Be 46 / Be23A OEM's Manual: Warranty
Be 46 / Be23A OEM's Manual: Warranty
Be 46 / Be23A OEM's Manual: Warranty
XX April 2006 1
Warranty
Bernini Design SRL (hereinafter "BD") warrants that Be46 shall be free from defect in material or
workmanship for a period of 3 years from the BD delivery date. BD shall, at its option, repair or replace the
product without charge. BD shall return the Be46 to the buyer with the Default parameters at no extra charge.
The buyer shall furnish sufficient information on any alleged defects in the product so as to enable BD to
determine their cause and existence. If the Be46 is not defective, or the product is defective for reason other
than covered by this warranty, the buyer will be charged accordingly. This warranty shall not apply if the Be46
has not been used in accordance with the User Manual and other operating instruction, particularly if any
defects are caused by misuse, improper repair attempts, negligence in use or handling.
This purchase is non-refundable.
WARNING!! High voltage is present inside the Be46. To avoid electric-shock hazard, operating
personnel must not remove the protective cover. Do not disconnect the grounding connection. The
Be46 can start the engine at anytime. Do not work on equipment, which is controlled by the Be46.
When servicing the engine, disconnect the battery and battery charger. We recommend that warning
signs be placed on equipment indicating the above.
Index:
WARNING:
This unit is not user serviceable and should be returned to Bernini-Design Company for
service and repair. Any alterations to the internal circuits will invalidate the warranty.
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 5
a) - Initial condition: no terminals are connected and the engine is not running.
b) - Connect the supply plug (#33=plus to 12V battery system, #35 if a 24V battery system
is used, and #34 = minus) to the battery of the engine. The allowed voltage range to operate
the Be46 is from 6 Vdc to 36 Vdc. The battery minus must be grounded only at the side of
the engine. It is dangerous to ground the minus wire of the Be46 supply in multiple sites:
different ground potentials may destroy the Be46 unit. As soon as power is supplied, the
Be46 performs an internal test and turns on all LEDs and displays for 3 seconds.
The version of the internal software (for example [2.0.08]) appears temporarily on the
display. The message [12 =] or [24 =] indicates the size of the connected battery.
Any failure during the cycle will produce a permanent ‘[Err]’ message on the display (section
6.16). If no errors are detected, one decimal point will ultimately be displayed in the Least
Significant Digit (*Note).
c)- Operate the pushbuttons on the front panel to read the parameters and check the
settings (see Section 5.02). Program the parameter [M_o.t.] according to the specification
of the engine manufacturer (see section 5.02D)
* NOTE: according to the setting of the parameter [OPt.2], the Be46 can enter directly into 'MANUAL' or AUTO
operating mode (see section 5.02F parameter [OPt.2]).
A) - Unplug the supply connector in order to turn off the Be46 unit.
B) - Before connecting the input terminals #17 to #23, make sure that all contact switches
are in the normal operational mode. Oil pressure input must be connected to a ‘closed
contact’ switch, and the rest of the terminals must be wired to a contact that matches the
programmed action (normally open/closed , section 5.02F)
C) - Test each output load before connecting the wires. As soon as you are sure that the
solenoids and relays are working properly, you may commence connecting terminal #25 to
#32.
CAUTION: The use of a suppression device on each relay is mandatory
D) - Connect the sender terminals #13 to #16 (check the resistance of the sensor with an
OHM-meter). The allowed range is up to 2000 OHM (5.02H).
E) - Connect the 'Alternator Control' terminal #8 to the W.L. and place a proper connection
for 12V (#8 and #9 to W.L./D+) or 24V (#7 and #8 to W.L./D+).
F) - Connect the Current Transformer to the #5 and #6 terminal inputs (the ‘S1’ terminal of
the C.T. must be grounded on C.T. side).
G) - Connect the pick-Up. In case of use of W, connect the RPM- to the plus of the battery.
H)- The last connection has to be the genertator connector plug (#N, #L1, #L2, #L3).
NOTE: Make sure that wire connections to a removable terminal block are securely
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 6
3.01 Be46 Initial Set Up (Be46 begins in 'OFF' operating mode if [OPt.2]=[0] see NOTE1)
- Push [START-ON] push button for at least 2 secs: the 'LAMP TEST' will take place. After
the test, the [AUTO-MAN] green LED will not illuminate indicating the ‘MANUAL’ operating
mode. The display menu will be automatically placed in 'Engine' mode, and displays 4
dashes to indicate a stand-by condition. Now the user can:
- put the Be46 in 'OFF' by means of the [STOP-OFF] pushbutton (section 3.05).
- put the Be46 in 'AUTO' by pushing [AUTO-MAN] pushbutton (see Section 4.02).
- START and STOP the set by using [START-ON] and [STOP-OFF] push buttons (see
sections 2.02, 2.03).
- browse the menus of the display (see Section 5.00).
NOTE1: the parameter [OPt.2] allows you to select the operating mode after the Power on
sequence (see section 5.02F).
The message ‘[Sta]’ is displayed in the 'Engine' menu during the Crank cycle.
The Be46 automatically detects the moment to disconnect the 'STARTER' as explained in
section 7.07.
The yellow LED ‘Engine’ flashes if one source of ‘Engine running’ signal is true. Further
action on the [START-ON] push button will be ignored. If the 'PREHEAT' function is
programmed, the ‘[HEAt]’ message appears on the display during the PREHEAT cycle. The
fuel solenoid is automatically disabled if the engine does not start properly within 20
seconds (e.g. the user has pushed the [START] pushbutton too quickly). In 'MANUAL'
operating mode, the 'UNDER FREQUENCY' and 'UNDER VOLTAGE' alarms are ignored.
the alarm memory is not empty, the red ‘Alarm’ LED flashes slowly, or one of the red LED
alarms energizes.
When the [<] or [>] pushbutton is pressed, the display shows the name of the parameter for
a short time. It then shows the value of the parameter. For example, [bAtt] and then [12.9].
If the [ACK] pushbutton is pressed and held, the name of the parameter is displayed
continuously ([bAtt]).
note [*] The yellow LED, 'Engine', blinks to indicate the ‘Engine Running Status’(see
section 7.07).
note [**] The first position of the display may show, automatically, any of the following
operating messages:
indicated within the square brackets, is the message that appears on the display. The
second symbol indicates the factory default (value programmed in factory).It is possible to
scan all parameters by using the [<] and [>] pushbuttons (see section 16.0 for Front Panel
details). The parameter name may be displayed at any time by pushing the [ACK]
pushbutton. The programming instructions are listed in section 5.06.
[Horn] ..........[20”] 5”- 15’ If you desire an alarm of greater duration than 15 minutes, you
must use the code [ - - ], and manually reset the alarm to end it (output#27).
Press the [ACK] push button to reset the alarm output at anytime.
[t. on] ...........[10”] Engine START DELAY: 1–59 seconds and 1-15 minutes. This timer
delays the start when the ‘A.M.F. input 2’ is activated.
[t.oFF] ..........[10”] Engine STOP DELAY: 1–59 seconds and 1-15 minutes. This timer
delays the stop when the ‘A.M.F. input 2’ returns to stand by.
[CooL]..........[10”] Engine Cooling Down Time: 0-59 seconds and 1-15 minutes. This
delay allows for the cooling down of the Generator-set.
[StoP]...........[10”] Energized to Stop Solenoid: 10-59 seconds and 1-15 minutes. Timer
to control the Stop-solenoid (output #31).
[HEAt]……...[0”] Glow Enable: 0-59 seconds and 1-15 minutes. Timer to control the Pre-
Glow (output #32). The code [0] disables the timer. The Glow output shuts
down before starting the engine. To obtain an output that shuts down when
the engine starts running you have to use the PREGLOW MODE1 (see
section 5.02E)
[t.GEn] .........[10”] Warm up: 0-59 seconds and 1-15 minutes. This timing allows the
warm up of the engine before closing the contactor.
[Ct r].............[500] Current Transformer Size: 10Aac up to 2000A/5A (10Aac step) and
2000 to 9900 (100Aac step).
[Hi I]............[---] Over Current Set Point: [---]= monitoring is disabled,1Aac to 2000 Aac
(step of 10Ac) and 2000Aac to 9900 Aac (step of 100Aac) .
[Lo U] ..........[180] Under Voltage: 61-999Vac ([---] =monitoring disabled).
[Hi U]...........[450] Over Voltage: 60-999Vac.
[PHAS] .........[3 Ph] Phase Selection: 3 phase (N-L1-L2-L3) or single phase (N-L1).
[VAc.r] .........[1] Voltage Reading Factor X1 or X2.
[Hi P] ............[---] kVA Setting: [---]=monitoring disabled and 1KVA to 9900KVA
[LoPr]...........[---] Oil Pressure Warning 0.1-20.0 Bar (the code '[---]' inhibits the display
and the alarm control).
[Hi°C] ...........[---] Temperature Warning 0-199 °C (the code '[---]' inhibits the display.
[M_o.t.] ........[ 0”] Oil pressure and High temperature alarms bypass: 0–59 seconds or 1-
15 minutes. This timing allows the Be46 to ignore the alarms of the engine
during the starting sequence. Set the delay timing accordig to the
specifications of the engine manufacturer (normally 10 seconds).
[out1].....[ ---] ‘Output 1’(#29) control: code [- -] to 15 (see the options available below).
[out2].....[ ---] ‘Output 2’(#30) control: code [- -] to 15 (see the options available below).
It is possible to program one of the following codes for each output. The output will energize
according to the event.
[In 1] [n.o.] ‘Temperature Input1’ switch polarity: normally open (the engine shuts down if
the contact closes) or normally closed [n.c.] (the engine shuts down if the contact opens).
[In 2] [n.o.] ‘A.M.F input 2’ switch polarity: normally open (the engine starts if the contact
closes) or normally closed [n.c.] (the engine starts if the contact opens).
[In 3] [n.o.] ‘External Stop Input 3’switch polarity: normally open (the engine shuts down if
the contact closes) or normally closed [n.c.] (the engine shuts down if the contact opens)
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 12
[In 4] [n.o.] ‘Auxiliary Alarm Input 4’ Switch Action: normally open (the engine shuts down
if the contact closes) or normally closed [n.c.] (the engine shuts down if the contact opens).
If the code [FUEL] is selected, the Be46 monitors the Fuel Level warning and enables the
reading of the Fuel level.
[FUEL] [ - - - ] Low fuel level warning setting: 1% to 25%. The code '[--]' disables the
warning.
[oPt.1] [ 1 ] Options 0 or 1. Option 1: the engine stops after a Cooling Down Time in
case of high temperature (input JB21). Option 0: the engine stops immediately
[oPt.2] [ 0 ] Options 0,1 and 2. After the power on, the Be46 will enter an operating
mode automatically, according to the following codes:
[0] = ‘OFF’ operating mode
[1] = ‘MANUAL’ operating mode
[2] = ‘AUTO’ operating mode
The following options allow you to control the relays on the Be15 board. The default options
disable the relays (factory setting).
[Ao.01] [- - -] Option for relay output 1 of the BE15 board ([- - -] disabled)
-
-[Ao.15] [- - -] Option for relay output 15 of the BE15 board ([- - -] disabled)
To select an option for an output, press [ACK] and [^] or [v] simultaneously. The list of the
programmable output options follows:
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 14
[0] Low Oil Pressure shutdown [25] AUTO operating mode status
[1] High temperature shutdown [26] Engine Running status
[2] BATTERY voltage alarms [27] Oil press./Engine temperature warnings
[3] Fuel level switch shut down [28] Low Oil pressure shutdown
[4] Emergency shut down [29] High temperature shut down
[5] Under Speed shut down [30] Fail to Stop status
[6] Over speed shut down [31] Fuel warnings and shut downs
[7] Under Frequency shut down [32] Emergency shut down or Input-4
[8] Over Frequency shut down [33] Speed /Frequency errors or shut downs
[9] BELT failure shut down [34] Alternator voltage alarm (Lo-V or Hi-V
[10] Under Voltage shut down or Alternator Failure)
[11] Over Voltage shut down [35] Overload shut down (Hi-I or Hi-P)
[12] Over Current shut down [36] FAIL to START shutdown
[13] POWER over the limit [37] BELT failure shut down
[14] FAIL to START shutdown [38] Mains contactor CLOSED (KM=ON)
[15] PICK-UP failure warning [39] Preglow 1 mode
[16] Alternator Failure shutdown [40] Generator KG =ON
[17] Memory Error [41] MANUAL mode
[18] Low Oil Pressure warning [42] OFF mode
[19] High Temperature warning [43] MAINS-FAULT
[20] Oil Sensor failure [44] MAINS-RESTORE
[21] Temperature sensor failure [ - - - ] INHIBIT
[22] FUEL LEVEL switch warning
[23] FUEL LEVEL sensor warning
[24] Auxiliary alarm INPUT 4 shut down
(*NOTE1): if the message [Err] appears on the display, we recommend that you repeat step
(H). If the problem persists, see section 5.08.
engine starts.
- This alarm is monitored in ‘AUTO’ operating mode
- Alarm outputs/programming: #27, #29 and #30/[out1][out2] option [ 10 ]
- ’Alarm’ menu message: [F AL]
(^) Note: this procedure will cancel the calibration constants and the Hour counter. The
Be46 will use the factory setting parameters as indicated in section 5.02.
(!) Note: if the display indicates the message [Err.], retry the procedure. If the message
persists, the Be46 should be returned to BERNINI DESIGN for repair.
11.00 TROUBLE-SHOOTING
WARNING: This unit is not user serviceable and should be returned to Bernini-Design
Company for service and repair. Any alterations to the internal circuits will invalidate
the warranty.
11.02 The Be46 presents all or some LEDs illuminated with very low intensity
-This could happen if the serial interface is properly connected, but the supply plug is not
connected. Verify the connection of the battery minus.
11.04 The reading of the Generator Set Current is not stable, or is incorrect:
-The current transformer (CT) is not grounded.
-Check for external A-meters: they must be connected in series not in parallel.
-Check to see if the size of the CT matches the programmable parameter [Ct r] (section
5.02B).
-The supply voltage is lower than 7 Vdc
11.08 The Engine stops without reason after a few seconds or minutes.
-Check the alarm on front panel or the message on the display.
-Test the voltage of the fuel solenoid output #24.
-Verify the battery voltage.
11.10 The Be46 does not enter the ‘AUTO’ operating mode.
Check to see if there is an alarm or a message on the front panel (red LED’s). The
procedure is to clear the alarm by means of [ACK] and ‘OFF’ push buttons.
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 23
(*) If in doubt, we recommend that you use the factory calibrations. Press the [^] and [v]
pushbuttons simultaneously for 2 seconds: the display blinks once in order to confirm the
use of the default calibration parameters.
Female Plug
RX INPUT 2 7
37 D-SUB MALE RTS OUT 4
25 CONTACTS
36
38 TX OUT 3 2
RX INPUT 3
37 MODEM
40 GND 7 3
TX OUT 2
38
D-SUB FEMALE 4 20
25 CONTACTS DTR OUT
39
RX INPUT 2 D-SUB MALE 5 7
37 GND
40
9 CONTACTS D-SUB MALE
TX OUT 3 6 6
38 DSR INPUT 25 CONTACTS
41
40 GND 5
7 2 3 ..... Indicates 9-poles
female plug (D-SUB)
D-SUB FEMALE
9 CONTACTS
96mm
Alarm
EXTERNAL STOP 3
#26 STARTER
TEMPERATURE 1
Program
REMOTE START
OIL PRESSURE
Power
TEMPERATURE
OIL PRESSURE
AMF INPUT 2
FUEL LEVEL
96mm
Engine
SENDER
SENDER
#29 PROG.OUTPUT 1
#30 PROG.OUTPUT 2
No Connection
94mm
N.C
24V
13 14 1516 17 18 19 20 2122 23 24 25 26 27 28 29 30 3132 12V
41 DSR INPUT
RS232C COMPUTER 40 GND
INTERFACE 39 DTR OUT REAR VIEW
(OPTION FOR RS485)
38
JL
TX OUT Recommended Panel Cut-out :
37 RX INPUT 91mm(+/-0.5)x91mm(+/-0.5)
36 COMPUTER
RTS OUT
INTERFACE
Generator Voltage Input RS232C 119mm
CT Input Miscellaneous Input
JC JD JG 74mm 45mm
5 6 7 8 9 10 11 12
N L1 L2 L3 MAGNETIC
PICK-UP
(up 15 KHz)
D+ - 24V
D+ - 12V
wires outlet
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 27
ALARM MENU
POWER (Red)
ENGINE Menu (Yellow)
Menu PROGRAM
(Yellow) Menu (Yellow)
BATTERY V/A/Hz/h
Alarm (Red) Alarm Menu
Program (Yellow)
OIL Power
Pressure V/A/Hz/h
Alarm (Red) Engine
TEMPER.
Alarm (Red)
EMERGENCY
Alarm (Red)
FUEL LEVEL
Alarm (Red)
OVERSPEED
Alarm (Red)
UP
Push Button
Alarm DOWN
Program Push Button
Power
V/A/Hz/h
Engine
Green LED
‘Auto’
Operating
Mode
ACK
Push Button
AUTO-MAN STOP-OFF
Push Button Push Button
START-ON
Push Button
Be23A/Be46 OEM’s MANUAL 2.X.XX April 2006 28
1) The Be23A and BE46 have the same software described in this user manual. The
Be23A has the same front panel as the previous BE23 model. The Be46 features a new
design on the front panel (full black colors)