detector base and a conventional detector base shall be
available.
4.1.5 The two types of bases specified in clause 4.1.4 shall incorporate the optional feature of being
able to lock the detectors in place once plugged in.
4.1.6 The addressable base must incorporate all the circuitry required for communicating detector
status to the control and indicating equipment, including the address setting switch.
4.1.7 Addressable detectors and modules must be able to transmit to the control and indicating
equipment a pre-set and unique identifier to detect unauthorised changes in the system
configuration.
4.1.8 The Fire Alarm contractor shall produce standard accessories for installing smoke detectors in
air ducts. This equipment shall be designed to accommodate the manufacturer's standard
smoke detectors and bases, both conventional and addressable.
4.1.9 It must be possible to connect and mix automatic detectors, manual call points and
addressable modules within the same zone sub-division of an addressable loop.
4.1.10 The Fire Alarm contractor shall have available suitable equipment to test and exchange all
four main types of automatic detectors.
4.1.11 The Fire Alarm contractor shall have available intrinsically safe versions of all four types of
automatic detectors, the plug-in bases and the line isolator.
4.1.12 The Fire Alarm contractor shall also have available an intrinsically safe version of the
addressable contact monitoring module for connection of 'simple apparatus' such as
conventional manual call points.
4.1.13 The intrinsically safe devices specified in clauses 4.1.10 and 4.1.11 shall be designed to
comply with BS5501: Pt.7 and be certified by BASEEFA to EEx ia IIC T5.
4.1.14 It shall be possible to connect several circuits of intrinsically safe addressable devices to a
standard addressable loop via standard BASEEFA approved safety barriers from the loop as
spurs.
4.1.15 All equipment connected to the system addressable loops, either directly or via interfaces,
shall be proofed against electrical noise, high frequency pulses and electromagnetic
influences from other equipment.
4.1.16 Both the conventional and addressable detector base shall be capable of driving a separate
alarm LED indicator module.
4.2.2 The ionisation smoke detectors shall meet the requirements of BS5445: Pt.7: 1984 (EN54:
Pt.7).
4.2.3 The ionisation smoke detectors shall have a sensitivity sufficient to be classified as 'B' or
better in BS5445: Pt.9: 1984 (EN54: Pt.9) test fires TF1, TF3 and TF4 and TF5.
4.2.4 The ionisation smoke detectors shall be approved and listed by the Loss Prevention Council
Board (LPCB).
4.2.5 The ionisation smoke detectors shall use a dual ionisation chamber in which the air is ionised
by a single radioactive source.
4.2.6 The radioactive source employed shall have an emission rating of less than 38 Kbq.
4.2.7 The ionisation smoke detectors shall be designed to have high resistance to contamination
and corrosion.
4.2.8 The ionisation detectors shall include RFI screening and feed-through connecting components
to minimise the effect of radiated and conducted electrical interferences.
4.2.9 The ionisation smoke detectors shall be suitable for operation in wind speeds of up to 5 m/s.
4.2.10 The ionisation smoke detectors shall incorporate screens to minimise the effect of small
insects.
4.2.11 The Fire Alarm contractor shall have available the following versions of the ionisation smoke
detector to meet different applications:
Analogue addressable
Analogue addressable - intrinsically safe
Two-state addressable - normal sensitivity
Conventional - high sensitivity
Conventional - high sensitivity - delayed response
Conventional - normal sensitivity
Conventional - normal sensitivity - delayed response
Conventional - low sensitivity
Conventional - normal sensitivity - intrinsically safe
4.2.12 The ionisation smoke detector shall incorporate an LED, clearly visible from the outside, to
provide indication of alarm actuation.
4.3.2 The optical smoke detectors shall meet the requirements of BS5445: Pt.7: 1984 (EN54: Pt.7).
4.3.3 The optical smoke detectors shall have a sensitivity sufficient to be classified as 'A' in BS5445:
Pt.9: 1984 (EN54: Pt.9) test fires TF2 and TF3.
4.3.4 The optical smoke detectors shall be approved and listed by the Loss Prevention Council
Board (LPCB).
4.3.5 The optical smoke detectors shall employ the forward light-scatter principle, using optical
components operating at a wavelength of 4.35 nm.
4.3.6 The design of the optical smoke detector sensing chamber shall be optimised to minimise the
effect of dust deposits over a period of time.
4.3.7 The optical smoke detectors shall incorporate screens designed to prevent all but the smaller
insects from entering the sensing chamber.
4.3.8 The optical smoke detectors shall incorporate a fin structure designed to totally eliminate the
effect of very small insects such as thunder flies.
4.3.9 The optical smoke detectors shall be designed to have high resistance to contamination and
corrosion.
4.3.10 The optical smoke detectors shall include RFI screening and feed-through connecting
components to minimise the effect of radiated and conducted electrical interferences.
4.3.12 The Fire Alarm contractor shall have available the following versions of the optical smoke
detector to meet different applications:
Analogue addressable
Analogue addressable - intrinsically safe
Two-state addressable - normal sensitivity
Conventional - high sensitivity
Conventional - normal sensitivity
Conventional - normal sensitivity - delayed response
Conventional - low sensitivity
Conventional - normal sensitivity - intrinsically safe
4.3.13 The optical smoke detector shall incorporate an LED, clearly visible from the outside, to
provide indication of alarm actuation.
4.4.2 The high performance optical smoke detectors shall be design in accordance with the
functional requirements of BS5445: Pt.7: 1984 (EN54: Pt.7).
4.4.3 The high performance optical smoke detectors shall have a sensitivity sufficient to be
classified as 'B' or better in BS5445: Pt.9: 1984 (EN54: Pt.9) test fires TF2 to TF5 inclusive
and as 'C' in test fire TF1.
4.4.4 The high performance optical smoke detectors shall be approved and listed by the Loss
Prevention Council Board (LPCB).
4.4.5 The high performance optical smoke detectors shall employ the forward light-scatter principle,
using optical components operating at a wavelength of 4.35 nm.
4.4.6 The high performance optical detectors shall monitor and use rapid changes in temperature to
increase the normal sensitivity of the light-scatter optical sensor to obtain an improved
response to fast burning fires.
4.4.7 The high performance optical detectors shall not generate an alarm condition from a rate of
rise of temperature or absolute temperature alone.
4.4.8 The design of the high performance optical smoke detector sensing chamber shall be
optimised to minimise the effect of dust deposits over a period of time.
4.4.9 The high performance optical smoke detectors shall incorporate screens designed to prevent
all but the very small insects from entering the sensing chamber.
4.4.10 The high performance optical smoke detectors shall incorporate a fin structure designed to
eliminate the effect of very small insects such as thunder flies.
4.4.11 The high performance optical smoke detectors shall be designed to have high resistance to
contamination and corrosion.
4.4.12 The high performance optical smoke detectors shall include RFI screening and feed-through
connecting components to minimise the effect of radiated and conducted electrical
interferences.
4.4.13 The Fire Alarm contractor shall have available the following versions of the high performance
optical smoke detector to meet different applications:
4.4.14 The high performance optical smoke detector shall incorporate an LED, clearly visible from
the outside, to provide indication of alarm actuation.
4.5.2 The infra-red flame detectors shall be approved and listed by the Loss Prevention Council
Board (LPCB).
4.5.3 The infra-red flame shall be able to detect a fuel fire of 0.1 square meter area from a distance
of 30 meters for the following fuels:
Petrol (gasoline)
N-heptane
Kerosene
Diesel oil
Alcohol (I.M.S)
Ethylene glycol
4.5.4 The infra-red flame detectors shall employ narrow band optical filters that block unwanted
radiation such as that emanating from the sun or tungsten filament lamps.
4.5.5 The infra-red flame detectors shall be designed to be sensitive to modulation of the received
radiation in a small range of frequencies corresponding to the flicker of flames.
4.5.6 The infra-red flame detectors shall be designed to have high resistance to contamination and
corrosion.
4.5.7 The electronic assembly of the infra-red flame detectors shall be encapsulated in high
resistivity epoxy resin.
4.5.8 The infra-red flame smoke detectors shall include RFI screening and feed-through connecting
components to minimise the effect of radiated and conducted electrical interferences.
4.5.9 The Fire Alarm contractor shall have available the following versions of infra-red flame
detectors to meet different applications:
4.5.10 The intrinsically safe versions of the infra-red flame detectors shall be suitable for use with
safe area circuits.
4.5.11 The infra-red flame detector shall incorporate an LED, clearly visible from the outside, to
provide indication of alarm actuation.
4.6.2 The heat detectors shall meet the requirements of either BS5445: Pt.5 (EN54: Pt.5) for
detectors suitable for normal environment or BS5445: Pt.8 (EN54: Pt.8) for detectors designed
for high ambient temperatures.
4.6.3 The heat detectors shall be approved and listed by the Loss Prevention Council Board
(LPCB).
4.6.4 The heat detectors shall employ two heat sensing elements with different thermal
characteristics to provide a rate of rise dependent response.
4.6.5 The temperature sensing elements and circuitry of the heat detectors shall be coated with
epoxy resin to provide environmental protection.
4.6.6 The heat detectors shall include RFI screening and feed-through connecting components to
minimise the effect of radiated and conducted electrical interferences.
4.6.7 The Fire Alarm contractor shall have available the following versions of the heat detectors to
meet different applications:
Analogue addressable
Analogue addressable - intrinsically safe
Two-state addressable - grade 1
Conventional - grade 1
Conventional - grade 1 - intrinsically safe
Conventional - grade 3
Conventional - grade 3 - intrinsically safe
Conventional - range 2 (98 C)
Conventional - range 2 - intrinsically safe
Conventional - static 60 C (grade 2)
Conventional - static 90 C
4.6.8 The heat detectors shall incorporate an LED, clearly visible from the outside, to provide
indication of alarm actuation.
4.7.2 The sensor cable of the linear heat detectors shall be unaffected by dust, moisture or vibration
and require little maintenance.
4.7.3 The detectors shall have a calibration switch mounted internally to set the alarm sensitivity
threshold.
4.7.4 The detectors shall generate an alarm condition if the pre-determined alarm threshold is
exceeded.
4.7.5 The detectors shall generate a fault condition if the sensor cable has an open or short circuit
condition present.
4.7.6 The detectors, upon detecting a cable open or short circuit or fault, shall be capable of
signalling the condition to the main fire controller.
4.7.7 The linear heat detectors shall meet the requirements of either BS5445: Pt.5 (EN54: Pt.5) for
detectors suitable for normal environment or BS5445: Pt.8 (EN54: Pt.8) for detectors designed
for high ambient temperatures.
4.7.8 The linear heat detectors shall be approved and listed by the Loss Prevention Council Board
(LPCB).
4.7.9 The detectors shall be suitable for use in hazardous areas and have mechanical protection for
cables in areas where damage may occur.
4.7.10 The detectors shall incorporate red Fire and yellow Fault LEDs, clearly visible from the
outside, to provide indication of alarm condition.
4.8.2 The beam smoke detectors shall project a modulated infra-red light beam from a transmitter
unit to a receiver unit. The received signal shall be analysed and, in the event of smoke being
present for a pre-determined period, an alarm condition is activated.
4.8.3 The detectors shall be capable of providing cover in open areas up to 100m in length and up
to 14m wide, giving an effective protection area of up to 1400sq m.
4.8.4 The fire alarm output of the detectors shall be activated in the event of smoke reducing the
signal strength between 40% and 90% for a period of approximately 5 seconds.
4.8.5 In the event of a power failure at the transmitter unit or if the transmitted signal is reduced by
more than 90% for a period in excess of 1 second, then a fault alarm condition shall be
indicated. This condition shall inhibit the fire alarm until the signal is restored.
4.8.6 The receiver unit of the detectors shall be capable of performing an automatic reset,
approximately 5 seconds after a fault is indicated, if the fault is no longer present.
4.8.7 The detectors shall include Automatic Gain Control (AGC) circuitry capable of providing
compensation for long-term degradation of signal strength caused by component ageing or
build-up of dirt on the optical surfaces of the transmitter and receiver unit lenses.
4.8.8 The beam smoke detectors shall meet the requirements of either BS5445: Pt.5 (EN54: Pt.5)
for detectors suitable for normal environment or BS5445: Pt.8 (EN54: Pt.8) for detectors
designed for high ambient temperatures.
4.8.9 The beam smoke detectors shall be approved and listed by the Loss Prevention Council
Board (LPCB).
4.8.10 The receiver unit of the detectors shall incorporate an alignment/fault lamp, clearly visible from
the outside, to provide indication of both alignment and fault conditions.
4.9.2 The aspirating smoke detectors shall provide a continuous analogue profile of ambient air
conditions.
4.9.3 The detectors shall be capable of responding to a developing fire situation with multiple staged
alarms.
4.9.4 The fire alarm output of the detectors shall be programmable to allow sufficient time for action
to be taken; from a detailed investigation of the cause of the alarm to a full-scale evacuation.
4.9.5 The design of the detectors shall be such that they can be integrated with a fire alarm system
and guard against specific pieces of equipment, such as computers, equipment racks, power
boards and telecommunications switching racks, as well as entire rooms or floors.
4.9.6 The detectors shall include a facility to allow sensitivity threshold adjustments to suit the needs
of particular environments.
4.9.7 Each detector shall be capable of monitoring an area up to 2000 sq m using easy to install
PVC conduit. (Depending on the level of risk or hazard involved, it may be appropriate to use
a greater number of detectors.)
4.9.8 The aspirating smoke detectors shall meet the requirements of either BS5445: Pt.5 (EN54:
Pt.5) for detectors suitable for normal environment or BS5445: Pt.8 (EN54: Pt.8) for detectors
designed for high ambient temperatures.
4.9.9 The aspirating smoke detectors shall be approved and listed by the Loss Prevention Council
Board (LPCB).
4.9.10 The detectors shall incorporate a LED indicator, clearly visible from the outside, to provide
indication of alarm or fault condition.
4.10.2 The remote indicator module shall be driven directly from its associated local detector.
4.10.3 The connection to the remote indicator module shall be monitored for open and short-circuits.
5.1.2 The addressable manual call point shall meet the requirements of BS5839: Pt.2.
5.1.3 The addressable call points shall be capable of operating by means of thumb pressure and
not require a hammer.
5.1.4 The addressable call points shall be capable of being mounted in weather-proof affording
protection to IP65.
5.1.5 The addressable call points shall incorporate a mechanism to interrupt the normal
addressable loop scan to provide an alarm response within less than 1 second.
5.1.6 The addressable call points shall be field programmable to trigger either an alert or an
evacuate response from the control and indicating equipment
5.1.7 The addressable call points shall be capable of being tested using a special 'key' without the
need for shattering the glass.
5.1.8 The addressable call points shall provide an integral red LED to indicate activation.
5.2.2 The conventional detector interface module shall be able to signal alarm, open-circuit fault,
short-circuit fault and power supply fault status.
5.2.3 The conventional detector interface module shall be capable of monitoring automatic
detectors and manual call points from existing conventional systems.
5.2.4 The conventional detector interface module shall provide integral red LED indication when in
the alarm state.
5.2.5 The conventional detector interface module shall operate from a monitored 24 V d.c. power
supply.
5.3.2 The contacts of the addressable relay output module shall be rated at a minimum of 1Amp at
24 V d.c.
5.3.3 The addressable relay output module shall monitor the relay coil for open-circuit and transmit
the fault signal to the control and indicating equipment
5.3.4 The addressable relay output module shall be capable of deriving its operating power from the
addressable loop.
5.3.5 The addressable relay output module shall provide a red LED indication that the relay has
operated.
5.4.2 The addressable contact monitoring module shall provide a red LED indication when the
contact has operated.
5.4.3 The addressable contact monitor module shall be capable of deriving its power directly from
the addressable loop.
5.5.2 The output of the addressable sounder driver module shall be rated at 500mA.
5.5.3 The addressable sounder driver module shall be capable of operating the sounders in a
pulsing or continuous mode as determined by the control and indicating equipment
5.5.4 The addressable sounder driver module shall provide the facility to monitor the wiring to the
sounders for open or short-circuit and transmit the necessary fault signal to the control and
indicating equipment
5.5.5 The addressable sounder driver module shall provide the facility to monitor for failure of the
power supply for the sounders and transmit the necessary fault signal to the control and
indicating equipment
5.5.6 The addressable sounder driver module shall provide a red LED indication that the sounder
circuit has been actuated.
5.6.2 The sounder booster module shall be capable of interfacing either to the common sounder
outputs of the control and indicating equipment or to the output of the addressable sounder
driver module.
5.6.3 The sounder booster module shall be designed to maintain the monitoring of the sounder
circuit and transmit a fault signal either via the addressable sounder driver module or directly
to the control and indicating equipment
5.7.2 The addressable power supply module shall derive its power from the 115/240 V a.c. mains
supply.
5.7.3 The addressable power supply module shall be able to contain and maintain in a charged
state a 24 V battery set of up to 15 A/h capacity.
5.7.4 The addressable module shall monitor the mains power supply and the battery and transmit a
fault signal as appropriate to the control and indicating equipment
5.8.2 The line isolator module shall derive power directly from the addressable loop.
5.8.3 The line isolator module shall provide an LED indication that the module has tripped.
5.9.2 The smoke damper module shall be fully addressable and provide one volt-free changeover
relay contact rated 240 V a.c. @ 5 Amps.
5.9.3 An external 24 V d.c. supply shall be provided to operate the changeover relay.
5.9.4 The changeover relay contact of the smoke damper module shall be monitored and controlled
by commands signalled from the fire alarm system control panel via the addressable loop.
5.9.5 The smoke damper module shall be capable of monitoring up to two external relay contacts.
5.9.6 The module shall derive its power directly from the addressable loop.
5.9.7 The outputs of the smoke damper module shall be capable of being controlled using a keypad
via the addressable loop.
5.9.8 The keypad shall be capable of forcing the relay outputs LOW, HIGH or AUTO. It shall also
be capable of reading the status of the relay outputs.
5.9.8 The smoke damper module shall have a red LED, clearly visible on the fascia panel of the
unit, to provide an indication of relay operation.
5.10.2 The shop unit module shall be fully addressable and provide multiple volt-free changeover
relay contacts rated 24 V d.c. @ 1 Amp.
5.10.3 An external 24 V d.c. supply shall be provided to operate the changeover relays.
5.10.4 The changeover relay contacts of the shop unit module shall be monitored and controlled by
commands signalled from the monitoring system control panel via the addressable loop
5.10.5 The shop unit module shall be capable of monitoring multiple external relay contacts.
5.10.6 The module shall derive its power directly from the addressable loop.
5.10.7 The shop unit module shall be capable of being link configured to provide 2 inputs/2 outputs, 4
inputs/4 outputs or 6 inputs/6 outputs as required.
5.10.8 The shop unit module shall have six consecutive addresses provided for configuration.
5.11.2 The plant interface module shall be fully addressable and provide multiple volt-free DPDT
changeover relay contacts rated 240 V a.c. @ 5 Amps.
5.11.3 An external 24 V d.c. supply shall be provided to operate the changeover relays.
5.11.4 The changeover relay contacts of the plant interface module shall be monitored and controlled
by commands signalled from the fire alarm system control panel via the addressable loop.
5.11.5 The module shall be capable of monitoring multiple external relay contacts.
5.11.6 The plant interface module shall derive its power directly from the addressable loop.
5.11.7 The plant interface module shall be capable of being link configured to provide
2 inputs/2 outputs, 4 inputs/4 outputs or 6 inputs/6 outputs as required.
5.11.8 The plant interface module shall have six consecutive addresses provided for configuration.
6 DOCUMENTATION
6.1.2 The Fire Alarm contractor shall provide a complete set of layout drawings and specifications
describing all aspects of the system, including:
1. Detailed component and equipment list with model and manufacturers part numbers.
2. Product sheets for each item of equipment.
3. Theory of Operations with description of system functions.
4. Written confirmation that a manufacturer trained representative will provide:
a) on-site supervision during system installation
b) perform all final testing and commissioning of the installed system
c) instruct operating personnel on all system operations.
6.1.3 The Fire Alarm contractor shall provide a schedule showing the times required to design,
build, install, test and commission the system. The schedule shall also include any special
requirements, such as additional training for operating personnel, etc.
6.2.2 As a minimum, the following documentation shall be provided for the system:
1. System description.
2. Checklist of equipment and components.
3. Installation instructions.
4. Equipment connection diagrams showing wiring detail of Addressable Device positions
with addresses.
5. Standby battery calculations showing system power requirements and formulas used to
calculate specified power.
6 Final testing instructions.
7. Commissioning instructions.
8. Certification documents.
9. Log book.
10. System operating instructions.
11. Routine maintenance instructions and schedules.
12. Remote monitoring link description and operating instructions (if this option is being
provided).
6.2.3 As a minimum, the following drawings shall be provided for the system:
6.2.4 The Fire Alarm contractor shall provide a complete set of system operating and service
manuals for the following:
1. Fire controller
2. Detectors
3. Call points
4. Sounders
5. Ancillary devices
6. Remote monitoring link (if this option is being provided).
6.2.5 The date for submission of all documentation shall be in accordance with the schedule
provided by the Fire Alarm contractor and as agreed with the customer.
7 INSTALLATION
7.1 General
7.1.1 Correct installation, combined with the use of high quality equipment, components and
cabling, ensures that the fire detection and alarm system shall operate as designed and
provide many years of trouble-free service.
7.1.2 The Fire Alarm contractor shall install the alarm system in accordance with the documented
installation instructions.
7.1.3 The Fire Alarm contractor shall provide all relevant installation documentation required for
each component of the system.
7.1.4 Installation of the system shall be in accordance with the recommendations set out in
BS 5839: Pt 1: 1988 (Fire detection and alarm systems for buildings - Code of practice for
system design, installation and servicing) and BS 7671 (Requirements for Electrical
Installations - IEE Wiring Regulations, Sixteenth Edition).
7.1.5 The Fire Alarm contractor shall be responsible for the correct siting of all equipment and
components of the system in accordance with previously agreed plans and drawings.
7.1.6 All cabling and wiring shall be tested before they are connected to the fire controller and its
associated devices.
WARNING If the tests are carried out after the cables and wires have been connected to the
controller and its devices, components within the controller and the devices will be damaged
by high voltages used during testing.
7.2 Materials
7.2.1 All cabling and wiring to be used in the system shall be fire resistant and approved to BSI and
LPCB specifications for use in fire detection and alarm systems.
7.2.2 Wiring used for driving devices requiring high currents (e.g. bells, etc.) shall limit the voltage
drop to less than 10% of the nominal operating voltage.
7.2.3 Cables used for the transmission of system data and alarm signals shall be in accordance
with the types recommended by the manufacturer of the fire alarm system.
7.2.4 The ends of all cables shall be sealed by means of proprietary seals and associated glands.
No heat shall be applied to any seal or termination. Cable tails shall be insulated by means of
blank PVC sleeving anchored and sealed into the seal.
7.2.5 Where protection of the cable glands is required or terminations are on display, the glands
shall be enclosed in red coloured shrouds of the appropriate British Standard colour.
7.2.6 All cables to brick/concrete shall be securly fixed by means of copper saddles sheathed with
red PVC. These saddles shall be provided near bends and on straight runs at intervals no
greater than recommended in the British Standards or by the manufacturer.
7.2.7 Where multiple cables are to be attached to a wall or soffit, copper saddles shall enclose all
cables and shall be secured by means of suitable masonry plugs and two round head plated
woodscrews
7.2.8 Where multiple cables are to be attached to the top of horizontal trays they shall be neatly run
and securely fixed at suitable intervals. Copper or plastic cable fixings shall be used.
7.2.9 At detector and sounder locations, cables shall be terminated in approved black
enamelled/galvanised BESA or MI Clamp type junction boxes. All other devices forming part
of the system shall utilise dedicated /custom back boxes.
7.3.2 All detectors shall be installed in the exact locations specified in the design drawings; thus
providing the best possible protection.
7.3.3 The type of detector installed in each particular location shall be the type specified in the
design drawings.
7.3.4 All detector bases shall be securely fixed to BESA boxes and allow for easy fitting and
removal of detectors.
7.3.5 Cable and wire entries to detector bases shall be fitted with grommets to prevent possible
damage to the insulation.
7.3.6 Cable and wire strain relief clamps shall be provided at all entries to detector bases.
7.3.7 Cable entries of detector bases used in environments with abnormal atmospheric or operating
conditions shall be appropriately sealed to prevent ingress of dust, water, moisture or other
such contaminants.
7.4.2 All control devices and associated modules shall be installed in the exact locations specified in
the design drawings.
7.4.3 The type of control device installed in each particular location shall be the type specified in the
design drawings.
7.4.4 All control devices and associated modules shall be securely fixed, and if required, marked
with appropriate notices, warnings, signs as applicable.
7.4.5 Cable and wire enteries to all control devices and associated modules shall be fitted with
grommets or glands so as to prevent possible damage to the insulation.
7.4.6 Cable and wire strain relief clamps shall be provided at entries to control devices and
associated modules as required.
7.4.7 Cable entries of control devices and associated modules used in environments with abnormal
atmospheric or operating conditions shall be appropriately sealed to prevent ingress of dust,
water, moisture or other such contaminants.
7.5.2 The fire controller and its associated component parts shall be installed in the location
specified in the design drawings.
7.5.3 The type of fire controller and its associated component parts installed shall be the type
specified in the design drawings.
7.5.4 The fire controller equipment shall be securely fixed, and if required, marked with appropriate
notices, warnings, signs as applicable.
7.5.5 Cable and wire entries to the fire controller and associated devices shall be fitted with
grommets or glands to prevent possible damage to the insulation.
7.5.6 Cable and wire strain relief clamps shall be provided at entries to fire controller and associated
devices as required.
7.5.7 The fire alarm system mains power connections to the fire controller equipment shall be
accordance with the guidelines set out in the relevant British Standards and the installation
instructions provided by the manufacturer.
7.5.8 The fire alarm system mains power isolating switch shall be coloured red and clearly labelled
FIRE ALARM: DO NOT SWITCH OFF.
7.5.9 Each circuit of the system shall be connected to the fire controller via associated fuse or circuit
breaker devices located within the fire controller unit.
7.5.10 All cables from the fire controller equipment to the detection and alarm devices shall be clearly
labelled as part of the fire detection and alarm system.
8 COMMISSIONING
8.1 General
8.1.1 Both the installation (see Section 7) and the commissioning activities shall be undertaken as a
single continuous operation.
8.1.2 Upon completion of the installation activity, the Fire Alarm contractor shall Test, Start-up,
Commission and Handover the system to the customer.
8.1.3 The Fire Alarm contractor shall make use of the following documents to record test results
and details of commissioning tests:
8.1.4 In addition, Point Description Sheets which are used to configure the text descriptions
displayed at the controller must be returned to the Fire Alarm contractor 21 days prior to the
date agreed for commencement of commissioning. Copies of Point Description Sheets are
provided to the customer upon receipt of the order for the fire system.
1. Detectors
2. Call Points
3. Sounders
4. Ancillary Devices
5. Fire Controller Equipment and Associated Devices
6. Auxiliary Equipment (e.g. Plant Interface Module, etc.)
7. Operating and Control Software.
8.2.2 The fire controller and associated devices and modules shall be tested in accordance with the
guidelines set out in BS 5839: Pt 1: 1988 and the testing instructions provider by the
manufacturer.
8.2.3 The Fire Alarm contractor shall start up and operate the system for a trial period to ensure that
it operates correctly.
8.2.4 The Fire Alarm contractor shall test all functions of the system, including the software, to
ensure that it operates in accordance with the requirements of the design specification and
relevant standards.
8.2.5 The Fire Alarm contractor shall undertake audibility tests during which the sounders may be
operated continuously over a period of two hours. (Should the customer require these tests to
be carried out at a separate visit, or out of normal working hours, this can be arranged at
additional cost.)
8.3 Commissioning
8.3.1 Commissioning of the system shall constitute practical completion
8.3.2 Following the satisfactory completion of installation, testing and start up, the Fire Alarm
contractor shall demonstrate to the customer that the system successfully performs all of the
functions set out in the design specification.
8.3.3 The Fire Alarm contractor shall provide the customer with an agreed quantity of spare parts
testing equipment and consumerables which are to be used during routine maintenance and
testing of the system.
8.3.4 The Fire Alarm contractor shall provide a customer appointed fire system supervisor with on-
site training in the use, operation and maintenance of the system and explain the procedures
to be followed in the event of fire and false alarms. The system supervisor shall also be
shown how to carry out routine maintenance and testing procedures, and how to keep the Log
Book. (also see Section 9).
8.3.5 The Fire Alarm contractor shall prepare a report detailing all tests performed during installation
and commissioning of the system. The report shall include the results of the tests and details
of any specific settings or adjustments made. Any outstanding tasks or activities which are to
be completed at another time shall also be included in the report.
8.3.6 The Fire Alarm contractor shall present an Acceptance Certificate for signature by the
customer.
8.4 Handover
8.4.1 The Fire Alarm contractor, upon completion of the commissioning activity, shall hand over the
system to the customer.
8.4.2 At the time of hand over, the Fire Alarm contractor shall provide the customer with the
following documentation:
9 TRAINING
9.1 General
9.1.1 The Fire Alarm contractor shall provide the customer with details of the training required by
personnel to operate and maintain the fire detection and alarm system.
9.1.2 The Fire Alarm contractor shall provide two levels of training:
9.1.3 The Fire Alarm contractor and the customer shall jointly agree the number of staff to attend
the training courses.
9.2.2 System supervisor training shall be given by an experienced and competent engineer familiar
with the fire system being installed.
9.2.2 The scope of training provided shall depend on the type, size and complexity of the system.
9.2.3 The Fire Alarm contractor shall initially provide technical training in all aspects of the system.
The trainee shall then be given full instructions in the use, operation and maintenance of the
system. This shall include instruction in the procedures to be followed in the event of fire and
false alarms, routine maintenance and testing procedures, and how to keep the Log Book.
9.3.2 The training sessions shall be given by an experienced and competent engineer familiar with
the fire system installed.
9.3.3 The scope of training provided shall include full operating instructions in the use of the fire
system. This shall include instruction in the procedures to be followed in the event of fire and
false alarms.
10.1 General
10.1.1 According to the recommendations in BS 5839: Pt 1: 1988 (clause 29), fire systems should be
regularly maintained under a maintenance agreement.
10.1.2 Fire and planning authorities, and in certain cases insurers, have powers to check that fire
systems are maintained. Failure to maintain the fire detection and alarm system could
contribute to death or injury in the event of fire.
10.1.3 The customer shall be responsible for ensuring that daily, weekly and monthly routine
maintenance is carried out in accordance with the recommendations set out in BS 5839: Pt 1:
1988 and the service and maintenance instructions provided by the Fire Alarm contractor or
manufacturer.
10.1.4 The Fire Alarm contractor shall provide detailed information about the maintenance services
which can be provided after hand over of the system.
10.1.5 If requested, the Fire Alarm contractor shall prepare and submit a draft maintenance contract
for consideration by the customer.
10.1.6 The draft contract shall include complete details of all materials and labour required to
maintain the system in correct working order. It shall also include details of the testing
procedures which will be carried out and specify the proposed number of visits per year.
10.2.2 Although the quantity of each item required is dependent upon the type and size of installation,
the system spares which should be considered for inclusion in the list are as follows:
Heat Detectors
Smoke Detectors
Flame Detectors
Call Points
Sounders
Beacons
Door Retention Units
Fuses
Circuit Breakers
10.2.3 The draft maintenance contract shall also include details of the system spares which are be
kept on-site for maintenance of the system.
10.2.4 The Fire Alarm contractor shall guarantee the availability of all system spares for a period of
not less than ten years.
10.3 System Test Equipment
10.3.1 The Fire Alarm contractor shall provide a detailed list of the system test equipment and
consumerables required on-site to maintain the system in perfect working order.
10.3.2 As the quantity of each item required is dependent upon the type and size of installation, the
system test equipment and consumables which should be considered for inclusion in the list
are as follows:
10.3.3 The draft maintenance contract shall also include details of the system test equipment and
consumerables which are be kept on-site for routine maintenance and testing of the system.
10.3.4 The Fire Alarm contractor shall guarantee the availability of all system test equipment and
consumables for a period of not less than ten years.