DC Resistance
sectional area construction diameter weight at 20 ºC Conductor Code
mm2 No. x Ø ( mm ) mm kg / km Ω / km
1.5 7 x 0.52 1.56 13.5 12.1000 C020000070IMX
2.5 7 x 0.67 2.01 22.4 7.41000 C020100070IMX
4 7 x 0.85 2.55 36.0 4.61000 C020200070IMX
6 7 x 1.04 3.12 54.0 3.08000 C020300070IMX
10 7 x 1.34 4.02 87.0 1.83000 C020400070IMX
16 7 x 1.68 5.04 138.0 1.15000 C020700070IMX
25 7 x 2.14 6.42 220.0 0.72700 C021400070IMX
35 7 x 2.52 7.56 305.0 0.52400 C022000070IMX
50 19 x 1.80 8.90 413.0 0.38700 C022700190IMX
70 19 x 2.14 10.70 601.0 0.26800 C023700190IMX
95 19 x 2.52 12.50 832.0 0.19300 C024600190IMX
120 37 x 2.03 14.21 1050.0 0.15300 C025500370IMX
150 37 x 2.25 15.75 1290.0 0.12400 C026200370IMX
185 37 x 2.52 17.50 1615.0 0.09910 C027300370IMX
240 61 x 2.25 20.25 2120.0 0.07540 C028300610IMX
300 61 x 2.52 22.50 2660.0 0.06010 C029200610IMX
400 61 x 2.92 26.10 3420.0 0.04700 C02A900610IMX
500 61 x 3.25 29.00 4460.0 0.03660 C02B800610IMX
In ground with In free air In duct In trench Internal cabling
Single-Core
protection Non-sheathed
Ladders / Trays Cables, with Solid, Stranded or
Flame Mechanical
Max. Operating Max. Short circuit Oil resistant Min. bending
In free air In ground propagation In trench Encased
impact or in Internal cabling
temperature temperature ASTM D 1047 radius (r) = 15 Ø
Ladders / Trays IEC 60332-1-2 surface
Fair conduit
APPLICABLE STANDARDS
alfanar PVC insulated, single-core, non-sheathed cables are designed and tested to meet or exceed the requirements
of IEC 60227-3 and BS EN 50525-2-31(1) standards.
However, alfanar can also supply a range of alternative designs to meet customer-specified requirements.
In free
Note air BS
(1): In duct
EN 50525-2-31:2011 In trench
standard for Single coreEncased or in
non-sheathed Internal
cables withcabling
Ladders / Trays surface conduit
thermoplastic PVC insulation rated 450/750 V (U0/U) replaces BS 6004:2000 standard.
CONDUCTOR CONSTRUCTION
Conductor
Plain annealed solid (Class 1), stranded (Class 2) or flexible (Class 5) circular copper
conductor.
In free air In duct In trench Encased or in Internal / external
Ladders / Trays surface conduit cabling
Insulation
Extruded layer of Polyvinyl chloride (PVC) compound.
Core Identification
In addition to the standard core identification colours, other colours are available on
request.
In ground In free air In duct In trench Internal cabling
Ladders / Trays
CABLE INSTALLATION
12
PVC INDOOR WIRES / IEC 60227-3, BS EN 50525-2-31
CU / PVC 450 / 750 V
DIMENSIONS AND
ELECTRICAL DATA
WEIGHTS
Nominal
Max. Conductor
cross Continuous Current Ratings (@ 40° C)
Resistance
sectional
area Approx. Approx.
3 loaded conductors Cable Code
DC at AC at 2 loaded conductors overall overall
(Three-Phase circuit)
20 °C 70 °C (Single-Phase circuit) diameter weight
Laying Conditions: Ambient air temperature of 40 ºC. In case of different laying conditions, appropriate correction (derating) factors from Annex
C have to be applied to cater for the actual installation conditions.
Single-Core Cables, with Stranded Copper Conductors,
PVC Insulated and PVC Sheathed
APPLICATIONS
These cables are intended for fixed installations, indoors and outdoors, in low voltage electricity systems. They are
normally used for the distribution of electrical energy in urban networks, power or switching stations, industrial
plants, as well as in switchgears, in applications where there is no risk of mechanical damage.
CABLE CHARACTERISTICS
Max. Operating Max. Short circuit Flame Oil resistant Mechanical UV Resistant Min. bending
temperature temperature propagation ASTM D 1047 impact radius (r) = 15 Ø
IEC 60332-1-2 Fair
APPLICABLE STANDARDS
alfanar Low Voltage power cables are designed and tested to meet all the requirements of the latest edition of IEC
60502-1 standard. In addition, alfanar can also supply a range of alternative designs to meet customer-specified
requirements.
CABLE CONSTRUCTION
Conductor
Plain annealed stranded circular or circular compacted copper conductor (Class 2 to
IEC 60228).
Insulation
Extruded layer of Polyvinyl Chloride (PVC) - Type (PVC/A) to IEC 60502-1.
Core Identification
° Red
Outer Jacket
Extruded layer of Polyvinyl Chloride (PVC) - Type (ST1) to IEC 60502-1.
Note: The core identification colour shown above is the most common. However, any other colour
can be provided upon a customer’s request (e.g. to HD 308 S2 or IEC 60445).
CABLE INSTALLATION
14
POWER CABLES / IEC 60502-1
CU / PVC / PVC 0.6 / 1 kV
DIMENSIONS AND
ELECTRICAL DATA
WEIGHTS
Nominal
cross Max. Conductor
Continuous Current Ratings
sectional Resistance
area Approx. Approx.
Cable Code
DC at AC at Buried direct in overall overall
In buried ducts In free air
20 °C 70 °C ground diameter weight
(a) (b) (c) (d) (e) (f) (g)
mm² Ω / km Ω / km
A A A A A A A mm kg / km
1.5 12.1000 14.4777 22 22 16 18 17 17 23 6.0 55 C208PA10100CB51IMR
2.5 7.4100 8.8661 29 29 21 24 23 23 30 6.4 70 C210PA10100CB51IMR
4 4.6100 5.5159 37 37 28 31 30 31 40 7.4 100 C212PA10100CB51IMR
6 3.0800 3.6853 46 46 34 39 38 39 50 7.9 125 C213PA10100CB51IMR
10 1.8300 2.1897 61 61 46 51 52 53 68 8.5 160 C314PA10100CB51IMR
16 1.1500 1.3762 79 79 60 66 69 70 90 9.5 225 C315PA10100CB51IMR
25 0.7270 0.8702 101 101 78 86 92 94 119 11.1 330 C316PA10100CB51IMR
35 0.5240 0.6274 121 121 94 104 113 116 147 12.1 425 C317PA10100CB51IMR
50 0.3870 0.4637 143 143 114 124 138 142 178 13.7 560 C318PA10100CB51IMR
70 0.2680 0.3217 175 175 141 152 175 180 225 15.3 770 C319PA10100CB51IMR
95 0.1930 0.2324 209 209 172 185 216 223 276 17.5 1045 C345PA10100CB51IMR
120 0.1530 0.1850 236 237 197 211 251 258 320 18.8 1285 C346PA10100CB51IMR
150 0.1240 0.1508 265 266 224 238 289 298 367 20.9 1580 C347PA10100CB51IMR
185 0.0991 0.1216 300 300 256 272 335 345 423 23.2 1970 C348PA10100CB51IMR
240 0.0754 0.0942 346 346 300 318 398 410 502 26.1 2555 C349PA10100CB51IMR
300 0.0601 0.0769 389 389 341 362 460 474 581 29.1 3165 C350PA10100CB51IMR
400 0.0470 0.0625 437 437 389 409 532 548 674 32.3 4050 C351PA10100CB51IMF
500 0.0366 0.0515 490 490 442 473 614 632 785 36.3 5190 C352PA10100CB51IMF
630 0.0283 0.0433 544 548 496 537 700 722 910 40.1 6520 C353PA10100CB51IMF
800 0.0221 0.0374 596 596 549 600 787 812 1042 44.0 8310 C354PA10100CB51IMF
1000 0.0176 0.0333 652 655 608 680 909 941 1229 52.8 10465 C255PA10100CB51IMF
Laying Conditions: Ambient air temperature of 40 ºC, Ambient ground temperature of 35 ºC, Soil thermal resistivity of 1.5 K·m/W and Depth of
laying of 0.5 m. In case of different laying conditions, appropriate correction (derating) factors from Annex C have to be applied to cater for the
actual installation conditions.
Single-Core Cables, with Stranded Aluminium Conductors,
PVC Insulated and PVC Sheathed
APPLICATIONS
These cables are intended for fixed installations, indoors and outdoors, in low voltage electricity systems. They are
normally used for the distribution of electrical energy in urban networks, power or switching stations, industrial
plants, as well as in switchgears, in applications where there is no risk of mechanical damage.
CABLE CHARACTERISTICS
Max. Operating Max. Short circuit Flame Oil resistant Mechanical UV Resistant Min. bending
temperature temperature propagation ASTM D 1047 impact radius (r) = 15 Ø
IEC 60332-1-2 Fair
APPLICABLE STANDARDS
alfanar Low Voltage power cables are designed and tested to meet all the requirements of the latest edition of IEC
60502-1 standard. In addition, alfanar can also supply a range of alternative designs to meet customer-specified
requirements.
CABLE CONSTRUCTION
Conductor
Stranded circular or circular compacted aluminium conductor (Class 2 to IEC 60228).
Insulation
Extruded layer of Polyvinyl Chloride (PVC) - Type (PVC/A) to IEC 60502-1.
Core Identification
° Red
Outer Jacket
Extruded layer of Polyvinyl Chloride (PVC) - Type (ST1) to IEC 60502-1.
Note: The core identification colour shown above is the most common. However, any other colour
can be provided upon a customer’s request (e.g. to HD 308 S2 or IEC 60445).
CABLE INSTALLATION
16
POWER CABLES / IEC 60502-1
AL / PVC / PVC 0.6 / 1 kV
DIMENSIONS AND
ELECTRICAL DATA
WEIGHTS
Nominal
cross Max. Conductor
Continuous Current Ratings
sectional Resistance
area Approx. Approx.
Cable Code
DC at AC at Buried direct in overall overall
In buried ducts In free air
20 °C 70 °C ground diameter weight
(a) (b) (c) (d) (e) (f) (g)
mm² Ω / km Ω / km
A A A A A A A mm kg / km
10 3.0800 3.7007 48 49 36 41 41 42 54 8.5 100 A314PA10100CB51IMR
16 1.9100 2.2950 61 61 46 51 53 55 70 9.5 130 A315PA10100CB51IMR
25 1.2000 1.4420 78 78 61 67 71 73 93 11.1 180 A316PA10100CB51IMR
35 0.8680 1.0432 94 94 73 80 88 90 114 12.1 215 A317PA10100CB51IMR
50 0.6410 0.7706 111 111 88 96 107 110 138 13.7 275 A318PA10100CB51IMR
70 0.4430 0.5329 136 136 110 118 136 140 174 15.3 350 A319PA10100CB51IMR
95 0.3200 0.3854 162 163 133 143 168 173 214 17.5 470 A345PA10100CB51IMR
120 0.2530 0.3052 184 185 153 164 195 201 249 18.8 555 A346PA10100CB51IMR
150 0.2060 0.2490 206 207 174 185 225 232 285 20.9 680 A347PA10100CB51IMR
185 0.1640 0.1989 235 234 200 212 262 270 329 23.2 845 A348PA10100CB51IMR
240 0.1250 0.1527 272 272 235 248 313 322 392 26.1 1075 A349PA10100CB51IMR
300 0.1000 0.1233 307 307 270 283 363 375 454 29.1 1330 A350PA10100CB51IMR
400 0.0778 0.0975 350 350 311 327 426 439 531 32.3 1665 A351PA10100CB51IMF
500 0.0605 0.0779 398 399 359 378 499 514 625 36.3 2095 A352PA10100CB51IMF
630 0.0469 0.0630 451 451 411 435 580 598 733 40.1 2595 A353PA10100CB51IMF
800 0.0367 0.0524 503 503 464 494 665 686 852 44.1 3220 A354PA10100CB51IMF
1000 0.0291 0.0450 561 563 523 569 782 809 1022 52.8 4080 A255PA10100CB51IMF
Laying Conditions: Ambient air temperature of 40 ºC, Ambient ground temperature of 35 ºC, Soil thermal resistivity of 1.5 K·m/W and Depth of
laying of 0.5 m. In case of different laying conditions, appropriate correction (derating) factors from Annex C have to be applied to cater for the
actual installation conditions.
Multi-Core Cables, with Stranded Copper Conductors,
PVC Insulated and PVC Sheathed
APPLICATIONS
These cables are intended for fixed installations, indoors and outdoors, in low voltage electricity systems. They are
normally used for the distribution of electrical energy in urban networks, power or switching stations, industrial
plants, as well as in switchgears, in applications where there is no risk of mechanical damage.
CABLE CHARACTERISTICS
Max. Operating Max. Short circuit Flame Oil resistant Mechanical UV Resistant Min. bending
temperature temperature propagation ASTM D 1047 impact radius (r) = 12 Ø
IEC 60332-1-2 Fair
APPLICABLE STANDARDS
alfanar Low Voltage power cables are designed and tested to meet all the requirements of the latest edition of IEC
60502-1 standard. In addition, alfanar can also supply a range of alternative designs to meet customer-specified
requirements.
CABLE CONSTRUCTION
Conductor
Plain annealed stranded circular (rm) or sector shaped (sm) copper conductor (Class 2 to
IEC 60228).
Insulation
Extruded layer of Polyvinyl Chloride (PVC) - Type (PVC/A) to IEC 60502-1.
Core Identification
°°
°°° Red, Black
°°°°
Red, Yellow, Blue
Red, Yellow, Blue, Black
Assembly
Cores are assembled together using Non-hygroscopic filler, if needed.
Outer Jacket
Extruded layer of Polyvinyl Chloride (PVC) - Type (ST1) to IEC 60502-1.
Note: The core identification colour shown above is the most common. However, any other colour
can be provided upon a customer’s request (e.g. to HD 308 S2 or IEC 60445).
CABLE INSTALLATION
18
POWER CABLES / IEC 60502-1
CU / PVC / PVC 0.6 / 1 kV
DIMENSIONS AND
ELECTRICAL DATA
Nominal WEIGHTS
cross
Max. Conductor Resistance Continuous Current Ratings Approx. Approx.
sectional Cable Code
area DC at AC at Laid in Laid in Laid in overall overall
20 °C 70 °C ground ducts free air diameter weight
mm² Ω / km Ω / km A A A mm kg / km
Two Core Cables
1.5 rm 12.1000 14.4777 27 19 21 9.9 145 C208PA10200CB01IMR
2.5 rm 7.4100 8.8661 36 24 28 10.8 185 C210PA10200CB01IMR
4 rm 4.6100 5.5159 47 32 38 12.7 260 C212PA10200CB01IMR
6 rm 3.0800 3.6853 58 40 48 13.8 330 C213PA10200CB01IMR
10 rm 1.8300 2.1898 76 53 65 15.0 420 C314PA10200CB01IMR
16 rm 1.1500 1.3763 98 70 86 17.0 580 C315PA10200CB01IMR
25 rm 0.7270 0.8703 127 92 116 20.1 855 C316PA10200CB01IMR
35 rm 0.5240 0.6276 152 111 142 22.2 1100 C317PA10200CB01IMR
Three Core Cables
1.5 rm 12.1000 14.4777 23 15 18 10.4 170 C208PA10300CB04IMR
2.5 rm 7.4100 8.8661 29 20 23 11.4 220 C210PA10300CB04IMR
4 rm 4.6100 5.5159 38 26 32 13.4 315 C212PA10300CB04IMR
6 rm 3.0800 3.6853 48 33 40 14.7 400 C213PA10300CB04IMR
10 rm 1.8300 2.1898 63 43 55 16.4 500 C314PA10300CB04IMR
16 rm 1.1500 1.3763 81 57 72 18.6 720 C315PA10300CB04IMR
25 rm 0.7270 0.8703 105 75 98 21.9 1020 C316PA10300CB04IMR
35 sm 0.5240 0.6276 117 85 107 21.2 1310 C417PA10300CB04IMR
50 sm 0.3870 0.4639 139 103 131 24.6 1715 C418PA10300CB04IMR
70 sm 0.2680 0.3220 170 128 166 27.7 2355 C419PA10300CB04IMR
95 sm 0.1930 0.2328 204 156 204 32.1 3205 C445PA10300CB04IMR
120 sm 0.1530 0.1856 231 178 235 34.0 3940 C446PA10300CB04IMF
Four Core Cables
1.5 rm 12.1000 14.4777 23 15 18 11.3 205 C208PA10400CB08IMR
2.5 rm 7.4100 8.8661 29 20 23 12.3 265 C210PA10400CB08IMR
4 rm 4.6100 5.5159 38 26 32 14.6 385 C212PA10400CB08IMR
6 rm 3.0800 3.6853 48 33 40 16.0 500 C213PA10400CB08IMR
10 rm 1.8300 2.1898 63 43 55 17.9 670 C314PA10400CB08IMR
16 rm 1.1500 1.3763 81 57 72 20.3 920 C315PA10400CB08IMR
25 rm 0.7270 0.8703 105 75 98 24.1 1295 C316PA10400CB08IMR
35 sm 0.5240 0.6276 117 85 107 24.5 1665 C417PA10400CB08IMR
50 sm 0.3870 0.4639 139 103 131 28.7 2220 C418PA10400CB08IMR
70 sm 0.2680 0.3220 170 128 166 32.3 3055 C419PA10400CB08IMR
95 sm 0.1930 0.2328 204 156 204 36.2 4200 C445PA10400CB08IMR
120 sm 0.1530 0.1856 231 178 235 39.6 5185 C446PA10400CB08IMF
150 sm 0.1240 0.1514 259 203 270 44.3 6390 C447PA10400CB08IMF
185 sm 0.0991 0.1224 292 232 311 49.1 7905 C448PA10400CB08IMF
240 sm 0.0754 0.0952 338 272 370 55.6 10280 C449PA10400CB08IMS
300 sm 0.0601 0.0780 381 310 426 61.7 12840 C450PA10400CB08IMS
400 sm 0.0470 0.0638 431 357 495 70.3 16455 C451PA10400CB08IMS
500 sm 0.0366 0.0531 484 405 568 77.8 21170 C452PA10400CB08IMS
Four Core Cables with Reduced Neutral
25 rm 16 rm 0.7270 / 1.1500 0.8703 / 1.3763 105 75 98 23.1 1215 C334PA10400CB08IMR
35 sm 16 rm 0.5240 / 1.1500 0.6276 / 1.3763 117 85 107 24.5 1480 C435PA10400CB08IMR
50 sm 25 rm 0.3870 / 0.7270 0.4639 / 0.8703 139 103 131 28.7 2005 C436PA10400CB08IMR
70 sm 35 sm 0.2680 / 0.5240 0.3220 / 0.6276 170 128 166 32.3 2745 C437PA10400CB08IMR
95 sm 50 sm 0.1930 / 0.3870 0.2328 / 0.4639 204 156 204 36.2 3700 C438PA10400CB08IMR
120 sm 70 sm 0.1530 / 0.2680 0.1856 / 0.3220 231 178 235 39.6 4665 C439PA10400CB08IMF
150 sm 70 sm 0.1240 / 0.2680 0.1514 / 0.3220 259 203 270 44.3 5605 C440PA10400CB08IMF
185 sm 95 sm 0.0991 / 0.1930 0.1224 / 0.2328 292 232 311 49.1 7035 C441PA10400CB08IMF
240 sm 120 sm 0.0754 / 0.1530 0.0952 / 0.1856 338 272 370 55.6 9045 C442PA10400CB08IMS
300 sm 150 sm 0.0601 / 0.1240 0.0780 / 0.1514 381 310 426 61.7 11290 C443PA10400CB08IMS
400 sm 185 sm 0.0470 / 0.0991 0.0638 / 0.1224 431 357 495 70.3 14375 C444PA10400CB08IMS
500 sm 240 sm 0.0366 / 0.0754 0.0531 / 0.0952 484 405 568 77.8 18415 C466PA10400CB08IMS
Laying Conditions: Ambient air temperature of 40 ºC, Ambient ground temperature of 35 ºC, Soil thermal resistivity of 1.5 K·m/W and Depth of
laying of 0.5 m. In case of different laying conditions, appropriate correction (derating) factors from Annex C have to be applied to cater for the
actual installation conditions.
Multi-Core Cables, with Stranded Aluminum Conductors,
PVC Insulated and PVC Sheathed
APPLICATIONS
These cables are intended for fixed installations, indoors and outdoors, in low voltage electricity systems. They are
normally used for the distribution of electrical energy in urban networks, power or switching stations, industrial
plants, as well as in switchgears, in applications where there is no risk of mechanical damage.
CABLE CHARACTERISTICS
Max. Operating Max. Short circuit Flame Oil resistant Mechanical UV Resistant Min. bending
temperature temperature propagation ASTM D 1047 impact radius (r) = 12 Ø
IEC 60332-1-2 Fair
APPLICABLE STANDARDS
alfanar Low Voltage power cables are designed and tested to meet all the requirements of the latest edition of IEC
60502-1 standard. In addition, alfanar can also supply a range of alternative designs to meet customer-specified
requirements.
CABLE CONSTRUCTION
Conductor
Stranded circular (rm) or sector shaped (sm) aluminium conductor (Class 2 to IEC
60228).
Insulation
Extruded layer of Polyvinyl Chloride (PVC) - Type (PVC/A) to IEC 60502-1.
Core Identification
°°
°°° Red, Black
°°°°
Red, Yellow, Blue
Red, Yellow, Blue, Black
Assembly
Cores are assembled together using Non-hygroscopic filler, if needed.
Outer Jacket
Extruded layer of Polyvinyl Chloride (PVC) - Type (ST1) to IEC 60502-1.
Note: The core identification colour shown above is the most common. However, any other colour
can be provided upon a customer’s request (e.g. to HD 308 S2 or IEC 60445).
CABLE INSTALLATION