EasyPact MVS - MVS08N3NF2L

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product data sheet MVS08N3NF2L

Characteristics EP MVS CB 800A 50kA 3P EF 240VAC ET2 fixed


electrical circuit breaker

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product EasyPact MVS
Range EasyPact
Product name MVS08N
Device short name MVS08N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
Network type AC
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET2I
Trip unit technology Electronic
Trip unit rating 800 A

Complementary
Network frequency 50/60 Hz
Control type Electrically operated
Mounting mode Fixed
Mounting support Base plate
Rail
Connection position Vertical
Horizontal
Location of connection Rear
[In] rated current 800 A at 40 °C
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2

Aug 13, 2021


1
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 800 A
Breaking capacity 50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
capacity
[Icw] rated short-time withstand current 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
Protection type Overload protection (long time)
Instantaneous short-circuit protection
Fault indication Internal fault
Overload
Short-circuit
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4...1 x In
Long time delay adjustment type Adjustable 9 settings
[Tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Thermal memory 20 minutes before and after tripping
Instantaneous pick-up adjustment type Adjustable 9 settings
Ii
Instantaneous pick-up adjustment 1.5...10 x Ir
range
Zone selective interlocking ZSI With
Current sensor rating range 400/2000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 352 mm
Width 422 mm
Depth 297 mm
Net weight 40 kg

Environment
Standards IEC 60947-2
Product certifications GOST
IEC
CCC
CCS
IP degree of protection IP40
Pollution degree 4 conforming to IEC 60664-1
Ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit

Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 38 kg

2
Package 1 Height 42 cm
Package 1 width 35 cm
Package 1 Length 50 cm

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
PVC free Yes

Contractual warranty
Warranty 18 months

You might also like