Fire Alarm Control Panels: Installation and Operation Manual
Fire Alarm Control Panels: Installation and Operation Manual
Fire Alarm Control Panels: Installation and Operation Manual
FPD-7024
Table of contents
1 Notices 6
1.1 FCC Compliance Notice 6
1.2 FCC Phone Connection to Users 6
1.3 Industry Canada Notice 7
1.4 Trademarks 7
2 Overview 8
2.1 System overview 8
2.2 Components 9
2.2.1 On-board conventional points 9
2.2.2 Off-board addressable points (with D7039 Multiplex Expansion Module) 9
2.2.3 Enclosure Housing 10
2.2.4 Remote LCD Keypads 10
2.2.5 Remote LED Annunciators 10
2.2.6 D7032 - use with the D7030X 10
2.2.7 Communicator 12
2.2.8 Users 13
2.2.9 Lightning protection 13
2.2.10 Battery backup calculation 13
2.2.11 Required batteries for existing load 16
2.2.12 Compatible devices 17
2.3 Parts List 19
3 Fire Safety 20
3.1 Smoke detector layout 20
3.1.1 General considerations 20
3.1.2 Family residences 20
3.2 Having and practicing an escape plan 21
4 Installation 22
4.1 Installation guide for UL Listed systems 22
4.1.1 FPD‑7024 UL Listings 22
4.1.2 Installation considerations 22
4.1.3 UL requirements 22
4.2 Installing the enclosure 25
4.3 Installing the FPD‑7024 26
4.4 Installing optional equipment 27
5 Connection 29
5.1 FACP terminal connection 29
5.2 Power supply connection 33
5.3 Option bus wiring requirements 34
6 System Operation 36
6.1 Modes of Operation 36
6.1.1 Normal 36
6.1.2 Off-normal Displays 36
6.1.3 Acknowledge 36
6.1.4 Alarm 36
6.1.5 Supervisory 36
6.1.6 Trouble 37
6.1.7 Fire Silence/Reset 37
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
4 en | Table of Contents Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Table of Contents | en 5
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
6 en | Notices Fire Alarm Control Panels
1 Notices
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Notices | en 7
1.4 Trademarks
All hardware and software product names used in this document are likely to be registered
trademarks and must be treated accordingly.
CleanMe is a trademark of GE Interlogix, Inc. in the United States and/or other countries.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
8 en | Overview Fire Alarm Control Panels
2 Overview
2.1 System overview
The FPD‑7024 Fire Alarm Control Panel is a fully integrated hard-wire fire alarm system. It can
support four input points (expandable to 255 using D7039 Multiplex Expansion Module and
the FPC‑7034 Four-Point Expander) and 16 individual users (expandable to 100 with the
D7039). The control panel has a built-in LCD keypad. Up to four additional keypads can be
used to provide user interface with the system and programming access for the installer. The
FPD‑7024 also includes the following features:
– Built-in dual-line communicator
– Menu driven keypad programming
– Freely programmable alphanumeric/alphabetical display
– 99 event history buffer
– 16 user codes
– UL Listed, CSFM, MEA Approved
When the D7039 Multiplex Expansion Module is installed, these additional features are
available:
– 247 additional addressable input points (255 total points)
– 499 Non-volatile event history buffer
– 100 user codes
For the location of the major items on the FPD‑7024 Control Board, see the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 9
2.2 Components
2.2.1 On-board conventional points
All on-board points and points implemented with the FPC-7034 work with two- or four-wire
detectors. The system has an optional alarm verification feature.
Supervisory Existing 8 mA to 20 mA
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
10 en | Overview Fire Alarm Control Panels
– Each point is individually supervised for proper connection to the common bus (when
over ten points are troubled, up to ten troubles are shown per bus and the balance of the
troubles is indicated by a common bus failure message).
– Response time can be set to fast, or programmed from 1 to 89 seconds.
– Input points on the SLCs are implemented with a D7042 Eight Input Remote Module.
Notice!
i Each D7030X processes 16 zones of information. If no D7032 is attached, only the lower eight
zones are shown.
Notice!
i The column labeled “shown on D7030X” in the LED assignments table below applies regard-
less if an attachment of a D7032 to any D7030X is made.
For LED assignments when up to eight D7030X/D7032 combinations are used, see the
following table:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 11
1 49 User defined
2 50 User defined
3 (reserved)
6 (reserved)
9 (reserved)
11 (reserved)
12 (reserved)
14 (reserved)
16 (reserved)
Table 2.3: LED display for Zones 49 to 64
See also
– D7032 - use with the D7030X, 10
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
12 en | Overview Fire Alarm Control Panels
2.2.7 Communicator
The communicator can report to two phone numbers or IP addresses with full single, double,
and back-up reporting. Communicates in SIA, Modem IIIa2, Contact ID, BFSK, and 3/1 and 4/2
Tone burst formats (available communication formats depend on phone or IP connection).
Notice!
i The communicator must be enabled and configured to operate. The communicator and phone
line monitors are disabled in the default factory configuration.
Phone Line and Phone Number/IP Selection: To ensure the delivery of critical reports, the fire
panel has two phone lines and two phone numbers or IP addresses that can be used for
reporting. Reports can be directed to one or both of two phone numbers or IP addresses
using the Report Steering feature in the control panel programming. Note that Account
Number 1 is used with Phone Number/IP 1, and Account Number 2 is used with Phone
Number/IP 2. Except for test reports, the control panel automatically selects the phone line or
IP address to use. If the report is not successful after two attempts on Line 1, the control
panel automatically switches and uses Phone Line 2. One exception is when test reports
(manual or automatic) are sent. Test reports are sent every 4 hours to 28 days. Each time a
test report is sent, the control panel alternates phone lines. This happens even if the monitor
says the line is bad. If the user sends two manual test reports, both phone lines can be tested.
The first report uses one line, and the second uses the other line. During normal operation,
the automatic test uses a different line each day. Because the control panel automatically
selects which line to use, both phone lines must use the same dialing sequences for sending
reports. For example, a line that requires a 9 to be dialed for an outside line cannot be paired
with a line that does not require a 9.
For more information on report steering, see Report Steering, 83.
Notice!
i PBX lines and ground start lines do not comply with NFPA requirements for digital communi-
cation.
While the control panel is idle, the FACP monitors the primary and alternate telephone lines by
monitoring the line for trouble. The FACP monitors each line every 12 seconds. When a trouble
still exists after three samples (36 seconds), the FACP sends a trouble report and activates
the yellow trouble LED and trouble relay.
Danger!
If the central station receives the automatic test report only every other day, this indicates
that one phone line at the protected premises is inoperative.
Correct this condition immediately, because other critical reports can be delayed when the
communicator is trying to send the test signal through the inoperative phone line (once each
48 hours).
Supplemental Reporting: While two independent phone lines are required for UL864 Central
Station service, the FACP can be configured with one phone line if the control panel is used
only for supplemental reporting on a local, remote station or auxiliary system.
To install the control panel with only one phone line, connect a jumper from T1 to T2 and a
jumper from R1 to R2. These jumper connections are shown in the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 13
2.2.8 Users
The system allows up to 16 individual users, or up to 100 users when the D7039 is installed. A
personal identification number (PIN, the four-digit code entered at the keypads) and an
authority level to determine which functions can be performed can be assigned to each user.
For PINs, see Personal identification numbers (PINs), 47.
Notice!
i This system is intended for installation entirely within one building.
Metal-oxide varistors (MOVs) and spark gaps provide protection from lightning surges and
static discharges.
FPC‑7034 44 mA 156 mA
Four‑Point
Expander
D7035/B Octal 8 mA + 30 mA 2
8 mA + 30 mA 2
Relay1
D7048/B Octal 10 mA 10 mA
Driver Module
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
14 en | Overview Fire Alarm Control Panels
FMR‑7036 80 mA 100 mA
Annunciator
Keypad
D7030X 27 mA 132 mA
Eight‑Point LED
Annunciator1
D7030X‑S2 35 mA 175 mA
Eight‑Point LED
Annunciator
D7030X‑S8 35 mA 175 mA
Eight-Point LED
Annunciator
D7032 Eight‑ 1 mA 90 mA
Point LED
Annunciator
Expander
FMR‑7033 80 mA 100 mA
Keypad 1
D7042/B 18 mA 18 mA
Addressable
Eight Point Input
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 15
Smoke Detectors
Other Sensors
Other
Notice!
i The required battery size to support the system can be calculated using the tables for Stand-
by load battery size, 16 and Alarm load battery size, 16.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
16 en | Overview Fire Alarm Control Panels
Standby load battery Capacityr required Capacity required for Capacity required for
size chart for 24 hours 48 hours 60 hours
Grand Total
Alarm Existing
D7030 Eight Point LED Identifies the location of a fire alarm for up to eight zones
Annunciator allowed per system.
D7030X Eight Point LED Identifies the location of a fire alarm for up to eight zones
Annunciator allowed per system.
D7030X‑S2 Eight Point LED An eight zone LED annunciator, of which two zones are
Annunciator reserved for supervisory functions. It has Power and
Trouble LEDs plus eight zone LEDs that can be labeled
individually.
D7030X‑S8 Eight Point LED An eight-zone LED annunciator, of which all eight zones are
Annunciator reserved for supervisory functions. It has Power and
Trouble LEDs plus eight-zone LEDs that can be labeled
individually.
D7032 Eight Point LED Attaches to a D7030X and identifies the location of a fire
Annunciator Expander alarm for eight additional zones.
FMR‑7033 Alphanumeric LCD The FMR‑7033 LCD Keypad combines remote annunciator
Keypad and controller functions for the FPD‑7024. Up to four
keypads can be connected.
FPC‑7034 Four Point Expander Allows the FPD‑7024 Control Panel to support four
additional loops. The FPC‑7034 plugs into the control panel
and provides four Class B, Style 4 loops that are identical
in characteristics to the loops on the control panel. One
FPC‑7034 is allowed per system.
D7035/B Octal Relay Module Provides eight Form C relay outputs for addition to the
system. The outputs are programmable and can be
activated by system events. Each output operates
independently of the other seven outputs for complete
flexibility. The D7035 connects to the option bus; up to
two are allowed per system. The D7035B comes installed
on a mounting skirt.
For required enclosure modification, see also the D7035
Installation Guide.
FPP‑RNAC‑8A‑4C Remote NAC Adds four NFPA 72 Class B, Style Y Notification Appliance
Power Supply Circuits through the option bus and is supervised by the
control panel. The FPP‑RNAC‑8A‑4C connects to the option
bus of the FPD‑7024 control panel and up to four are
allowed per system.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
18 en | Overview Fire Alarm Control Panels
Device Function
D7042/B Eight‑Input Remote Provides eight Class B, Style 4 input points. Connect up to
Module 15 modules to MUX Bus A, and 15 on MUX Bus B. The
D7042 is powered by 12 VDC supplied by the option bus
power terminals, in addition to the two‑wire data
connection. The D7042 can not be used on a signal line
circuit (SLC) configured for Class A, Style 6 operation.
D7048/B Octal Driver Module Provides eight open‑collector transistor outputs for
addition to the FPD‑7024 Fire Alarm Control panels. It
connects to the control panels through the option bus.
D7044 MUX Single Input Connects a normally‑open contact device to the multiplex
Module bus of the FPD‑7024 with a supervised local loop. The
D7044 draws operating power from the FPD‑7024.
D7044M MUX Mini Contact Connects a contact device to the multiplex bus of the
Module FPD‑7024 with a supervised input loop. The D7044 draws
operating power from the FPD‑7024.
D7052 MUX Dual Input Fire Connects to the multiplex bus of the FPD‑ 7024 and
provides two supervised input zones for connecting
conventional normally-open inputs. The D7052 draws
operating power from the FPD‑7024.
D7053 MUX I/O Module Fire Connects to the multiplex bus of the FPD‑7024 and
implements a supervised local loop, and a Form C relay
output. Up to 20 modules can be connected to each MUX
bus. The D7053 draws operating power from the
FPD‑7024.
D7050/TH MUX Smoke Detector The D7050/TH is a photo-electric smoke detector with a
heat option. It connects to the multiplex bus of the
FPD‑7024. The D7050 draws operating power from the
FPD‑7024.
DX4020 / B420 models The Conettix DX4020 and B420 models are communication
devices that manages secure, two-way IP communications
over Ethernet networks.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 19
9 17 25 33 41 49 57 65
16 24 32 40 48 56 64 72
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
20 en | Fire Safety Fire Alarm Control Panels
3 Fire Safety
Danger!
No fire detection device or system is 100% foolproof.
This fire alarm system can provide early warning of a developing fire. Such a system, however,
does not ensure protection against property damage or loss of life resulting from a fire. Any
fire alarm system can fail to warn for any number of reasons (such as smoke not reaching a
detector that is behind a closed door).
Notice!
i This system must be regularly tested (when installed, when modified, and at least annually
thereafter) to ensure continued performance.
When considering detectors for residential applications, refer to NFPA Standard 72, The
National Fire Alarm Code. This standard is available at a nominal cost from: The National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269.
Notice!
i For added early warning protection, install detectors in all separate areas including the base-
ment, bedrooms, dining room, utility room, furnace room, and hallways.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Fire Safety | en 21
1 Bedroom 5 Basement
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
22 en | Installation Fire Alarm Control Panels
4 Installation
4.1 Installation guide for UL Listed systems
4.1.1 FPD‑7024 UL Listings
The FPD‑7024 is UL Listed for the following:
– Commercial Fire Alarm (UL Standard UL864)
– Type Service: Auxiliary, Local, Central Station, and Remote Station
– Type Initiating: Automatic, Manual, Sprinkler Supervisory, and Waterflow
Install the control panel according to NFPA 72 for Commercial Fire installations.
4.1.3 UL requirements
Notice!
i The system must be tested after installation and after any re-programming, including pro-
gramming performed by downloading.
When used in UL Listed installations, the control panel must conform to certain programming
requirements. For a list of the required program entries specific UL Listed installations, see
the Programming features for UL864 table, 49.
Commercial Fire Alarm (Central Station [DACT] and Local)
Required Accessories
– At least one Bosch Security Systems, Inc. Model F220‑P Smoke Detector with an F220
Family Base; or another UL Listed compatible smoke detector.
– At least one Horn Strobe or Bell (provides 85 dB for UL985 and NFPA 72 requirements;
other UL Listed compatible devices listed for regulated 24 V can be used) is required for
this application and must be installed inside the protected area.
– Four-wire detectors must be used with UL Listed power supervision devices. A
compatible UL Listed four-wire detector is the Bosch Security Systems, Inc. F220‑P in an
F220‑B6 Family Base. A compatible UL Listed relay is the Bosch Security Systems, Inc.
D275.
– All points must be used with the resistor provided.
Report Programming
– Program non-supervisory and supervisory reports for those points used.
– Program trouble reports.
– Set AC Failure Report Delay for a delay of 1 hour to 3 hours.
– Set automatic test report frequency to occur at least every 24 hours.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Installation | en 23
Timer Programming
– Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silence
operation.
Point Programming
– For fire points: open = trouble, latching.
Alarm Output Programming
– Program notification appliance circuits to activate from the appropriate input points.
Communications Programming
– If used for Central Station Service, select a communication format compatible with the
central station. Enable monitoring of both phone lines.
UL Listed Accessory Devices
D132B Multi-use Reversing Relay Module
The D132B is a multi-purpose, fully configurable, smoke power-reversing module for activating
detectors with local annunciation. The D132B operates both two-wire and four-wire circuits
and also works with Class A or Class B initiating circuits. An alarm latch connection is
provided to allow an initiating loop to be held in alarm after the detector loop power is
reversed to activate any sounders. The D132B does not affect compatibility between the FACP
and detectors, or the FACP and Notification Appliance Circuits (NACs).
See also the D132B Installation Guide for detailed installation instructions for the D132B
module. One of the installation options shown in the D132B Installation Guide is also shown in
the following figure:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
24 en | Installation Fire Alarm Control Panels
5 Latch 11 24 V NACs
6 NAC
D185 Reverse Polarity Module
The D185 Reverse Polarity Module is a UL Listed module that connects the control panel with
either a single set or a pair of leased telephone company (TELCO) lines in NFPA 72 remote
station applications. It relays system alarm status information from the control panel to a
monitoring station. The D185 operates with either 12 VDC or 24 VDC supply.
For typical wiring of the D185 module, see the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Installation | en 25
3 D275 bu blue
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
26 en | Installation Fire Alarm Control Panels
5. Install and tighten the remaining two screws in the bottom mounting holes.
6. Knock out the desired wire entrances on the enclosure.
For mounting hole locations, see the following figure:
Notice!
i If using the knockouts located at the bottom of the enclosure, install batteries in a separate
enclosure.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Installation | en 27
Warning!
Before the circuit board is installed, connect the supplied ground wires between the door and
! the enclosure and from the transformer to the enclosure using the supplied nuts. Both
grounds connect to the stud in the enclosure to the left of the circuit board.
For installation illustrations, see the figures for Enclosue installation, 26 and for Standoff and
support post installation, 27.
1. Insert the three support posts in the enclosure’s retainer holes.
2. Press the 1/8 in. nylon standoffs (P/N: F01U034705) into the retainer holes.
3. Slide the top of the control panel onto the retainer tabs (the slots under the top of the
frame). When the control panel is in the retainer tabs, it rests on the posts.
4. Secure the bottom of the circuit board by inserting and tightening the screws at the two
bottom corners through the support posts and the retainer holes.
For installing standoffs and support posts, see the following figure:
4Z EXP DETECTED
MUX DETECTED
Press the [*/BACK] key to confirm the installation of the device and automatically set it up for
supervision.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
28 en | Installation Fire Alarm Control Panels
If the [*/BACK] key is not pressed during the power-up time-out period, the control panel
resumes operation using the last confirmed status of the affected expander and displays an
installation error condition.
Warning!
Expansion devices such as point expanders and multiplex expanders are disabled if they are
! removed from the control panel configuration after installation. You cannot disable supervi-
sion of these devices when they are installed.
For additional information, see the installation instructions for the specific expanders.
Notice!
EEPROM fault at first installation
When the D7039 Multiplex Expansion Module is first installed, the system displays an EE-
i PROM fault. Execute the default procedure to synchronize the EEPROM on the expansion
module to the EEPROM in the control panel. Remove power to the control panel, then reapply
power and re-install option bus devices after the default procedure.
Notice!
Loss of programming
i Replacing a D7039 Multiplex Expansion Module causes the loss of programming of expansion
points and PINs. Reprogram all multiplex point and PINs if you replace the D7039.
When the D7039 is first installed, or anytime the control panel is powered with a D7039 that
has no points programmed, the system automatically starts the multiplex auto-programming
process:
AUTO PROGRAM?
_______:YES(1) NO(0)
Pressing the [1] key starts auto-programming, and pressing [0/Prog] allows the control panel
to continue normal startup. The menu automatically closes with NO selected if no key is
pressed after several minutes.
For detailed instructions on the auto-programming mode, see Auto Program, 93.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Connection | en 29
5 Connection
5.1 FACP terminal connection
Danger!
Incorrect connections may result in damage to the unit and personal injury.
Warning!
! Before servicing this equipment, remove all power including the transformer, battery and
phone lines.
Notice!
i Shared cable is not recommended for option bus, telephone or NAC wiring.
2 Class B, Style B
3 EOL relay
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
30 en | Connection Fire Alarm Control Panels
Notice!
All wiring except battery terminal and primary AC power is power-limited. Primary AC and bat-
i tery wires must be separated from other wires by at least ¼ in. (64 mm) and tied to prevent
movement.
RD red
BN brown
supervised:
YE yellow
WH white
BK black
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Connection | en 31
3 Relay 3
Notice!
i For connection to listed power limited Class 2 or Class 3 sources only. Contacts rated at
5.0 A, 24 V.
Notice!
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
32 en | Connection Fire Alarm Control Panels
DX4020,
B420 models,
ITS-DX4020-G
Notice!
i Unswitched unsupervised Auxiliary Power: 24 V, 1.0 A maximum (unfiltered).
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Connection | en 33
Danger!
Explosion and burn hazard!
Do not short terminals!
Batteries:
Danger!
Shock Risk!
Do to risk of shock and/or damage to the transformer a wire mut must be in place over the
unused black or yellow wire.
Connect the earth ground to the threaded ground stud on the left side of the enclosure.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
34 en | Connection Fire Alarm Control Panels
Primary:
YE yellow WH white
BK black
Notice!
i Shared cable is not recommended for option bus, addressable points bus, telephone, or NAC
wiring.
Notice!
i To comply with UL, do not share supplementary devices with primary device on the option
bus.
Avoid shielded or twisted pair-wire except for special applications where a reduced length of
wiring (approximately 50%) is acceptable for tolerating a harsh electrical environment.
The length of wire allowed between the control panel and the last device on a wiring run
depends on the existing current draw on that wiring run. Reducing the number of devices on a
wiring run allows the individual runs to be longer.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Connection | en 35
Add together the alarm existing current draw by all the devices on the wiring run to determine
the maximum allowed distance between the option bus terminals on the control panel and the
last device on the wire run (the device farthest from the control panel).
To determine the maximum allowed length for the run, add up the total alarm load for option
bus devices on the wire run. For example, if the total load of option bus devices on a
particular run is 400 mA, the maximum length of the run can be up to 500 ft (152 m). No more
than 4 000 ft (1 219 m) of wire can be connected to the option bus terminals, even if the
individual lengths of the runs are all within limit.
For the allowed lengths for18 AWG (1.2 mm) wire, see the following figure:
Notice!
The graph is for 18 AWG cable!
i For16 AWG (1.5 mm) wire, cable lengths can be 1.5 times longer. For14 AWG (1.8 mm) wire,
cable lengths can be 2.5 times longer. The 4 000 ft (1 219 m) maximum length of connected
wire still applies.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
36 en | System Operation Fire Alarm Control Panels
6 System Operation
6.1 Modes of Operation
There are four modes of system operation for the FPD‑7024: normal, alarm, supervisory, and
trouble.
6.1.1 Normal
When the system operates normally, it shows SYSTEM NORMAL on the top line of the display,
the Power LED lights steadily, and no other LEDs are lit. The bottom line indicates the existing
date MM/DD/YY and time HH:MM. If the system is programmed to require a PIN, the second
line of the LCD screen shows ENTER PIN.
XXX/XXX FIR: XXXXX One or more fire or waterflow points are in alarm.
XXX/XXX TRB: XXXXX A trouble condition exists (AC power failure, phone line
trouble, and so on).
Table 6.1: Off-normal displays
6.1.3 Acknowledge
When the control panel is off-normal, the control panel’s piezo (buzzer) can be silenced
without silencing the NACs or resetting the control panel. Press the [ACK] button on the local
or remote keypad to silence only the piezo.
6.1.4 Alarm
When an alarm occurs, the top line shows the number of alarms and the point that is in alarm.
The bottom line alternates between the instructions and the programmed description for the
affected point. When you back out of the detail view and go to the group view by pushing the
[4/<] key, the top line of the display shows ALARM (XXX), where XXX indicates the number of
alarms. This display overrides any other system display. The built-in sounder turns on with a
steady tone, and outputs programmed to activate with the existing alarm condition(s)
activate.
When the control panel is not scanning the inputs, as during smoke power reset, alarm
verification delay, or on-site programming, the trouble LED flashes to indicate this condition.
6.1.5 Supervisory
When a Supervisory condition occurs, the top line shows the number of supervisories and the
point that is in the supervisory condition. The bottom line alternates between the instructions
and the programmed description for the affected point. When you back out of the detail view
and go to the group view by pushing the [4/<] key, the top line of the display shows
supervisory (XXX), where XXX indicates the number of supervisory conditions. The bottom line
indicates more instructions. The built‑in sounder beeps. Outputs programmed to activate with
the existing condition(s) then activate.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 37
6.1.6 Trouble
When a trouble condition occurs (such as cut wiring for a point or AC power fails), the
sounder beeps every 10 seconds. The Trouble LED lights and the LCD shows the trouble
condition. When you back out of the detailed screen when the [4/<] key is pressed the group
is entered and shows TROUBLE (XXX). The system can diagnose and show a variety of trouble
conditions, including those affecting the input points, NAC circuits, power, battery, system
grounding, and internal operations of the fire control panel. Notify your installing company
immediately if the system trouble message appears.
Press the [Acknowledge] key to silence the system trouble beep.
Danger!
Fire Alarm!
During a fire alarm, exit from the premises immediately. Do not enter the premises unless ac-
companied by the appropriate emergency services' personnel, or until they have given the OK
to enter.
DANGER!
When it is determined that there is no fire, you can silence the horns or bells to allow more
investigation of the devices that initiated the alarm, or you can reset the system to return it to
normal operation.
Notice!
Before resetting fire alarms
Before using the [Reset] key, determine which smoke detector sounded the alarm so that the
i monitoring company can check that the system is operating correctly. If the control panel is
being used as an addressable control panel, use the [History] key to determine which address
is in alarm.
NOTICE!
If the system is configured to allow alarm silencing, the [Silence] key turns off the horns or
bells, but does not reset the alarm status and does not return the activated input to normal
service. Detectors that were activated stay in alarm and can be checked (usually by observing
an LED on the device) to see which detector caused the alarm. When the detectors causing
the alarm are identified, reset the system to return it to normal service.
The [Reset] key clears the system alarm status, and briefly turns off power to the detectors to
reset them. This command is required after any fire alarm affecting a point programmed for
latching operation (which is the normal configuration). This operation is also required to reset
Class A, Style 6 multiplex (SLC) wiring fault troubles.
The software automatically supervises the system software for proper operation. If the system
fails, a CPU FAULT message appears, and the nature of the failure can be optionally recorded
in the history buffer. To enable history buffer recording for CPU faults, program Output Zone
D of onboard Relay 2 to Zone 51 (unused). The history buffer message, if enabled, shows
CPUFLTxxx, where xxx is an error code. If the display shows CPU FAULT, contact Bosch
Security Systems, Inc. Technical Support and report the history buffer code along with a
description of the operations that caused the fault. Unusual conditions during programming
and debugging operations can result in a CPUFLT message in the history buffer. If, this occurs
when the control panel is in service, report it to Technical Service.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
38 en | System Operation Fire Alarm Control Panels
6.2.6 Drill
The drill command activates all NACs and no relays. It creates a history log entry and, as an
option, can be reported to the central station.
6.2.7 Disable
Use the disable command to disable input points, outputs, or the dialer. When any device is
disabled, the system shows this condition on the LCD and on the system trouble LED. The
Disable All Inputs operation takes several seconds to perform, during which time the system
display remains fixed.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 39
6.2.8 History
Notice!
i If a system without a D7039 Multiplex Expansion Module loses all power (AC and standby bat-
tery), all history events are cleared.
The HISTORY option is a chronological list of system events that occurred. Press the [History]
key to HISTORY select from the Main Menu (SYSTEM NORMAL display).
On an FPD-7024 FACP with a D7039 Multiplex Expansion Module, up to 499 History events are
supported.
On an FPD-7024 FACP without a D7039 Multiplex Expansion Module, up to 99 History events
are supported.
After you press the [History] key, the most recent system event appears on the top line of the
LCD with the time and date below it.
Example: (Assume you pressed the [History] key at the Main Menu):
While the first event shows, the bottom line toggles every four seconds between the time and
date that the event occurred.
To return to a previous screen in the history buffer, press [2/▲].To scroll to the next event
record, press [8/▼].
For abbreviations used in history events, see the following table:
F Fire W Waterflow
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
40 en | System Operation Fire Alarm Control Panels
For additional history log ID information, see the Modem IIIa2 reporting table, 105.
6.3 Keypads
6.3.1 Built-in keypad
The keypad built into the control/communicator is an alphanumeric LCD keypad. It has a two-
line by 16-character display to provide information on various control panel functions. Usually,
the first line shows the off-normal condition, while the second line describes specific details
that might be relevant to the existing system status. A built-in sounder annunciates keystroke
entries and acts as a warning device.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 41
1 Green Power LED - is on when the AC 9 [#/Enter] key - to accept data when in
power is present, and flashes when the programming mode.
the unit is operating from battery
power.
2 Yellow Trouble LED - lights when the 10 [History] key - to view system events.
system detects a problem with wiring
or internal circuitry. The Trouble LED
flashes while programming mode is
active and whenever inputs are not
active, such as during smoke power
reset or alarm verification.
3 Red Alarm LED - lights when the 11 [Reset] key - briefly (programmable
system registers an alarm and was not from 1 to 16 seconds) turns off power
reset. to the detectors to reset them and
clears any off- normal conditions.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
42 en | System Operation Fire Alarm Control Panels
4 Yellow Silenced LED - lights when the 12 [Silence] key - mutes the bell or sirens
user manually silences an alarm for an alarm condition, if the system is
condition (fire or water flow), turns off so configured.
when the condition that was silenced
is corrected.
5 [Disable] key - used to disable or 13 [Drill] key – used to activate the NACs
re‑enable inputs, NACs or relays manually. It creates a history log entry
(outputs), and the dialer. and as an option reports to the central
station.
6 [Test] key - used to select one of seven 14 Yellow Supervisory LED - lights
special test modes. 1
whenever the system registers a
supervisory condition.
For abbreviations on the keypad and control panel, see Control Panel Display Descriptions,
100.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 43
1 LEDs 3 Keys
2 Keypad Display
6.4 Testing
Select any of seven special test modes using the [Test] key on the built‑in and FMR‑7033
keypads.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
44 en | System Operation Fire Alarm Control Panels
Notice!
This test is available only if your system sends alarms and system information to a monitoring
i service, and was programmed by the security installing company to permit communicator
tests.
NOTICE!
Warning!
Reset upon termination of test
Terminating the communicator test function (with the [*/Back] key) resets the communicator
! and discards all unsent reports. When an off-normal condition occurs during a Communicator
test, the test automatically resets, clearing all reports, so the off-normal conditions are sent
normally.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 45
5. Show Status: After you select a device and press [#/Enter], this test shows detailed
status information for the selected device. Eight conditions (not all status conditions
apply to or are supported by all devices) are shown. See the display shown below (which
updates automatically every five seconds). For this option, you can view the status of any
MUX device regardless of which bus you selected to test when test mode was entered.
– XxLxRxDxMxTxFxAx
x is either 0 or 1 depending on whether the condition is false or true (0=false and 1=true). The
letters indicate the condition:
– X: Reserved for future use.
– L: Commanded relay state - this is how the output relay should be set. R: Actual relay
state - this is how the output relay is actually set.
– D: Detector dirty - the detector is excessively sensitive.
– M: Missing device - the device cannot be found on the loop. Unless a device was
programmed into the system (such as using MUX EDIT), it is not considered missing.
– T: Tamper – the detector’s case was opened.
– F: Loop fault - the loop from a contact input device is open, or the device is faulted. A:
Loop alarm - the point is in alarm.
Pressing [*/Back] ends the display for any of these modes.
Examples: X0L0R0D0M0T0F0A0 (relay off, not dirty, not missing, no tamper, no fault and no
alarm).
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
46 en | System Operation Fire Alarm Control Panels
Zone Condition
52 General Fire Alarm, Waterflow (non-silenceable). Same as Zone 53, but remains
active even while system is silenced.
53 General Fire Alarm (silenceable). Active when a fire alarm condition is present;
does not activate for waterflow.
54 Activates for approximately 7 sec before dialing, to initiate dial tone on a ground
start phone system.
59 Alarm Verification. Active while alarm verification is in progress. This starts with
the first detection of an alarm to be verified and clears in two minutes, or when
system is reset.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels System Operation | en 47
Zone Condition
62 General Trouble. Active while any system trouble is present, not active in test and
programming modes.
Maximum (1) All control panel operations, including programming, and disable
Medium (2) System test modes, fire drill, reset, silence, view history
Notice!
i You must enable and configure the communicator before it works. The communicator and
phone line monitors are disabled in the default factory configuration.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
48 en | System Operation Fire Alarm Control Panels
Notice!
To disable a phone number, set the FORMAT to 0=disable. To completely disable the commu-
i nicator, set FORMAT to 0=disable for both phone numbers, and set MONITOR to 0=NO for
both phone lines.
Notice!
i Do not install this control panel on a phone line that might be required for other emergency
use.
When events occur, the communicator sends them to the monitoring station in priority order
according to NFPA requirements. Fire and waterflow alarms are sent first, followed by
supervisory alarms and trouble reports and then all other reports. Priority reporting can send
a Restoral report after several alarm reports in a situation where a point sends multiple
alarms, implying that a point is restored when it has returned to alarm. The following
sequence, (alarm, restore, alarm) is sent as (alarm, alarm, restore) when priority sorting is
applied.
Warning!
Event sorting can hide unrestored points
! Priority sorting on events sent to a monitoring station can cause the message sequence to im-
ply that a point is restored when it is not.
The communicator can store 32 events while waiting for the monitoring station to accept the
events. If more than 32 reportable events occur before the monitoring station accepts events,
some event information is lost and a Data Lost report is sent to the central station.
The FPD‑7024’s communicator is equipped with a line seizure relay to prevent interference
with outgoing event reports. In a system where the fire communicator shares the phone line
with other equipment on the premises, the phone line might be unavailable to the other
equipment for up to 15 min has a fault with the central station acceptance of the event data.
Phone lines for fire control panels must not be shared with other equipment.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Programming | en 49
7 Programming
Danger!
Untested systems!
After any programming change, and especially after remote programming changes, completely
check the operation of the control panel. Hazards to life and property can result if the system
is not tested to detect possible improper programming.
DANGER!
Warning!
Improper system operation!
When programming the system, enter only valid types of information within the ranges speci-
! fied in the programming table. Incorrect programming results in improper system operation.
When using built-in programming, invalid input values might not be rejected in every case. En-
sure that you enter only the intended values while programming to prevent improper system
operation.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
50 en | Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Programming | en 51
Notice!
i A different character is entered each time a numeric key is pressed. For example, pressing
[2/▲] repeatedly enters A, B, C, 2, A, B, and so on.
Key Values
SPACE 1 , ‛ & / # ! 1
1
A B C 22
2
D E F 32
3
G H I 42
4
J K L 52
5
M N O 62
6
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
52 en | Programming Fire Alarm Control Panels
Key Values
P R S 72
7
T U V 82
8
W X Y 92
9
0 Q Z 0
Prog
*
Back
1
Press [1] nine times to reach this value.
2
Press the listed key four times to reach this value.
Table 7.3: Programming points using alphanumics
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Programming | en 53
1 Number keys (including 0) - used to 4 [Disable] key - moves the cursor one
enter alphanumeric values. space to the left.
2 [*/Back] key - used to exit alpha 5 [Silence] key – moves the cursor one
programming, or exit the programming space to the right.
mode entirely.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
54 en | Programming Fire Alarm Control Panels
BFSK
Similar to the programming of system events for 4/2 formats, five system events can be
programmed for two unique digits each when the BFSK format is used. This programming is
done under
7- PROG FORMATS, 3- BFSK RPT CODS.
The BFSK format supports only a three-digit account number. The control panel sends the first
three digits that are programmed. The BFSK (and tone burst) format requires that an A (hex
character) be entered at the control panel to cause the receiver to display 0. The BFSK format
can report only eight points, so Points 8 to 255 are all reported as point “8”.
SIA
The SIA reports are fixed, and do not require programming.
Contact ID
The Contact ID reports are fixed and do not require programming.
3/1
The 3/1 reporting codes are determined by the programming of the 4/2 codes. Send only
Digit 1 (left digit of the two-digit code) and the first three digits of the account number.
Modem IIIa2
The Modem IIIa2 reports are fixed and do not require programming.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Programming | en 55
CMND/#
1-PROG TIME 1-SYSTEM
1-TEST TIME
2-AUTO TEST 2-TEST FREQ
1-UPDATE BUS
3-PROG SYSTEM 4-OPTION BUS 2-SETUP KEYPDS
DRILL 5-PIN
1-LOCAL
REQUIRED?
2-REMOTE
6-NAC SIL
PROG/0 1-AUDIBLE ONLY
MODE
2-AUDI & VISI
7-REMOTE PGM
0-FUNCTION
1-ALARM/TROUBLE
2-OUTPUT ZONE
3-VERIFICATION
4-LATCHING
1-POINT 5-DESCRIPTION
NUMBER <DRILL> NEXT PNT
<HIST> PREV PNT
0-CONFIGURE 1-FIRE
1-LOCAL ONLY 2-WATERFLOW
2-POINT 2-(reserved) 3-SUPERVISORY
4-PROG INPUTS FUNCTION 3-SILENCEABLE 4-(reserved)
4-LOOP RESPONSE 5-RESET
5-(reserved) 6-SILENCE
<DRILL> NEXT FCT 7-AC FAULT
<HIST> PREV FCT
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
56 en | Programming Fire Alarm Control Panels
7.6 Shortcuts
You can use shortcuts to reduce repetition and provide speedy instructions for programming
the control panel.
The first level in the system is the Main Menu. For all system programming, <PROG/0> is your
Main Menu choice. Therefore, the first number in the shortcut is “0”.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Programming | en 57
The second level in your system provides eight options: PROG TIME, SECURITY,
PROG SYSTEM, PROG INPUTS, PROG OUTPUTS, PROG ACCOUNTS, PROG FORMATS, and
HISTORY DEFAULTS. When the D7039 MUX Expander is installed, a ninth option appears:
PROGRAM MUX. The second number in the shortcut enters the Level 2 option and allows
access to Level 3.
Level 3 provides the third set of options that branch from Level 2. The third number in the
shortcut represents the option chosen in Level 3.
For an example of the shortcut to TEST FREQ and TEST TIME, see the following figure. The
sample of the Program Menu Tree shows that to get to TEST TIME and TEST FREQ, you must
go to PROG/0 in Level 1, PROG TIME in Level 2, and AUTO TEST in Level 3. The shortcut is
simply a list of the keys you press to get to the fourth level option. Once you enter the
shortcut, follow the procedural description that appears on the screen of the specific function
you are programming.
2
1 3
Shortcut = 012
4 6 7 8
3 Use "2" to select AUTO TEST from Sub- 7 Third number in shortcut
Level 3. Follow the procedural
description that appears on the
screen.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
58 en | Programming Fire Alarm Control Panels
inhibited (but alarm monitoring continuing), the system indicates SYSTEM TROUBLE,
RMT PRG ACTIVE during remote programming. Sounders do not activate during this mode, but
other outputs programmed for Zone 62, general system trouble, do activate.
Trouble conditions that occur during a remote programming session are not annunciated at
the control panel until the remote programming session ends. These conditions are available
in the remote programmer diagnostic displays during the session. Alarm conditions terminate
remote programming and are shown immediately.
When remote programming is disabled, you can still connect to the control panel for
diagnostics and view the existing programming (except PIN numbers). To actually change
programming, enable remote programming.
To enable remote programming, refer to the following programming items:
– 0-3-7 Remote Programming, 67
– 0-6-1 Computer PH/IP, 78
– 0-6-1 Account Number 1, 78
– 0-6-2 Dialing Type, 82
– 0-6-4 Ring Count, 84
– 0-6-6 Machine Bypass, 85
An access code with maximum authority (1) is needed to begin remote programming from the
panel.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 59
Enter the date followed by the [#/Enter] key. The following window appears:
Use this feature to program the time of day at which automatic tests occur. This feature uses a
24‑hour clock (for example, 11:00 p.m. = 2300).
The following window appears:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
60 en | Control Panel Programming Fire Alarm Control Panels
AUTOMATIC TEST
1-TEST TIME
2-TEST FREQNCY
This feature allows you to program how often the automatic test reports are sent. The first
test is sent when the programmed test time matches the system time. Subsequent reports are
sent according to the selected interval.
The following window appears:
AUTOMATIC TEST
1-TEST TIME
2-TEST FREQNCY
AUTO FRQNCY ( )
1-4 HOURS
2-12 HOURS
3-24 HOURS
4-7 DAYS*
5-28 DAYS*
* For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
Press the number key that corresponds to your selection. The existing setting is displayed in
parentheses on the first line. After you have programmed the test frequency, the previous
window appears.
This feature enables automatic adjustment of system time for Daylight Saving Time. The dates
for the adjustment are pre-programmed in the system.
The following window appears:
DAYLIGHT SAV
1-DISABLE
2-ENABLE
Press [1] to select DISABLE or [2] to select ENABLE. After you have programmed this feature,
the previous window appears.
8.2 SECURITY
SECURITY
1-PINS
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 61
2-AUTHORITY
The Programmer PIN is the code used by the installer to configure and operate the panel.
Factory default code is 9876 and may be changed at any time.
The following window appears:
PROGRAM PINS
1-PROGRAMR PIN
2-USER PINS
USER 0
ENTER PIN:_______
Enter the PIN and press [#/Enter]. After you have programmed the Programmer PIN, the
previous window appears.
Program User PINs
Up to 15 additional user codes (or up to 99 additional users when the D7039 is installed) can
be programmed to protect the system from unauthorized operation and allow a record to be
kept of actions by individual system users.
The following window appears:
PROGRAM PINS
1 - PROGRAMR PIN
2 - USER PINS
OTHER PINS
USER (01-15)
Enter the user for whom you want to program a PIN and press [#/Enter]. Example: For User 5,
press [5]. The following window appears:
USER 5
ENTER PIN:_______
Enter the PIN and press [#/Enter]. After you have programmed the user PIN, the previous
window appears.
8.2.2 Authority
Shortcut: 0-PROG, 2-SECURITY, 2-AUTHORITY
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
62 en | Control Panel Programming Fire Alarm Control Panels
AUTHORITY
USER (01 - 15)
Enter the user for whom you want to program the authority level and press [#/Enter]. The
following window appears and scrolls through the following choices:
Press the number key that corresponds to your selection. The existing setting is shown in
parentheses on the first line. After you have programmed the user authority, the previous
window appears.
TIMERS
1 - SMOKE RESET
2 - AC FAIL DLY
3 - AUTO SILENCE
4 - (reserved)
5 - DISPLAY RATE
Smoke reset
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 63
This feature determines how long the smoke detector power is off after reset. No alarms are
registered by the system for 5 sec after power is returned.
The display scrolls through the TIMERS options. Press [1] for Smoke Reset. The following
window appears:
Enter the time and press [#/Enter]. The existing setting is shown in parentheses on the first
line. After you have programmed the smoke reset, the previous window appears.
AC fail delay
This feature sets the number of hours the control panel waits after an AC failure before
sending an AC Failure report. A setting of DC causes the system to send a report when 25% of
the battery capacity is used.
The display scrolls through the TIMERS options. Press [2] for AC FAIL DELAY. The following
window appears:
AC FAIL DELAY
1 - WAIT FOR DC
2 - ENTER TIME
The wait for DC function causes the AC fail report to be sent when the battery is 25%
depleted, based on the measured voltage of the battery. If you want to WAIT FOR DC (25
percent of capacity), press [1]. The existing setting is displayed in parentheses on the first
line, either “DC”, or the number of hours selected. After you program the AC Fail Delay, the
previous window appears.
To ENTER TIME press [2]. The following window appears:
* For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
Enter the time and press [#/Enter]. The existing setting is shown in parentheses on the first
line. After you program the AC Fail Delay, the previous window appears.
Notice!
i When Wait For DC is the existing selection, the Enter Time menu displays DC as the time in
hours.
Auto silence
This feature silences the sounding of an alarm condition on selected NACs after a certain
amount of time. When you use Auto Silence, pressing [0/Prog] disables the feature and the
only way to turn off an alarm is to manually silence it. Entering between 5 min and 99 min
means that the alarm sounds for that much time before automatically silencing.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
64 en | Control Panel Programming Fire Alarm Control Panels
Notice!
If the condition that caused and alarm is not corrected after an alarm is silenced (automatical-
i ly or manually), the alarm sounds again after 24 hours. The system must eventually be reset
after silencing to allow the alarmed zones to restore and detect new alarms.
The display scrolls through the TIMERS options. Press [3] for AUTO SILENCE. The following
window appears:
AUTO SILENCE (__)
(0, 5-99 min):_______
Enter desired length of time (or press [0/Prog] to disable) and press [#/Enter]. The existing
setting is shown in parentheses on the first line. After you program the auto silence, the
previous window appears.
Display rate
Set the speed at which menus are displayed on the LCD (in units of 0.25 sec).
The display scrolls through the TIMERS options. Press [5] for DISPLAY RATE. The following
window appears:
DSPLY RATE (__)
.25 X (1-16):_______
Enter desired value and press [#/Enter]. The existing setting is shown in parentheses on the
first line. After you program the display rate, the previous window appears.
When AC power is available, the control panel uses the line frequency to stabilize the real-
time clock. This setting must match the frequency of the local AC power (60 Hz in the US).
The following window appears:
Press the number key that corresponds to your selection and press [#/Enter]. The existing
setting is shown in parentheses on the first line. After you program AC Line Synch, the
previous window appears.
When devices are added or removed from the option buses, this feature queries both option
buses and updates the list of connected devices. This enables the new devices and removes
supervision for devices no longer present.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 65
Warning!
Inoperable, unsupervised devices!
! Be sure the count of devices displayed when this operation completes matches the number of
devices installed on both buses. Devices not detected during the update bus operation will
not operate and will not be supervised.
Notice!
i These menu items are allowed only at the local keypad.
Press [1] to program the system to update the bus. After you program Update Bus, the
following window appears:
UPDATE COMPLETE
TOT BUS DEVS: X
This feature tells the system how many keypads to supervise. It automatically performs an
update bus operation as it completes.
OPTION BUS
1 - UPDATE BUS
2 - SETUP KEYPDS
# OF KEYPADS (__)
(0-4):_______
Enter the desired value and press [#/Enter]. The existing setting is shown in parentheses on
the first line. After you set up the keypads, the update bus operation proceeds, then the
previous window appears.
A PIN can be required before performing operations. Enter the PIN at the local or built-in
keypad.
The following window appears:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
66 en | Control Panel Programming Fire Alarm Control Panels
PIN REQUIRED?
1- LOCAL
2- REMOTE
Press [1] to require a PIN at the local keypad. The following window appears:
Press the number key that corresponds to your selection. The existing setting is shown in
front of the colon on the second line. After making your selection, the previous window
appears.
Remote
PIN REQUIRED?
1- LOCAL
2- REMOTE
Press the number key that corresponds to your selection and press [#/Enter]. The existing
setting is shown in front of the colon on the second line. After you select the PIN requirement,
the previous window appears.
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
Notice!
A PIN can be required before operations can be performed using the remote keypads on the
i option bus. If the remote keypads are not otherwise secured, this option must be set to YES
to comply with NFPA and Local requirements.
NAC silence mode allows notification devices to be silenced from the control panel. Any
output configured as silenceable is silenced upon silence operation. You can define audible
only or audible and visible by this option. If silenced, a relay is completely turned off.
The following window appears:
1-AUDIBLE ONLY
2-AUDI & VISI
Press [1] to configure the audible output to be silenceable leaving the visible output to
display. Press [2] to configure both the audible and visible outputs to be silenceable.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 67
Remote programming allows the panel to be called from a remote site by phone to reconfigure
any of the programmable options. When remote programming is disabled, you can still
connect to the control panel for diagnostics and to view the existing program. PIN numbers
are suppressed while remote programming is disabled.
REMOTE PGM
0- DISABLE
1- ENABLE
Press [0/Prog] to select DISABLE or [1] to select ENABLE, and the previous window appears.
Danger!
After any programming change, and especially after remote program changes, completely
check operation of the control units. Hazards to life and property can result if the system is
not tested for incorrect programming.
Notice!
i Point functions allow quick programming of similarly functioning points (for example, pull sta-
tions, smoke detectors) with common settings.
PROG POINT
0- FUNCTION
1- ALARM/TROUBL
2- OUTPUT ZONE
3- VERIFICATION
4- LATCHING
5- DESCRIPTION
<DRILL> NEXT PNT
<HIST> PREV PNT
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
68 en | Control Panel Programming Fire Alarm Control Panels
Pressing [Drill] retrieves the next point. For instance, if you are programming Point 2 and you
press [Drill], you retrieve the setting for Point 3.
Pressing [History] retrieves the previous point. For instance, if you are programming Point 2
and you press [History], you return to the setting for Point 1.
Assigning point functions
This feature assigns each point to one point function. A point function is a set of
characteristics that you can assign to selected points. There are 16 point functions to choose
from.
For more information about point functions, see Point function, 70. For the limitations when
assigning points to point functions that were programmed with a response time other than
Fast, see Loop response, 72.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [0/Prog] to select FUNCTION. The following window appears:
Enter the function number you wish to assign to the point and press [#/Enter]. The existing
setting is shown in parentheses on the first line. After you assign a point function, the previous
window appears.
Alarm/Trouble status
This feature allows you to program the system response to an open loop condition. A shorted
loop always causes an alarm condition.
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
ALARM: A point in an open circuit state causes an alarm.
TROUBLE: If a point is in an open circuit state, the system responds with a trouble condition.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [1] to select ALARM/TROUBLE. The following window appears:
Press [1] to select ALARM on open loop and ALARM on shorted loop or [2] to select TROUBLE
on open loop and ALARM on shorted loop. The previous window appears. The existing setting
is shown in parentheses on the first line.
Output zones
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [2] to select OUTPUT ZONE. The following window appears:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 69
Press the number key that corresponds to your selection. ZZZ indicates the point being
programmed. The existing setting is shown on the second line. After you set up the output
zone, the previous window appears.
Verification
This feature resets the detector once to determine if the alarm recurs before annunciating or
sending a signal. The total delay introduced by this feature is equal to the smoke power reset
time plus five seconds. Alarm verification cannot be selected for points that are configured as
WATERFLOW or SUPERVISORY types.
Enter the point number you wish to verify and press [#/Enter]. The display scrolls through the
PROG INPUT options.
Press [3] to select VERIFICATION. The following window appears:
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press either [1] to verify or [0/Prog] to not verify. The previous window appears.
Latching
If a zone is non-latching, the system resets the alarm status automatically (but does not reset
smoke power) when the input restores to the standby condition. Otherwise, the system must
be manually reset.
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [4/◄] to select LATCHING. The following window appears:
LATCHING? ZZZ
:YES(1)NO(0)
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press the number key that corresponds to your selection. Select YES for alarm.
The previous window appears.
Point description
For this feature, use the numeric keys to enter alphanumeric information to identify each input
(such as initiating circuit). The system allows one 16-character description per input. Enter the
point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [5] to select DESCRIPTION. The following window appears:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
70 en | Control Panel Programming Fire Alarm Control Panels
Enter the description using the numeric, [Silence] and [History] keys, then press [#/Enter] to
save the description.
There are 16 point functions, each of which has programmable features for: configuration
(fire, waterflow, and so on), local only operation, silencing, and loop response.
Notice!
i At default, points 9 to 255 are programmed as Function 10 which is set as Fire. Function 11 is
set as Supervisory. Function 04 is set as Waterflow 16 second.
Enter the function number you wish to program and press [#/Enter]. The following window
appears:
PROG FUNCT
0- CONFIGURE
1- LOCAL ONLY
2- (reserved)
3- SILENCABLE
4- LOOP RESPONS
5- (reserved)
<DRILL> NXT FCT
<HIST> PREV FCT
– Fire: When activated, the point shows FIRE ALARM on control panel and keypads,
activates selected output devices, and sends a Fire Alarm report (if programmed). Fire
points are defaulted to a latch when first configured.
– Waterflow: When activated, the point shows WATERFLOW ALARM on control panel and
keypads, activates selected output devices, and sends a Waterflow Alarm report (if
programmed). Waterflow points are defaulted to a non-verify characteristic when first
configured.
– Supervisory: When activated, the point shows SUPERVISORY ALARM on control panel
and keypads, and sends a Supervisory Alarm report (if programmed). Supervisory points
are defaulted to a non-verify characteristic when first configured.
– Reset: When activated, the point initiates a control panel-reset operation to clear alarms
and reset smoke detectors. Only points 1 to 8 can be configured as reset points.
– Silence: When activated, the point initiates a control panel silence operation to turn off
sounders if the control panel is configured to allow silencing. Only points 1 to 8 can be
configured as silence points.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 71
– AC Fault: When activating, the control panel waits for the AC Delay Timer to expire
before indicating or sending a trouble condition. When the timer expires, it shows an AC
Fault on the control panel and the trouble LED turns on.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG FUNCTION options.
Press [0/Prog] to select CONFIGURE. The following window appears:
ACTVTN TYPE ( )
1- FIRE
2- WATERFLOW
3-SUPERVISORY
4- (reserved)
5- RESET
6- SILENCE
7- AC FAULT
Press the number key that corresponds to your selection. (The existing setting is shown in
parentheses on the first line.) The previous window appears.
Local only
Enabling this feature provides the input point for local annunciation only, with no
communicator report. Enter the point number you wish to program and press [#/Enter]. The
display scrolls through the PROG FUNCTION options.
Press [1] to select LOCAL ONLY. The following window appears:
LOCAL ONLY
_______: YES (1)NO(0)
Press either [1] to enable or [0/Prog] to disable. The previous window appears.
Silencing
This feature determines if an output zone (1 to 50) follows the Silence button (relays reset,
NACs silence).
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG FUNCTION options.
Press [3] to select SILENCEABLE. The following window appears:
SILENCABLE? (FF)
_______: YES (1)NO(0)
Press [1] for relays to reset and NACs to silence when the Silence button is pressed, or press
[0/Prog] for relays to remain latched until reset and NACs to continue sounding when the
Silence button is pressed.
Notice!
When an output is assigned to more than one zone, the programming of the zone that triggers
i the output controls the output. When more than one zone triggers the output, if one of the
zones is programmed as non-silencing, the output will be non-silencing.
NOTICE!
The previous window appears. FF indicates the function being programmed.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
72 en | Control Panel Programming Fire Alarm Control Panels
Loop response
This feature allows you to configure points to activate with standard response time (setting 1)
or one system-wide programmed response time (setting 2).
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG FUNCTION options.
Press [4/<] to select LOOP RESPONSE. The following window appears:
* For acceptable programming selections for UL864 9th edition Listed applications, see the
Programming features for UL864 table, 49.
Press the number key that corresponds to your selection (the existing setting is displayed in
parentheses on the first line). The previous window appears.
When you select a programmed response time, the system asks you to enter a response time
from 1 sec to 89 sec that applies to all functions. All functions share a single programmable
response time setting. If this time is set for multiple functions, the last time set is used.
When set for fast response operation, multiplex points typically have a response time.
Response time is (the maximum time an input must be held to guarantee an alarm) of
approximately 1 sec. Response time increases as points on the bus remain off-normal (in
alarm or with a loop or detector trouble), to a maximum of 20 sec in the extreme case of all
points on the bus being in trouble and one point in alarm. On a fully loaded system with only a
few points in alarm or trouble, fast response time remains at approximately 1 sec. For
programmed response, the response time tolerance is ±3 sec when only a few points are off-
normal, and increases by up to 20 sec when all points are off-normal.
On-board points have a response time tolerance of ±1 sec for programmed response time, and
+0.5 sec or - 0.25 sec for fast response time.
Notice!
Up to 20 points can be assigned to point functions that were programmed with a response
time other than Fast. If more than 20 points are assigned to functions programmed with a re-
i sponse time other than Fast, an error message appears: MAX PROGRAMD POINTS EXCEE-
DED. Switching a point function from Fast to Programmed can cause this error, depending on
how many points reference the point function.
<DRILL> NEXT FCT: Pressing [Drill] retrieves the next function. For instance, if you are
programming Point Function 2 and you press [Drill], you retrieve the setting for Point
Function 3.
<HIST> PREV FCT: Pressing [History] returns you to the previous function. For instance, if you
are programming Point Function 2 and you press [History], you return to the setting for Point
Function 1.
Point copy allows you to copy the settings you entered for one point to one or more other
points.
The following window appears:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 73
COPY FROM
POINT:_______
Enter the point you wish to copy from and press [#/Enter]. COPY TO FIRST POINT:_______
Enter the first point you wish to copy to and press [#/Enter]. COPY TO LAST POINT:_______
Enter the last point you wish to copy to and press [#/Enter]. The PROG INPUTS menu appears.
This feature does not copy the description. Point copy is intended for use only on input
points. Do not copy from an output point (future use), or copy over a programmed output
point. The copy operation automatically stops, with an error message, if outputs are
encountered. While copying to a large number of points, the remote keypads might briefly
show system fault, because the keypads are not updated during the copy operation.
The main control panel includes two local NACs (NAC 1 and NAC 2). The FPD‑7024 can also
support up to four FPP‑RNAC‑8A‑4C Remote NAC Power Supplies, which offers a total of 16
remote NACs (four NACs per RNAC).
The following window appears:
NAC OUTPUTS
1- LOCAL
2- REMOTE 1
3- REMOTE 2
4- REMOTE 3
5- REMOTE 4
The display scrolls through the NAC options. Press [1] for LOCAL. The following window
appears:
ONBOARD NAC
1- NAC #1
2- NAC #2
Press the number key that corresponds to your selection. The display scrolls through the
following selection:
PROG NAC
1- AUTO SILENCE
2- CONFIGRATION
3- ZONE ASSIGNS
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
74 en | Control Panel Programming Fire Alarm Control Panels
NAC CONFIG ( )
1- STEADY
2- PULSING
3- CALIFORNIA MARCH
4- TEMPORAL
5- WHEELOCK
6- GENTEX
7- SYSTEM SENSOR
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
These selections control the pattern (code) for the selected NAC. Press the number key that
corresponds with the desired pattern:
– Steady: Output turns on and stays on while the NAC is active.
– Pulsing: Output turns on for 0.5 sec and off for 0.5 sec.
– California March: Output turns on for 0.25 sec and off for 0.25 sec.
– Temporal: Output turns on and off to implement the ANSI standard evacuation pattern
(Temporal code 3).
– Wheelock: Output is configured to support Wheelock devices with synchronization
capability, including the ability to silence the horn of a combination horn strobe. The
Wheelock configuration is not supported by remote NACs implemented using a Remote
NAC power supply.
– Gentex: Output is configured to support Gentex devices with synchronization capability,
including the ability to silence the horn of a horn strobe combination.
Notice!
i The Gentex option does not synchronize to the UL864 9th Edition standard.
Notice!
i XX” indicates the existing setting for each of the four output zone settings.
Enter the desired zone to activate this output and press [#/Enter]. You are asked to enter up
to four zones (A, B, C, D). Enter 00 (or leave it set at “00”) for any unused zones to prevent
unintentional output activation. After all four zones are programmed, the previous window
appears.
For a list of pre-assigned zones, see the following table:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 75
54 Ground Start
57 Communication Trouble
59 Alarm Verification
60 AC Failed
62 General Trouble
Remote NACs
Use only with the FPP‑RNAC‑8A‑4C. The display scrolls through the NAC options. Press [2]
for REMOTE 1, [3] for REMOTE 2, [4] for REMOTE 3, or [5] for REMOTE 4. One of the
following windows appears:
REM EXP NAC #1 REM EXP NAC #2 REM EXP NAC #3 REM EXP NAC #4
1 - NAC #1 1 - NAC #1 1 - NAC #1 1 - NAC #1
2 - NAC #2 or 2 - NAC #2 or 2 - NAC #2 or 2 - NAC #2
3 - NAC #3 3 - NAC #3 3 - NAC #3 3 - NAC #3
4 - NAC #4 4 – NAC #4 4 - NAC #4 4 - NAC #4
Press the number key that corresponds with the NAC you want to program. The display scrolls
through the following selections:
PROG NACs
1- (reserved)
2- CONFIGURATION
3- ZONE ASSIGNS
The options for remote NACs are the same as for local NACs.
Output Configuration:
Steady: Programmed to turn on steadily for a fire alarm.
Pulsing: Programmed to pulse for a fire alarm at 0.5 sec on and 0.5 sec off.
California March: Output turns on for 0.25 sec and off for 0.25 sec.
Temporal: Programmed to pulse for a fire alarm in Temporal 3.
Zone Assignment: Assign each output up to four zones. ZONE A, B, C, or D (00 = disabled) (1
to 63).
Press the number key that corresponds to your selection. After you program the local NACs,
the previous window appears.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
76 en | Control Panel Programming Fire Alarm Control Panels
The main control panel includes three on-board relays (Relay 1, Relay 2, and Relay 3). The
FPD‑7024 can also support up to two D7035 Octal Relay Modules (Remote Relay 1 and
Remote Relay 2), that offer a total of 16 remote relays (eight relays per module).The following
window appears:
RELAY OUTPUTS
1- LOCAL
2- REMOTE 1
3- REMOTE 2
4- MULTIPLEX
Notice!
i The option for multiplex relay programming is visible only if the D7039 Multiplex Expander is
installed.
Local Relays
ONBOARD RELAY
(1-3):
Enter the number corresponding to the relay to be programmed and press [#/Enter]. The
display asks you to enter four zones to activate this output:
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar
display for Zones B, C and D will appear to allow up to four zones to be assigned to this
output. When all four zones are assigned, the previous window appears.
For pre-assigned zones, see Pre-assigned zone quick reference, 74.
An output point cannot be assigned to more than four zones. Each output does not need to be
assigned to four zones. Each zone can have any number of outputs assigned to it.
Remote relays
The display scrolls through the Relay options. Press [2] for REMOTE 1 or [3] for REMOTE 2.
The following window appears:
REMOTE RELAY @ x
(1 - 8):
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 77
Notice!
The @ x shows the address of the relay module in the system. The lower number address is
i Relay 1; the higher one is Relay 2.When you address a MUX Module, you assign an address. If
you have a dual point, it would have two consecutive addresses.
Enter the relay you wish to assign and press [#/Enter]. The display shows:
Enter the output number (00 to 63) you want to assign to Zone A and press [#/Enter]. A
similar display for Zone B appears. When all four zones are assigned, the previous window
appears.
For pre-assigned zones, see Pre-assigned zone quick reference, 74.
An output point cannot be assigned to more than four zones. Each output does not need to be
assigned to four zones. Each zone can have any number of outputs assigned to it.
Multiplex relays
Warning!
! Do not use this menu to program addresses configured as inputs.
The display scrolls through the Relay options. Press [4/◄] for MULTIPLEX. The following
window appears:
MUX OUTPUT
(009 - 255):
Enter the number corresponding with the output to be programmed and press [#/Enter]. The
output number of a multiplex relay is the second point of an I/O module. Adding 1 to the
address of the I/O module gives the address of the relay in the module. When the relay is
selected, the display asks you to enter four zones to activate this output:
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar
display for Zone B, C and D appears, allowing up to four zones be assigned to this input. When
all four zones are assigned, the previous window appears.
An output point cannot be assigned to more than four zones. Each output does not need to be
assigned to four zones. Each zone can have any number of outputs assigned to it.
7- ALT.COMM
The system can be programmed with two reporting phone numbers or IP addresses. Phone/
IP #1 is used with Account Number 1; Phone/IP #2 is used with Account Number 2. Remote
programming occurs on Line 1 using Phone/IP #3.
– PHONE/IP #1: Phone Number 1 or IP address 1
– PHONE/IP #2: Phone Number 2 or IP address 2
– COMPTR PHONE: Sets the Phone Number or IP Address to call for remote programming.
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
The following window appears:
Press the number key that corresponds with the phone number you wish to configure
(example is Phone #1). The following window appears:
Press the number key that corresponds with your selection. Refer to the next four sub-
sections (Number, Format, Account Numbers and Tone) for explanations of the phone number
options.
Number/IP address
The display scrolls through the Phone /IP Number options. Press [1] for NUMBER. The
following window appears:
Press [1]. Press [TEST][4] to add the wait for dial tone, and then enter the phone number and
press [#/Enter]. The previous menu appears. You can include several other special control
characters in the phone number by pressing [Test] followed by a digit.
For a list of control characters, see the following table:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 79
Several keys assist when you enter phone or IP numbers. For these keys, see the following
table:
Press Action
Notice!
For a phone number, you must enter 1 as a prefix before the special character >. Except for
unusual situations, all phone numbers should have the wait for dial tone character as the sec-
ond digit. This ensures that reports are delivered as quickly as possible, even if an incoming
i phone call must be disconnected. For example, you would program 1>18002890096 for the
phone number 1 800-289-0096.
If the wait for dial tone is not specified, the control panel waits 7 sec after going off-hook,
and then dials whether or not the dial tone is present.
To enter a central station IP address in either phone number 1 or 2 in the control panel,
replace all three phone numbers with an IP address. To distinguish an IP address from a
phone number, enter 0 as the first digit, followed by the 12 digit IP address.
Notice!
The IP address must be 12 digits long.For example, if the IP address is 172.30.1.101, the
i phone number is programmed as 0 172 030 001 101. Do not add the spaces. They are inclu-
ded for readability.
For programming an IP address and bit locations, see the following table:
IP8 IP9 IP10 IP11 IP12 Ack Wait Ack Wait Ack Wait
N2 N1 N0
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
80 en | Control Panel Programming Fire Alarm Control Panels
For example, if the necessary wait time is 30 sec, digits 14 through 16 should be 0, 3, 0
respectively.
In larger installation sites using alternate communications as a destination, set the wait time
to a higher value to compensate for network congestion delays. This wait time is also used for
the heartbeat acknowledge wait time. This is calculated using the following formula:
Value = (D14 X 100 + D15 X 10 + D16), where DXX is a digit number from the table entitled IP
address digit or bit location, 79. If the programmed value exceeds 255, it is read as 255.
A time-out on an alternate communication path is treated the same way as a negative
acknowledgement and results in the same event routing default scheme used with phone
reporting to the central station. This allows alternate communications to be the primary or
secondary reporting paths to an actual phone number for a single reporting destination.
For the alternate communications path, see the following table:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 81
The port numbers identify the control panel when it sends reports to the Netcom module. (For
normal installation, set this to 07700).
The display scrolls through the Phone or IP Number options. Press [2] for PORT NUMS. The
following window appears:
The existing number is shown on the top line. Enter the new number on the second line and
press [#/Enter]. The previous window appears. Enter hexadecimal digits A through F by
pressing [Test] followed by [1] for A, [2] for B, [3] for C, [4] for D, [5] for E and [6] for F.
Notice!
i For more information about using Netcom communications, see also the Installation Guides for
the B420 models, the DX4020, or the ITS-DX4020-G.
Format
Use this feature to select which communication format to use or to disable communication for
the phone or IP number. To disable the dialer, set the format for Phone Lines 1 and 2 to
disabled and turn off the monitoring feature of both lines.
The display scrolls through the Phone or IP Number options. Press [3] for FORMAT. The
following window appears:
PHONE/IP FORMAT ( )
0- DISABLE
1- 3/1 REPORT
2- 4/2 REPORT
3- BSFK REPORT
4- SIA, 110 RPRT
5- CONTACT ID
6- SIA, 300 RPRT
7- MDM 3A2
Press the number key that corresponds to your selection. The previous window appears.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
82 en | Control Panel Programming Fire Alarm Control Panels
Notice!
i If using the B420 models, the DX4020, or the ITS-DX4020-G for reporting events, the Modem
IIIa2 and Contact ID formats are possible:
Account Numbers
The account numbers identify the control panel when it sends reports to the central station.
The display scrolls through the Phone or IP Number options. Press [4] for ACCOUNT NUMS.
The following window appears:
The existing number is shown on the top line. Enter the new number on the second line and
press [#/Enter]. The previous window appears. Enter hexadecimal digits A through F by
pressing [Test] followed by [1] for A, [2] for B, [3] for C, [4] for D, [5] for E and [6] for F.
Tone
The FREQ (_) programming items (refer to window below) modify the reporting format when
3/1 or 4/2 tone burst reporting is selected for the format. Select three parameters with one
setting: data tone frequency, acknowledge tone frequency, and data rate. The frequency that
the control panel uses to send data pulses can be set for 1900 Hz (19D) or 1800 Hz (18D).
The frequency of the acknowledge tone from the receiver to which control panel responds can
be set to 1400 Hz (14A) or 2300 Hz (23A). The rate at which the data pulses are sent can be
set to 10, 20, or 40 pulses per second (10PS, 20PS or 40PS).
The display scrolls through the Phone/IP Number options (refer to 52). Press [5] for TONE.
The following window appears:
FREQ (__)
1- 19D, 14A, 10PS
2- 18D, 23A, 10PS
3- 19D, 14A, 20PS
4- 18D, 23A, 20PS
5- 19D, 14A, 40PS
6- 18D, 23A, 40PS
Press the number key that corresponds to your selection. The previous window appears.
In addition to features associated with each phone and IP number, each phone line has
associated features.
PHONE CONTROL
1- LINE #1
2- LINE #2
Press the number key that corresponds with your selection. Line 1 and Line 2 have the same
options. The following window appears:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 83
PHONE CONTROL #1
1- MONITOR LINE
2- DIALING TYPE
For explanations of the phone control options, see the following sections for Monitor Line and
Dialing Type.
Monitor Line
The phone line monitor feature, that supervises the connection of the phone line to the
control panel, can be disabled for each phone line. If an IP address is entered for the Phone/
IP number, set the monitor to No. If this is not programmed to No, a trouble is generated.
Choose Line 1 or Line 2 (see the window above). The display scrolls through the Phone
Control options. Press [1] for MONITOR LINE. The following window appears:
MONITOR LINE #1
_______: YES (1) NO (0)
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
Press [1] for YES or [0/Prog] for NO. The previous window appears.
Dialing Type
This feature determines the format the control panel uses for dialing on each phone line. The
TONE/PULSE setting first tries tone dialing. If that fails, it switches to pulse dialing. If an IP
address is entered in for the Phone/IP number, the control panel ignores this setting.
Choose Line 1 or Line 2 (see the window below). The display scrolls through the Phone
Control options. Press [2] for DIALING TYPE. The following window appears:
Press the number key that corresponds to your selection. The previous window appears.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
84 en | Control Panel Programming Fire Alarm Control Panels
Notice!
If any reports are directed to Phone/IP Number 2 (including the default, PHONE 2 BACKUP), a
i phone number and account number must be programmed for Phone/IP Number 2. The con-
trol panel indicates a COMM FAULT if it sends a report (using Phone Number 1 parameters)
which references unprogrammed Phone/IP Number 2 parameters.
REPORT STEERING
1- NONSUP ALRM
2- SUPVSY ALRM
3- NONSUP RSTR
4- SUPVSY RSTR
5- TROUBLE
6- TESTS
7- SILENCE
8- RESET
9- FIRE DRILL
Press the number key that corresponds to your selection. Selecting, for example
NONSUP ALRM produces the following window:
Notice!
Set to 0 the number of phone rings before the control panel seizes the line to attempt remote
programming. The number of phone rings before the panel seizes the line to attempt remote
i programming must remain at 0 for UL864 local, auxiliary or remote station installations. If an
IP address is entered in for the Phone/IP number, the panel will ignore this setting. When the
ring count is set to 0, remote programming must be answered on site. Once answered, the
panel will prompt for a password.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 85
RING COUNT
(01-15, 00=DIS) _______
Enter the information and press [#/Enter]. The previous window appears. An entry of [0/Prog]
[0/Prog] disables ring detection.
For acceptable programming selections for UL864 9th edition Listed applications, see
Programming features for UL864, 49.
The system default is to try ten times to communicate an event. Bosch recommends setting
this to five tries. This parameter determines after which attempt the system indicates a failure
condition. (After reporting a failure, the system continues to communicate until it reaches ten
times). Do not select 1 or a failure is indicated whenever a report is sent.
The following window appears:
Enter the information and press [#/Enter]. The previous window appears.
The downloading computer must redial the control panel if an answering machine answered
the phone before the control panel. When this option is selected, if the control panel detects
the phone line ringing within one minute of when the last ringing cycle stopped, it answers on
the first ring and seizes the phone line. If an IP address is entered in for the Phone/IP number,
the control panel ignores this setting.
The following window appears:
MACHINE BYPASS
_______: YES (1) NO (0)
Enter the information and press [#/Enter]. The previous window appears.
This prompt is used with the B420 models, DX4010, DX4020 or ITS-DX4020-G.
If using the DX4010 select 1-serial; for all others, select 0-network. The following window
appears:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
86 en | Control Panel Programming Fire Alarm Control Panels
Notice!
This feature offers the use of hexadecimal digits (0 through F). Because the specific keys A
i through F are not available on the keypad, use the following equivalent keys: History=A,
Test=B, Disable=C, Drill=D, Silence=E, and Reset=F
NOTICE!
4/2 Zone reports consist of an event type (first digit) and a point number (second digit).
These reports apply only to points, and only when a 3/1 or 4/2 format is selected.
The following window appears:
Press the number key that corresponds with your selection of event type (D1 stands for
digit 1). Press [#/Enter].
Pressing [9] retrieves the second digit options (point numbers). The following window
appears:
Press the number key that corresponds to your selection. A window based on your previous
selection allowing entry of hex digits appears:
FIRE ALARM D1 ( )
0 THRU 9
<HISTORY>:A
<TEST>:B
<DISABLE>:C
<DRILL>:D
<SILENCE>:E
<RESET>:F
Enter the digit that corresponds to the selected condition by pressing a number key or one of
the special keys if a hex character is needed. Press [#/Enter] and the previous display
appears.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 87
4/2 Report Codes apply to system conditions but only when 3/1 or 4/2 format is selected. Two
digits can be programmed to be sent for each condition. The conditions that can be
programmed are:
– System in test, system in test restore: sent for walk test operations
Silence: sent when the silence key is pressed
Fire drill, fire drill restore: sent for fire drill operations
Open reset report: sent when the reset key is pressed
Low battery, low battery restore, AC failure, AC failure restore: sent for power problems
Test report: sent for manual or automatic communicator tests
Off normal at test: sent if the panel is off-normal at the automatic test time
Phone trouble, restore: sent for phone line problems
System trouble, restore: sent for general system problems
The following window displays:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
88 en | Control Panel Programming Fire Alarm Control Panels
SYSTM IN TST ( )
0 THRU 9
<HISTORY>: A
<TEST>: B
<DISABLE>: C
<DRILL>: D
<SILENCE>: E
<RESET>: F
Enter digits that correspond to the selected condition by pressing a number key, or one of the
special keys if a hex character is needed. Press [#/Enter] and the previous display appears.
When BFSK reporting is used, most reporting codes are fixed and do not need programming.
There are five reports that the control panel can send that are not standard BFSK codes:
Off normal at test: Sent if the panel is off-normal at the automatic test time.
Open reset report: Sent when the reset key is pressed.
Silence: Sent when the silence key is pressed.
Fire drill, fire drill restore: Sent for fire drill operations.
The following window displays:
Press the number key that corresponds to your report code selection. A window allowing
entry of two hex digits appears.
PROG DEFAULTS
1- CLEAR HSTRY
2- DEFAULT EE
3- ALT 4/2 CDES
4- (reserved)
You can use this option to clear some or all of the history records in the system.
The following window appears:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 89
Enter the number of history records you wish to delete, and press [#/Enter]. The previous
menu appears.
8.8.2 Default EE
Warning!
Lost programming!
All programming, including zone configurations and option installations, are lost when this op-
! eration is performed. You must turn control panel power off and on after resetting the de-
fault, to reinstall the four zone expanders and the MUX expander. You must update the option
bus and set up keypads (PROG SYSTEM MENU) to reinstall option bus devices.
You can set the control panel back to the original factory-programming configuration with this
option. You are asked to press [#/Enter] to complete the operation. Press [*/Back] to cancel
the operation.
The following window appears:
SETTING EEPROM
TO DEFAULT...
When the operation is complete, the previous menu appears. This operation takes several
minutes when the D7039 Multiplex Expander is installed.
You can set all of the programming for 4/2 codes to an alternative set of default reports, as
described in Appendix D, 110. To cause a complete control panel default, use the default EE
option.
The following window appears:
SETTING EEPROM
TO DEFAULT...
Warning!
1. Unprogrammed devices on the bus will not operate or be supervised
! 2. This menu is accessible only when the D7039 Multiplex expander is installed.
3. Do not install more than one device programmed to the same address on the bus. Doing so
can inhibit alarm reporting from both devices.
Notice!
i Intermittent trouble reports from a particular MUX point address can indicate that more than
one device was programmed to that address.
PROGRAM MUX
1- MUX EDIT
2- MUX PROGRAM
3- BUS TYPE
4- AUTO PROGRAM
To add MUX devices to the system, use the MUX Edit option. Each device must have a unique
address programmed using the address switches.
The following window appears:
Press the number that corresponds with the device you are adding or press [0/Prog] if you are
removing a device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The device type window
appears again allowing additional devices to be added. Eight points are added at once when
the D7042 is added to the control panel.
To add MUX devices to the system simultaneously while programming an address into the
device itself, use the MUX Program option. This programs a specified address into the device,
and also sets the control panel to use the device.
Warning!
Programming issues!
The D7042 is programmed using switches and cannot be added using the MUX Program fea-
All programming is performed on Bus A, including addresses 129 to 255 that can only be
installed on Bus B for operation. Be sure to connect devices with addresses 129 to 255 to
Bus B, not to Bus A.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 91
If no devices are connected on Bus A, the following window appears. Otherwise an error
message appears.
PROGRAM MUX
1- NORMAL
2- FAST
Select normal programming to add one or two devices. Select fast programming to program
larger quantities of identical devices to sequential addresses.
Normal Programming
If normal programming is selected, the following menu appears allowing selection of the
device type being programmed:
Enter the number that corresponds with the device you are adding, or select 0 if you are
removing a device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The display asks you to
attach the device being programmed to the terminals for MUX bus A (see the following
window). You can simply hold the device wires on the terminals for the few seconds it takes
to program. The programming operation retries up to three times if the device does not
connect right away.
If the device added is an I/O module, you are asked to enter the four zones to control the relay
output, just as for other relay devices:
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar
display for Zone B, C and D appears allowing up to four zones to control this output. When all
four zones are assigned, the previous window appears. It confirms the programming operation
and returns to the previous menu.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
92 en | Control Panel Programming Fire Alarm Control Panels
ERROR -
DEVICE FAILED
Fast Programming
Fast programming proceeds the same as normal programming, except that when the device is
programmed you are asked to remove the device:
Then, you are asked to attach the next device at the next address:
This process continues until you press [*/Back]. All devices to be programmed must be of the
same type.
This option configures the system for two independent Class B, Style 4 buses allowing
addresses up to 255.
Notice!
i Class A operation is not supported by the D7042 Eight Input Module; do not select Class A
operation.
Press [2] to select Class B operation if the setting was changed from the default setting.
For wiring details for a Class B configuration, see also the D7042/D7042B Multiplex Eight Input
Remote Modules Installation Instructions (P/N: 42638)
For more information regarding Class A and Class B wiring instructions, see also the D7039
Multiplex Expansion Module’s Installation Guide (P/N: 38685).
For mounting locations inside the FPD‑7024’s enclosure and wiring possibilities for the D7039
and its I/O module, see the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 93
This option provides a convenient way for the installer to configure the FPD‑7024 to operate
with the existing devices on the multiplex buses by scanning the buses for missing or new
multiplex devices.
The following display appears:
AUTO PROGRAM?
_______:YES(1) NO(0)
Press [1] to continue with auto programming or [0/Prog] to cancel. When you press [1], the
FPD‑7024 checks for existing programming errors in which devices are programmed
incorrectly in the space required for a lower-addressed multi-point device (such as a dual
point module). If a point is found to be programmed under another device, the following error
message appears for five seconds, and the auto programming process aborts:
ADDRESS ERROR 1
AT ADDRESS xxx
If no errors are found, the FPD‑7024 starts a scanning process that takes approximately one
minute to complete, while showing the following display:
AUTO PROGRAM
SCANNING
PLEASE WAIT...
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
94 en | Control Panel Programming Fire Alarm Control Panels
When the scanning is completed, the FPD‑7024 checks for missing devices. Missing devices
are addresses with no devices on the multiplex buses, but are programmed into the
FPD‑7024’s site-specific memory area. If missing devices are detected, the FPD‑7024 shows
the following menu (where xxx is the address of the first point of the missing device):
MISSING PT @ xxx
0- DELETE POINT
1- KEEP POINT
2- DEL REMAIN
3- KEEP REMAIN
DELETE POINT: If selected, the missing point and any addresses it implemented (up to eight
for an octal input module) are permanently deleted from the site specific memory area. If the
deleted device is an I/O module, the output zones that were programmed for the relay are
reset to 0. If additional devices are found to be missing, the above display is repeated for each
missing device.
KEEP POINT: If selected, the FPD‑7024 retains the programming for the existing point and
continues scanning for additional missing points.
DEL REMAIN: If selected, the following prompt # KEY TO CONFIRM appears at the FPD‑7024.
If the [#/Enter] key is pressed, all the missing points are deleted from the site-specific memory
area and the auto program process continues with the devices found menu. If any other key is
pressed, the existing point is kept and the control panel continues scanning for additional
missing devices.
KEEP REMAIN: If selected, no additional points are deleted and the auto program process
continues with the Devices Found menu. Points individually deleted with the Delete Point
command before selecting the Keep Remain command stay deleted when Keep Remain is
selected.
Warning!
Missing points!
Use the DEL REMAINING feature with caution. Any devices missing from the multiplex buses
! during the DEL REMAINING operation, even momentarily, are permanently deleted. These
points do not operate, and do not generate trouble conditions even if they are returned to the
bus.
When the delete point operation is finished, the FPD‑7024 shows for five seconds the total
number of points that were deleted from the control panel (xxx indicates the number of points
that were removed from the control panel’s site specific configuration).
AUTO PROGRAM
xxx POINTS DELETED
Confirm that only the expected number of points was removed from the system. Points that
are removed from the control panel’s site-specific configuration do not operate and are not
supervised even if they are returned to the bus.
When the point delete process completes, the auto programming process automatically
checks for new devices on the buses. New devices are found when a device is present on one
of the multiplex buses, but its address is not programmed into the control panel’s site-specific
memory. If new devices are detected, the FPD‑7024 shows the following menu (where xxx is
the address of the first new device found):
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 95
Use this menu to define the device type. Press the number key that corresponds with the
device type installed at the address. If a detected device should not be installed and should be
left inactive, press [0/Prog] to bypass the new device.
Warning!
Device malfunction!
! Ensure that the correct device type is selected for each point. Incorrectly specified device
types can cause multiplex devices to malfunction or fail to operate.
All inputs are configured to use Point Function 10 as they are added. Points added during auto
programming are configured for the following operation:
– Point Function 10 (Fire Alarm, Fast Response, Non-silenceable, Not Local-only)
– Open Status = Trouble
– Output Zone 9
– Alarm Verify = NO
– Latching = YES
The programming of input points can be changed when auto programming completes using
the input-programming menu.
When I/O modules are added during auto programming, the relay (second point) is configured
to activate on any alarm, non-silenceable (Zone 63). This can be changed when auto
programming completes by using the output-programming menu.
The FPD‑7024 performs some basic error checks when new devices are added. The following
errors can be shown during the process of adding a device:
ADDRESS ERROR #
AT ADDRESS xxx
In the previous message, # is replaced by a code number and xxx is replaced by the affected
address that indicates the type of error.
For code numbers and corresponding error message descriptions, see the following table:
1 New point is under an existing The new point is in the space required for an
point existing multi-address device. This is checked
when auto programming first starts.
2 Point overlaps existing point There are already devices configured at one of
the addresses required for the new multi-point
device.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
96 en | Control Panel Programming Fire Alarm Control Panels
4 Too many multiplex relays Only 20 input output devices can be supported
on a given bus.
Table 8.7: Auto programming error messages
For details on installation restrictions, see also the specific device’s installation instructions
When the point adding operation completes, the FPD‑7024 shows for five seconds the total
number of points that were added to the control panel. Confirm that the number of devices
added matches the expected number.
AUTO PROGRAM
xxx POINTS ADDED
Warning!
Undetected devices!
! If a new device is not detected on the bus during the point adding operation, the device does
not operate and does not generate trouble conditions even if it remains connected to the bus.
When the point adding operation completes, the display shows the total number of points on
the system:
AUTO PROGRAM
xxx MUX POINT
AUTO PROGRAM
RESTORING
PLEASE WAIT...
Warning!
Test for proper operation!
! As with any programming change to a system, test the system for proper operation before re-
turning it to service. At least test each added multiplex point after auto programming com-
pletes. Test according to NFPA 72.
To remove a previously programmed multiplex device, use the MUX Edit feature.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Control Panel Programming | en 97
PROGRAM MUX
1- MUX EDIT
2- MUX PROGRAM
3- BUS TYPE
4- AUTO PROGRAM
From the Program MUX menu, press [1] to select MUX Edit. The following window appears:
Press [0/Prog] for No Device. Then enter the address for the point you wish to delete.
After the device is successfully deleted, you return to the Device Type (MUX Edit) sub-menu.
An unsuccessful deletion results in an error message (see below) followed by the Device Type
(MUX Edit) sub-menu.
ERROR –
DEVICE FAILED
Warning!
Dual point removal!
! If you remove one point of a dual point address (for example, a D7042 Eight Point Input Mod-
ule), the second point (and subsequent points) at this address are also removed. For exam-
ple, if the first point of a D7042 is removed, the remaining seven points are also removed.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
98 en | Specifications Fire Alarm Control Panels
9 Specifications
Notice!
i When a local relay is programmed for trouble it is energized in the normal state. This causes
the common and normally-open terminals to be shorted when not in the trouble condition.
Electrical
Power (Notification Appliance Circuit Each NAC has 24 VDC nominal, unfiltered
[NAC])2: power with up to 2.5 A capacity (but limited
by overall 4.0 A capacity)
Environmental
Notification patterns: Configurable for steady, pulsing, California March, ANSI code 3,
synchronized Wheelock, synchronized Gentex, and synchronized
System Sensor.
Relays
Local (on-board): The main control panel includes Three Form “C” relays. The relay
contacts are rated at 5 A, 28 VDC. No over existing limiting is
performed on the contacts of these relays. The default selection
for the relays is to indicate general alarm and general system
trouble and supervisory. By using point or zone mapping, they
can be programmed to activate in a wide variety of conditions.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 99
10 Appendices
10.1 Appendix A: Abbreviations on Control Panel Display
Abbreviation Definition Abbreviation Definition
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
100 en | Appendices Fire Alarm Control Panels
FIRE DIRTY PT XX A smoke detector with the Chamber Check feature indicates a dirty
chamber.
FIRE TRBL PT XXX Trouble condition for specific points on the system. Check control
panel wiring and field wiring for shorts or opens. Also check point
programming to ensure the control panel knows what points belong
on the system.
FIRE TROUBLE General fire zone trouble message. Refer to the second line of
display for more information.
INST FLT 4Z EXP There is a missing FPD-7034 Four Zone Expander Board, or the
expander appeared unexpectedly since the last time the system
was powered.
INST FLT MX EXP There is a missing D7039 MUX Expander Module, or the expander
appeared unexpectedly since the last time the system was
powered.
MUX BUS A FAILURE A wiring problem on Bus A or Bus B in Class B mode occurred.
MUX BUS B FAILURE Check the wiring for shorts or opens.
MUX CPU FAILURE A CPU failure on the D7039 Expander Board occurred. Ensure that
the D7039 is correctly installed on the header pins. If the message
persists, call for service immediately.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 101
SYSTEM TROUBLE General trouble message. Refer to second line of the display for
more information.
TRBL OPEN LNAC A Local NAC circuit is open. Check the field wiring and the EOL
resistor.
TRBL OPEN RNAC An FPD‑7038 Remote NAC circuit is open. Check the field wiring
and the EOL resistor.
TRBL OPT BUS@XX A wiring fault on option bus terminals 7 to 14, as well as specific
address problems with option bus devices occurred. Check the
wiring for the specific device address shown.
TRBL OVRC LNAC An overexisting condition on one of the NAC circuits occurred.
TRBL OVRC RNAC Check the field wiring on the notification appliances for shorts.
TRBL SHRT RNAC A short on the FPD‑7038 Remote NAC circuit occurred.
TROUBLE AC FAIL AC power failure to the control panel. Check the circuit breaker or
fuse for AC power problem.
TROUBLE ANN Trouble with one or more annunciators connected to the control
panel.
TROUBLE COMM FLT A communicator problem occurred. Check the control panel’s
phone lines and programming for the communicator problem.
TROUBLE EXP An FPD‑7034 Four Zone Expander board problem occurred. Ensure
that the FPD‑7034 is properly connected to the FPD‑7024 PCB.
TROUBLE GRND FLT A ground fault problem occurred. Ensure that no control panel
wiring is shorted to the earth ground.
TROUBLE KPAD@XX A specific keypad address failure occurred. Check the keypad’s
wiring and address settings.
TROUBLE LOW BATT The control panel’s battery charger is not working, or the backup
batteries are missing.
TROUBLE MUX CLASS A A failure on the MUX wiring in Class A mode occurred. Check the
wiring for shorts or opens.
TROUBLE PHONE A problem with the control panel’s phone lines occurred. Check the
phone wiring and line monitor programming.
TROUBLE RELAY@XX One of the control panel’s auxiliary relays might be shorted.
TROUBLE SMK PWR A short on the smoke power terminals 24 and 25 occurred.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
102 en | Appendices Fire Alarm Control Panels
i For information about the receiver output when the Modem IIIa2 reporting format is used with
a Bosch Security Systems, Inc. receiver, see Modem IIIa2 reporting, 105.
Notice!
Cause of Hazard
i When the Modem IIIa2, SIA or Contact ID reporting formats are used, an additional numeric
identifier is sent with system trouble messages that provide a specific indication of the partic-
ular fault. This identifier is also recorded in the history log (see History log, 108).
For report codes (Items in boldface type are not programmable), see the following table:
POINT WATERFLOW 13 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz
DISABLE
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 103
POINT SUPERVISORY 14 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz
DISABLE
POINT MONITOR 15 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz
DISABLE
POINT WATERFLOW 17 see #16 P see #16 P see #16 Ez SHz 3 113 00 zzz
RESTORE
POINT SUPERVISORY 18 see #16 P see #16 P see #16 Ez SRz 3 200 00 zzz
RESTORE
POINT MONITOR 19 see #16 p see #16 p see #16 Ez URz 3 140 00 zzz
RESTORE
POINT WATERFLOW 21 see #20 p see #20 p see #20 Ez SJz 3 373 00 zzz
TROUBLE RESTORE
POINT SUPERVISORY 22 see #20 p see #20 p see #20 Ez SJz 3 373 00 zzz
TROUBLE RESTORE
POINT MONITOR 23 see #20 p see #20 p see #20 Ez UJz 3 373 00 zzz
TROUBLE RESTORE
POINT FIRE DIRTY 24 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
POINT WATERFLOW 25 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
DIRTY RESTORE
POINT SUPERVISORY 26 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
DIRTY RESTORE
POINT MONITOR 27 see #20 p see #20 p see #20 Ez UJz 3 373 00 zzz
DIRTY RESTORE
POINT WATERFLOW 29 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
DISABLE RESTORE
POINT SUPERVISORY 30 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
DISABLE RESTORE
POINT MONITOR 31 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
DISABLE RESTORE
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
104 en | Appendices Fire Alarm Control Panels
MANUAL TEST 58 see #50 see #50 see #50 see #50 see #50 EE RX0 1 601 00
000
DATA LOST 59 see #56 see #56 see #56 see #56 see #56 FD RT0 1 354 00
000
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 105
EEPROM FAILURE 60 see #56 see #56 see #56 see #56 see #56 FD UT18 1 307 00
018
EEPROM RESTORAL 61 see #57 see #57 see #57 see #57 see #57 ED UJ18 3 307 00
018
SMOKE POWER FAULT 62 see #56 see #56 see #56 see #56 see #56 FD YP0 1 320 00
000
SMOKE POWER 63 see #57 see #57 see #57 see #57 see #57 ED YQ0 3 320 00
RESTORE 000
Notes:
c: system trouble condition code
p: programmable digit for each zone u: user ID digit
z: zone digit
Table 10.3: Reporting summary for fire communicator
Notice!
i Cause of Hazard
The Modem IIIa2 reports are fixed and do not require programming.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
106 en | Appendices Fire Alarm Control Panels
POINT FIRE ALARM RESTORE 16 dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW RESTORE 17 dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY RESTORE 18 dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR RESTORE 19 dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT FIRE TROUBLE RESTORE 20 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW TROUBLE RESTORE 21 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY TROUBLE RESTORE 22 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR TROUBLE RESTORE 23 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 107
POINT WATERFLOW DIRTY RESTORE 25 dd/dd tt:tt ql ACCT aaaa ANALOG RESTORE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISO Y DIRTY RESTORE 26 dd/dd tt:tt ql ACCT aaaa ANALOG RESTORE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR DIRTY RESTORE 27 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT FIRE DISABLE RESTORE 28 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW DISABLE RESTORE 29 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY DISABLE RESTORE 30 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR DISABLE RESTORE 31 dd/dd tt:tt ql ACCT aaaa FIRE TBL RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
SYSTEM IN TEST RESTORE 41 dd/dd tt:tt ql ACCT aaaa WALK TEST END
+++ ACCT aaaa AREA=1 ID=uuu
FIRE DRILL RESTORE 44 dd/dd tt:tt ql ACCT aaaa FIRE WALK END
+++ ACCT aaaa AREA=1 ID=uuu
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
108 en | Appendices Fire Alarm Control Panels
REMOTE PROGRAMMING FAIL 66 dd/dd tt:tt ql ACCT aaaa RAM ACCESS FAIL
Notes:
dd/dd tt:tt: date and time
aaaa: account number
ccc: numeric identifier
uuu: user ID
zzz: point
Table 10.4: Modem 111a2 reporting
The following table provides event numbers and their condition as they appear in the history
log.
Option bus device at address 2 failed 3 Class A, Style 6 wiring failure on MUX 53
bus
Option bus device at address 6 failed 7 Remote NAC module 1, output 1 wiring 57
fault
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 109
Option bus device at address 7 failed 8 Remote NAC module 1, output 2 wiring 58
fault
Option bus device at address 8 failed 9 Remote NAC module 1, output 3 wiring 59
fault
Option bus device at address 9 failed 10 Remote NAC module 1, output 4 wiring 60
fault
Option bus device at address 10 failed 11 MUX bus A (9-128) hardware failure 61
Option bus device at address 11 failed 12 MUX bus B (129-255) hardware failure 62
Option bus device at address 14 failed 15 Remote NAC module 2, output 1 wiring 65
fault
Option bus device at address 15 failed 16 Remote NAC module 2, output 2 wiring 66
fault
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 111
PROG TIME
AUTO TEST
TEST FREQ: 3 hr to 24 hr
SECURITY
PINS
PROGRAMMER: 9876
User 2 = 0000
AUTHORITY
USER 1: 2
OTHERS: 0
PROG SYSTEM
TIMERS
AC FAIL DELAY: 6 hr
OPTION BUS
SETUP KEYPAD: 0
PIN REQUIRED:
LOCAL: 0- No
REMOTE: 1- Yes
PROG INPUTS
Point Function 2 = 2
Point Function 3 = 3
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
112 en | Appendices Fire Alarm Control Panels
Point Function 4 = 4
Point Function 5 = 5
Point Function 6 = 6
Point Function 7 = 7
Point Function 8 = 8
Point Zone 2 = 2
Point Zone 3 = 3
Point Zone 4 = 4
Point Zone 5 = 5
Point Zone 6 = 6
Point Zone 7 = 7
Point Zone 8 = 8
Point Zone 9 - 19 = 9
Point Zone 20 - 39 = 10
VERIFICATION: No
LATCHING: Yes
LOCAL ONLY no no no
SILENCEABLE no no no
PROG OUTPUTS
NACs
NAC #1:
CONFIGURATION: Steady
ZONE ASSIGNS:
Zone A: 53
Zone B: 61
Zone C: 0
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 113
NACs
Zone D: 0
NAC #2:
CONFIGURATION: Steady
ZONE ASSIGNS:
Zone A: 53
Zone B: 61
Zone C: 0
Zone D: 0
RNACs
RNAC 1
Outputs 1, 2, 3, 4
Configuration: Steady
Zone Assignment:
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
RNAC 2
Outputs 1, 2, 3, 4
Configuration: Steady
Zone Assignment:
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
RNAC 3
Outputs 1, 2, 3, 4
Configuration: Steady
Zone Assignment:
Zone A: 53
Zone B: 0
Zone C: 0
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
114 en | Appendices Fire Alarm Control Panels
RNACs
Zone D: 0
RNAC 3
Outputs 1, 2, 3, 4
Configuration: Steady
Zone Assignment
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
RELAYS
LOCAL:
RELAY #1
Zone A: 63
Zone B: 0
Zone C: 0
Zone D: 0
RELAY #2
Zone A: 62
Zone B: 0
Zone C: 0
Zone D: 0
RELAY #3
Zone A: 58
Zone B: 0
Zone C: 0
Zone D: 0
REMOTE
REMOTE 1 (D7035)
Relay 1 / Zone A: 63
Relay 2 / Zone A: 62
Relay 3 / Zone A: 61
Relay 4 / Zone A: 60
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 115
REMOTE
Relay 5 / Zone A: 58
Relay 6 / Zone A: 57
Relay 7 / Zone A: 56
Relay 8 / Zone A: 53
REMOTE 2
Relay 1 / Zone A: 1
Relay 2 / Zone A: 2
Relay 3 / Zone A: 3
Relay 4 / Zone A: 4
Relay 5 / Zone A: 5
Relay 6 / Zone A: 6
Relay 7 / Zone A: 7
Relay 8 / Zone A: 8
PROG ACCOUNTS
PHONE NUMBERS
PHONE 1, 2
FORMAT: 0 - Disable
PHONE CONTROL
LINE 1, 2
MONITOR: No
REPORT STEERING
RING COUNT: 00
COMM TRIES: 10
MACH BYPASS: No
ALTER COMM 0
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
116 en | Appendices Fire Alarm Control Panels
PROG FORMATS
2 - WATERFLOW D1: 0
3 - SUPERVISE D1: 0
4 - TROUBLE D1: 6
6 - DISABLE D1: B
8 - MORE
1 - POINT 1 D2: 1
2 - POINT 2 D2: 2
3 - POINT 3 D2: 3
4 - POINT 4 D2: 4
5 - POINT 5 D2: 5
6 - POINT 6 D2: 6
7 - POINT 7 D2: 7
8 - POINT 8 D2: 8
1 - POINT 9 D2: 9
2 - POINT 10 D2: 0
SYSTM IN TST: 33
SILENCE: 9F
FIRE DRILL: 33
LOW BATTERY: 69
AC FAILURE: 60
AC FAIL RST: 70
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 117
TEST REPORT: 30
PHONE 1 TRBL: 31
PN 1 TRB RST: 35
PHONE 2 TRBL 32
PN 2 TRB RST: 36
SYSTEM TROUB: 33
OPEN/RESET: FD
SILENCE: FD
FIRE DRILL: FD
HISTORY DEFAULTS
ALT 4/2 CODES
WATERFLOW D1: 0
SUPERVISE D1: 0
TROUBLE D1: 6
DISABLE D1: 5
MONITOR D1 0
POINT 1 D2: 1
POINT 2 D2: 2
POINT 3 D2: 3
POINT 4 D2: 4
POINT 5 D2: 5
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
118 en | Appendices Fire Alarm Control Panels
POINT 6 D2: 6
POINT 7 D2: 7
POINT 8 D2: 8
POINT 9 D2: 9
POINT 10 D2: 0
SYSTM IN TST: 33
SILENCE: 9F
FIRE DRILL: 33
LOW BATTERY: 69
AC FAILURE: 60
AC FAIL RST: 70
TEST REPORT: 30
PHONE 1 TRBL: 31
PN 1 TRB RST: 35
PHONE 2 TRBL 32
PN 2 TRB RST: 36
SYSTEM TROUB: 33
Multiplex
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Appendices | en 119
Warning!
! High voltage!
The voltage present during ringing for an incoming call can be over 100 VAC.
1. Use a voltmeter to measure the voltage present across each phone line (Tip to Ring)
while the phone line is idle. This standby telco battery voltage is typically in the range of
30 VDC to 50 VDC, but any voltage above 5 VDC is accepted by the control panel. The
polarity of the voltage does not matter.
2. Check for other devices that might use the phone line, such as fax machines, credit card
verifiers or PBX systems. If the devices cannot be removed, ensure they are wired so that
the control panel’s line seizure relay disconnects them when needed. Measure the line
voltage while these devices are in use. Ensure that it stays above 5 V.
Notice!
i NFPA 72 requirements mandate a dedicated phone line for fire reporting.
3. Check for intermittent faults in the phone line. Make a test call and confirm that the line
is free of distortion and noise. Temporarily swap Lines 1 and 2 on the control panel and
check if the problem indication moves to the control panel’s other phone line channel. If
so, the phone line is causing the problem rather than the line monitor.
4. Confirm that the fault message is phone fault and not com fault. Com fault is often
caused by failing to program a phone number or account number for Phone Number 2
while routing reports to Line 1, Backup Line 2. If only one phone number is available for
reporting, set report direction for all events to phone 1 only. Com fault can also happen if
one of the phone lines has telco battery voltage, but does not complete a call. Make test
calls to the receiver(s) on both phone lines, listening for the receiver ACK tone.
5. Ensure that two phone lines are available. In accordance with NFPA requirements, the
Auto-test report is sent on a different phone line each time it is sent. If only one phone
line is connected to the control panel, a Com fault is generated on every other test call.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY, 14450
USA
www.boschsecurity.com
© Bosch Security Systems, Inc., 2012