Contents
Contents
1. For Your Safety ....................................................................................................................... 29
1.1. Safety Symbols used in this Manual...................................................................................... 29
2. Intended Use ........................................................................................................................... 30
3. Product Description ................................................................................................................ 30
4. Product Features ..................................................................................................................... 30
5. Indicating and Control Elements ...................................................................................... 31
6. Electrical Connections and Installation .......................................................................... 32
7. Dräger REGARD 2400 / 2410 and Catalytic Bead Sensors ................................... 37
8. Accessories ............................................................................................................................... 37
8.1. Installation of a Semi-Bridge Converters.............................................................................. 37
8.2. Polytron EC Transmitter to Dräger REGARD 2410 via a Safety Barrier ...................... 38
8.3. Digital Inputs............................................................................................................................... 39
8.4. RS485 Output Terminal Dräger REGARD 2400 / 2410 ............................................... 39
8.5. Configuration Set Dräger REGARD 2400 / 2410 ............................................................ 39
9. I/O Module ............................................................................................................................... 40
10. Relay Module ........................................................................................................................... 41
11. The Dräger REGARD 2400 / 2410 Menu ...................................................................... 43
11.1. The Menu Flow-Chart ............................................................................................................... 43
12. Configuration .......................................................................................................................... 47
13. Maintenance .............................................................................................................................. 47
13.1. Inhibit............................................................................................................................................ 47
13.2. Adjustment of the Semi-Bridge Converter for SE Ex Sensing Heads ........................... 47
13.3. Potentiometers and Test Points at the Converter .............................................................. 49
14. Technical Data ........................................................................................................................ 50
15. Order List .................................................................................................................................. 53
Zulassungen / Appovals........................................................................................................ 54
Konformitätserklärung / Decaration of Conformity...................................................... 57
28
For Your Safety
Maintenance
The control unit must be inspected and serviced regularly by trained service personnel. Repair
of the control unit may only be carried out by trained service personnel. We recommend that a
service contract be obtained with Dräger Safety and that all repairs also be carried out by
them. Only authentic Dräger spare parts may be used for maintenance.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in physical
injury.
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in damage to
the product.
Furthermore, there are more general notes which are indicated as follows:
29
Intended Use
Product Description
Product Features
2. Intended Use
The Dräger REGARD 2400 / 2410 is used to monitor combustible, toxic, and/or other gases
and to control alarm signals, display units and other devices via alarm relays.
DANGER
Dräger REGARD 2400 / 2410 must not be used and is not approved for use in areas where
flammable and explosive gas mixtures may occur. Danger of explosion!
3. Product Description
Dräger REGARD 2400 / 2410 is a freely programmable controller unit for the connection of
up to four transmitters. Gases of different types can be monitored. The unit can be operated
with 1 or 2 alarm thresholds. Depending on the version, Dräger REGARD 2400 / 2410 provi-
des up to six relays. Four of these can be set according to the customer requirements; two
relays are fixed - one for activating an acoustic alarm (e.g. horn) and one for indicating fault
conditions.
4. Product Features
— Suitable for DIN rail mounting or wall mounting
— Supply voltage 24 VDC / 110 VAC / 230 VAC
— Up to four 4...20 mA transmitter or Pellistor sensing heads
— 1 fault signal via relay
— 1 horn contact via relay
— Up to 2 alarm signals via relays
— Up to 2 freely adjustable alarm thresholds
— Latching, hysteresis or pulse outputs
— Display of current gas reading
— Test function for output relays
— Line-break and short-circuit monitoring of sensor wiring
— 1 reset button for horn and alarms
— LEDs for alarm, horn and fault
— Communication port for optional modules
— 2 digital inputs
30
Indicating and Control Elements
18 35
Power Reset
A2 x10 Horn Error
A1
Channel A B C D
Concentration
F1 F2 A B C
REGARD 2410 D
00233025_01.eps
1 17
31
Electrical Connections and Installation
DANGER
Mains voltage (230 V, 50 Hz)
Contact with this voltage can cause serious burns or even death.
Work on electrical circuits shall only be carried out by a quallified electrician. Disconnect the
mains voltage before installation!
WARNING
The VDE regulations, the local accident-prevention regulations and these instructions for
use must be observed al all times!
The installation of the control unit shall be done in accordance with industrial standard fixed
cable such as NYM-J, 3 x 1.5 mm2. The supply voltage for the control unit must be equipped
with a separate fuse (maximum 1 A).
18 35
+ S – + S – + S – + S – + D1 – + D2 –
Channel A Channel B Channel C Channel D Digital Digital
Input Input
Power supply
24 V DC
Alarm 1
Alarm 2
Error
Horn
+ – A B COM
00333025_01.eps
1 17
32
Electrical Connections and Installation
The table shows the connection on the terminals of the Dräger REGARD 2410 / 2410.
Terminal Description
1 +24 V
24 VDC Input
2 0V
3 A
4 RS485 Interface B
5 COM
6
Fault norm. closed
7
8
Alarm 1 norm. closed
9
10
Alarm 2 norm. closed
11
16
Horn norm. open
17
18 +24 V
19 Channel A signal
20 0V
21 +24 V
22 Channel B signal
23 0V
24 +24 V
25 Channel C signal
26 0V
27 +24 V
28 Channel D signal
29 0V
30 +24 V
31 Digital Input D1
32 0V
33 +24 V
34 Digital Input D2
35 0V
33
Electrical Connections and Installation
00433025_01.eps
123 456
A B COM + D HU GND optional: 0V 24VDC
— When switched on, Dräger REGARD 2400´s error- and alarm relays are normally energi-
zed and contacts 8-9, 11-12, 14-15 are open. The horn relay remains unchanged when
switched on (factory set configuration).
— All relays are freely configurable via software.
DANGER
Mains voltage (230 V, 50 Hz)
Contact with this voltage can cause serious burns or even death.
Work on electrical circuits shall only be carried out by a quallified electrician. Disconnect the
mains voltage before installation!
WARNING
The VDE regulations, the local accident-prevention regulations and these instructions for
use must be observed al all times!
34
Electrical Connections and Installation
24 V DC 110/230 V AC N
Output Input L
24 V DC GND
B1 B2
Input +24 V (N) (L)
Error Alarm 2 Alarm 1 Horn
Channel Channel
C D
19 20 21 22 23 24
00533025_01_en.eps
Channel Channel
A B
123 456 7 8 9 10 11 12 13 14 15 16 17 18 N L
A B COM + D HU GND optional: 0V 24VDC
35
Electrical Connections and Installation
The table shows the connection on the terminals of the Dräger REGARD 2400.
36
Dräger REGARD 2400 / 2410 and Catalytic Bead Sensors
Accessories
8. Accessories
8.1. Installation of a Semi-Bridge Converters
Only Dräger REGARD 2400
The catalytic sensor in the Polytron SE Ex forms one half of a Wheatstone bridge while the
converter board has to provide the second half of this bridge. Therefore it is necessary to use
a semi-bridge converter (Part No. SC00016), if one or more Polytron SE Ex sensing heads are
connected to a Dräger REGARD 2400. Thus the converter powers the sensor and converts
the semi-bridge signal into a 4...20 mA signal, suitable for internal processing within the Drä-
ger REGARD 2400.
Procedure:
● Switch off the supply voltage.
● Remove the short-circuit strap and insert the converter.
Channel D
Channel C
Channel B
Channel A
00633025_01.eps
* (Polytron SE Ex sensors)
37
Accessories
230 VAC
24 VDC
A 12 7 + GND
+
Polytron –
B 10 9
GND
2
00733025_01_en.eps
Safety Barrier
e.g. Stahl 9160/13-11-11
When using Safety Barriers from other suppliers, it is recommended that you refer to the
Installation and Operating manual of the specific Safety Barrier being used.
* EC Transmitter: A transmitter for electrochemical sensors for the detection of toxic gases or oxygen.
38
Accessories
A maximum of 4 modules can be connected via the 2nd RS485 port to one Dräger REGARD
24xx unit.
Possible combinations:
Dräger
REGARD 2400/2410 I/O Modul Relay Modul
Number of modules 1 1 0 to 3
1 0 0 to 4
39
I/O Module
9. I/O Module
18 35
A B Com A B Com S1 0V S2 0V S3 0V S4 0V S5 0V S6 0V
RS 485 Analog Output 4...20 mA
00833025_01_en.eps
1 17
The I/O module (input-output module) has 6 digital inputs and 6 analog outputs. The module
communicates with the Dräger REGARD 2400 / Dräger Regard 2410 via the RS485 connec-
tion.
To connect the module with the Dräger REGARD 24xx the terminals A / B / COM must be
used.
The module needs a seperate 24 VDC supply.
Digital Inputs: The digital inputs can be used as an alarm function or horn reset. For the alarm
function 2 alarms can be configured with a low or high signal. For the horn reset it's possible
to configure a rising or falling signal.
Analog Outputs: Each output can be configured as a 4... 20 mA output to every channel. It is
also possible to set an output to control the power supply.
40
Relay Module
Relay module
00933025_01.eps
The Relay module has 12 free programmable relays. The Relay module makes it possible to
create single alarms. The module communicates with the Dräger REGARD 2400 / 2410 via
the RS485 connection.
To connect the module with the Dräger REGARD 2400 / 2410 the terminals A / B / COM
must be used.
The module needs a seperate 24 VDC supply.
The configuration of the module is done via Configuration Software.
For configuration details please refer to the Software Configuration Instructions.
Possible combinations:
Dräger
REGARD 2400/2410 I/O Module Relay Module
Number of modules 1 1 0 to 3
1 0 0 to 4
41
Relay Module
Module address
0 0
1 1
01033025_01.eps
address
0 0
4 This represents module one
1 1
1 0
5 This represents module two
0 1
0 1
6 This represents module three
1 0
1 1
7 This represents module four
0 0
IMPORTANT NOTICE:
When an I/O module is installed the addressing of the relay modules must be 1 to 3 only.
The configuration address in the configuration software and the relay modules must be the
same.
42
The Dräger REGARD 2400 / 2410 Menu
INHI: Inhibit mode. Freezing all relays at the current status for a time of 20 minutes. Pass-
word protected.
MOFF: Average value Off. Freezing the average values for the next 20 minutes. Password
protected.
TOUT: Testing the output relays. Password protected.
SOFT: Showing the Software Version.
MOD: Showing communication details like address (MADR), serial comunication (MCON)
and baud rate (MBAU).
LOG: Showing the status of the datalogger.
On the following 3 pages the menu-structure of the Dräger REGARD 2400 / 2410 is descri-
bed.
To get to the different menu point the buttons F1, F2 or F1+F2 (together) have to be used.
43
The Dräger REGARD 2400 / 2410 Menu
Menu
Value
F1 F2 Error F1+F2
INHI Inhibit Function
Code
Inhibit Function F1+F2 OK Activated
F1 F2 Error F1+F2
MOFF Average Value
Code
Average Value OFF F1+F2 OK OFF
F1 F2 Error F1+F2
TOUT Sub Menu
Code
Relay Test F1+F2 OK Relay Test
F1 F2 F1+F2
SOFT V2.1
Software Version F1+F2 Software Version
F1 F2 F1+F2
MOD Sub Menu
Modbus Slave Setting F1+F2 Modbus Slave
F1 F2
01133025_01_en.eps
F1+F2
LOG L OK OK
Logger Status F1+F2 L ER ERROR
44
The Dräger REGARD 2400 / 2410 Menu
Relay-Test-Menu
F1+F2 x current conditon
L de-energized
F2 H energized
T1 x
Alarm relay 1
F1+F2
F1
F2
T2 x
Alarm relay 2
F1+F2
F1
F2
THUx
Horn relay
F1+F2
F1
01233025_01_en.eps
F2
TERx
Error relay
F1+F2
F1
45
The Dräger REGARD 2400 / 2410 Menu
Configuration-Information-Menu
F2
A No A1Hy A2Hy R2 x
Number of * Hysteresis * Hysteresis
threshold 1 F2 threshold 2 F2 Function relay 2 F2
measuring gas
F1 o. F2 F1 F1
HU x
A Sp Linkage to alarm F2
Max range relays
F1 o. F2 F1
01333025_01_en.eps
A Mi HUxx
* Interval of Time function of
average value horn relay
F1 o. F2 * : depending on the variant and settings F1 o. F2
46
Configuration
Maintenance
12. Configuration
The configuration of the Dräger REGARD 2400 / 2410 is done by configuration software.
CAUTION
After any work with the configurration software the programming of the unit must be tested
at the control unit!
13. Maintenance
13.1. Inhibit
The "Inhibit" function on the Dräger REGARD 2400 / 2410 locks all relays while calibrating or
configuring the unit. The "Inhibit" mode will reset itself automatically after 20min. To activate
"Inhibit" see Flow-Chart on page 44.
47
Maintenance
48
Maintenance
Potentiometer +
„Adjust sensor sensitivity“
–
Potentiometer +
„Adjust sensor zero“
–
Potentiometer –
01433025_01_en.eps
„Adjust sensor supply current“ – Measuring point converter current
+ +
49
Technical Data
50
Technical Data
51
Technical Data
I/O Module
Supply Voltage d.c. 24 VDC ±10 %
Power Consumption Approx. 3 W
Communication RS485
Input 6 digital inputs
Output 6 analogue outputs
Ambient Conditions Temperature: –20 oC to 60 oC
Relative Humidity: 10 % to 90 % r.h.
Cable Terminals Screw terminals for
solid wires up to 4 mm2 or
stranded wires up to 2.5 mm2
Dimensions (H x W x D) 90 mm x 105 mm x 72 mm
Case Material Plastic
Protection IP20
Relay Module
Supply Voltage d.c. 24 VDC ±10 %
Power Consumption Approx. 6 W
Communication RS485
Output Relays 12 freely configurable relays
Relay Contacts potential-free
50 VAC, 2 A
Ambient Conditions Temperature: –20 oC to 60 oC
Relative Humidity: 10 % to 90 % r.h.
Cable Terminals Screw terminals for
solid wires up to 4 mm2 or
stranded wires up to 2.5 mm2
Dimensions (H x W x D) 160 mm x 84 mm x 60 mm
52
Order List
53
Zulassungen / Appovals
Zulassungen / Appovals
54
Zulassungen / Appovals
55
Zulassungen / Appovals
56
Zulassungen / Appovals
57
Konformitätserklärung / Decaration of Conformity
58
Dräger Safety AG & Co. KGaA
Revalstraße 1
D-23560 Lübeck
Germany
Tel. +49 451 8 82- 0
Fax +49 451 8 82- 20 80
www.draeger.com