EasyPact CVS - LV510331

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Product data sheet LV510331

Characteristics circuit breaker EasyPact CVS100F, 36 kA at 415


VAC, 25 A rating thermal magnetic TM-D trip unit,
3P 3d

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Easypact CVS100...250
Product or component type Circuit breaker
Device short name CVS100F
Device application Distribution
Poles description 3P
Protected poles description 3d
Earth leakage protection (Vigi add on) Without
[In] rated current 100 A at 40 °C
Breaking capacity code F
Network type AC
[Icu] Breaking capacity 36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Utilisation category Category A
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 25 A at 40 °C
Protection type Short-circuit protection (magnetic)
Overload protection (thermal)

Complementary
Network frequency 50/60 Hz
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front

Mar 5, 2021
1
Downside connection Front
Connections - terminals Screw connection
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
Thermal protection adjustment range 17.5…25 A
[Ics] rated service breaking capacity 18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 30000 cycles
Electrical durability 12000 cycles 415 V In conforming to IEC 60947-2
Connection pitch 35 mm
Contact position indicator Yes
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
Instantaneous pick-up adjustment type Fixed
Ii
Instantaneous pick-up adjustment 300 A
range
Height 161 mm
Width 105 mm
Depth 86 mm
Net weight 1.8 kg

Environment
Electrical shock protection class Class II
Standards EN 60947-2
IEC 60947-2
Product certifications IEC
GOST
IP degree of protection IP40
Pollution degree 3 conforming to IEC 60664-1
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C

Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 1.71 kg
Package 1 Height 11.5 cm
Package 1 width 14 cm
Package 1 Length 19.5 cm

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information

2
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

Contractual warranty
Warranty 18 months

3
Product data sheet LV510331
Dimensions Drawings

4
Product data sheet LV510331
Assembly

5
Product data sheet LV510331
Performance Curves

You might also like