SRDK Series
SRDK Series
SRDK Series
The AMI magnet (6T) in Osujilab is cryo-cooled by continuous Helium supply by a Sumitomo Compressor
operating at a pressure of ~2.2 MPa. The superconductor in the magnet is cryo-cooled by a cold-head
(Sumitomo Inc.) attached to the magnet. Continuous Helium supply is necessary to maintain the
superconductivity in the system. There are two flux lines (supply and return), 6m long connecting the
He-compressor and the cold-head. The flux lines, cold-head and the compressor have self-locks to
isolate them to avoid contamination. When flux lines are disassembled from the cold-head or He-
compressor the locks will automatically be locked. When the pressure in the He-compressor goes below
1.6 MPa, the compressor should be re-filled with Helium (UHP-300, 99.999% purity). Please follow the
instructions before start refilling the He-compressor. If the He-compressor or flux lines are
contaminated, the pressure reading in the He-compressor will drop (usually it will be zero), also when
the He-gas leaks out of the system. Once the system is contaminated, it is advised to get in touch with
Sumitomo Inc. to do a cleaning service.
Figure1: (a) Zero pressure reading due to contamination of the system. In this case the He-gas was escaped through
accidently loosened screws (b). During operation the pressure reading is about 2-2.2 MPa. However, when the He-
compressor or is switched off, the pressure reading is non-zero (~1.6MPa). If the compressor pressure reads zero, it
would not re-start.
Chilled-water supply is connected to the He-compressor to dissipate the heat from the return supply.
When the temperature of the chilled-water supply rises, the He-compressor might shuts down
automatically, and subsequently the magnet temperature will rise. Sometimes, the main power-supply
switch at the back panel will turn off by itself. Then it has to be turned back on as shown in Figure 2.
Most often, switching OFF the drive switch and turning back ON will resume the He-compressor.
Figure2: (a) The main power switch is at the back-panel of the compressor is turned off. To turn it on, rotate the
black switch by 90 deg (ref Figure 6). (b) Front panel switch and the operating hours of the He-compressor.
40088.7h are elapsed as shown in the front panel reading. The maximum operating hours of the instrument
without maintenance is 30,000h. After that the regular service of the He-compressor is recommended-especially
adsorber has to be replaced.
There are two ways to do service on He-compressor and cold-head servicing if the Cold-head or the He-compressor
is contaminated or needs a service. If the compressor/cold-head parts are performing well and only if the parts are
exposed to air, Sumitomo can do an onsite service. Also they can do the adsorber replacement. However if the
motor capsule needs a replacement, then most likely the instrument has to go to the Sumitomo Chicago facility for
service (but check with Roy Roub if they can replace the capsule also by an onsite service). Sumitomo can send a
reconditioned and qualified end/displacer assembly upon request (contact Roy Roub for pricing). Prior
to reconnecting flux lines and the He-compressor, make sure those parts are clean and not
contaminated and also filled with Helium gas (99.999% purity). Please check the price quote prior to
sending the parts to Sumitomo and making an onsite service (onsite service is pricy but faster).
Note: If the cold head or flux line is contaminated (or exposed to air) as judged by the pressure
reading at the He-compressor, the compressor should not be switched on. Contact Roy Roub at
Sumitomo Inc. to proceed further with the repair/service. The cold-head can be removed from the
magnet and can be send out for repair (special care should be taken to release the excess He-gas
residing inside the cold-head prior to unscrewing the 4 screws as shown in the Figure3, for that
appropriate fittings should be used-contact Roy Roub to buy the fittings and couplings.
Figure3: (a) In order to pull the cold head unit out of the magnet, 4 hex screws (OUTER ONES)
should be removed as shown in the cartoon. The cold-head should be taken out very slowly (b). Before
disassembling the cold-head, the He-flux lines should be disconnected, and the excess gas should be vent using
appropriate couplings, one by one, first for the supply line and then the return line.
Once the cold-head is carefully removed from the magnet, it has to be kept in a holder/shield provided
by the Sumitomo and keep it safely. The old cold head should be sending back to Sumitomo.
Figure 4: (a) A top view of magnet (helium chamber) after removing the cold head (c) New replacement coldhead,
already cleaned by the Sumitomo. The coldhead can be taken out from the casing by unscrewing the 4 large hex-
screws (same screws are being used to attach to the magnet). When we request exchange of cold head in the
future, we will receive the same fully tested coldhead with attachments from Sumitomo. When it is taken out we
need to purge it with He-gas. Also the inner portion (a) of the magnet also should be purged for some time with
low pressure He-gas before assembling the cold-head to the magnet. (c) The refurbished cold-head sent by
Sumitomo will be filled with He-gas, therefore it has to be vent before start connecting to the magnet (Youngwoo
please confirm this step-I am confused why it was not directly connected, then we did not need to re-purge the gas
again? Confirm it with Roy, may be?).
Figure 5: (a) The magnet chamber was cleaned with Kim wipe (ethanol) and then subsequently purging with He-gas
prior to attaching the cold-head. (b) Disassembling the refurbished cold-head from the casing by unscrewing the 4
hex screws.
After connecting cold-head to the magnet, it has to be purged with He-gas prior to re-connecting the flux lines-
otherwise the flux lines and the He-compressor will be contaminated.
Figure 6: (a) The He-compressor is powered off. (b) The main power is turned back on. For purging the cold head
without connecting the flux-lines, the cold-head drive should be turned on (c): however in the image it is off). Cold-
head drive switch should be turned off after reconnecting the flux lines and the He-compressor in the normal
operational mode.
Figure 7: (a) For purging the cold-head, the gas inlet from helium gas cylinder (not from helium compressor) should
be connected to supply inlet of the cold-head using appropriate fittings (gas connector). Outlet was kept opened
using gas connector. The fuse and the main power switch to the He-compressor should be kept in the ON position
(b).
Figure 8: (a) After making all connections from the He-tank to the supply line and keeping the return open, and
keeping the pressure around 10 Psi (for few min) and then to about 100 Psi as shown in (b), the cold-head has to be
purged. Before starting the automatic purging using the He-compressor, the compressor main power switch and
the drive switch should be kept ON.
After purging the cold-head from the He-cylinder using He-compressor settings for about 20min, the return valve
can be closed. Close the He-tank, and the supply inlet. Now the Cold-head is ready to be connected to the He-flux
lines. First, connect the flux lines to the He-compressor and then to the cold-head. Make sure that the main power
switch and the front panel switch of the compressor are turned off prior to re-connecting the flux lines. Then turn
off the cold-head drive switch. Now the He-compressor is ready to operate. Switch on the front panel power
switch, then the compressor will start operating. Initially the pressure reading will be around 2.6 MPa, but it will
reduce slowly to 2.2 MPa over about 24h of operation.
Serial #
He-compressor service:
● Sumitomo (SHI) Cryogenics of America, Inc. ●1500-C Higgins Road, ● Elk Grove Village, ● IL 60007
PH # 847-290-5801 / Fax# 847-290-1984
Personal Contact: "Skica, Aya" <[email protected]>
The weight of the He-compressor is about 100 pounds and the wooden crate has about 250 Pounds. Therefore we need
to contact Fed Ex-freight service for shipping.
Cold-head service:
3. If the motor capsule, heat exchanger, oil separator, or control board require replacement
there is additional cost.
4. Gasline service: $300 each. Includes gas cleanup, leak check, and replace Aeroquip
fittings.
6. Shipping invoice (empty wooden crates to us and the shipping the instruments back to us)
will be send to us separately. We will use our credit card to pay for the shipping from here
to their Chicago facility.
Tasks:
Technical Manual
Page
DESCRIPTION ....................................................................................................................... 1
SPECIFICATIONS .................................................................................................................. 3
Minimum Bend Radius ...................................................................................................... 3
Pressure and Temperature Ratings................................................................................... 3
Identification Labels........................................................................................................... 3
Installation Tools ............................................................................................................... 4
MAINTENANCE ..................................................................................................................... 5
Disconnect Gas Lines ....................................................................................................... 5
From the Compressor .................................................................................................. 5
From the Cold Head ..................................................................................................... 6
Leak Check ....................................................................................................................... 6
Gas Line Repair ................................................................................................................ 7
Venting .............................................................................................................................. 7
Repair Self-Sealing Couplings ........................................................................................... 8
Replace the Gasket Seal .............................................................................................. 8
Repair or Replace a Coupling....................................................................................... 9
Charge Pressure Verification........................................................................................... 10
Gas Cleanup and Recharging ......................................................................................... 11
PARTS ................................................................................................................................. 13
Ordering .......................................................................................................................... 13
Parts Identification and Numbers..................................................................................... 13
ILLUSTRATIONS
Figure 1 Typical Helically Corrugated Gas Line Construction ......................................... 1
Figure 2 Break Gas Line Connection from Compressor .................................................. 6
Figure 3 Disconnect Gas Line from Compressor ............................................................ 6
Figure 4 Break Gas Line Connection from Cold Head .................................................... 6
Figure 5 Disconnect Gas Line from Cold Head ............................................................... 6
Figure 6 Aeroquip Male Coupling Parts .......................................................................... 8
Figure 7 Remove Coupling from Gas Line ...................................................................... 9
Figure 8 Aeroquip Female Coupling Parts ...................................................................... 9
Figure 9 Parts Identification .......................................................................................... 13
SJM P/N261320A
i
(This page is intentionally blank.)
ii
DESCRIPTION
Gas lines are needed to connect compressors to cold heads (expanders) to complete the
system. Gas lines are constructed from helically corrugated stainless steel tubing covered with
metal braid or from soft copper tubing. All gas lines are equipped with Aeroquip self-sealing
couplings and are furnished cleaned, charged with helium gas and leak checked.
Each cryogenic system includes interconnecting gas lines to carry helium gas refrigerant to and
from the components. A gas line carries high-pressure gas from the compressor to the cold
head and another gas line returns lower pressure gas to the compressor.
Flexible gas lines simplify installation. The self-sealing couplings maintain the gas charge and
purity by minimizing gas loss when connections are being made or broken and by preventing
the entrance of contaminants. Dust plugs protect the coupling threads from damage and also
help to maintain cleanliness.
1
(This page is intentionally blank.)
2
SPECIFICATIONS
Identification Labels
Labels on the gas lines identify their function in the system as follows:
SUPPLY (color coded red) Helium gas supply to the cold head from the
compressor.
RETURN (color coded green) Helium gas return from the cold head to the
compressor.
Separate labels are furnished by SCAI with standard gas lines for the customer to attach to the
gas lines. See the Installation section in the System manual.
3
Specifications
Installation Tools
Properly sized open-end wrenches are needed to install and remove gas lines. SCAI can
furnish (optional) one each:
Wrench, 1" open end x 3/4" open end P/N SK30017C3
Wrench, 1 1/8" open end x 5/8" open end P/N SK30017C2
Wrench, 1 3/16" open end x 1 3/16" ratchet P/N SK30017C1
For MRI systems with an RF shield, gas feedthroughs may be furnished for gas line installation through
the shield. Special wrenches may be required to fit the feedthroughs.
4
MAINTENANCE
AVOID INJURY. Extreme cold can cause frostbite. When handling system
components, be careful not to touch any frosted parts.
AVOID INJURY. Disconnect gas lines only when the compressor is stopped.
Disconnecting the cold head while it is cold can create excessively high internal
pressure as the gas warms. Material failure and uncontrolled pressure release
can cause injury.
AVOID INJURY. Use two wrenches when disconnecting a gas line coupling to
avoid loosening the compressor’s or cold head’s coupling. Gas pressure can
project the coupling with enough force to cause injury.
AVOID GAS LEAKS. Keep the gas line couplings aligned when making or
breaking a coupling connection. Leaks can occur due to the weight of the gas
line or due to a sharp bend near the connection. Crimping from repeated
bending and repositioning can cause damage to gas lines.
5
Maintenance
Leak Check
Leakage of helium gas is the only likely problem to originate on a gas line. Use of a helium
mass spectrometer leak detector is recommended. If no mass spectrometer is available, a
liquid leak detector solution may be used on the coupling joints.
With the gas lines connected to the compressor and to the cold head, leak check the connected
coupling joints.
6
Maintenance
The flat gasket in the face of the male coupling seals the joint. A leak at this gasket seal can be
detected only when a gas line is connected. A leak here can be caused by:
Leaks at welded joints require special skills to repair. Consult an SCAI Service Center.
Leaks at the self-sealing couplings can be repaired by replacing worn or damaged parts.
Vent the gas line before beginning to disassemble it except when replacing a gasket seal.
When couplings are frequently disconnected and reconnected, it is important to wipe the
mating parts (threads and faces) with a clean, lint-free tissue or cloth.
Venting
Tools required: Adapter fitting with valve, 8M Aeroquip, P/N SK8217A2.
Open-end wrenches
NOTE
Adapter fittings are available as optional accessories from SCAI.
1. Disconnect the gas line from the system. Install a dust cap on each of the male couplings of
the compressor and cold head, or on the RF feedthroughs, if used in the system.
2. Be sure the valve on adapter fitting SK8217A2 is closed. If only one coupling on the gas
line is to be repaired, install the adapter fitting on the good coupling. Use two wrenches.
3. Slowly open the valve on the adapter fitting to vent the entire charge of helium gas.
4. Close the adapter fitting’s valve. Do not remove the adapter fitting. It will be used for gas
cleanup and recharging.
NOTE
Gas cleanup and recharging of the gas line are always required if a coupling
has been repaired. Instead of venting the gas line to atmospheric pressure,
some operators prefer to connect an adapter fitting and a charge line to the
coupling not being repaired, to purge the gas line with helium during repair. Set
the helium gas regulator at 35 kPa (5 psig) or less to prevent air from entering
the gas line and contaminating it.
7
Maintenance
Damaged threads, leaking seals or a leaking valve assembly may require replacement of
coupling parts or replacement of the complete coupling half.
From repeated connecting and disconnecting the coupling, the gasket face seal just inside the
face of a male coupling may begin to leak and require replacement. The gasket seal is replaced
while the gas line is disconnected.
1. Carefully pierce or pry the old gasket face seal and pull it from its recessed ring in the body
of the coupling. Discard the face seal. See Figure 6.
2. Using isopropyl alcohol on a clean, cotton swab, carefully remove any remaining adhesive
from the coupling’s recess. Avoid getting alcohol on the face of the poppet.
3. Dry the recessed surface with a clean, lint free cloth.
4. Do not apply any adhesive. Press a new gasket seal into the recessed ring.
8
Maintenance
9
Maintenance
8. Thoroughly degrease or apply Locquic Primer T (a degreasing agent) to the threads of the
adapter and to the internal threads of the coupling body. Do not get Primer T on the O-ring
or any of its seating surfaces.
9. Allow about 5 minutes for the primer to dry. Apply Loctite 242 to one full thread in the
coupling adapter. Use a needle applicator. Start at the second thread from the lead thread
and work toward the hexagon. Shake the Loctite before use.
10. Assemble the coupling body to the adapter. Use two wrenches. Hold the adapter with one
wrench and screw the two parts together. Tighten the size 8 Aeroquip coupling parts to
4.85 – 6.25 kgf m (35 – 45 ft. lbs.).
11. Allow at least a 6-hour curing period before applying gas pressure.
This procedure describes the process for checking and, if necessary, correcting the helium gas
charge pressure in refrigeration system gas lines.
PRESERVE YOUR WARRANTY. Any helium gas used in this procedure should
be of high purity. A purity level 0f 99.999% is required.
PREVENT EQUIPMENT DAMAGE. Keep the gas line couplings aligned when
making or breaking a coupling connection. Leaks can occur due to the weight of
the gas line or due to a sharp bend near the connection. Crimping from repeated
bending and repositioning can cause damage to gas lines.
1. Verify the pressure gauge tool [P/N 268150C2] has a minimum charge pressure of 20 psig.
2. If the charge pressure in the tool is too low, use the charge adapter tool [P/N 255919B2] to
charge the pressure gauge tool to 50 psig. If the pressure gauge tool is completely empty,
purge the pressure gauge tool with helium gas by “flushing through” with the exhaust valve
open. After purging, close the exhaust valve and establish the proper charge pressure in
the pressure gauge tool. Close the exhaust valve. Remove the charge adapter from the
pressure gauge tool.
10
Maintenance
3. Unthread the dust cap from one end of the gas line to be checked. Be sure the valve on the
pressure gauge tool is closed before it is connected. Connect the male Aeroquip end of the
pressure gauge tool to the gas line using two wrenches.
4. Read the pressure.
4.1. If the pressure is low, but > 20 psig, use the charge adapter to add helium gas to the
gas line to reach the specified equalization pressure.
4.2. If pressure in the gas line is <20 psig, perform a clean–up on the gas line.
5. When finished checking or pressurizing the gas line, make sure the gauge tool is charged to
50 psig helium gas for storage.
6. Disconnect the male Aeroquip end of the pressure gauge tool from the gas line using two
wrenches.
7. Screw the dust cap finger tight on to the gas line coupling.
This completes the procedure for checking the charge pressure in a gas line.
NOTE
Adapter fittings are available as optional accessories from SCAI.
2. Connect a charge line to the pressure regulator of a helium gas cylinder containing 99.995%
pure helium gas with a dew point less than -50º C (-58º F) at 2065 kPa (300 psig).
AVOID INJURY. Never use compressed gas from a cylinder without a proper
regulator. Overpressure can cause personal injury if the system equipment
ruptures.
11
Maintenance
3. Open the gas cylinder valve. While connecting the charge line to the valve on one of the
adapter fittings, thoroughly purge the charge line from the regulator. It is important to
remove all air contaminants to prevent them from entering the gas line.
4. Adjust the gas cylinder regulator to 690 kPa (100 psig). Open the valve on the adapter
fitting and charge the gas line to 690 kPa (100 psig).
5. Close the valve on the helium gas cylinder (not on the regulator).
6. Open the vent valve. Watch the regulator’s pressure gauge. When the pressure falls to
35 – 70 kPa (5 – 10 psig), close the vent valve. Open the gas cylinder valve to increase the
pressure to 690 kPa (100 psig). Close the gas cylinder valve.
7. Repeat step 6 five (5) times.
8. Close the valve on the adapter fitting used for charging. Open the gas cylinder valve.
Adjust the pressure regulator to the equalization pressure of the system. Refer to the
Specifications section in the System manual.
9. Open the valve on the adapter fitting and charge the gas line to the equalization pressure.
10. Close the valve on the adapter fitting. Close the gas cylinder valve. Disconnect the charge
line from the adapter fitting. Store the charge line to keep it clean.
11. Remove the adapter fittings.
12
PARTS
Ordering
Order parts by part number and name. See Figure 9.
NOTE
Gas lines used to carry refrigerant gas between the compressor and the cold head
typically are furnished with size 8 Aeroquip couplings.
13
(This page is intentionally blank.)
14
MANUAL NUMBER: CD32ZZ-063I
DATE: December 18 / 2003
OPERATION MANUAL
SRDK Series CRYOCOOLER
TEL: +81-424-68-4240
FAX: +81-424-68-4219
E-mail: [email protected]
URL: http://www.shi.co.jp/cryopage
EC DECLARATION OF CONFORMITY
We, Sumitomo Heavy Industries, ltd., declare The products comply with the following
herewith that the cryocooler listed below, on council directives:
the basis of its design and engineering as ・Machinery 98/37/EC
well as in the embodiment which we have ・Low Voltage 73/23/EEC
placed on the market, comply with the ・EMC 89/336/EEC, 92/31/EEC
applicable safety and health requirements set ・Amendment Directive: 93/68/EEC
forth in EC directives.
Applicable standards:
This declaration becomes invalid if ・Machinery EN60204-1 (1997)
modifications are made to the product without ・Low Voltage EN61010-1 (1993; +A2)
consultation with us. ・EMC EN55011 (1991)
EN50082-2 (1995)
Designation of the Cryocooler;
Cryocooler Model SRDK series Applied national standards and technical
Consists of specifications:
・Cold Head Model; ・MITI Directory No. 51*
RDK-408D, RDK-408S, ・UL 471**
RDK-400B, RDK-415D
・Compressor Unit Model; * MITI : Japan Ministry of Trade and Industry
CSA-71A, CSW-71C, CSW-71D **UL : Underwriters Laboratories Inc. (USA)
TABLE OF CONTENTS
TABLE OF CONTENTS
CROSS REFERANCE 1
BEFORE USING EQUIPMENT 2
SAFETY PRECAUTIONS 3
INSPECTION 7
PACKING AND RETURN 8
REGULATORY REQUIREMENTS 9
PRESSURE UNIT CONVERSION TABLE 10
1 INTRODUCTION 11
1-1 GENERAL INFORMATION 11
1-2 SRDK SERIES CRYOCOOLER 12
1-3 THEORY OF OPERATION 14
2 INSTALLATION 16
2-1 GENERAL 16
2-2 TOOLS FOR INSTALLATION 16
2-3 MOVING 17
2-4 SITE REQUIREMENT 18
2-4-1 REQUIRED FOR AIR COOLED COMPRESSOR UNIT 19
2-4-2 REQUIRED FOR WATER COOLED COMPRESSOR UNIT 20
2-5 COLD HEAD INSTALLATION 21
2-6 COMPRESSOR UNIT INSTALLATION 22
2-7 CONNECTING FLEX LINES 24
2-8 COLD HEAD POWER CABLE CONNECTION 31
2-9 INPUT POWER CABLE CONNECTION 35
3 OPERATION 36
3-1 PRELIMINARY CHECKS 37
3-2 START-UP OPERATION 38
3-3 SHUT-DOWN OPERATION 39
3-4 NORMAL OPERATION 40
4 FUNCTIONAL CHECK 41
4-1 SIMPLE PROBLEM 41
4-1-1 PRESSURE 41
4-1-2 ROOM TEMPERATURE 41
4-1-3 MAIN POWER PHASE 41
4-2 HELIUM LEAK 42
TABLE OF CONTENTS
5 MAINTENANCE 43
5-1 GENERAL INFORMATION FOR THE MAINTENANCE 44
5-2 COLD HEAD MAINTENANCE 45
5-3 COMPRESSOR UNIT MAINTENANCE 45
5-4 HELIUM GAS CHARGING 46
7 OPERATING LOG 55
REVISION CONTROL
CROSS REFERENCE
CROSS REFERENCE
Thoroughly read this manual and following manuals before using this equipment.
・ This service manual is intended only for the exclusive service personnel.
・ Sumitomo Heavy Industries will not be responsible for any accidents, failures, non-conformities, etc.
caused by operations by any persons other than service personnel according to the descriptions in this
manual.
・ This service manual describes important information such as the installation method, operation method
and maintenance of this equipment.
・ Using the equipment without observing the descriptions in this manual may result in malfunction of the
equipment or may be hazardous to the physical body of the operator. Sumitomo Heavy Industries will
provide no guarantee in this case.
・ No part of this manual may be reproduced without the consent of Sumitomo Heavy Industries, Ltd. The
use of this manual for other purposes is prohibited.
SAFETY PRECAUTIONS
SAFETY PRECAUTIONS
This service manual uses the following signs and expressions to describe items requiring strict observance
to prevent injury to the operator and other persons, damage to this equipment, the customer's equipment
and property, etc.
WARNING “WARNING”
Indicates a potentially hazardous situation that may cause injury to the operator or
people around the equipment in the event of improper handling taking no account of
this description.
When using this equipment, be sure to adhere to this description.
CAUTION “CAUTION”
Indicates a potentially hazardous situation that may result in misoperation, malfunction,
or damage of the customer's equipment, etc. in the event of improper handling taking
no account of this description.
When using this equipment, be sure to adhere to this description.
SAFETY PRECAUTIONS
“WARNINGS”
Make sure no power is applied to the compressor unit before starting the installation. Failing to observe this
precaution may result in electric shock.
Do not install the equipment near places subject to condensation such as a watering place. Failing to
observe this precaution may result in electric shock or malfunction.
Do not install the equipment in a dusty environment. Failing to observe this precaution may result in electric
shock or malfunction.
Make sure the power specification of the cryocooler used conforms to the customer's power supply before
using the equipment. Using the cryocooler with a non-conforming power supply may result in electric shock
or malfunction.
If the compressor unit used is the CSW-71D (water cooled, high voltage type), pay attention to the setting of
the applicable input supply voltage. The product is shipped with the input supply voltage set to 480V.
Before installing the equipment, be sure to check your supply voltage and change it to the appropriate setting
if necessary. Operating the equipment with your supply voltage different from the setting of the compressor
unit may result in electric shock or malfunction.
Make sure no power is applied to the compressor unit before starting operation when connecting or
disconnecting the cold head power cable. Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power source before
connecting or disconnecting the input power cable to the Compressor Unit, and then remove the input power
cable from the main power. Failing to observe this precaution may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under any
circumstances. Failing to observe this precaution may result in electric shock.
Pay special attention to its wiring when using the external connector on the compressor unit. Connecting a
jumper wire between Pins No.6 - No.8, No.6 - No.13 and No.6 - No.15 may result in misoperation in some of
safety devices in the equipment, causing electric shock, burn or malfunction.
Be sure to turn off and Lock Out with OFF position the customer's main power before performing
maintenance work such as replacement of fuses. Failing to observe this precaution may result in electric
shock.
SAFETY PRECAUTIONS
The minimum bending radius of the flex lines is 300 mm (11. 81 inches). Bending the flex lines at a smaller
angle may cause explosion or escape of gas, and so this should be avoided.
Do not disassemble the equipment for purposes other than maintenance specified in this service manual
under any circumstances. Disassembling the equipment may result in electric shock, explosion or escape
of gas.
The cold head, compressor unit, compressor adsorber and flex lines are pressurized with helium gas.
Purge the helium gas from all pressurized components before disposing. Open the purging valve gradually
or it may result in serious injury.
Do not break the vacuum with the low temperature of cold head second stage when removing the cold head
from the vacuum chamber. Breaking the vacuum may result in serious damage, explosion or escape of
gas. Keep the Flex Lines connected and maintain the high vacuum of the chamber and wait until the cold
head second stage temperature rises up to 100K before removing the cold head.
WARNING Do not touch the cooler fin of the Compressor Unit during fin cleaning. Touching the fin may cause the injury.
The Adsorber weight is about 11.0kg. When replace the adsorber, be careful of handling so that it may not get
hurt.
SAFETY PRECAUTIONS
“CAUTIONS”
This cryocooler is intended for the exclusive use indoors. It cannot be used outdoors. Failing to observe
this precaution may prevent the cryocooler from operating normally.
Do not use inverter for the main power source of the compressor unit. Operating with inverter may result in
the damage or malfunction of the compressor electric circuit.
Avoid using the transformer for the main power source of the compressor unit. If the transformer is
installed at the upstream of the unit, lacking phase protection circuit with the cryocooler occurs in a
malfunction. That may result in misoperation or malfunction. When using the transformer, install the other
lacking phase protection device in upstream of the transformer.
The cryocooler ON/OFF frequency must be less than 6 times per hour, and the ON/OFF interval must be
more than 3 minutes. The frequent ON/OFF operation may result in damage of compressor capsule or
malfunction.
Do not get on the compressor unit or put an object on top of it. Failing to observe this precaution may
prevent the cryocooler from operating normally or cause injury.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing to secure
enough space may result in misoperation or malfunction. (See the technical instruction of the compressor
unit used, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), sufficient space is required for
venting. Failing to secure sufficient space may result in misoperation or malfunction. (See the CSA-71A
technical instruction, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), it should be installed in a clean
environment. Installing it in a dusty environment such as inside a factory will require frequent cleaning of
the cooler fins or may result in misoperation or malfunction.
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water with
appropriate temperature, flow rate and water quality. Using inappropriate cooling water may result in
misoperation or malfunction. (See the technical instruction of the compressor unit used, for details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), do not use the demineralized
water for cooling water. Using demineralized water for cooling water may result in water leakage or
malfunction.
Be extremely careful not to damage the cylinder when mounting the cold head. Damaging the cylinder may
result in misoperation or malfunction.
Be sure to check the flat rubber gasket of the self seal coupling of the cold head and compressor unit for dirt,
dust or to see whether the flat rubber gasket is attached correctly, before connecting the flex lines.
Connecting the flex lines with an abnormal flat rubber gasket setting may cause escape of gas.
When connecting the flex lines to the cold head, be sure to start with the flex line on the "Return" side.
Starting with the flex line on the "Supply" side may cause misoperation.
This cryocooler (cold head, compressor unit, compressor adsorber, flex lines) is shipped with a helium gas
at about 1.62 MPa (16.5 kgf/cm2G, 235 psig) sealed in. Be sure to adjust the pressure to an appropriate
value according to the cold head used before operating the equipment. Using the cryocooler at an improper
pressure may cause misoperation.
The cold head drive switch provided with the compressor unit is only used for maintenance. Be sure to turn
it OFF in normal operation. Using the compressor unit with the cold head drive switch turned ON may result
in misoperation or malfunction.
The coldhead employs the special seal to the 2nd stage. The 2nd stage displacer is fit tightly in the cylinder.
Make sure the 2nd stage temperature is less than 28 deg.C before starting up the cryocooler, or the
coldhead may make grinding noise.
Pay attention to the contamination when charging a helium gas. The contamination may result in
occurrence of the noise from the Cold Head or decreasing the cooling capacity.
INSPECTION
INSPECTION
“IMPORTANT”
If any irrecoverable damage is found by a test at the time of reception of the equipment described in this
service manual, please contact Sumitomo Heavy Industries.
The Cryocooler Model SRDK Series should be thoroughly inspected for evidence of damage upon receipt.
Proceed as follows to unpack and check the shipping damages as soon as you receive it.
1) Inspect the outside of each shipping container for visible damage. If you will be making a damage
claim, keep the shipping container, packing materials.
2) Carefully unpack the Cold Head, Compressor Unit, Flex Lines and Cables and inspect them for
damage.
COLD HEAD
Inspect the exterior of the Cold Head for evidence of damage.
(a) Overall exterior.
(b) Bent or dent of cylinder.
(c) Mounting flange and its sealing surfaces.
COMPRESSOR UNIT
The compressor should not be tilted by more than 30 degree at any time. Tilting the Compressor Unit
upside down causes damage of compressor capsule or oil contamination of the Helium gas line.
Inspect the exterior of the Compressor Unit for evidence of damage.
(a) Overall exterior.
(b) Oil leakage.
(c) Filling pressure.
2
The pressure gauge will be indicated 1.60 - 1.65 MPa (16.3 - 16.8 kgf/cm G, 232 -239 psig) minimum at
2
20 deg.C (68 deg.F). If the gauge indicates less than 1.60 MPa (16.3 kgf/cm G, 232 psig), refill Helium
gas as described in “TECHNICAL INSTRUCTION” of Compressor Unit used. If the gauge indicates 0
2
MPa (0 kgf/cm G, 0 psig), there is a risk of helium contamination and Compressor Unit must be
replaced.
Reinstall the caps on all Aeroquip connector to protect from the damage during transportation or shipping.
Reuse the package that was used for shipping.
Pack the Compressor Unit and Cold Head securely and properly.
Attach the caution label to prevent the tilting the Compressor Unit or upside down during transportation.
“IMPOTANT”
If you return the water-cooling type compressor unit to Sumitomo Heavy Industries, please let out the
cooling water.
REGULATORY REQUIREMENTS
REGULATORY REQUIREMENTS
The SRDK Series Cryocooler is designed and manufactured in accordance with following standards.
EC Directives (EC)
・ EN60204-1 (1997)
・ EN61010-1 (1993; +A2)
・ EN55011 (1991)
・ EN50082-2 (1995)
0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 [MPa] 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.0 0 1 3 4 6 7 9 10 12 13
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 0.1 14 16 17 19 20 22 23 25 26 28
2.0 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.9 3.0 0.2 29 30 32 33 35 36 38 39 41 42
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 0.3 43 45 46 48 49 51 52 54 55 57
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5.0 0.4 58 59 61 62 64 65 67 68 70 71
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 0.5 72 74 75 77 78 80 81 83 84 85
6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 7.0 0.6 87 88 90 91 93 94 96 97 99 100
7.1 7.2 7.3 7.4 7.5 7.7 7.8 7.9 8.0 8.1 0.7 101 103 104 106 107 109 110 112 113 114
8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9.0 9.1 0.8 116 117 119 120 122 123 125 126 128 129
9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 10.0 10.1 0.9 130 132 133 135 136 138 139 141 142 143
10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9 11.0 11.1 1.0 145 146 148 149 151 152 154 155 156 158
11.2 11.3 11.4 11.5 11.6 11.7 11.8 11.9 12.0 12.1 1.1 159 161 162 164 165 167 168 170 171 172
12.2 12.3 12.4 12.5 12.6 12.8 12.9 13.0 13.1 13.2 1.2 174 175 177 178 180 181 183 184 185 187
13.3 13.4 13.5 13.6 13.7 13.8 13.9 14.0 14.1 14.2 1.3 188 190 191 193 194 196 197 199 200 201
14.3 14.4 14.5 14.6 14.7 14.8 14.9 15.0 15.1 15.2 1.4 203 204 206 207 209 210 212 213 214 216
15.3 15.4 15.5 15.6 15.7 15.8 15.9 16.0 16.1 16.2 1.5 217 219 220 222 223 225 226 227 229 230
16.3 16.4 16.5 16.6 16.7 16.8 16.9 17.0 17.1 17.2 1.6 232 233 235 236 238 239 241 242 243 245
17.3 17.4 17.5 17.6 17.7 17.9 18.0 18.1 18.2 18.3 1.7 246 248 249 251 252 254 255 256 258 259
18.4 18.5 18.6 18.7 18.8 18.9 19.0 19.1 19.2 19.3 1.8 261 262 264 265 267 268 270 271 272 274
19.4 19.5 19.6 19.7 19.8 19.9 20.0 20.1 20.2 20.3 1.9 275 277 278 280 281 283 284 285 287 288
20.4 20.5 20.6 20.7 20.8 20.9 21.0 21.1 21.2 21.3 2.0 290 291 293 294 296 297 298 300 301 303
21.4 21.5 21.6 21.7 21.8 21.9 22.0 22.1 22.2 22.3 2.1 304 306 307 309 310 312 313 314 316 317
22.4 22.5 22.6 22.7 22.8 23.0 23.1 23.2 23.3 23.4 2.2 319 320 322 323 325 326 327 329 330 332
23.5 23.6 23.7 23.8 23.9 24.0 24.1 24.2 24.3 24.4 2.3 333 335 336 338 339 341 342 343 345 346
24.5 24.6 24.7 24.8 24.9 25.0 25.1 25.2 25.3 25.4 2.4 348 349 351 352 354 355 356 358 359 361
25.5 25.6 25.7 25.8 25.9 26.0 26.1 26.2 26.3 26.4 2.5 362 364 365 367 368 369 371 372 374 375
26.5 26.6 26.7 26.8 26.9 27.0 27.1 27.2 27.3 27.4 2.6 377 378 380 381 383 384 385 387 388 390
27.5 27.6 27.7 27.8 27.9 28.1 28.2 28.3 28.4 28.5 2.7 391 393 394 396 397 398 400 401 403 404
28.6 28.7 28.8 28.9 29.0 29.1 29.2 29.3 29.4 29.5 2.8 406 407 409 410 412 413 414 416 417 419
29.6 29.7 29.8 29.9 30.0 30.1 30.2 30.3 30.4 30.5 2.9 420 422 423 425 426 427 429 430 432 433
2
[kgf/cm G] [psig]
2
1 [MPa] = 10.2 [kgf/cm G] 1 [MPa] = 114.9 [psig]
1 INTRODUCTION
This manual provides instructions for initial inspection, installation, operation and service for the
component of SRDK Series Cryocooler system in Table 1.1.
COMPONENT MODEL
COLD HEAD
RDK-408D2
4K COLD HEAD RDK-408D
RDK-415D
RDK-408S2
10K COLD HEAD
RDK-408S
SINGLE STAGE COLD HEAD RDK-400B
COMPRESSOR UNIT
AIR COOLED (Low Voltage) CSA-71A
WATER COOLED (Low Voltage) CSW-71C
WATER COOLED (High Voltage) CSW-71D
FLEX LINE*
20 A x 6 m (19.7 feet)
SUPPLY (Female - Female) 20 A x 20 m (69.6 feet)
20 A x 6 m (19.7 feet) + Buffer Tank
20 A x 6 m (19.7 feet)
RETURN (Female - Female) 20 A x 20 m (69.6 feet)
20 A x 6 m (19.7 feet) + Buffer Tank
COLD HEAD POWER CABLE 6 m (19.7 feet)
* To operate the RDK-415D and RDK-400B (including the special flange model) with specified cooling capacity, use
the 20A x 20m flex line or 20A x 6m flex line + Buffer Tank.
The SRDK Series Cryocooler consists of a Cold Head, Compressor Unit, Flex Lines, and Cold Head
Power Cable.
The RDK series Cold Head is a GM cycle cryo-refrigerator. The function of the Cold Head is to produce
continuous closed-cycle refrigeration at temperatures, depending upon the heat load imposed.
The Cold Head has three (3) major components: the drive unit; the cylinder; and the displacer-regenerator
assembly, which is located inside the cylinder.
RDK-408D2 & RDK-408D & RDK-415D 4K Cold Heads are applied rare earth material for the second
stage displacer to produce 4K temperature. The second stage cooling capacity is approximately 1.0W at
4.2K for RDK-408D2 & RDK-408D, and 1.5W at 4.2K for RDK-415D.
RDK-408S2 & RDK-408S 10K Cold Head is the standard type Cold Head which are modified to produce
more cooling capacity for the second stage cold station compared with SHI previous standard type Cold
Head.
The second stage cooling capacity of RDK-408S2 & RDK-408S Cold Head is approximately 5W at 10K.
RDK-400B Single Stage Cold Head has only first stage displacer for cooling the shield.
The cooling capacity of RDK-400B is approximately 54W at 40K.
The Compressor Unit is required to operate the Cold Head. The Compressor Unit will provide the power
and the high-pressure helium gas for the Cold Head, and consisted of a compressor capsule, a cooling
system and lubricating oil mist Adsorber.
Functionally, the high-pressure helium gas from the Compressor Unit will be supplied to the Cold Head
through the helium gas supply connector. The supply gas will be passed into the displacer-regenerator
assembly, come out through the displacer-regenerator assembly to the crankcase through the motor
housing, and finally will be returned to the Compressor Unit through the helium gas return connector. The
helium gas expansion in the displacer-regenerator assembly will provide cooling condition for the first and
second-stage cold stations.
The Cryocooler requires the routine maintenance to keep the performance. The Adsorber replacement of
the Compressor Unit is required every 20,000 operating hours. The acting parts replacement of the Cold
Head is required to maintain every 10,000 operating hours.
Cooling Air
Flow
Cold Head
Supply Flex Line Power Cable
(yellow mark)
Cold Head
Compressor Unit
Cold Head
Supply Flex Line Power Cable
(yellow mark)
Cold Head
Cooling Water
Flow
Return Flex Line
(green mark)
Compressor Unit
The GM cycle is shown schematically in Figure 1.2 and consisted of a cylinder, closed at both ends, and
containing a displacer of a length about three quarters of the cylinder. The displacer is connected to a
drive mechanism so that it can be operated reciprocating action in the cylinder. The two volumes, one for
above and another for below the displacer, can be varied from zero to maximum but the total volume
remains constantly.
Compressor
Outlet Valve
Inlet Valve
Regenerator Displacer
The two spaces are connected through a thermal regenerator and to a gas supply. The gas supply
system is consisted of inlet and outlet valves, a helium gas compressor and high and low pressure
reservoirs. The valves are coupled to the rotary drive mechanism and their operation is synchronized with
the position of the displacer. A heat exchanger is included downstream of the helium gas compressor to
cool down the gas to ambient temperature after compression.
The pressure above and below the displacer will be the same level except for small pressure drops across
the regenerator when gas is flowing through it. The basic function for the displacer will be required to
displace a volume in the cylinder so that the gas will be moved up and down in the cylinder without
mechanical work.
Pressure in the system is increased or decreased by operation of the inlet or outlet valves.
The displacer is fit loosely in the cylinder except at the top equipped with a dynamic (sliding) seal to prevent
gas leakage through the space between displacer and cylinder.
The regenerator will be consisted of metallic material divided finely will cool the gas passing downward to
the cold space and heat the gas passing upward from the cold space.
PRESSURE BUILD-UP
INTAKE STROKE
With the inlet valve open, the displacer is moved from the
bottom to the top of the cylinder. This displaces high
pressure fluid from the space above the displacer,
volume 1, through the regenerator, to the space below
the displacer, volume 2. In passing through the
regenerator, the gas cools causing the pressure to
Volume 2
decrease and further gas to enter the system to maintain
the maximum cycle pressure.
INTAKE STROKE
EXHAUST STROKE
With outlet valve open, the displacer moves from the top
to bottom of the cylinder, displacing fluid from volume
2(below) to volume 1, above the displacer. As it flows
through the regenerator, the fluid is heated to near
ambient temperature by the matrix. This process, can
be produced the cool in the matrix ready for the gas
entering in the succeeding cycle.
EXHAUST STROKE
2-1 GENERAL
2 INSTALLATION
Make sure no power is applied to the compressor unit before starting the installation. Failing to
observe this precaution may result in electric shock.
2-1 GENERAL
This section describes the installation of the Cold Head and the Compressor Unit, and how to connect the
Flex Lines and electrical cables. Be sure to read this section before installing the cryocooler.
The following tools are required for SRDK Series Cryocooler Installation.
TOOLS REMARK
1 1“ Open-end wrench For Flex Line connection
2 1-1/8“ Open-end wrench For Flex Line connection
3 1-3/16“ Open-end wrench For Flex Line connection
4 Vacuum grease For O-ring of Vacuum Chamber
5 Screwdriver (phillips(+), flathead(-)) For Cold Head Cable and Input Power Cable connection
6 Liquid Leak Detector For leak check
7 Cotton wipers For leak check
8 Bar wrench for M4 For Cold Head Installation to Vacuum Chamber
2-3 MOVING
2-3 MOVING
COMPRESSOR UNIT
The compressor should not be tilted by more than 30 degrees at any time.
Tilting the Compressor Unit causes damage of Compressor Capsule or oil contamination of the Helium
Gas Line.
COLD HEAD
The Cold Head Cylinder should not be bent or dent. The surface flatness of the Cold Head heat station
is critical to the thermal contact. Damage of the surface will cause performance loss.
Avoid using the transformer for the main power source of the compressor unit. If the
transformer is installed at the upstream of the unit, lacking phase protection circuit with the
cryocooler occurs in a malfunction. That may result in misoperation or malfunction. When
using the transformer, install the other lacking phase protection device in upstream of the
transformer.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing
to secure enough space may result in misoperation or malfunction. (See the technical
instruction of the compressor unit used, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), sufficient space is
required for venting. Failing to secure sufficient space may result in misoperation or
malfunction. (See the CSA-71A technical instruction, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), it should be installed
in a clean environment. Installing it in a dusty environment such as inside a factory will require
frequent cleaning of the cooler fins or may result in misoperation or malfunction.
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water
with appropriate temperature, flow rate and water quality. Using inappropriate cooling water
may result in misoperation or malfunction. (See the technical instruction of the compressor unit
used, for details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), do not use the
demineralized water for cooling water. Using demineralized water for cooling water may result
in water leakage or malfunction.
“IMPORTANT”
See “TECHNICAL INSTRUCTION” of Compressor Unit used, for detail of Site Requirement.
The Compressor Unit can be installed at the field as complying with the Site Requirement;
・ An almost level and even area in the field will be selected to install the Compressor Unit.
・ An area to be influenced by splashing water and/or dusts will not be selected to install the Compressor
Unit.
・ A clean environmental condition without dirt and/or free from an exhausted heat will be selected to install
the Compressor Unit in the field.
・ An efficient ventilated area will be required to free from an exhausted heat of the Compressor Unit in the
field.
・ A suitable air conditioning capacity will be secured for an installing area for the Compressor Unit in the
field.
・ Any object and/or obstacle cannot be positioned on a ventilation fan outlet in a top area of the enclosure
and/or on surroundings of the Compressor Cooler.
・ Any heat sensitive object cannot be positioned on surroundings of the Compressor Unit.
POWER SOURCE
Ensure the correct AC power source is available for the Compressor Unit. See “TECHNICAL
INSTRUCTION” of CSA-71A, for AC power source requirement.
SERVICE AREA
Air-cooled Compressor Unit should have enough space for air-flow as shown in “TECHNICAL
INSTRUCTION” of CSA-71A.
・ An almost level and even area in the field will be selected to install the Compressor Unit.
・ An area to be influenced by splashing water and/or dusts will not be selected to install the Compressor
Unit.
・ A clean environmental condition without dirt and/or free from an exhausted heat will be selected to install
the Compressor Unit in the field.
・ A quality of cooling water will be secured to use for an appropriate cooling of the Compressor Unit.
・ Any heat sensitive object cannot be positioned on surroundings of the Compressor Unit.
POWER SOURCE
Ensure the correct AC power source is available for the Compressor Unit. See “TECHNICAL
INSTRUCTION” of Compressor Unit used, for AC power source requirement.
COOLING WATER
Ensure the correct cooling water is available for the Compressor Unit. See “TECHNICAL
INSTRUCTION” of Compressor Unit used, for the cooling water requirements.
ANTIFREEZE
Operating with Antifreeze (50/50 % mixture of water and ethylene glycol), the flow rate shall be 10%
larger than water flow rate and the pressure drop through the cooling water line will be 40% larger.
The larger circulating pump will be required for the Antifreeze. The admissible capacity range for
2
circulation pump will be more than 8 liter/min (2.1 gal./min) for flow rate and 0.29 MPa (3 kgf/cm G, 42
psig) for the pressure drop.
SERVICE AREA
The Compressor Unit should have enough space as shown in “TECHNICAL INSTRUCTION” of
Compressor Unit used.
Do not break the vacuum with the low temperature of cold head second stage when removing
the cold head from the vacuum chamber. Breaking the vacuum may result in serious damage,
explosion or escape of gas. Keep the Flex Lines connected and maintain the high vacuum of
the chamber and wait until the cold head second stage temperature rises up to 100K before
removing the cold head.
The following procedures describe the inspection and installation of the Cold Head.
INSPECTION
Inspect the following parts of the Cold Head before installation for evidence of damage:
(1) Overall exterior.
(2) Bent or dent of cylinder.
(3) Supply and Return Aeroquip fittings.
(4) Cold Head power connector.
(5) Mounting flange and its sealing surface.
(6) Sealing surface or O-ring groove of User’s vacuum chamber.
INSTALLATION
The Cold Head can be mounted in any desired position and orientation.
Install the Cold Head into User’s cryostat or vacuum chamber with a prudent care.
Do not install the equipment in a dusty environment. Failing to observe this precaution may
result in electric shock or malfunction.
Do not get onto the compressor unit or put an object on top of it. Failing to observe this
precaution may prevent the cryocooler from operating normally or cause injury.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing
to secure enough space may result in misoperation or malfunction. (See the technical
instruction of the compressor unit used, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), sufficient space is
required for venting. Failing to secure sufficient space may result in misoperation or
malfunction. (See the CSA-71A technical instruction, for details.)
The procedures including the inspection and installation of the Compressor Unit will be mentioned below.
INSPECTION
1) Inspect the compressor overall exterior for damage, and evidence of oil leakage.
2) Make sure that the static pressure is specified value with supply pressure gauge of the Compressor
Unit. The static pressure needs to be adjusted for the type of Cold Head as described follows;
RDK-408D2 --------- 1.60 - 1.65 MPa at 20 deg.C (68 deg.F)
2
RDK-408D (16.3 - 16.8 kgf/cm G, 232 - 239 psig)
RDK-415D
If the gauge reads less than specified value, refill Helium gas as described in Section 5-4.
2
If the gauge reads 0 MPa (0 kgf/cm G, 0 psig), there is a risk of helium contamination and the
Compressor Unit must be replaced.
3) Inspect following parts of the Compressor Unit before installation for evidence of damage.
(a) Overall exterior.
(b) Supply and Return Aero-quip type fittings.
(c) Gas charge Aero-quip type fittings.
(d) Oil leakage around the base panel.
INSTALLATION
Install the Compressor Unit to a level surface (less than 5 degrees). During installation, do not tilt the
Compressor Unit more than 30 degrees. The Compressor Unit can travel with 4 casters, and two of them
are with lock-devices. After positioning the Compressor Unit, the casters can be locked.
The minimum bending radius of the flex lines is 300 mm (11. 81 inches). Bending the flex lines
at a smaller angle may cause explosion or escape of gas, and so this should be avoided.
Be sure to start with the flex line on the "Return" side when connecting the flex lines to the cold
head. Starting with the flex line on the "Supply" side may cause misoperation.
“IMPORTANT”
When connecting the flex lines, tighten the self-seal coupling nut by hand at the first turn and finally
tighten it firmly using 3 wrenches. However, be careful not to tighten it excessively. The maximum
allowable tightening torque is 45 N・m.
Make the connections between the Cold Head and Compressor Unit as follows;
FUNDAMENTAL
The Cold Head can be operated with a rotary valve to control the gas inlet / outlet timing of the
refrigeration cycle. The pressure difference between the supply and the return can be available to get
the seal between the rotary valve and the valve plate (as shown in the Figure). The return pressure
must be less than supply pressure in connecting the Flex Line. To avoid the malfunction of the Cold
Head, careful handling must be taken in connecting Flex Line.
In case the Cold Head will be operated with miss-connected flex lines, for example “Supply line” to
“Return connector” and “Return line” to “Supply connector”, the Rotary Valve will be pushed back by the
Supply pressure and the Cold Head will malfunction with no intake/exhaust noise.
Rotary Valve
Bearing
Return (Pr)
Return (Pr)
Supply (Ps) Supply (Ps)
Valve Plate
To Displacer
CONNECTING PROCEDURE
1) Remove all protective caps of the supply and return Flex Lines, Cold Head and Compressor Unit.
2) Check all the flat rubber gaskets of self-sealing connectors to make sure of being clean and properly
positioned.
3) Connect the Flex Lines (both Supply and Return) to the Compressor Unit.
In case of using the “Buffer Tank”, insert the “Buffer Tank” between the Compressor Unit and Flex Lines.
Refer to the Figure 2.1, outline view of the “Buffer Tank”, and the Figure 2.2, “Buffer Tank”
interconnecting diagram.
1) Connect the female coupling of “Tee-Adapter” to the male connector of the Compressor Unit for both
“Supply” and “Return”.
2) Place the “Buffer Tank” at the right side of the Compressor Unit.
3) Connect the “Tee-Adapter” and “Buffer Tank” by two “8A x 1m Flex Line”.
4) Connect the Flex Lines to the Tee-Adapters. Do not miss-match the “Supply” and “Return” marking
for both Flex Lines and Compressor Unit
LEAK CHECK
Check the helium gas leak of all connecting coupling as following procedure after connecting all Flex
Lines.
2) Keep watching carefully the sprinkled area and no gas leaking will be confirmed without any bubbling.
3) In case the bubbling is found, tighten the connecting coupling again and re-check the leakage. Do
not over tighten the connector.
2) Connect the ground terminal of the Cold Head Cable (green color wire with ring terminal) to rear
cover of Cold Head Drive Motor.
3) Mount the Terminal Cover on the Cold Head Motor with securing four(4) screws.
1) Connect the ground terminal of the Conversion Connector (green color wire with ring terminal) to
rear cover of Cold Head Drive Motor.
2) Set the connector of the Conversion Connector to the terminal pins on the Cold Head Drive Motor.
3) Mount the Terminal Cover on the Cold Head Motor with securing four(4) screws.
Connect the other end of the Cold Head Power Cable to the Cold Head Power Connector on the rear
panel of the Compressor Unit.
If the compressor unit used is the CSW-71D (water cooled, high voltage type), pay attention to
the setting of the applicable input supply voltage. The product is shipped with the input supply
voltage set to 480V. Before installing the equipment, be sure to check your supply voltage and
change it to the appropriate setting if necessary. Operating the equipment with your supply
voltage different from the setting of the compressor unit may result in electric shock or
malfunction.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power
source before connecting or disconnecting the input power cable to the Compressor Unit, and
then remove the input power cable from the main power. Failing to observe this precaution
may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under
any circumstances. Failing to observe this precaution may result in electric shock.
Avoid using the transformer for the main power source of the compressor unit. If the
transformer is installed at the upstream of the unit, lacking phase protection circuit with the
cryocooler occurs in a malfunction. That may result in misoperation or malfunction.
When using the transformer, install the other lacking phase protection device in upstream of the
transformer.
“IMPORTANT”
This cryocooler is provided with a phase reverse protection circuit for the input power. If the input
power is connected with reverse phase, the cryocooler does not start.
“IMPORTANT”
See “TECHNICAL INSTRUCTION” of Compressor Unit used, for detail of Input Power Connection.
3 OPERATION
Make sure the power specification of the cryocooler used conforms to the customer's power
supply before using the equipment. Using the cryocooler with a non-conforming power supply
may result in electric shock or malfunction.
If the compressor unit used is the CSW-71D (water cooled, high voltage type), pay attention to
the setting of the applicable input supply voltage. The product is shipped with the input supply
voltage set to 480V. Before installing the equipment, be sure to check your supply voltage and
change it to the appropriate setting if necessary. Operating the equipment with your supply
voltage different from the setting of the compressor unit may result in electric shock or
malfunction.
Do not change the setting of the dial above the main power switch of the compressor unit under
any circumstances. Failing to observe this precaution may result in electric shock.
The coldhead employs the special seal to the 2nd stage. The 2nd stage displacer is fit tightly in
the cylinder. Make sure the 2nd stage temperature is less than 28 deg.C before starting up the
cryocooler, or the coldhead may make grinding noise.
“IMPORTANT”
This cryocooler is provided with a phase reverse protection circuit for the input power. If the input
power is connected with reverse phase, the cryocooler does not start.
Prior to starting Cryocooler, confirm that the Compressor Unit and the Cold Head are installed correctly as
described in Section 2.
For RDK-408D2 & 408D & 415D For RDK-408S2 & 408S & 400B
3-2 START UP
The cold head drive switch provided with the compressor unit is only used for maintenance. Be
sure to turn it OFF in normal operation. Using the compressor unit with the cold head drive
switch turned ON may result in misoperation or malfunction.
The coldhead employs the special seal to the 2nd stage. The 2nd stage displacer is fit tightly in
the cylinder. Make sure the 2nd stage temperature is less than 28 deg.C before starting up the
cryocooler, or the coldhead may make grinding noise.
“IMPORTANT”
This cryocooler is provided with a phase reverse protection circuit for the input power. If the input
power is connected with reverse phase, the cryocooler does not start.
1) Make sure that the pressure gauge of the Compressor Unit is indicating correct static pressure of
your system with supply pressure gauge.
2) Check the setting of “Drive Switch”, “Cold Head Drive Switch” and “Remote Drive Switch”.
“Drive Switch” --- OFF Position
“Cold Head Drive Switch” --- OFF Position
“Remote Drive Switch” --- INT Position (for Water Cooled Compressor Unit only)
For Air Cooled Compressor Unit For Water Cooled Compressor Unit
For Air Cooled Compressor Unit For Water Cooled Compressor Unit
The cold head drive switch provided with the compressor unit is only used for maintenance. Be
sure to turn it OFF in normal operation. Using the compressor unit with the cold head drive
switch turned ON may result in misoperation or malfunction.
The coldhead employs the special seal to the 2nd stage. The 2nd stage displacer is fit tightly in
the cylinder. Make sure the 2nd stage temperature is less than 28 deg.C before starting up the
cryocooler, or the coldhead may make grinding noise.
For Air Cooled Compressor Unit For Water Cooled Compressor Unit
For Air Cooled Compressor Unit For Water Cooled Compressor Unit
“IMPOTANT”
If the compressor unit used is the CSA-71A (air cooled, low voltage type), note that the noise level of the
whole equipment may exceed 70 dBA depending on the environment it is used in.
EXHAUST SOUND
Starting Cryocooler, you can hear the gas inlet/outlet sound from the Cold Head. The sound of the
Cold Head is 60 rpm at 50 Hz and 72 rpm at 60 Hz respectively. During this checking, the Compressor
2
operating pressure will be around 2.5 MPa (25.5 kgf/cm G, 362 psig).
4 FUNCTIONAL CHECK
This section describes several simple problems that usually occurred. If you have trouble that you cannot
fix according to the following procedure, proceed to “TROUBLE SHOOTING FLOW CHART” described in
Section 6.
4-1-1 PRESSURE
Cryocooler is designed and manufactured to get cooling capacity with specified Helium Gas Pressure. It is
highly recommended to check the pressure. If the indicated pressure is higher than specified value,
reduce the pressure. If it is lower, charge the helium gas. See “TECHNICAL INSTRUCTION” of Cold
Head used, to see the specified pressure of your system.
After replacing Cold Head, it will be necessary to charge the Helium Gas because the temperature of the
Cold Head is usually lower than room temperature, therefore the system always lose helium gas.
Room temperature affects the Cryocooler performance. It is highly recommended to keep the room
temperature in the specified range. See “TECHNICAL INSTRUCTION” of Compressor Unit used, for
details.
The Cryocooler operates with 3 phase mains frequency. The Compressor Units are equipped with phase
reverse protection circuit to protect the Compressor Unit from reverse revolution. The Compressor Unit
will not start, in case the main power is reverse phase. A procedure for the diagnosis of phase failure for
input power caused by miss-wiring will be performed, if the Compressor Unit cannot be operated as normal
in a condition of the “Drive Switch - ON” under the “Main Power Switch - ON”.
The Cold Head cannot be performed a required cooling power in normal operations, as the result of the
He-gas pressure reducing gradually in the Cold Head in condition of occurring a He-gas Leak in the
Cryocooler. The Compressor unit will be shut down as the function of the Low Pressure Switch to be
sensed and excessive lower He-gas pressure, and verify the charged He-gas pressure in the Compressor
Unit as specified pressure. The charged He-gas pressure will be indicated individually for each
application, and see “TECHNICAL INSTRUCTION” of the Cold Head used.
A Leak detector will be applied to leak area hunting for convenience, and “Liquid Leak Detector” also will
be useful to check the He-gas leaking of couplings for the Flex Line by watching any bubbling carefully, if
the Leak Detector not in use at the field.
5 MAINTENANCE
Make sure no power is applied to the compressor unit before connecting or disconnecting the
cold head power cable. Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power
source before connecting or disconnecting the input power cable to the Compressor Unit, and
then remove the input power cable from the main power. Failing to observe this precaution
may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under
any circumstances. Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the customer's main power before performing
maintenance work such as replacement of fuses. Failing to observe this precaution may result
in electric shock.
Do not disassemble the equipment for purposes other than maintenance specified in this
service manual under any circumstances. Disassembling the equipment may result in electric
shock, explosion or escape of gas.
The cold head, compressor unit, compressor adsorber and flex lines are pressurized with helium
gas. Purge the helium gas from all pressurized components before disposing. Open the
purging valve gradually or it may result in serious injury.
Do not break the vacuum with the low temperature of cold head second stage when removing
the cold head from the vacuum chamber. Breaking the vacuum may result in serious damage,
explosion or escape of gas. Keep the Flex Lines connected and maintain the high vacuum of
the chamber and wait until the cold head second stage temperature rises up to 100K before
removing the cold head.
WARNING The Adsorber weight is about 11.0kg. When replace the adsorber, be careful of handling so that
it may not get hurt.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing
to secure enough space may result in misoperation or malfunction. (See the technical
instruction of the compressor unit used, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), sufficient space is
required for venting. Failing to secure sufficient space may result in misoperation or
malfunction. (See the CSA-71A technical instruction, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), it should be installed
in a clean environment. Installing it in a dusty environment such as inside a factory will require
frequent cleaning of the cooler fins or may result in misoperation or malfunction.
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water
with appropriate temperature, flow rate and water quality. Using inappropriate cooling water
may result in misoperation or malfunction. (See the technical instruction of the compressor unit
used, for details.)
The cold head drive switch provided with the compressor unit is only used for maintenance. Be
sure to turn it OFF in normal operation. Using the compressor unit with the cold head drive
switch turned ON may result in misoperation or malfunction.
The SRDK CRYOCOOLER system is to be required the routine maintenance for long term and continuous
as every 10,000 Hrs on an actual installation.
The basic maintenance work is to replace the existing Cold Head composed of acting parts for every
10,000 Hrs operation and additional replacement of oil mist Adsorber of the Compressor Unit for every
20,000 Hrs operation as mentioned in Table 5.1.
The Cold Head is required to replace the sliding parts inside every 10,000 Hrs. This is not a user’s
Maintenance. Replace the Cold Head completely at site and return it to Sumitomo Heavy Industries, Ltd.
for refurbishment.
“IMPORTANT”
See “TECHNICAL INSTRUCTION” of Compressor Unit used, for detail of the Compressor Unit
maintenance.
The Compressor Units are required to replace Adsorber every 20,000 Hrs. The Adsorber is compatible
for both air-cooled and water-cooled Compressor.
“IMPORTANT”
The filling pressure of the cryocooler varies in accordance with the compressor and coldhead
temperature. Make sure the cryocooler is powered off and compressor and coldhead temperatures are
almost same as room temperature before adjusting the helium gas pressure.
Charge helium gas, if the pressure indication of the Compressor Unit is lower than specified value.
After stopping the cryocooler, the pressure indication on the Indoor Unit pressure gauge shows lower than
actual filling pressure, because of the low temperature of the coldhead. The coldhead temperature and
compressor unit temperature needs to be equal to ambient temperature to check the actual filling
pressure.
The filling pressure indication depends on the temperature of cryocooler components, such as Coldhead,
Outdoor Unit, Indoor Unit and Flex Lines. In case the room temperature is relatively low, the filling pressure
indicates lower. In case the room temperature is relatively high, the filling pressure indicates higher.
Refer to the ambient temperature to adjust the filling pressure precisely.
REQUIRED TOOLS
The following tools are required to charge helium gas to the Cryocooler system.
TOOLS REMARK
1 Gas charging tool for the Compressor Unit.
2 3/4“ Open-end wrench.
3 5/8“ Open-end wrench.
4 Pressure regulator for helium gas bottle
5 Helium gas bottle Purity of 99.999% up
PROCEDURE
1) Remove the protective cap from the gas charge coupling on the Compressor Unit. Connect a
pressure regulator and charging line to a helium bottle (purity 99.999% up). Connect a gas charging
tool to the Compressor Unit after closing the valve of gas charging tool.
2) Open the valve of pressure regulator slightly and slowly. Purge a Helium Gas for about 30 seconds
to vent the contamination in the charging line. Reduce the helium gas flow by controlling the valve of
pressure regulator and keep the slight helium gas flow.
3) Purge the air in the gas charging tool for about 5 seconds by opening the valve of gas charging tool.
Reduce the helium gas flow by controlling the valve of gas charging tool and keep the slight helium
gas flow.
4) Connect a charging line to a gas charging tool. Shut the valve of gas charging tool immediately.
2
5) Set the pressure regulator around 1.65 - 1.70 MPa (16.8 - 17.3 kgf/cm G, 239 - 246 psig).
6) Open the valve of gas charging tool slightly and slowly. Charge Helium gas till the pressure gauge of
the Compressor Unit indicates specified filling pressure and shut the valve. See “TECHNICAL
INSTRUCTION” for more detail of the pressure, Cold Head used.
7) Shut the valve of gas charging tool and pressure regulator. Disconnect the charging line and gas
charging tool from the Compressor Unit.
8) Set the protective cap to gas charge coupling on the Compressor Unit.
Make sure no power is applied to the compressor unit before starting operation when connecting
or disconnecting the cold head power cable. Failing to observe this precaution may result in
electric shock.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power b
connecting or disconnecting the input power cable to the Compressor Unit, and then remove the
input power cable from the main power. Failing to observe this precaution may result in electric
shock.
Pay special attention to its wiring when using the external connector on the compressor unit.
Connecting a jumper wire between Pins No.6 - No.8, No.6 - No.13 and No.6 - No.15 may result
in misoperation in some of safety devices in the equipment, causing electric shock, burn or
malfunction.
Be sure to turn off and Lock Out with OFF position the customer's main power before performing
maintenance work such as replacement of fuses. Failing to observe this precaution may result
in electric shock.
Do not disassemble the equipment for purposes other than maintenance specified in this
service manual under any circumstances. Disassembling the equipment may result in electric
shock, explosion or escape of gas.
Do not break the vacuum with the low temperature of cold head second stage when removing
the cold head from the vacuum chamber. Breaking the vacuum may result in serious damage,
explosion or escape of gas. Keep the Flex Lines connected and maintain the high vacuum of
the chamber and wait until the cold head second stage temperature rises up to 100K before
removing the cold head.
WARNING The Adsorber weight is about 11.0kg. When replace the adsorber, be careful of handling so that
it may not get hurt.
If the compressor unit used is the CSA-71A (air cooled, low voltage type), sufficient space is
required for venting. Failing to secure sufficient space may result in misoperation or
malfunction. (See the CSA-71A technical instruction, for details.)
If the compressor unit used is the CSA-71A (air cooled, low voltage type), it should be installed
in a clean environment. Installing it in a dusty environment such as inside a factory will require
frequent cleaning of the cooler fins or may result in misoperation or malfunction.
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water
with appropriate temperature, flow rate and water quality. Using inappropriate cooling water
may result in misoperation or malfunction. (See the technical instruction of the compressor unit
used, for details.)
The cold head drive switch provided with the compressor unit is only used for maintenance. Be
sure to turn it OFF in normal operation. Using the compressor unit with the cold head drive
switch turned ON may result in misoperation or malfunction.
The major trouble at the customer site can be solved by following trouble shooting flow chart.
In case, the trouble can not be solved by these flows, please make contact to SHI.
Customer Support
TEL No. +81-424-68-4264
FAX No. +81-424-68-4462
Oversea Bases
SHI-APD Cryogenics, Inc.
Adress; 1833 Vultee Street, Allentown, PA 18103-4783, USA
TEL No. +1-610-791-6700
FAX No. +1-610-791-0440
E-mail [email protected]
URL http://www.apdcryogenics.com
6 TROUBLE SHOOTING
Case of Trouble
Abnormal noise
from Cold Head
FLOW D
Abnormal noise
from Compressor Unit
FLOW D
FLOW A
Reference; < For CSA-71A > Reference; < For CSW-71D > Reference;
Check the ambient temperature Abnormal Compressor Unit Check the dust of Abnormal CSA-71A Check the input power voltage CSW-71D
heat exchanger Abnormal
Technical Insuruction Technical Insuruction and frequency setting of Technical Insuruction
Section 1-1 Section 3-1-2 the Compressor Unit Section 2-2
Adjust the filling pressure Correct the error(s) Correct the error(s)
Normal Reference;
Normal Reference;
Compressor Unit Normal
Operation Manual
Technical Insuruction
Section 4-2
Section 3-2
FLOW B
Reference;
Operation Manual
Section 4-1-3, 4-1-4
Compressor Unit
The Compressor Unit stoped with Technical Insuruction
the Main Power Switch tripped Section 2-2
and Drive Switch "ON" Reference;
Operation Manual
Check the input Section 4-1-3, 4-1-4
Compressor Unit
power cable connection
Reference; Abnormal Technical Insuruction
Compressor Unit (No connection, Section 2-2
Technical Insuruction Reverse phase, etc.)
Section 2-2
Correct the error(s)
Check the input power cable Reference; Reference; Reference;
Abnormal Compressor Unit Normal Compressor Unit Compressor Unit
connection
Technical Insuruction Technical Insuruction Technical Insuruction
Section 2-2 Section 3-2 Section 1-3-2
Check the user's power source Reference; Reference; Correct the error(s)
Compressor Unit Normal CSW-71D
(Fuse(s), circuit breakers, Abnormal Technical Insuruction Technical Insuruction
capacity and circuit wiring) Section 1-1, 2-2 Section 2-2
Correct the error(s) < For CSW-71D > Reference; Check the customer's
Check the input power voltage CSW-71D remort circuit
Abnormal Technical Insuruction
Abnormal
Normal and frequency setting of (Over current caused by
the Compressor Unit Section 2-2 short circuit, etc.)
use
FLOW C
Reference;
Reference; Reference;
CSW-71C, CSW-71D
Operation Manual Operation Manual
Technical Insuruction
Section 4-1-1 Section 2-8
Section 1-1
Adjust the filling pressure Correct the error(s) Correct the error(s)
Normal Reference;
Normal
Normal
Operation Manual
Section 4-2
FLOW D
Reference;
Reference; Reference;
CSW-71D
Operation Manual Operation Manual
Technical Insuruction
Section 2-8 Section 2-7
Section 2-2
7 OPERATING LOG
7 OPERATING LOG
Maintaining a log of the records of the temperature indication and pressure during normal operation is a
valuable means for troubleshooting. A sample operating log is mentioned to Figure 7.1. It is highly
advisable to create and maintain a detailed operating log for your Cryocooler.
page .
OPERATING LOG
SRDK Series CRYOCOOLER
Installation Date .
Cold Head Serial Number : .
Compressor Unit Serial Number : .
Elapsed Lowest Supply
Date Time Remarks
Time Temperature Pressure
REVISION CONTROL
REVISION CONTROL
Manual
Revision Remarks Date
No.
-A Publication of first edition. DEC. 10 / 1999
-B Change the SHI address. JAN. 25 / 2001
-C Change the description of start up operation. MAR. 21 / 2001
-D Add the start-up temperature CAUTION. JAN. 21 / 2002
-E Add the description of helium gas charging. APR. 1 / 2002
-F Change the WARNING descriptions. JUL. 11 / 2002
CD32ZZ-063 -G Add the transformer-use CAUTION. FEB. 28 / 2003
-H Change the division name. JUN. 9 / 2003
Add the description for the RDK-408D2 and S2
-I DEC. 18 / 2003
Cold Head.
TECHNICAL INSTRUCTION
CSW-71C
COMPRESSOR UNIT
E-mail: [email protected]
URL: http://www.shicryogenics.com
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
TABLE OF CONTENTS
TABLE OF CONTENTS
CROSS REFERANCE 1
1 GENERAL INFORMATION 2
1-1 SPECIFICATIONS 2
1-2 CONSTRUCTION 6
1-2-1 CONTROLS AND COUPLINGS 6
1-2-2 GAS AND OIL FLOW IN THE COMPRESSOR UNIT 9
1-2-3 INTERNAL COMPONENTS 11
1-3 ELECTRICAL DESCRIPTION 13
1-3-1 EXTERNAL CONNECTOR 13
1-3-2 SAFETY DEVICES 14
2 INSTALLATION 15
2-1 SITE REQUIREMENT 17
2-2 INPUT POWER CABLE CONNECTION 19
3 MAINTENANCE 21
3-1 PERIODICAL MAINTENANCE 22
3-1-1 REPLACEMENT OF THE COMPRESSOR ADSORBER 23
3-2 FUSE REPLACEMENT 27
APPENDIX 28
ELECTRICAL SCHEMATIC
DRAWINGS
REVISION CONTROL
CSW-71C
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
CROSS REFERENCE
CROSS REFERENCE
Thoroughly read this manual and following manuals before using this equipment.
CSW-71C 1
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-1 SPECIFICATIONS
1 GENERAL INFORMATION
1-1 SPECIFICATIONS
The specifications of CSW-71C Helium Compressor Unit are summarized in Table 1.1.
CSW-71C 2
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-1 SPECIFICATIONS
The typical flow characteristics are shown in Figure 1.1, and cooling water requirement are shown in
Table 1.2.
For Water
11 3.0
Cooling Water Flow Rate
[gallon/min.]
Admissible Range Admissible Range
[liter/min.]
8 2.0
7
6 1.5
5
1.0
4
3 0.5
0 4 8 12 16 20 24 28 32 30 40 50 60 70 80 90
Cooling Water Inlet Temperature [deg.C] Cooling Water Inlet Temperature [deg.F]
For Antifreeze (50/50 % mixture of water and ethylene glycol or propylene glycol.)
The larger circulating pump will be required for the Antifreeze
11 3.0
10
Cooling Water Flow Rate
Cooling Water Flow Rate
2.5
9
Admissible Range Admissible Range
[gallon/min.]
[liter/min.]
8
2.0
7
6 1.5
5
1.0
4
3 0.5
0 4 8 12 16 20 24 28 32 30 40 50 60 70 80 90
Cooling Water Inlet Temperature [deg.C] Cooling Water Inlet Temperature [deg.F]
0.20 30.0
20.0
0.10
10.0
0.00 0.0
4.0 5.0 6.0 7.0 8.0 9.0 10.0 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
CSW-71C 3
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-1 SPECIFICATIONS
CSW-71C 4
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-1 SPECIFICATIONS
CSW-71C 5
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
1-2 CONSTRUCTION
The function of the Compressor Unit is to supply high pressure He gas to the Cold Head and
re-compress the returned He gas from the Cold Head. The Compressor Unit consists of the following
major components: a Compressor Capsule, a Cooling system, Oil separation and injection system, and
Adsorber.
The controls and coupling for CSW-71C are described in Table 1.3 and Figure 1.3.
CSW-71C 6
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
COLD HEAD CONNECTOR : To use for connecting the Cold Head Cable to supply a Cold Head
10
(JC) driving power.
To use for the external signal output of condition monitoring for the
compressor unit. The connector to be “D-Sub 15 Pins (Female type)” in
use.
EXTERNAL CONNECTOR : Warning; Pay special attention to its wiring when using the external connector on
11
(JR) the Compressor Unit.
Connecting a jumper wire between Pins No.6 - No.8, No.6 - No.13 and
No.6 - No.15 may result in misoperation in some of safety devices in
the equipment, causing electric shock, burn or malfunction.
12 HE-GAS SUPPLY CONNECTOR To use for connecting a Flex Line (for Supply He-gas line)
13 HE-GAS RETURN CONNECTOR To use for connecting a Flex Line (for Return He-gas line)
14 HE-GAS CHARGE CONNECTOR To use for charging and refilling a He-gas.
COOLING WATER INPUT
15 A connector for cooling water inlet. (PT3/8 inch, Female type)
CONNECTOR
COOLING WATER OUTPUT
16 A connector for cooling water outlet. (PT3/8 inch, Female type)
CONNECTOR
CSW-71C 7
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
CSW-71C 8
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
The flow diagram for CSW-71C Compressor Unit is shown in Figure 1.4.
Internal components diagram and its functions are described in Figure 1.5 and Table 1.4.
1) Low pressure He gas discharged from a Cold Head can be led through a HE-GAS RETURN
CONNECTOR to the Compressor Unit.
2) The low pressure (Return) He gas can pass through a STORAGE TANK and a FILTER, and flow
into a COMPRESSOR CAPSULE.
3) The low pressure He gas will be compressed and pressurized in the COMPRESSOR CAPSULE,
and the high pressure with high temperature He gas after the compression will be discharged from
the COMPRESSOR CAPSULE outlet.
4) The high pressure with high temperature He gas will be led to a water cooled HE-GAS COOLER
and cooled down in the cooler.
5) The high pressure He gas after cooling will flow into an OIL SEPARATOR to separate an almost all
of lubricating oil mist from the high pressure He gas.
6) The separated lubricating oil can be returned to the COMPRESSOR CAPSULE through a lub oil
return pipings.
7) The high pressure He gas discharged from the OIL SEPARATOR will be led to an ADSORBER.
8) The remained lub oil contents in the high pressure He gas can be adsorbed through an active
charcoal layer to make the high pressure He gas being pure.
9) The pure high pressure He gas can be supplied to the Cold Head through a HE-GAS SUPPLY
CONNECTOR.
CSW-71C 9
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
CSW-71C 10
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
The parts list and its functions are described in Table 1.4.
The He-gas flow diagram and internal components are shown in Figure 1.4 and Figure 1.5.
CSW-71C 11
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
1-2 CONSTRUCTION
CSW-71C 12
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
Pay special attention to its wiring when using the external connector on the compressor unit. Connecting a jumper
wire between Pins No.6 - No.8, No.6 - No.13 and No.6 - No.15 may result in misoperation in some of safety devices
in the equipment, causing electric shock, burn or malfunction.
“IMPORTANT”
See “ELECTRICAL SCHEMATIC” of CSW-71C Compressor Unit, for detail.
“IMPORTANT”
The maximum allowable tightening torque of the D-Sub Connector lock screw (#4-40UNC) is 0.17 Nm.
External Connector can be used monitoring the status of the Compressor Unit and the remote control
sequences of the Compressor Unit are described in Table 1.5.
The “D-sub” pins indicated in Figure 1.6 on the control panel for the Compressor Unit can be applied to
an initial condition monitoring for a first-aid diagnostics of the Compressor Unit by means of measuring
the each item with a digital Volt/Ohm Meter. The Fault Condition classified the digital meter reading as
referred to the Table 1.5 can be identified simply an actual operation condition of the Compressor Unit
in the field.
8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
Figure 1.5 EXTERNAL CONNECTOR WIRING ON THE COMPRESSOR UNIT
CSW-71C 13
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
ITEM FUNCTIONS
Setting temperature; 110 deg.C ---- approx.
To shut down the Compressor Unit and signal a high temperature alarm to the
THERMOSTAT : (TS1)
External Connector, in case of higher temperature of a compressed He-gas at a
compressor outlet than the setting temperature.
Setting temperature; 60 deg.C ---- approx.
To shut down the Compressor Unit and signal a high temperature alarm to the
THERMOSTAT : (TS2)
External Connector, in case of higher temperature of a compressed He-gas at a
He-gas cooler outlet than the setting temperature.
Setting temperature; 60 deg.C ---- approx.
To shut down the Compressor Unit and signal a higher temperature alarm to the
THERMOSTAT : (TS3)
External Connector, in case of higher temperature of a water at a cooling water
outlet than the setting temperature.
To stabilize a pressure for even of the He-gas between the Supply and Return
SOLENOID VALVE : (YV)
piping, at a shut off the Compressor Unit.
Setting pressure;
“Operate” 2.55 MPa ---- approx.
HIGH PRESSURE SWITCH : “Reset” 2.26 MPa ---- approx.
(PSH) To adjust a Supply He-gas pressure smoothly by a function of the pressure
switch for Open and/or Shut, in case of higher pressure of the Supply He-gas
than the setting pressure.
Setting Pressure;
“Operate” 0.15 MPa ---- approx.
LOW PRESSURE SWITCH :
To shut down the Compressor Unit and signal a Low pressure alarm to the
(PSL)
External Connector, in case of lower pressure of a compressed He-gas caused
by a smaller quantity of He-gas than original filling in the compressor unit.
Setting pressure;
“Operate” 2.61 - 2.75 MPa
“Reset” 2.50 MPa ---- minimum
RELIEF VALVE
To adjust a Supply He-gas pressure smoothly by a function of the Relief Valve
for blowing off the He-gas to the atmosphere, in case of higher pressure of
Supply He-gas than the setting pressure.
Setting current; 29 A
MAIN POWER SWITCH :
To shut down the Compressor Unit, in case of occurring over-current and/or
(QF1)
short-circuit than the setting current.
PHASE FAILURE To avoid starting-up of the Compressor Unit in case of an abnormal operation
PROTECTION CIRCUIT : caused by irregular connecting of Input Power Cable such as failure connecting.
FUSE : To protect the Compressor Unit from the over-load caused by short-circuit and/or
(FU1, FU2, FU3) any other electrical failure in the DC power or the Solenoid Valve.
CSW-71C 14
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
2 INSTALLATION
2 INSTALLATION
<Warning about electric shock>
WARNING This cryocooler includes a high-voltage section. Touching it may result in electric shock. Handle it with extreme
care.
Make sure no power is applied to the compressor unit before starting the installation. Failing to observe this precaution
may result in electric shock.
Do not install the equipment near places subject to condensation such as a watering place. Failing to observe this
precaution may result in electric shock or malfunction.
Do not install the equipment in a dusty environment. Failing to observe this precaution may result in electric shock
or malfunction.
Make sure the power specification of the cryocooler used conforms to the customer's power supply before using the
equipment. Using the cryocooler with a non-conforming power supply may result in electric shock or malfunction.
If the compressor unit used is the CSW-71D (water cooled, high voltage type), pay attention to the setting of the
applicable input supply voltage. The product is shipped with the input supply voltage set to 480V. Before installing
the equipment, be sure to check your supply voltage and change it to the appropriate setting if necessary. Operating
the equipment with your supply voltage different from the setting of the compressor unit may result in electric shock or
malfunction.
Make sure no power is applied to the compressor unit before starting operation when connecting or disconnecting the
cold head power cable. Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power source before connecting
or disconnecting the input power cable to the Compressor Unit, and then remove the input power cable from the main
power. Failing to observe this precaution may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under any circumstances.
Failing to observe this precaution may result in electric shock.
The minimum bending radius of the flex lines is 150mm (intermediate), 300 mm (terminal). Bending the flex lines at
a smaller angle may cause explosion or escape of gas, and so this should be avoided.
Do not disassemble the equipment for purposes other than maintenance specified in this service manual under any
circumstances. Disassembling the equipment may result in electric shock, explosion or escape of gas.
Install the cryocooler in the ventilated area, otherwise it may result in asphyxiation in case the helium gas is purged or
leaked.
Do not put the heat sensitive or flammable object neat the Compressor Unit, or result in fire, injury or malfunction of the
WARNING system.
CSW-71C 15
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
2 INSTALLATION
This cryocooler is intended for the exclusive use indoors. It cannot be used outdoors. Failing to observe this
precaution may prevent the cryocooler from operating normally.
Do not use inverter for the main power source of the compressor unit. Operating with inverter may result in the
damage or malfunction of the compressor electric circuit.
Avoid using the transformer for the main power source of the compressor unit. If the transformer is installed at the
upstream of the unit, lacking phase protection circuit with the cryocooler occurs in a malfunction. That may result in
misoperation or malfunction. When using the transformer, install the other lacking phase protection device in
upstream of the transformer.
Do not get on the compressor unit or put an object on top of it. Failing to observe this precaution may prevent the
cryocooler from operating normally or cause injury.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing to secure enough
space may result in misoperation or malfunction. (See the technical instruction of the compressor unit used, for
details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water with appropriate
temperature, flow rate and water quality. Using inappropriate cooling water may result in misoperation or
malfunction. (See the technical instruction of the compressor unit used, for details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), do not use the demineralized water for
cooling water. Using demineralized water for cooling water may result in water leakage or malfunction. (See the
technical instruction of the compressor unit used, for details.)
Be sure to check the flat rubber gasket of the self seal coupling of the cold head and compressor unit for dirt, dust or
to see whether the flat rubber gasket is attached correctly, before connecting the flex lines. Connecting the flex lines
with an abnormal flat rubber gasket setting may cause escape of gas.
This cryocooler (cold head, compressor unit, compressor adsorber, flex lines) is shipped with a helium gas at about
1.62 MPa sealed in. Be sure to adjust the pressure to an appropriate value according to the cold head used before
operating the equipment. Using the cryocooler at an improper pressure may cause misoperation.
Pay attention to the contamination when charging a helium gas. The contamination may result in occurrence of the
noise from the Cold Head or decreasing the cooling capacity.
CSW-71C 16
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
Avoid using the transformer for the main power source of the compressor unit. If the transformer is installed at the
upstream of the unit, lacking phase protection circuit with the cryocooler occurs in a malfunction. That may result in
misoperation or malfunction. When using the transformer, install the other lacking phase protection device in
upstream of the transformer.
Secure enough space around the compressor unit for heat radiation and maintenance. Failing to secure enough
space may result in misoperation or malfunction. (See the technical instruction of the compressor unit used, for
details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water with appropriate
temperature, flow rate and water quality. Using inappropriate cooling water may result in misoperation or
malfunction. (See the technical instruction of the compressor unit used, for details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), do not use the demineralized water for
cooling water. Using demineralized water for cooling water may result in water leakage or malfunction. (See the
technical instruction of the compressor unit used, for details.)
・ An almost level and even area in the field will be selected to install the Compressor Unit.
・ An area to be influenced by splashing water and/or dusts will not be selected to install the
Compressor Unit installation area.
・ A clean environmental condition without dirt and/or free from an exhausted heat will be selected to
install the Compressor Unit in the field.
・ A quality of cooling water will be secured to use for an appropriate coolant for the Compressor Unit.
・ Any heat sensitive object cannot be positioned on surroundings of the Compressor Unit.
POWER SOURCE
Ensure the correct AC power source is available for the compressor. See Table 1.1 for the power
requirements for your system.
COOLING WATER
Ensure the correct cooling water is available for the compressor. See Figure 1.1 and Table 1.2. for
the cooling water requirements for your system.
Operating with Antifreeze (50/50 % mixture of water and ethylene glycol), the flow rate shall be larger
than the water. See Figure 1.1 and Table 1.2. for the cooling water requirements for your system.
SERVICE AREA
The Compressor Unit should have enough space as shown in Figure 2.1.
CSW-71C 17
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
CSW-71C 18
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power source before connecting
or disconnecting the input power cable to the Compressor Unit, and then remove the input power cable from the main
power. Failing to observe this precaution may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under any circumstances.
Failing to observe this precaution may result in electric shock.
Avoid using the transformer for the main power source of the compressor unit. If the transformer is installed at the
upstream of the unit, lacking phase protection circuit with the cryocooler occurs in a malfunction. That may result in
misoperation or malfunction. When using the transformer, install the other lacking phase protection device in
upstream of the transformer.
“IMPORTANT”
This cryocooler is provided with a phase reverse protection circuit for the input power. If the input
power is connected with reverse phase, the cryocooler does not start.
“IMPORTANT”
See “ELECTRICAL SCHEMATIC” of CSW-71C Compressor Unit, for detail.
“IMPORTANT”
See “INPUT POWER CABLE LV” of “DRAWINGS” for detail.
Upstream Protection
Use the fuses or circuit breakers as upstream protection of L1, L2, L3. The recommended rating of
the protection is maximum 60A.
CSW-71C 19
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
See the Table 1.1 for power requirements. The cables are marked with label and connect as follows:
For
Compressor Unit
WIRING DIAGRAM
FIELD GROUNDING
TEMINAL TEMINAL
For User's L1 L2 L3
Power Source
L1
L2
L3
Ground
CSW-71C 20
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
3 MAINTENANCE
3 MAINTENANCE
<Warning about electric shock>
WARNING This cryocooler includes a high-voltage section. Touching it may result in electric shock. Handle it with extreme
care.
Make sure no power is applied to the compressor unit before starting the installation. Failing to observe this precaution
may result in electric shock.
Be sure to turn off and Lock Out with OFF position the main power of the customer's power source before connecting
or disconnecting the input power cable to the Compressor Unit, and then remove the input power cable from the main
power. Failing to observe this precaution may result in electric shock.
Do not change the setting of the dial above the main power switch of the compressor unit under any circumstances.
Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the customer's main power before performing maintenance work
such as replacement of fuses. Failing to observe this precaution may result in electric shock.
Do not disassemble the equipment for purposes other than maintenance specified in this service manual under any
circumstances. Disassembling the equipment may result in electric shock, explosion or escape of gas.
The cold head, compressor unit, compressor adsorber and flex lines are pressurized with helium gas. Purge the
helium gas from all pressurized components before disposing. Open the purging valve gradually or it may result in
serious injury.
When scrapping the CryoCooler, handle it as Industrial Waste and pass it over to legally qualified disposer.
Install the cryocooler in the ventilated area, otherwise it may result in asphyxiation in case the helium gas is purged or
leaked.
The Adsorber weight is about 11.0kg. When replace the adsorber, be careful of handling so that it may not get hurt.
WARNING
Secure enough space around the compressor unit for heat radiation and maintenance. Failing to secure enough
space may result in misoperation or malfunction. (See the technical instruction of the compressor unit used, for
details.)
If the compressor unit used is a water-cooled type (CSW-71C, CSW-71D), use cooling water with appropriate
temperature, flow rate and water quality. Using inappropriate cooling water may result in misoperation or
malfunction. (See the technical instruction of the compressor unit used, for details.)
The cold head drive switch provided with the compressor unit is only used for maintenance. Be sure to turn it OFF
in normal operation. Using the compressor unit with the cold head drive switch turned ON may result in
misoperation or malfunction.
CSW-71C 21
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
CSW-71C Compressor Unit is to be required the routine maintenance. The basic maintenance work is to
replace the oil mist Adsorber of the Compressor Unit for every 20,000 Hrs operation as mentioned
Table 3.1.
CSW-71C 22
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
Do not disassemble the equipment for purposes other than maintenance specified in this service manual under any
circumstances. Disassembling the equipment may result in electric shock, explosion or escape of gas.
The cold head, compressor unit, compressor adsorber and flex lines are pressurized with helium gas. Purge the
helium gas from all pressurized components before disposing. Open the purging valve gradually or it may result in
serious injury.
When scrapping the CryoCooler, handle it as Industrial Waste and pass it over to legally qualified disposer.
Install the cryocooler in the ventilated area, otherwise it may result in asphyxiation in case the helium gas is purged or
leaked.
The Adsorber weight is about 11.0kg. When replace the adsorber, be careful of handling so that it may not get hurt.
WARNING
The Oil Mist Adsorber is required to replace for every 20,000 Hrs operation.
TOOLS REMARKS
1 1“ open-end wrench For Aero-quip coupling
2 1-1/8“ Open-end wrench For Aero-quip coupling
3 1-3/16“ Open-end wrench For Aero-quip coupling
4 Snoop liquid For leak check
5 Cotton wipers For leak check
6 13 mm Open-end wrench For fixing nut for Adsorber
7 Screw driver (phillips(+)) For side panel of Compressor Unit.
CSW-71C 23
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
PREPARATION
1) Shut down the Cryocooler.
2) Disconnect the Input Power Cable from the Compressor Unit.
3) Disconnect the Supply and Return Flex Lines from the Compressor Unit.
3) Remove the Nut secured the Adsorber to Rear Panel. Use two wrenches.
CSW-71C 24
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
4) Remove the Nut and Washer secured the Adsorber to the base panel of the Compressor Unit.
CSW-71C 25
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
2) Secure the Adsorber to the base panel of the Compressor Unit by tightened Nut and Washer.
Tightening Torque: 14.5 Nm
5) Sprinkle “Liquid Leak Detector” on the Flex line connecting coupling, in case the bubbling is found,
tighten the connecting coupling again and re-check the leakage.
Ensure that the pressure gauge indication is specified value for the type of Cold Head. Charge
the helium gas, in case of low pressure indicating.
CSW-71C 26
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
Do not change the setting of the dial above the main power switch of the compressor unit under any circumstances.
Failing to observe this precaution may result in electric shock.
Be sure to turn off and Lock Out with OFF position the customer's main power before performing maintenance work
such as replacement of fuses. Failing to observe this precaution may result in electric shock.
Fuses are equipped inside of the Fuse Box for the Control Box.
1) Loosen the screws that hold the compressor side panel, and remove the panel.
FU3
FU2
FU1
CSW-71C 27
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
APPENDIX
APPENDIX
ELECTRICAL SCHEMATIC
DRAWINGS
CSW-71C 28
TECHNICAL INSTRUCTION Sumitomo Heavy Industries, Ltd.
REVISION CONTROL
REVISION CONTROL
Manual
Revision Remarks Date
No.
-A Publication of first edition. DEC. 10 / 1999
-B Change the Electrical Schematic Diagram. APR. 4 / 2000
-C Delete the description of “water temp. alarm signal“. JAN. 11 / 2001
-D Change the SHI address. JAN. 25 / 2001
-E Delete the description of spare fuse. JAN. 30 / 2001
-F Change the Electrical Schematic Diagram. FEB. 19 / 2001
-G Change the specification of power requirement. MAR. 21 / 2001
Add the specification of recommended power
-H APR. 1 / 2002
requirement and description of demineralized water.
-I Change the dimension. MAY 31 / 2002
Correct the descriptions of Input Power Cable
-J JUL 11 / 2002
Connection.
-K Add the transformer-use CAUTION FEB. 28 / 2003
CD32ZZ-068 -L Change the division name. JUNE 9 / 2003
Add the description for the RDK-408D2 and S2
-M DEC. 18 / 2003
Cold Head.
The information of the SHI inquiries and
typographical error was corrected.
-N JAN. 12 / 2006
The descriptionof the Cooling Water requirement
was revised.
Electrical Schematic (2/2) was corrected.
-P Add the specification for the D-Sub Connector lock AUG 21 / 2008
screw tighten torque.
-Q The Humidity Range was added. DEC. 1 / 2009
CSW-71C