PLC Generador Kipor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Harsen®

Manual

GU601A
Genset Controller

HM1001ER1
Manual HM1001ER1 The interpretation of the Symbol

The interpretation of the Symbol:

WARNING:
A WARNING indicates a potentially hazardous situation which, if not
avoided, could result in death, serious personal injury or property
damage.

CAUTION:
A CAUTION indicates a potentially hazardous situation which, if not
avoided, could result in damage to equipment or property.

NOTE:
A NOTE provides other helpful information that does not fall under the
warning or caution categories.

Harsen® I
Manual HM1001ER1 The interpretation of the Symbol

WARNING:
Read this entire manual pertaining to the work to be performed before
installing, operating, or servicing this controller. Practice all plant and
safety instructions and precautions. Failure to follow instructions can
cause personal injury and/or property damage.

The engine or other type of prime mover should be equipped with an


overspeed shutdown device to protect against runaway or damage to
the prime mover with possible personal injury, loss of life, or property
damage.

The overspeed shutdown device must be totally independent of the


prime mover control system. An over temperature or low pressure
shutdown device may also be needed for safety, as appropriate.

CAUTION—BATTERY CHARGING
To prevent damage to a controller that uses an alternator or battery-
charging device, make sure the charging device is turned off before
disconnecting the battery from the system.

Controllers contain static-sensitive parts. Observe the following


precautions to prevent damage to these parts:

Do not disassemble the rear back of controller or touch the


components and conductors on a printed circuit board.

Harsen® II
Manual HM1001ER1 History

History

No. Rev. Date Editor Validation Changes

1 HM1001ER1 2011.1.1 P.L New

Harsen® III
Manual HM1001ER1 Contents

Contents

1. Description……………………………………………………………………………………………………1

2. Outline Dimension Drawings and Controller Wiring……………………………………………………


2
3. Panel Operation………………………………………………………………………………………………5

4. Installation Guide…………………………………………………………………………………………… 6

5. Control and Operation Instruction…………………………………………………………………………


7
6. Measure and Display Data…………………………………………………………………………………11

7. Pre-alarm and Shutdown Alarm……………………………………………………………………………


12
8. Parameter Settings…………………………………………………………………………………………16

9. LCD Display and Menu System……………………………………………………………………………


22
10. Preparation before Starting the Controller………………………………………………………………
25
11. Technical Specification………………………………………………………………………………………
26

Harsen® IV
Manual HM1001ER1 Description

1. Description

The GU601A is an Auto Control and Safety Protect Module for Genset. Either AUTO or MAN mode can
be chosen through the panel push button. When the controller is running in MANUAL mode, the Start
and Stop push buttons control the starting of the Genset. In AUTO mode, the preset “remote start
signal” controls the Genset. The module displays operational status and parameters on the front panel
LCD. Its main characteristics as below:

l Adopts MPU as core.


l The protective parameters can be configured neatly through the panel push button and LCD.
l Measure and display parameters, such as frequency and voltage of generator, battery voltage, oil
pressure, coolant temperature and running hour of the engine.
l Set fuel mode (N.C. or N.O.) via procedure.
l 5 relay control outputs, except for fuel and start (crank) relay output, the rest are configurable.
l 5 digital inputs, except for oil pressure and engine temperature, the rest are configurable.
l With optional modes of built-in P/T-sensor for user.
l Equipped with built-in communication interface to configure parameters by PC.
l All connections of controller are by secure plug and socket, for ease and convenience to connect,
move, maintain and replace the device.

This manual is only suitable for GU601A Intelligent Controller, user must carefully read this
manual first.

Harsen® Page 1/26


Manual HM1001ER1 Outline Dimension Drawings and Controller Wiring

2. Outline Dimension Drawings and Controller Wiring

2.1 Following Details:

Module Dimensions W88mm×H75mm


Panel Cutout W78mm×H65mm
Thickness D48mm (without connection)

Harsen® Page 2/26


Manual HM1001ER1 Outline Dimension Drawings and Controller Wiring

2.2 Terminal Connections:

Pin no. Function Description Signal Dim


1 Phase voltage input 1mm²
0-300Vac
2 Neutral 1mm²
3 LOP sensor or switch signal LOP sensor (<2KΩ) 1mm²
4 HET sensor or switch signal HET sensor (<2KΩ) 1mm²
5 Configurable digital input signal 1 low level is active 1mm²
6 Configurable digital input signal 2 low level is active 1mm²
7 Configurable digital input signal 3 low level is active 1mm²
8 Fuel solenoid relay output N.O. contact, 3A/30Vdc 1mm²
9 Start (Crank) relay output N.O. contact, 3A/30Vdc 1mm²
10 Configurable output relay 1 N.O. contact, 3A/30Vdc 1mm²
11 Configurable output relay 2 N.O. contact, 3A/30Vdc 1mm²
12 Configurable output relay 3 N.O. contact, 3A/30Vdc 1mm²
13 Charge excitation power output if not used, do not connect to negative 1mm²
14 Battery supply (+B) 1mm²
12V/24V (8-35Vdc continuous)
15 Battery supply (-B) 1mm²

NOTE:
l Pin no. “3” and “4” is for “LOP sensor or switch signal” and “HET sensor
or switch signal” input respectively. Either switch or sensor can be
chosen. When sensor is used, according to the actual situation, increase
the cross section area of cable to reduce the cable resistance from
controller to engine, to ensure the accuracy of measured values for both
oil pressure and engine temperature.

CAUTION:
l If pin no. “13” is not used, DO NOT connect to negative.

Harsen® Page 3/26


Manual HM1001ER1 Outline Dimension Drawings and Controller Wiring

2.3 Typical Wiring Diagram


LOAD

CONFIG. INPUT
COOLANT TEMP.

OIL PRESSURE
CONFIG. OUTPUT
GU601A
CRANK
FUEL

DC POWER
(12/24V)

Fuse protection with a rating of 0.5A must be provided externally to the Controller.

Harsen® Page 4/26


Manual HM1001ER1 Panel Operation

3. Panel Operation

The operation panel consists of 3 sections: LCD display indicating measurement parameters, LED
indicator for common failure, and push buttons for Genset and selection of control modes.

The LCD circularly displays different measuring parameters. When failure occurs, LCD displays the
corresponding fault icon. LCD also has a backlight so that the operator can clearly read information day
or night. After pressing any button the backlight will automatically turn off in a certain time.

The LCD display and its control push buttons provide a friendly operation interface for the operator to
conveniently read information and parameter setting.

3.1 Control buttons and LEDs

Function Description Tag

Scroll Button
Enter into submenu / Modify / confirm modification / scroll menu to
display.

AUTO Mode Button / LED


The push button is used for selecting “AUTO mode”. When the
controller is running in AUTO mode, the LED above the push button
illuminated. The activation and deactivation of the “remote start signal
input” controls the starting and stopping of the Genset.

MAN Mode Button / LED


The push button is used for selecting “manual mode”. When the
controller is running in MANUAL mode, the LED above the push button
illuminated. The Start and Stop push buttons control the starting and
stopping of the Genset..
START / VALUE INCREASE “+” Push Button
The push button is used for manually start the Genset .When the
controller is in MANUAL mode, press this push button to start the
generator.

When in parameter setting mode, this push button is used to increase


values.
STOP / RESET / VALUE DECREASE “-” Push Button
The push button is used for MANUALLY stops the Genset. When the
controller is in MAN mode, press and hold this button more than 2sec
to stop the Genset.

If failure occurs, press this button, the shutdown alarm lockout can be
cleared.

When in parameter setting mode, this push button is used to decrease


values.

COMMEN FAILURE LED


LED will flash when pre-alarm (Warning) occurs.
LED will illuminate permanently when shutdown alarm occurs.

Harsen® Page 5/26


Manual HM1001ER1 Installation Guide

4. Installation Guide

4.1 The cutout dimensional drawing installed on panel as above attached.

l The controller is fixed by 2 special fittings. The shock-proof equipment must be mounted if the
enclosure is mounted on Genset or other heavy vibrant device. A readily accessible disconnect
device shall be incorporated external to the equipment.

4.2 Please refer to the above Typical Wiring Diagram 2.3 for connection.

4.3 Installation of engine LOP and HET sensors:

Description Terminal
LOP sensor/ LOP switch 3 3 4
HET sensor/ temp switch 4
Sensor Com. Port Battery negative (Genset enclosure) GU601A CONTROLLER

CAUTION:
l Pin no. “3” and “4” is for “LOP sensor or switch signal” and “HET sensor
or switch signal” input respectively. Either switch or sensor can be
chosen. When sensor is used, according to the actual situation, increase
the cross section area of cable to reduce the cable resistance from
controller to engine, which ensures the accuracy of measured values for
both oil pressure and engine temperature.
l If both switches and sensors are required for oil pressure and engine
temperature, connect Pin no. “3” and “4” as above, and connect 2
configurable inputs to the switches of oil pressure and temperature, then
configure parameters by setting.

Harsen® Page 6/26


Manual HM1001ER1 Control and Operation Instruction

5. Control and Operation Instruction


The controller has 2 modes: AUTO and MANUAL.

5.1 Operation Mode Setting:

Operation Description

Press and hold the “AUTO” button for 2sec, the LED above the button
is illuminated; the controller is running in “AUTO” mode.

Press and hold the “MAN” button for 2sec, the LED above the button is
illuminated; the controller is running in “MAN” mode.

NOTE: Only 1 mode can be selected from above 2 modes.

5.2 AUTO control Sequence:

Controller is running in “AUTO” mode.


First of all, one of configurable inputs must be defined as Remote Start Signal.
When the remote start signal is active, the controller implements following procedure:

The Start delay timer is activated, when it times out the Preheat relay output is energized (if preheat
function selected), the timer starts. When it times out, the fuel relay output is energized, and operates the
fuel solenoid of the engine. After 300ms delay, the start (crank) relay output is energized; the start motor
engages and begins to crank. When the engine speed reaches the crank cutout RPM, the start relay
output is de-energized and the safety-on delay starts. When the safety-on times out, if the controller
detects that the parameters of the Genset such as voltage, frequency, oil pressure, coolant temperature
are normal, and no other failure is detected this indicates the Genset has successfully started and running
normally. The LCD displays the Genset Measuremen parameters.

NOTE:
l When remote signal is active, the start-delay timer is activated. During
this period, if remote start signal is inactive, the start delay timer
terminates immediately; the controller will recovers to the original standby
status.
l During cranking or idle period, if remote start signal is inactive, controller
stops the start procedure and recovers to original standby status.
l One configurable input must be set as “Remote Start Signal”, or it will not
implement the start procedure in “AUTO” mode.

NOTE:
l While cranking, engine ignites. The start motor will power off when the
output frequency of generator reaches the preset value (configurable
crank cutout value), or if there are one of the following conditions occur:
A. Generator’s voltage reaches 80% of rated voltage;
B. Cranking time’s up,
C. LOP switch is opened and the delay time’s up.
D. Oil pressure switch is opened or oil pressure is higher than crank
cutout value.
E. Cutout P-delay time’s up.
l Controller can not implement crank procedure if the frequency of
generator reaches the preset value (configurable cranking cutout value)
or LOP switch is opened.

Harsen® Page 7/26


Manual HM1001ER1 Control and Operation Instruction

CAUTION:
l To avoid damage to the start motor please make sure the generator’s
voltage is higher than the measurable value of controller while cranking,
since the crank cutout signal is sensed from the generator voltage and
frequency.

If you have selected idle function, the idle relay will be closed at the same time as the crank relay is
closed. The timers of idle and safety-on delay will begin counting down at the same time, and in priority
to display the shorter one on the LCD, and the following procedure is the same as above.

During the crank period, if the engine can not ignite and controller will not output start signal during crank
rest, Fail to Start icon on LCD flashes at this time. Once crank rest timer times out the start relay
energizes once again and will attempt to start engine again.

The above procedure will be repeated until engine successfully ignites or reaches the preset number of
crank attempt. However, if any shutdown alarm occurs during crank, controller will stop cranking
immediately and only can be restarted after clearing failure and reset.
Start Failure: when the above procedure repeats again and again and reaches the preset number of
crank attempt, the crank relay output is then de-energized. The failure LED illuminates and the LCD
displays Fail to Start.

CAUTION:
l If Fail to Start occurs, operator must check the whole Genset system to
find out failure reason, only after clearing the failure can press
“STOP/RESET” button to relieve fault lock out status, and restart the
Genset.

Generator shutdown sequence:


When the remote start signal is deactivated, the timer for cool down is activated, When it times out, the
fuel relay de-energizes, the timer for cool down is activated,

Stop Failure: When cool down times out, the fuel relay opens and the timer for Stop delay begins.
When it times out, if controller detects that the voltage and frequency of generator or oil pressure of
engine are greater than the preset values, the Fail to stop LED illuminates and the LCD displays Fail to
stop.

NOTE:
l After stop failure, the controller will not energize the crank relay output if
the failure has not been removed and the controller reset.

5.3 MAN control sequence:

Controller is in “MANUAL” mode.

Generator starting sequence:

Pressing “START” button the fuel relay energises, and operates the fuel solenoid of engine. After 300ms
delay, the start relay output is energized, the start motor engages and begins to crank. When the engine

Harsen® Page 8/26


Manual HM1001ER1 Control and Operation Instruction

speed reaches the crank cutout RPM, the start relay output is de-energized and the safety-on delay starts.
When the safety-on times out, if the controller detects that the parameters of the Genset such as voltage,
frequency, oil pressure and coolant temperature are normal, and no other failure is detected this indicates
the Genset has successfully started and running normally. The LCD displays the Genset Measurement
parameters.

5.4 The start and stop sequence of engine whose fuel solenoid is N. O. type:

Start control sequence:

During the starting sequence, the fuel relay of controller will not energize, fuel solenoid is no power, so
no signal is required for fuel solenoid to activate.

Stop control sequence:

During the stopping sequence, the fuel relay energizes, fuel solenoid is on power and energizes, and
the engine begins to stop. After a delay (same as stop delay) fuel relay de-energizes, disconnecting the
supply for the fuel solenoid.

Other control sequence is same as engine whose fuel solenoid is N. C. type.

5.5 Idle function:

For idle function configure one of the configurable outputs as idle.

Refer to the flow chart 5.7 for start and stop for idle control flows.

5.6 Preheat function:

For Preheat function, configure one of the configurable outputs as Preheat. The controller has 3
selectable preheat control modes as below:

Mode 1 — during preheat time, preheat relay output energizes.


Mode 2 — during preheat time, preheat relay output energizes until the successful ignition.
Mode 3 — during preheat time, preheat relay output energizes until safety-on delay times out.

During crank period, the Preheat relay output will not energize in any of above modes.

Refer to the flow chart 5.7 for start and stop for Preheat control flows.

When the Preheat relay output energizes, LCD displays the icon of preheat operating status:

Harsen® Page 9/26


Manual HM1001ER1 Control and Operation Instruction

5.7 Flow chart for start and stop

T1- start delay T4- safety-on delay


T2- crank time T5- idle time
T3- pre-heat time T6- stop delay

NOTE:
l If T4 is longer than T5, low oil pressure protection is ignored during T5.
l If T4 is shorter than T5, low oil pressure protection becomes effective
after T4 in T5.

Harsen® Page 10/26


Manual HM1001ER1 Measure and Display Data

6. Measure and Display Data

Gen AC phase voltage Vac


Generator frequency Hz
Engine speed RPM (signal derived from generator frequency)
Battery voltage Vdc
Genset Running hour Hour
Engine coolant temperature ℃/℉ (signal from engine HET sensor)
Engine oil pressure Bar / PSI (signal from engine LOP sensor)

Harsen® Page 11/26


Manual HM1001ER1 Pre-alarm and Shutdown Alarm

7. Pre-alarm and Shutdown Alarm

7.1 Pre-alarm (Warning)


NOTE: (Pre-alarms are non-critical failure conditions and do not affect the operation of the generator
system, they serve for drawing the operators’ attention to an undesirable condition so they can remove
it to ensure continuous running of the system. When Pre-alarms occur, the LED indicator flashes, but
failure will not be locked out and the unit will not shutdown. Once the Pre-alarm failure is removed the
Pre-alarm LED will automatically turn off.)

Pre-alarm / Description LCD Display

CHARGE FAILURE: After safety-on times up, if the charging voltage


from the excitation contact of alternator is lower than the “charge V
Pre-alarm”, the common failure LED indicator ( ) flashes, the LCD
displays charge failure icon:

BATT. UNDER VOLT: if controller detects that battery voltage has


fallen below the “Batt. Under volt”, common failure LED indicator
flashes. For example, “Batt. Under volt” preset as: 23.6V, when battery
voltage falls below this value, LCD flashing low value icon:

BATT. OVER VOLT: if controller detects that battery voltage has


exceeded the “Batt. Over volt”, common failure LED indicator flashes.
For example, “Batt. Over volt” preset as: 28.2V, when battery voltage
exceeds this value, LCD flashing high value icon:

LOW OIL PRESS: if controller detects that the engine oil pressure has
fallen below the “Oil-P low preALM” after the safety-on timer expired,
common failure LED indicator flashes. For example, “Oil-P low preALM”
preset as: 2.2BAR, when engine oil pressure falls below this value,
LCD flashing low value icon:

HIGH TEMP: if controller detects that engine coolant temperature has


exceeded the “high temp pre-alarm”, common failure LED indicator
flashes. For example, “high temp pre-alarm” preset as: 95℃, when
engine coolant temperature exceeds this value, LCD flashing high
value icon:

OVER SPEED: if engine speed exceeds the “Over SP preALM”,


common failure LED indicator flashes. For example, “Over SP
preALM” preset as: 1600RPM, when engine speed exceeds this value,
LCD flashing high value icon:

UNDER SPEED: if engine speed falls below the “Under SP preALM”


after the safety-on timer has expired, common failure LED indicator
flashes. For example, “Under SP preALM” preset as: 1440RPM, when
engine speed falls below this value, LCD flashing low value icon:

GEN. OVER VOLT: if controller detects that any phase output voltage
of generator has exceeded the “GEN-V over preALM” after the safety-
on timer has expired, common failure LED indicator flashes. For
example, “GEN-V over preALM” preset as: 253V, when the output
voltage of generator exceeds this value, LCD flashing high value icon:

Harsen® Page 12/26


Manual HM1001ER1 Pre-alarm and Shutdown Alarm

GEN. UNDER VOLT: if controller detects that any phase output voltage
of generator has fallen below the “GEN-V under preALM” after the
safety-on timer has expired, common failure LED indicator flashes. For
example, “GEN-V under preALM”” preset as: 198V, when the output
voltage of generator falls below this value, LCD flashing low value
icon:

AUXILIARY PRE-ALARM: if a configurable input is defined as pre-alarm,


when the input signal is active, common failure LED indicator flashes.
LCD displaying Aux. pre-alarm icon:

NOTE:
l To make “low oil pressure” and “high temperature” pre-alarm active, you
must use LOP sensor and HET sensor, if you only use LOP and HET
switches, both pre-alarms are inactive.

CAUTION:
l Under the period of safety-on delay, some pre-alarms are inactive, the
safety-on time must be carefully and properly set to make Genset have
full protection.

Harsen® Page 13/26


Manual HM1001ER1 Pre-alarm and Shutdown Alarm

7.2 Shutdown Alarm


NOTE: (shutdown alarm failures immediately lock out the system and stop the Genset. The failure must
be removed and the controller reset before restarting the Genset.)
Shutdown Alarm / Description LCD Display

START FAILURE: if engine does not fire after the preset number of
crank attempt has been made, the Shutdown alarm LED illuminates.
LCD displays “start failure” icon:

STOP FAILURE: if engine does not stop after the stop delay expired,
the Shutdown alarm LED illuminates. LCD displays stop failure icon:

EMERGENCY STOP: Configure a configurable input as emergency stop,


when the input signal is active, controller immediately stops all relay
control outputs except alarm, Genset is shut down, the Shutdown alarm
LED illuminates, LCD displays emergency stop icon:

LOW OIL PRESS: if controller detects that the oil pressure level still falls
below “Oil-P low Alarm” or LOP switch closes after the safety-on timer
has expired, engine stops immediately, the Shutdown alarm LED
illuminates. LCD displays low oil pressure icon:

ENGINE HIGH TEMP: if controller detects that engine coolant


temperature has exceeded the “Coolant Alarm” or HET switch closes,
engine stops immediately, the Shutdown alarm LED illuminates. LCD
displays high temperature icon:

OVER SPEED: if controller detects that engine speed exceeds “Over SP


Alarm”, engine stops immediately, the Shutdown alarm LED illuminates.
LCD displays over speed icon:

GEN. OVER VOLT: After safety-on delay times out, if controller detects
that the output voltage exceeds the “GEN-V over Alarm”, the engine
will be shut down immediately, the Shutdown alarm LED illuminates.

GEN. UNDER VOLT: After safety-on delay times out, if controller


detects that the output voltage of controller is lower than the “GEN-V
under Alarm”, the engine will be shut down immediately, the
Shutdown alarm LED illuminates.

AUXILIARY FAILURE: If a configurable input has been defined as


Shutdown Alarm, when the input signal is active, common failure LED
illuminates. LCD displays Aux. shutdown alarm icon:

Harsen® Page 14/26


Manual HM1001ER1 Pre-alarm and Shutdown Alarm

Code Table for Failure:


Code Name Code
CHARGE FAILURE ENGINE HIGH TEMP
BATT. UNDER VOLT OVER SPEED
BATT. OVER VOLT UNDER SPEED
START FAILURE GEN. OVER VOLT
STOP FAILURE GEN. UNDER VOLT
EMERGENCY STOP P-SENSOR OPEN
LOW OIL PRESS

NOTE:
l Engine speed signal is derived from generator output voltage frequency, it
is used for control and failure protection parameters, for convenience of
user, some data is expressed by RPM, RPM = Hz * 60 / pair of poles.
l While the Genset is running, if there is high coolant temperature, low oil
pressure or over speed failure the controller will shutdown it immediately
without delay. During the cool down period, if there is low oil pressure
failure, the controller will shut down the Genset immediately without
delay.

CAUTION:
l During the period of safety-on delay, low oil pressure protection is
inactive. To avoid starting an engine with no oil, you must make sure the
oil levels are normal and the the safety-on time shall be carefully and
properly set for the first commissioning.

Harsen® Page 15/26


Manual HM1001ER1 Parameters Setting

8. Parameters Setting
8.1 System Parameters:

NO. Items Preset Value Range


1.1 VT ratio 1.0 1.0-100.0
1.2 Rated ph-voltage 220 45-9999Vac
1.3 Startup mode 0 0-1 / 0 (MAN) / 1 (AUTO)
1.4 Oil pressure unit 0 0-1 / 0 (BAR) / 1 (PSI)
1.5 Temperature unit 0 0-1 / 0 (℃) / 1 (℉)
1.6 Comm. Address 1 1-247
1.7 Default settings
1.8 On-line update
1.9 Scroll time 0S 0-10 S / 0 (not used)

NOTE:
l For 1.3 Startup Mode, When parameter is configured as “1”, the
controller will be in AUTO mode when it is powered on; When parameter
is configured as “0”, the controller will be in Manual mode when it is
powered on.
l After the oil pressure and temperature units changed, the corresponding
failure alarm value must be reset according to actual situation.
l Engine speed is calculated by the number of “pair of poles”. RPM=Hz *
60 / pair of poles, when rated frequency is 50 Hz, if pair of poles set as
“2”, then running speed is 1500 RPM, if pair of poles set as “1” , then
running speed is 3000 RPM.

8.2 Generator Parameters:

NO. Items Preset Value Range


2.1 V under Alarm 0 20-200% / 0 (not set)
2.2 V under preALM 90% 20-200% / 0 (not set)
2.3 V over preALM 115% 20-200% / 9999 (not set)
2.4 V over Alarm 9999 20-200% / 9999 (not set)
2.5 Alarm delay 10S 0-600 S

8.3 Engine Parameters:


NO. Items Preset Value Range
3.1 Pair of poles 2 1-4
3.2 Fly wheel teeth 120 2-300
3.3 Fuel mode 0 0-1 / 0(NC) / 1 (NO)
3.4 T-sensor type 3 0-15 / 0 (not used)
3.5 P-sensor type 4 0-15 / 0 (not used)
3.6 Start delay 10S 0-300 S
3.7 Crank attempt 3 times 1-10 times
3.8 Crank time 5S 0-30 S
3.9 Crank rest 10S 0-300 S

Harsen® Page 16/26


Manual HM1001ER1 Parameters Setting

3.10 Crank cutout RPM 300RPM 1-9999 RPM


3.11 Crank cutout Oil-P 1.0BAR 0.1-150.0BAR/999.9(not set)
3.12 cutout P-delay 0 1-60 S / 0(not set)
3.13 Preheat delay 3S 0-300 S
3.14 Preheat mode 1 1-3
3.15 Idle delay 0 0-9999 S
3.16 Safety-on delay 10S 0-600 S
3.17 Cool down delay 300S 0-600 S
3.18 Stop delay 20S 0-60 S
3.19 Under SP Alarm 0RPM 0-9999 RPM / 0 (not set)
3.20 Under SP preALM 1440RPM 0-9999 RPM / 0 (not set)
3.21 Over SP preALM 1600RPM 1-9999 RPM / 9999 (not set)
3.22 Over SP Alarm 1710RPM 1-9999 RPM / 9999 (not set)
3.23 Oil-P low Alarm 1.1BAR 0-45.0 BAR
3.24 Oil-P low preALM 1.4BAR 0-45.0 BAR
3.25 Coolant preALM 92℃ 70-320℃ / 9999 (not set)
3.26 Coolant Alarm 100℃ 70-320℃ / 9999 (not set)
3.27 Batt. Undervolt. 8.0V 1.0-25.0V / 0 (not set)
3.28 Batt. overvolt. 28.0V 1.0-35.0V / 99.9 (not set)
3.29 Charge V Pre-alarm 8.0V 1.0-25.0V / 0 (not set)

8.4 Configurable Inputs and Outputs:


NO. Items Preset Value Range
4.1 Configurable input 1 8 0-12 (define code as 8.7)
4.2 Configurable input 2 7 0-12 (define code as 8.7)
4.3 Configurable input 3 12 0-12 (define code as 8.7)
4.4 Input 1 delay 2S 0-60 S
4.5 Input 2 delay 2S 0-60 S
4.6 Input 3 delay 2S 0-60 S
4.7 Configurable relay 1 2 0-80 (define code as 8.8)
4.8 Configurable relay 2 3 0-80 (define code as 8.8)
4.9 Configurable relay 3 5 0-80 (define code as 8.8)
NOTE: D-Input Delay is only for 1 to 4 codes in 8.7.

8.5 Calibration Menu:


NO. Items Preset Value Range
5.1 GEN. V1 offset ±10.0%
5.2 Pressure offset ±10.0%
5.3 Temperature offset ±10.0%
5.4 Batt. V offset ±10.0%

Harsen® Page 17/26


Manual HM1001ER1 Parameters Setting

8.6 The optional items for P/T-sensor:


Code The brand model of LOP sensor The brand model of HET sensor
0 not used not used
1 close for low oil pressure close for high temperature
2 open for low oil pressure open for high temperature
3 VDO 5 bar VDO 120 ℃
4 VDO 10 bar VDO 150 ℃
5 Datcon 7 bar Datcon
6 Murphy 7 bar Murphy
7 Pre-set 1 PT100
8 Pre-set 2 Pre-set 1
9 Pre-set 3 Pre-set 2
10 Pre-set 4 Pre-set 3
11 configured by user Pre-set 4
12 configured by user

NOTE:
l When the controller leaves factory, the optional types and functions of
LOP sensor and HET sensor have been preset as the above table. If the
using sensor is not listed in this table, the user can select “configurable”,
and write sensor parameters to controller via software.

l LOP sensor parameter addendum:


VDO 5 bar:
P(Bar) 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5
P(PSI) 0 7.3 14.5 21.8 29.0 36.3 43.5 50.8 58.0 65.3 72.5
R(Ω) 11 29 47 65 82 100 117 134 151 167 184

VDO 10 bar:
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R(Ω) 10 31 52 71 90 106 124 140 155 170 184

Datcon 7 bar:
P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9
P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
R(Ω) 240 200 165 135 115 95 78 63 48 35 25

Murphy 7 bar:
P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9
P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
R(Ω) 240 205 171 143 123 103 88 74 60 47 33

Harsen® Page 18/26


Manual HM1001ER1 Parameters Setting

Pre-set 1:
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R(Ω) 15 31 49 66 85 101 117 132 149 164 178

Pre-set 2:
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R(Ω) 30 41 65 88 110 115 145 150 172 185 190

Pre-set 3:
P(Bar) 0.0 1.7 3.4 5.2 6.9 8.6 10.3
P(PSI) 0 25 50 75 100 125 150
R(Ω) 21 36 52 72 84 100 120

Pre-set 4:
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 6.5 7.0 8.0 9.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 94.3 101.5 116.0 130.5
R(Ω) 251 195 155 127 107 88 72 65 61 54 48

l HET sensor parameter addendum:


VDO 120℃:
T(℃) 40 50 60 70 80 90 100 110 120 130 140
T(℉) 104 122 140 158 176 194 212 230 248 266 284
R(Ω) 291 197 134 97 70 51 38 29 22 18 15

VDO 150℃:
T(℃) 50 60 70 80 90 100 110 120 130 140 150
T(℉) 122 140 158 176 194 212 230 248 266 284 302
R(Ω) 322 221 155 112 93 62 47 37 29 23 19

Datcon:
T(℃) 40 50 60 70 80 90 100 110 120 130 140
T(℉) 104 122 140 158 176 194 212 230 248 266 284
R(Ω) 900 600 400 278 200 141 104 74 50 27 4

Murphy:
T(℃) 40 50 60 70 80 90 100 110 120 130 140
T(℉) 104 122 140 158 176 194 212 230 248 266 284
R(Ω) 1029 680 460 321 227 164 120 89 74 52 40

PT100:
T(℃) -100 -50 0 20 40 60 80 100 150 200 300
T(℉) -148 -58 32 68 104 140 176 212 302 392 572
R(Ω) 60 81 100 108 116 123 131 139 157 176 212

Harsen® Page 19/26


Manual HM1001ER1 Parameters Setting

Pre-set 1:
T(℃) 20 30 40 50 60 70 80 90 100 110 120
T(℉) 68 86 104 122 140 158 176 194 212 230 248
R(Ω) 900 600 420 282 152 113 86 62 48 40 30

Pre-set 2:
T(℃) 30 50 60 70 80 90 100 110 120
T(℉) 86 122 140 158 176 194 212 230 248
R(Ω) 980 400 265 180 125 90 65 50 38

Pre-set 3:
T(℃) 20 30 40 50 60 70 80 90 100 110 120
T(℉) 68 86 104 122 140 158 176 194 212 230 248
R(Ω) 805 540 380 260 175 118 83 58 42 30 21

Pre-set 4:
T(℃) 28 35 40 50 60 70 80 90 95 98
T(℉) 82 95 104 122 140 158 176 194 203 208
R(Ω) 579 404 342 250 179 136 103 77 67 63

8.7 The optional items for configurable input:

Code Optional Function NOTE


0 not used
1 Pre-alarm (active immediately) low level is active
2 Shutdown Alarm (active immediately) low level is active
3 Pre-alarm (active after safety-on delay) low level is active
4 Shutdown Alarm (active after safety-on delay) low level is active
5 LOP switch low level is active
6 HET switch low level is active
7 Emergency stop low level is active
8 Remote start signal low level is active
9 Reserved low level is active
10 Reserved low level is active
11 Low fuel level low level is active
12 Lamp test low level is active

Harsen® Page 20/26


Manual HM1001ER1 Parameters Setting

8.8 The optional items for configurable output:

Code Failure Type Define Code Failure Type Define


0 Not used 1 Reserved
2 Alarm 3 Pre-alarm
4 Idle 0 (N.C.) 5 Preheat
6 Speed up 7 Reserved
8 Fuel pump control 9 Running
10 System in AUTO mode 11 Reserved
12 System in MAN mode 13 Reserved
14 Idle 1 (N.O.) 15 Reserved
16 Reserved 17 Fail to start

NOTE:
l If define one configurable relay as Speed up, the relay will close after the
engine has successfully started. If there is idle function, the relay will
close after idle timer times out.

Harsen® Page 21/26


Manual HM1001ER1 LCD Display and Menu System

9. LCD Display and Menu System

Using a backlit TN type LCD to display data and information. After pressing any push button the
backlight will automatically turn off in a preset time. In normal operating status, you can set the page
scroll time to circularly display each page of measuring data. Press “ ” manually scrolls to view each
measuring data. When failure occurs, LCD displays the corresponding failure icon.

Press and hold “ ” button 2sec to enter into parameters setting menu, then use “ ” or “ ” to scroll
page, press “ ” again to select the required modify item, press “ ” or “ ”, LCD displays 0 0 0 0 when
prompted to enter password, then use “ ” or “ ” to modify the first digital value, press “ ” move to
modify the next one, after this, the first digital value will be displayed as “H”. Press “ ” to confirm after
the password is set as 2213, then you can modify parameters. Otherwise it will prompt to key in
password again. Press and hold “ ” for more than 2sec to quit parameters setting mode after finishing
configuration.

9.1 Static LCD displays

Controller is in standby status:

Operation Description

LCD displays detected battery voltage and running hour:

Controller is normally running, circularly displays each measuring data:

→ → → →

→ →

NOTE:
l When T-sensor or P-sensor is set as “not used”, LCD will not display
related measuring data.

Harsen® Page 22/26


Manual HM1001ER1 LCD Display and Menu System

9.2 Setting running parameters

For example: (setting VT rate at 2.0)

Operation Description

Press and hold “ ” 2sec, enter into parameters setting menu, then LCD
displays:

press “ ”, then LCD displays:

press “ ”, then LCD displays:

Press “ ” or “ ” to key in password: (2213), press “ ”, then LCD


displays:

Press “ ” or “ ” to change parameter, change to 2.0, then LCD


displays:

Press “ ” to confirm, then press “ ”, then LCD displays:

Press “ ” again to quit, or press and hold “ ” for more than 2sec to
quit parameter settings menu:

For example: (setting controller crank attempt at 2)

Operation Description

Press and hold “ ” 2sec, enter into parameters settings menu, then
LCD displays:

Press “ ” 20 times, then LCD displays:

Press “ ” again, then LCD displays:

Press “ ”, then LCD displays:

Press “ ” or “ ” to key in password: (2213), press “ ”, then LCD


displays:

Press “ ” or “ ” change parameter, change at 2, Press “ ” confirm


change, and then press and hold “ ” for more than 2sec will quit
parameter settings menu.

Harsen® Page 23/26


Manual HM1001ER1 LCD Display and Menu System

For example: (resume parameters of controller to factory default)

Operation Description

Press and hold “ ” 2sec, enter into parameter settings menu, then LCD
displays:

Press “ ” 6 times again, then LCD displays:

press “ ”, prompted to key in password, then LCD displays:

Press “ ” or “ ” to enter password: (2213), press “ ”, then LCD


display:

Press “ ” to recover default, press and hold “ ” for more than 2sec will
quit parameter settings menu.

For example: (configure controller as online program mode)

Operation Description

Press and hold “ ” 2sec, enter into parameter settings menu, then LCD
displays:

Press “ ” 7 times, then LCD displays:

Press “ ” again, then LCD displays:

Press “ ” or “ ” to enter password: (3132), press “ ”, then LCD


displays:

Press “ ” again to enter into online program mode, use the


communication cable and the software to program, please make sure
the power supply is normal during programming, the controller will
reset automatically after programming. If you have entered into this
mode already, but you do not program, you need to turn the controller
off to exit this mode.

Harsen® Page 24/26


Manual HM1001ER1 Preparation before Starting the Controller

10. Preparation before Starting the Controller

10.1 Make sure the controller is correctly installed to meet the ambient requirements.

10.2 Confirm all wiring connections of the controller meet the correct electric specification and
corresponding to “2.3 typical wiring diagram”. Ensure the correct polarity of the DC supply source
and that it has been protected by an external fuse. Otherwise damage to the controller may occur.

10.3 We recommend mounting an “Emergency Stop” button externally. The emergency stop input could
be connected to N.O. contact of emergency stop push button, and the other contactor point be
connected to the battery negative.

10.4 Switch on DC working power, make sure the preset parameters meet practical operating conditions,
such as P-sensor mode, T-sensor mode, etc.

Harsen® Page 25/26


Manual HM1001ER1 Technical Specification

11. Technical Specification

DC working power
Voltage range: 12V/24V (8-35V continuous)
Cranking drop outs: 0V for 100mS, assuming dc supply was at least 10V before dropout and recovers
to 5V
Max. operating current: @12V 150mA, @24V 75mA
Standby current: TBA
AC input voltage: phase voltage15-300Vac RMS (AC frequency≥40 Hz)
AC input frequency: 3-70Hz (voltage ≥15V)
Accuracy: 1%
Control relay outputs: 3A/30Vdc
Protection: IP65 (when correctly installed)
Operating ambient temperature: -20 to 70℃
Storage ambient temperature: -30 to 80℃

Harsen® Page 26/26


Manual HM1001ER1 LCD Display and Menu System

Service Hotline
4008883388

More technical support,


Please browse our website: www.jnhharsen.com

You might also like