Easygen - Exciter-10: Salient Features
Easygen - Exciter-10: Salient Features
Easygen - Exciter-10: Salient Features
Product Specification
B37909
to install, operate,
and diagnose
Woodward’s easYgen | exciter-10 (EX-10) module is a power electronics
component designed to provide excitation current to the generator that is No extra configuration
controlled by the Active Voltage Regulator (AVR) feature in the easYgen- tool required
3400/3500XT genset controls. On-board protection
schemes: Current
The active voltage regulation concept intends to substitute a traditional limitation, Short
voltage regulation configuration by simplifying the overall topology. The circuit, Over-
easYgen internal controller regulates generator output voltage by sending a temperature
pulse width modulation (PWM) signal to the excitation module. The excitation
module controls generator excitation and therefore generator output voltage. Status LEDs for local
This topology eliminates the redundant voltage and current sensing from a annunciation
traditional voltage regulator and also makes a feedforward control architecture Seamless integration
at AVR level simplifying the cascaded PID control topology. For power input, with easYgen-
EX-10 interfaces with any of the following excitation systems: Self/Shunt 3400/3500XT genset
Excitation, Auxiliary winding/AREP Excitation and Permanent Magnet (PMG) controls
Excitation systems to make it a standard yet versatile solution.
Active voltage
Regulation (AVR)
APPLICATION
2B
0B
Soft start control
easYgen Genset control
with AVR logic Generator Under frequency (Volt
/ Hz) regulation
Voltage & Current
Sensing Voltage droop
compensation
Compact design
Line drop
compensation
Excitation Excitation Fault Ride Through
command current
(FRT) support
Excitation CE marked
module
Active Voltage Regulator UL pending
Released
FEATURES
Current limitation – limit can be adjusted via a potentiometer (IEXC.)
Over-temperature protection – as the heat sink temperature crosses a threshold EX-10 output shuts-off
Short-circuit protection – when transient current output exceeds a threshold, the EX-10 decreases the
excitation output to below 0.2A until shutdown
In conjunction with easYgen-3400/3500XT genset controls, the active voltage regulator system offers:
Automatic Voltage Regulation (AVR)
Soft start functionality
Under frequency regulation (Volt/Hz) defined by five configurable points and activated by
LogicsManager
Line drop compensation via AnalogManager
Power factor and kvar control
Voltage droop compensation
Fault Ride Through (FRT) support
Setpoint configuration and AVR status overview on the easYgen screen and on Woodward ToolKit
Service Tool
SPECIFICATIONS
Eletrical Housing
Connection ................... plug terminals 2.5 mm²
Power consumption ...................... max. 450 VA
At max. Continuous Rating. Weight ......................................... approx. 770 g
Max. Continuous Field Current Output ........ 6 A
Max. Forcing Field Current Output ............ 10 A Environmental
(for 10 s) Ambient temp. ........ -40 to 80 °C / -40 to 176 °F
Max. AC Voltage Input ..................... 260 Vrms (operation, when mounted in landscape
(X1:X2, Z1:Z2) orientation)
PWM Input Signal .............. 500 Hz, 5~20 V DC Ambient temp. ........ -55 to 85 °C / -67 to 185 °F
(storage)
PWM duty cycle ................................... 0~100%
Ambient humidity ........... 93 %, non-condensing
Approvals
Vibration
UL ........................................................ Pending
5.05 G, 1 mm amplitude, 69 Hz in 3 orthogonal
CE In conformity with the applicable planes
requirements of the following Standards
EN 61000-6-2, 2005: Generic Standards - Generator Excitation Types
Immunity for Industrial Environments Self / Shunt Excitation, Internal / Auxiliary
Winding Excitation, Permanent Magnet (PMG),
EN 61000-6-4, 2007: Generic Standards - Single or Three Phase
Emissions for Industrial Environments
EN 61010-1, 2010: Safety requirements for
electrical equipment for measurement, control,
and laboratory use - Part 1: General
Requirements
Released
DIMENSIONS
CONNECTION DIAGRAM
24B3-Terminal Connector (Excitation command)
3B 3B4-Terminal Connector Function (Excitation power supply input)
16B
4BTerminal Label
17B 5BPMG Excitation
18B 6BSelf excitation
19B 7BAux. winding excitation
20B
25BTerminal Label
4B 26BFunction
5B 27BAccording easYgen-3400/3500XT Connection
6B
8BX1
21B 9BPhase A
2B 10BSingle phase A
23B 1BWinding 1 A
24B
28BPWM−
7B 29BPWM neg. input
8B 30BTerminal 20
9B
12BZ1
25B 13Bn.c.
26B 14Bn.c.
27B 15BWinding 2 A
28B
31BPWM+
10B 32BPWM pos. input
1B 3BTerminal 19
12B
16BX2
29B 17BPhase B
30B 18BSingle phase B
31B 19BWinding 1 B
32B
34BShield
13B 35BShield
14B 36BTo the common Protective Earth (PE)
15B
20BZ2
3B 21BPhase C
34B 2Bn.c.
35B 23BWinding 2 B
36B
South America
Tel.: +55 19 3708 4760
[email protected]
Europe
Tel. Stuttgart: +49 711 78954
510
Tel. Kempen: +49 2152 145
331
[email protected]
Russia
Tel.: +49 711 78954-515
[email protected]
China
Tel.: +86 512 8818 5515
[email protected]
India
Tel.: +91 124 4399 500
[email protected] AVR DISPLAY SCREENS
The AVR related parameters can be accessed directly through the easYgen screens.
ASEAN & Oceania
Tel.: +49 711 78954 510
[email protected]
www.woodward.com
Subject to alterations, errors
excepted.
B37909- 2020/2/Stuttgart