Power Line Carrier Communication (PLCC) : Content
Power Line Carrier Communication (PLCC) : Content
Power Line Carrier Communication (PLCC) : Content
Asif Eqbal
Power Line Carrier Communication - PLCC (photo: Z anith T ransf ormers & Swithgears Pvt. Ltd)
Content
Advantages of Digital PLCC over Analog ones
Typical signal to noise ratio calculation by considering a line of 295 kilometers
SNR (Signal-to-Noise Ratio) Calculation
Introduction
Use of PLCC in modern electrical power system is mainly for telemetry and telecontrol. Tele
means remote. Telemetry refers to science of measurement from remote location.
Different types of data transmission system can be used depending upon the network
requirement and conditions.
For
large power system power line carrier communication is used for data transmission as well as
protection of transmission lines. Carrier current has a frequency range of 30 to 200 kHz in USA
and 80 to 500 kHz in UK.
Each end of transmission line is provided with identical PLCC equipment consisting of
equipment:
Distance protection relay in relay panel at one end of the transmission line gets the input from
CT and CVT in line. The output of relay goes to modem of PLCC.
The output of PLCC goes to coupling
capacitor and then to transmission line
and travels to another end where it is
received through coupling capacitor
and inputted to relay and control panel
at that end.
Go to Content ↑
PLCC scheme
PLCC in modern electrical power system substation is mainly used for following purpose:
Inter trip command can be issued by relay due to tripping of circuit breaker at any one end.
To trip the line circuit breaker nearest to the fault, this is done by:
a) Distance protection relay (V/I characteristics)
b) Differential comparison method
c) Phase comparison method
Simplex
Duplex
Multiplex
Time division Multiplex
Many factors will affect the reliability of a power line carrier (PLC) channel.
The goal is to get a signal level to the remote terminal that is above the sensitivity of the
receiver, and with a signal-to-noise ratio (SNR) well above the minimum, so that the receiver
can make a correct decision based on the information transmitted.
If both of these requirements are met then the PLC channel will be reliable.
The factors affecting reliability are:
The above list may not be all inclusive, but these are the major factors involved in the success
or failure of a PLC channel.
Go to Content ↑
1. Coupling Capacitor
Coupling capacitor
connects the carrier
equipment to the
transmission line. The
coupling capacitor’s
capacitance is of
such a value that it
offers low impedance
to carrier frequency
(1/ωC) but high
impedance to power
frequency (50 Hz). PLCC component - Coupling Capacitor
To decrease the impedance further and make the circuit purely resistive so that there is no
reactive power in the circuit, low impedance is connected in series with coupling capacitor to
form resonance at carrier frequency.
Go to Content ↑
The carrier energy on the transmission line must be directed toward the remote line terminal
and not toward the station bus and it must be isolated from bus impedance variations. This
task is performed by the line trap.
The line trap is usually a form of a parallel resonant circuit which is tuned to the carrier energy
frequency.
A parallel resonant circuit has high impedance at its tuned frequency, and it then causes most
of the carrier energy to flow toward the remote line terminal. The coil of the line trap provides a
low impedance path for the flow of the power frequency energy.
Since the power flow is rather large at times, the coil used in a line trap must be large in terms
of physical size.
Hence a line trap unit/Wave trap is inserted between busbar and connection of coupling
capacitor to the line. It is a parallel tuned circuit comprising of inductance (L) and capacitance
(C). It has low impedance (less than 0.1?) for power frequency (50 Hz) and high impedance to
carrier frequency.
This unit prevents the high frequency carrier signal from entering the neighboring line.
Go to Content ↑
The carrier transmitters and receivers are usually mounted in a rack or cabinet in the control
house, and the line tuner is out in the switchyard.
This then means there is a large distance between the equipment and the tuner, and the
connection between the two is made using a coaxial cable.
The coaxial cable provides
shielding so that noise
cannot get into the cable
and cause interference. The
coaxial cable is connected to
the line tuner which must be
mounted at the base of the
coupling capacitor.
Go to Content ↑
The purpose of the hybrid circuits is to enable the connection of two or more transmitters
together on one coaxial cable without causing intermodulation distortion due to the signal from
one transmitter affecting the output stages of the other transmitter. Hybrids may also be
required between transmitters and receivers, depending on the application.
The hybrid circuits can, of course, cause large losses in the carrier path and must be used
appropriately. High/low-pass and band-pass networks may also be used, in some applications,
to isolate carrier equipment from each other.
5. Line Tuners
The purpose of the line tuner in conjunction with the coupling capacitor is to provide low
impedance path for the carrier energy to the transmission line and a high impedance path to
the power frequency energy.
The line tuner/coupling capacitor combination provides a low impedance path to the power line
by forming a series resonant circuit tuned to the carrier frequency.
On the other hand, the capacitance of the coupling capacitor is high impedance to the power
frequency energy. Even though the coupling capacitor has high impedance at power
frequencies, there must be a path to ground in order that the capacitor may do its job. This
function is provided by the drain coil, which is in the base of the coupling capacitor. The drain
coil is designed to be low impedance at the power frequency and because of its inductance it
will have high impedance to the carrier frequency.
Thus the combination of the line tuner, coupling capacitor, and the drain coil provide the
necessary tools for coupling the carrier energy to the transmission line and blocking the power
frequency energy. One last function of the line tuner is to provide matching of impedance
between the carrier coaxial cable, usually 50 to 75 ohms, and the power line which will have an
impedance of 150 to 500 ohms.
Go to Content ↑
Oscillator can be crystal oscillator with which operation for a particular bandwidth can be
achieved. The output voltage of a oscillator is held constant by voltage stabilizer.
The output of oscillator is fed to amplifier so that loses in transmission can be compensated.
Losses occurring in carrier current is termed as attenuation of carrier signal.
They are mainly: Losses in coupling equipment which are constant losses for a given carrier
frequency bandwidth.
Frequency spacing is a
process using different
carrier frequency in
two adjacent PLCC component - Master oscillator and amplif iers
transmission lines.
Wave trap/Line trap
help in accomplishing this.
Go to Content ↑
Over voltage can be caused due to lightning, switching and sudden loss of load etc.
They produce stress on coupling equipment and line trap units. Non linier resistor in series
with protective gap is connected across the line trap unit and inductor of coupling unit.
Top
Power Line Carrier (PLC) Signal propagation along high voltage lines depends entirely on the
construction of transmission lines, mainly on the configuration and characteristics of all
conductors and on the ground resistance optimum coupling allows to make the best use of a
given transmission line.
Transposition may introduce additional attenuation which can generally not be predicted with
simple rules. Most transposition schemes result in high attenuation poles at certain frequencies
such frequencies cannot be used for PLC communications.
In critical cases, however, computer calculation may be necessary, for which the following
data is required:
Go to Content ↑
Where:
a1 = 0.029 dB/Km
Coupling Loss = Loss in Coupling equipment + tapping loss + paralleling loss + by pass
losses in case of bypasses + cable loss.
Go to Content ↑
Signal level (speech) = +35 dB & 38 dB (Corresponding to 20 Watt (43 dBm PEP) and 40 watts
respectively)
Signal to noise ratio = (Signal level (speech) at receiver side on line side – Noise level in speech
band)
= +10.35 -(-15.5 dB) = 25.85 dB (considering PLC terminal power output as 20 watts)
= 28.85 dB (considering PLC terminal power output as 40 watts which is recommended for
better SNR).
Go to Content ↑