Product Specification
B37909

easYgen | exciter-10 Salient Features


 Eliminate redundant voltage and current sensing 
o No PT/CT connection to the AVR 
 Simplify voltage control topology 
o No cascaded PID loops 
 Compatible with all types of synchronous generators 
o Shunt, Auxiliary Winding, PMG Excitation 
 Standard simulation files available to speed‐up 
design/certification process 

Excitation module for


 Simple plug and play
synchronous generators excitation module
 Easy and convenient
DESCRIPTION
1B

to install, operate,
and diagnose
Woodward’s easYgen | exciter-10 (EX-10) module is a power electronics
component designed to provide excitation current to the generator that is  No extra configuration
controlled by the Active Voltage Regulator (AVR) feature in the easYgen- tool required
3400/3500XT genset controls.  On-board protection
schemes: Current
The active voltage regulation concept intends to substitute a traditional limitation, Short
voltage regulation configuration by simplifying the overall topology. The circuit, Over-
easYgen internal controller regulates generator output voltage by sending a temperature
pulse width modulation (PWM) signal to the excitation module. The excitation
module controls generator excitation and therefore generator output voltage.  Status LEDs for local
This topology eliminates the redundant voltage and current sensing from a annunciation
traditional voltage regulator and also makes a feedforward control architecture  Seamless integration
at AVR level simplifying the cascaded PID control topology. For power input, with easYgen-
EX-10 interfaces with any of the following excitation systems: Self/Shunt 3400/3500XT genset
Excitation, Auxiliary winding/AREP Excitation and Permanent Magnet (PMG) controls
Excitation systems to make it a standard yet versatile solution.
 Active voltage
Regulation (AVR)
APPLICATION
2B

0B
 Soft start control
easYgen Genset control
with AVR logic Generator  Under frequency (Volt
/ Hz) regulation
Voltage & Current
Sensing  Voltage droop
compensation
 Compact design
 Line drop
compensation
Excitation Excitation  Fault Ride Through
command current
(FRT) support
Excitation  CE marked
module
Active Voltage Regulator  UL pending
Released

FEATURES
 Current limitation – limit can be adjusted via a potentiometer (IEXC.)
 Over-temperature protection – as the heat sink temperature crosses a threshold EX-10 output shuts-off
 Short-circuit protection – when transient current output exceeds a threshold, the EX-10 decreases the
excitation output to below 0.2A until shutdown

In conjunction with easYgen-3400/3500XT genset controls, the active voltage regulator system offers:
 Automatic Voltage Regulation (AVR)
 Soft start functionality
 Under frequency regulation (Volt/Hz) defined by five configurable points and activated by
LogicsManager
 Line drop compensation via AnalogManager
 Power factor and kvar control
 Voltage droop compensation
 Fault Ride Through (FRT) support
 Setpoint configuration and AVR status overview on the easYgen screen and on Woodward ToolKit
Service Tool

SPECIFICATIONS

Eletrical Housing
Connection ................... plug terminals 2.5 mm²
Power consumption ...................... max. 450 VA
At max. Continuous Rating. Weight ......................................... approx. 770 g
Max. Continuous Field Current Output ........ 6 A
Max. Forcing Field Current Output ............ 10 A Environmental
(for 10 s) Ambient temp. ........ -40 to 80 °C / -40 to 176 °F
Max. AC Voltage Input ..................... 260 Vrms (operation, when mounted in landscape
(X1:X2, Z1:Z2) orientation)
PWM Input Signal .............. 500 Hz, 5~20 V DC Ambient temp. ........ -55 to 85 °C / -67 to 185 °F
(storage)
PWM duty cycle ................................... 0~100%
Ambient humidity ........... 93 %, non-condensing

Approvals
Vibration
UL ........................................................ Pending
5.05 G, 1 mm amplitude, 69 Hz in 3 orthogonal
CE In conformity with the applicable planes
requirements of the following Standards
EN 61000-6-2, 2005: Generic Standards - Generator Excitation Types
Immunity for Industrial Environments Self / Shunt Excitation, Internal / Auxiliary
Winding Excitation, Permanent Magnet (PMG),
EN 61000-6-4, 2007: Generic Standards - Single or Three Phase
Emissions for Industrial Environments
EN 61010-1, 2010: Safety requirements for
electrical equipment for measurement, control,
and laboratory use - Part 1: General
Requirements
Released

DIMENSIONS

CONNECTION DIAGRAM
24B3-Terminal Connector (Excitation command)
3B 3B4-Terminal Connector Function (Excitation power supply input)
16B

4BTerminal Label
17B 5BPMG Excitation
18B 6BSelf excitation
19B 7BAux. winding excitation
20B

25BTerminal Label
4B 26BFunction
5B 27BAccording easYgen-3400/3500XT Connection
6B

8BX1
21B 9BPhase A
2B 10BSingle phase A
23B 1BWinding 1 A
24B

28BPWM−
7B 29BPWM neg. input
8B 30BTerminal 20
9B

12BZ1
25B 13Bn.c.
26B 14Bn.c.
27B 15BWinding 2 A
28B

31BPWM+
10B 32BPWM pos. input
1B 3BTerminal 19
12B

16BX2
29B 17BPhase B
30B 18BSingle phase B
31B 19BWinding 1 B
32B

34BShield
13B 35BShield
14B 36BTo the common Protective Earth (PE)
15B

20BZ2
3B 21BPhase C
34B 2Bn.c.
35B 23BWinding 2 B
36B

LED1: Operation LED2: Protection

Normal Operation Green Off 37B2-Terminal Connector (Excitation current output)


37B

Current limitation Off Blinking red 2/s 38BTerminal Label


38B 39BFunction
39B

Short-circuit Off Blinking red 5/s


40BF+
40B 41BExcitation field positive
41B

Over-temperature Off Illuminated red 42BF −


42B 43BExcitation field negative
43B
Released

TOOLKIT CONFIGURATION & VISUALIZATION SOFTWARE


Woodward’s ToolKit, available to download from woodward.com is the service tool to program and
CONTACT troubleshoot the AVR feature and the full control in general.

North & Central America


Tel.: +1 (208) 278 3370
Tel.: +1 (970) 962-7272

[email protected]

South America
Tel.: +55 19 3708 4760
[email protected]  
 
Europe
Tel. Stuttgart: +49 711 78954
510
Tel. Kempen: +49 2152 145
331
[email protected]

Middle East & Africa


Tel.: +971 (2) 678 4424
[email protected]

Russia
Tel.: +49 711 78954-515
[email protected]

China
Tel.: +86 512 8818 5515

[email protected]

India
Tel.: +91 124 4399 500
[email protected] AVR DISPLAY SCREENS
The AVR related parameters can be accessed directly through the easYgen screens.
ASEAN & Oceania
Tel.: +49 711 78954 510

[email protected]

www.woodward.com
Subject to alterations, errors
excepted.

Subject to technical modifications.

This document is distributed for


informational purposes only. It is not ORDERING INFORMATION
to be construed as creating or
becoming part of any Woodward
Company contractual or warranty
obligation unless expressly stated in WOODWARD PRODUCT ORDERING NUMBER #
a written sales contract.

We appreciate your comments


about the content of our easYgen | exciter-10 10-012-909
publications. Please send comments
For more information contact:

including the document number


below to
[email protected] RELATED PRODUCT INFORMATION
© Woodward
All Rights Reserved
PRODUCT TECHNICAL
WOODWARD PRODUCT
SPECIFICATION MANUAL

easYgen-3400/3500XT-P1 37583 37580

easYgen-3400/3500XT-P2 37583 37581

easYgen | exciter-10 B37909 B37910