Ground Fault Relay-1C: Specification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GROUND FAULT RELAY-1C

Flush mounted type Socket type

Specification

Model No DGF-P11(Socket type) DGF-P12(Socket type)


Part DGF-F11(Flush mounted) DGF-F12(Flush mounted)
Auxiliary power AC 110/220V common(DC110/220V Option)
Frequency 50/60㎐ common
Operating current setting 0.1-0.3-0.5-1-3-5-7-10-Lock 10-15-20-25-30-35-40-50-Lock
Operating time setting INST-0.1-0.3-0.5-0.7-1-2-3-Lock INST-0.1-0.3-0.5-0.7-1-2-3-Lock
Operation Indicator LED lamp (red color)
Reset Auto / Manual
Extent of supply voltage 85~115% of rated voltage
Ambient temperature -10℃~+50℃
Power consumption 3VA
Insulation resistane DC 500V, less than 100㏁
Dielectric strength primary-case ; AC 2,000V, Secondary-case : AC500V / 1minute
Contact capacity AC 125V 5A / DC 30V 5A
Weight 0.6㎏
Case ABS Resin/Black N1.5
ZCT(Input) ZCT Rating 200㎃/100mV(DZR, ZR, ZS, ZB type 사용)

Features
The static GFR with a sensor(Toroidal CT) is for ground fault current detection and has an output contact for a fault circuit trip. The
relay is combined with a sensor which is calibrated as a set. The operating current in the specification means 1ry current of the CT.
While the 1ry current is reached at set value. the output of the relay is closed.
Since the 2ry output of the sensor is connected to the input of the relay. it is recommended that the relay with a sensing CT has to
be ordered as a set. Model. “-F□□” is for semi-flush mounting type and “-P□□” is for pin type with a base socket. Refer
to the drawings in the instruction for more information.

140 DEESYS TOTAL PRODUCTS GUIDE


Application
The GFR may be applied where fault circuits should be cut off detecting current, lo and unbalanced current. Ic in the non-grounding
network. Capacitive components existing in the bus side from ZCT is balanced between earth and three phase conductors at the
normal condition. The balanced capacitive components of three phases are broken as soon as for one of three phases being
grounded. And then the capacitive current becomes to flow thru the ZCT. The fault current(lo + lc) can be set by rotary switches on
the front plate of the relay. Time delay function is selected by the time switch as well. By turning to <LOCK> of the rotary switches
for operating current and/or operating time, the function(s) can be disabled. Reset function for output contact can be selected either
on Manual or on Auto.

Setting, Testing, and Operation


1. Current Set : There is a 9 step switch on the front plate for current set. One of 8 step(0.1, 0.3, 0.5, 1, 3. 5. 7. 10(A)) and lock,
can be selected.
2. Time Set : There is a 9 step switch on the front plate for time set. a Instant set. 7 steps of delay time and a Lock set.
3. Power LED(Green) is lighted while aux. power is ON.
4. Trip LED(Red) is Lighted when any fault occurs and the output contact(terminal Ta and Tc) is closed at a same time.
5. Manual/Auto switch can be selected either Manual or Auto for reset. “Maunal” means for manual reset of output contact by
pressing reset button and “Auto” means for automatic reset of output contact as soon as the fault current cleared.
6. Reset button is used for resetting TRIP LED and an output contact when Manual/ Auto switch has been turned to Manual.
7. Test button is used for self-circuit test. If the button is pressed manually, the output contact(a) is closed and TRIP LED is lighted
simultaneously.
Note:Do not press the <Test> button during in service. Main CB may be opened

Test Procedure (Refer to the figure)


1. 2ry of sensor(k & l) and GFR(Terminal 7 & 8) are connected with wire.
2. Terminal 1 & 3 for AC 220V or terminal 1 & 2 for AC 110 aux. power is connected to a source.
3. One line with an A-meter from current source is installed through the sensor CT.
4. GFR is set at 10A tap with current dial and 0.1 sec. tap with time dial on the front plate.
5. Aux. power switch is“ON”. Then the power LED on the front plate may be lighted.
6. Current through the sensor CT is set 12A (120% of set value) using current source.
7. Switch current source instantaneously and watch through-current on A-meter whether 120% of set value is flowed.
Then, confirm time on the time counter if it is counted 0.1±10%sec. (±10% of time set value) and if the trip LED is lighted.
8. Press RESET button for reset. If Reset selection is turned to Auto, the output contact will reset automatically, but the trip LED
shall be reset manually like doing at Manual.
9. Other ranges can be tested same as the above procedure.

DEESYS TOTAL PRODUCTS GUIDE 141


GROUND FAULT RELAY-1C
Internal block diagram

External wiring diagram

142 DEESYS TOTAL PRODUCTS GUIDE


Dimension
● Socket Type

MODEL : DGF-P11, DGF-P12, DER-P03, P11, P12 1,2 : AC110V / 120V


1,3 : AC220V / 240V
4,5,6 : a,b,c - Contact
7,8 : Z,C,T Input

● Flush mounted type

1,2 : AC110V/120V
1,21,2
: AC110V/120V
: AC110V/120V
1,2 : AC110V/120V
1,3 : AC220V/240V
1,31,3
: AC220V/240V
: AC220V/240V
4,5,6 : a,b,c1,2
1,3 : AC220V/240V ::AC110V/120V
- Contact
1,2 AC110V / 120V
4,5,6
4,5,6: a,b,c
: a,b,c
- Contact
- Contact
1,3
1,3 :: AC220V/240V
AC220V / 240V
1,2 ::AC110V/120V
4,5,6 a,b,c7,8- Contact
: Input
Z,C,T Input
7,87,8
: Z,C,T
: Z,C,T Input 4,5,6 : a,b,c - Contact
4,5,6 : a,b,cInput
- :Contact
MODEL : DGF-F11, F12, DER-F11, F12 1,3: Z,C,T
7,8
Cutting Size : 56x94mm : AC220V/240V
Input 7,8 : Z,C,T1,2 AC110V/120V
4,5,6 : a,b,c - Contact 7,8 : Z,C,T Input
1,3 : AC220V/240V
7,8 : Z,C,T Input
4,5,6 : a,b,c - Contact
7,8 : Z,C,T Input

External dimension
GFR-M10/M05, ELR M10/M05, ELR-A10/A05

DEESYS TOTAL PRODUCTS GUIDE 143