TVSS Asco Power Serie 400

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

400 SERIES

Model 420 (SPDEE Series)


Data Sheet

Features:
• UL 1449 Fourth Edition listed
• 50kA 8 x 20µs
• Type 1: UL 1449 4th Edition, CSA 22.2 No. 269.1
• 200kA SCCR (most models)
• Complies with UL 96A 12th Edition master label requirements for
lightning protection systems
• Voltage specific design
• Tri-Mount installation for more mounting flexibility:
– Same unit mounts on pipe nipple, bracket or DIN-Rail
• Visual diagnostics: easy to see; easy to understand
• 10-year limited warranty

Performance Specifications Green=Go Visual Diagnostic Monitoring


50kA 8 x 20µs per mode/per phase Green LED visible = okay, Green LED extinguished = replace
UL 1449 tested Inominal: 20kA (highest UL rating available) LED visible from multiple sides and angles - better viewing
UL 1449 tested SCCR: 200kA Every MOV is Monitored as opposed to ‘power is present’
Individually fused & thermally protected MOVs
Repetitive impulse: 5000 - 3kA - 8 x 20µs; 1000 - 10kA - 8 x 20µs Tri-Mount Installation

Physical Specifications
Relative humidity range: 0 - 95% non-condensing
Operating frequency: 47 - 63 Hz
Typical operating temperature: -25° C (-13° F) to +60° C (140° F)
Storage temperature Std. 0.75 in. - 14 DIN-Rail Mount Bracket Mount
Response time: < 1 nanosecond Nipple (rail not incl.) for flat surfaces
Solid state bi-directional operation
NEMA 4X polycarbonate enclosure — UL 746C(f1), UL 94-5VA
Quality, Standards and Validation
10-year limited warranty
Pre-wired with 3 feet (0.91 meter) of #10 AWG conductor
UL 1449 4th Edition file: VZCA.E321351 at www.UL.com, cUL
Typical connection: #10 AWG to 30A breaker
Type 1: UL 1449 Fourth Edition, CSA 22.2 No. 269.1
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, C62.45-2002,
Dimensions (in. / mm) C62.62-2010 and C62.72-2016
IEC 61643, CE
Complies with UL 96A 12th Edition master label requirements for lightning
protection systems
Operational test performed before shipment
ISO 9001:2008 Certified quality management system
ISO 17025:2005 Certified test lab
RoHS-compliant

(L-BRACKET IS INCLUDED)

Weight:1.60 lbs (0.73 kg)


Sized for std 35mm Din-Rail
Model 420 Catalog Numbers

System Configuration

}v }v
Phase A (BLK) BLKPhase A (BLK) BLK
BLK BLK BLK
1 POLE/ SINGLE

Neutral (WHT) Neutral (WHT)


WHT WHT
WHT WHT W
Ground (GRN) Ground (GRN) GRN GRN G
UL 1449 Fourth Edition Test Data
Voltage Catalog Number L-N L-L N-G L-G In SCCR MCOV
120V 420120NP05NWSJ10 700 - 600 1200 20kA 200kA 150
220V 420220NP05NWSJ10 1200 - 1000 1800 20kA 200kA 320
240V 420240NP05NWSJ10 1200 - 1000 1800 20kA 200kA 320
277V 420277NP05NWSJ10 1200 - 1000 1800 20kA 200kA 320

}v } v Phase A (BLK)
Phase A (BLK) BLK BLK BLK BLK BLK

}v Neutral (WHT) } v WHT


Neutral (WHT) WHT WHT
WHT WHT WH T
2 POLE

BLK BLK
BLK BLBLK
K BL
Phase C (BLK) Phase C (BLK)
Ground (GRN) Ground (GRN) GRN GGRN
RN G

L-N L-L N-G L-G In SCCR MCOV


120/240V 420120SP05NWSJ10 700 1200 600 1200 20kA 200kA 150
277/480V or 240/480V 420277SP05NWSJ10 1200 2000 1000 1800 20kA 200kA 320
Phase A (BLK) Phase A (BLK) BLK BLK
BLK BLK BLK
A B Phase
A B (BLK) B Phase B (BLK)
BLK BLK BLK BLK BLK

N Neutral (WHT)
N Neutral (WHT) WHT WHT WHT
WHT WHT
v v
Hot (BLK) BLK Hot (BLK) BLKBLK BLK BLK
WYE

C C
Ground (GRN) Ground (GRN) GRN GRN GR
L-N L-L N-G L-G In SCCR MCOV
208Y/120V 420120YP05NWSJ10 700 1200 600 1200 20kA 200kA 150
380Y/220V 420220YP05NWSJ10 1200 2000 1000 1800 20kA 200kA 320
480Y/277V 420277YP05NWSJ10 1200 2000 1000 1800 20kA 200kA 320
600Y/347V 420347YP05NWSJ10 1500 2500 1200 2500 20kA 200kA 420

Phase A (BLK) BLK


Phase A (BLK) BLK BLK BLK BL

Phase B (ORNG) Phase B (ORNG)


v v
ORNG ORNG ORNG ORNG ORN
HI-LEG

Phase C (BLK) Phase C (BLK)


BLK BLK BLK BLK BL
Neutral (WHT) Neutral
WHT(WHT) WHT WHT WHT W
Ground (GRN) Ground (GRN) GRN GRN
L-N L-L N-G L-G In SCCR MCOV
120/240V HI-LEG 420240HP05NWSJ10 700 / 1200 1200 /1500 600 1200 / 1500 20kA 200kA 150/320

K) v vPhase
Phase
A (BLK)
A (BLK) BLK
BLK BLK

K ) Phase
Phase
B (BLK)
B (BLK) BLK
BLK BLK
K ) Phase
Phase
CC(BLK)
(BLK) BLK
BLK BLK
DELTA

N) Ground
Ground
(GRN)
(GRN) GRN
GRN GRN

L-N L-L N-G L-G In SCCR MCOV


240V 420240DP05AWSJ10 - 1500 - 1200 20kA 200kA 320
480V 420480DP05AWSJ10 - 3000 - 1800 20kA 200kA 552
600V 420600DP05AWSJ10 - 2500 - 2500 20kA 200kA 690

Schneider Electric schneider-electric.us/surge


se.com/us/en/work/support/customer-care/ | 1-877-342-5173
© Copyright March 2021. Publication DS-70117 RevW