Buyers Guide PDF
Buyers Guide PDF
Buyers Guide PDF
Buyer´s Guide
Contents
Table of Contents
Chapter-Page
Explanations B-1
Other data and/or special applications not covered in this Buyer’s Guide will be quoted on request.
For information on Configurable Switchgear Solutions with LTB and HPL SF6 Circuit Breakers –
(i.e. Withdrawable Circuit Breakers, Disconnecting Circuit Breakers and Line Entrance Modules),
please see separate brochures.
See specially Buyer’s and Application Guide, Compact air insulated HV switchgear solutions with
Disconnecting Circuit Breaker. Catalogue publication 1HSM 9543 23-03en.
Further information about controlled switching applications and Switchsync™ controllers is found in
Controlled Switching, Buyer’s Guide/Application Guide. Catalogue publication 1HSM 9543 22-01en.
Explanations
General
Standard/Customer There are international and national standards, as well as customer specifications. ABB can
specification meet most requirements, as long as we are aware of them.
IEC or ANSI (ANSI/IEEE) are the most common standards. In case of doubt, please enclose
a copy of specification with the enquiry.
Tests Type tests (design tests) and routine tests (production tests) are required by standards.
Type tests
Type tests are performed only once on one representative test object in accordance with
applicable standards and are not repeated without extra charge. The purpose of the type
tests is to verify the ratings of the design.
Routine tests
Routine tests are performed on each circuit breaker before delivery in accordance with appli-
cable standards. The purpose of the routine tests is to verify the assembly and the function
on every individual circuit breaker. Routine test certificates are sent to the user with each
delivery.
Please see special chapter page T-1, Quality Control and Testing.
Rated voltage The rated voltage is the maximum voltage (phase-phase), expressed in kV rms, of the
system for which the equipment is intended.
It is also known as maximum system voltage.
Rated insulation level The combination of voltage values which characterizes the insulation of a circuit breaker with
regard to its capability to withstand dielectric stresses.
The rated value given is valid for altitudes ≤1000 m above sea level. A correction factor is
introduced for higher altitudes.
The definition “Across isolating distance” is only applicable for disconnectors and discon-
necting circuit breakers.
Rated LIWL The lightning impulse test is performed with a standardized wave shape 1.2/50 µs for simu-
lation of lightning over-voltage.
The rated Lightning Impulse Withstand Level (LIWL) indicates the required withstand level
phase-to-earth (phase-to-ground), between phases and across open contacts. The value is
expressed in kV as a peak value.
For voltages ≥300 kV two values are stated by IEC, a LIWL voltage on one of the main ter-
minals and power frequency voltage on the other.
Example 420 kV: 1425 (+240) kV.
Alternatively a LIWL pulse with the sum of the two voltages (1665 kV) can be applied on one
terminal, while the other is grounded.
BIL (Basic Insulating Level) is an old expression but means the same as LIWL.
Rated Full Wave is often used in older ANSI/IEEE standards but means the same as LIWL.
Rated This test is to show that the apparatus can withstand the power frequency over-voltages
Power Frequency that can occur.
Withstand Voltage
The Rated Power Frequency Withstand voltage indicates the required withstand voltage
phase-to-earth (phase-to-ground), between phases and across open contacts. The value is
expressed in kV rms.
Rated SIWL For voltages ≥300 kV the power-frequency voltage test is partly replaced by the switching
impulse test. The wave shape 250/2500 µs simulates switching over-voltage.
The rated Switching Impulse Withstand Level (SIWL) indicates the required withstand level
phase-to-earth (phase-to-ground), between phases and across open contacts. The value is
expressed in kV as a peak value. The switching impulse is required only for voltages ≥300
kV. Two values are stated by IEC, a SIWL voltage on one of the main terminals and power
frequency voltage on the other.
Example 420 kV: 900 (+345) kV.
Alternatively a SIWL pulse with the sum of the two voltages (1245 kV) can be applied on one
terminal, while the other is grounded.
General
Rated Chopped Wave The rated chopped wave impulse withstand level at 2 μs and 3 μs respectively,
Impulse Withstand indicates the required withstand level phase-to-earth (phase-to-ground) and
voltage Phase-to-earth across open contacts.
and Across open gap
The chopped wave impulse is only referred to in ANSI/IEEE standards and
hence, not applicable for IEC.
Rated frequency The rated (power) frequency is the nominal frequency of the system expressed
in Hz, which the circuit breaker is designed to operate in.
The rated normal current is based on a maximum ambient temperature of +40 °C.
At higher temperatures derating of the normal current might be necessary.
Rated short-time The rated short-time withstand current is the maximum current (expressed
withstand current in kA rms) which the equipment shall be able to carry in closed position for a
specified time duration. The rated short-time withstand current is equal to the
rated short-circuit breaking current.
The peak value is related to the rms value of the rated short-circuit breaking
current, frequency and time constant (τ). Specified values are:
- 2.5 x rated short-time withstand current at 50 Hz at τ = 45 ms
- 2.6 x rated short-time withstand current at 60 Hz at τ = 45 ms
- 2.7 x rated short-time withstand current at 50/60 Hz at τ > 45 ms
Explanations
System and Switching Conditions
Earthing of the The earthing of the network may vary with region and rated voltage.
network
For higher rated voltages, networks tend to have effectively earthed network. For
lower rated voltages, networks usually have non-effectively earthed neutral (isolated or
resonant earthed).
The type of earthing is an important parameter for defining the transient recovery voltage.
First-pole-to-clear- The first-pole-to-clear-factor (kpp) is depending on the earthing of the network. The
factor first-pole-to-clear-factor is used for calculating the transient recovery voltage for three-
phase faults.
A special case is when there is a three-phase fault without involving earth. This case
corresponds to kpp = 1.5. This case is covered by the ANSI/IEEE standards.
Rated Transient The rated transient recovery voltage (TRV) is the peak transient voltage (expressed in
Recovery Voltage kV) that corresponds to the first-pole-to-clear when interrupting a three-phase fault at
rated short-circuit current.
The rated transient recovery voltage (uc) is calculated as follows (based on IEC):
Where:
Ur = Rated voltage (kV)
kpp = first-pole-to-clear-factor
kaf = Amplitude factor (According to IEC: 1.4 at 100% short-circuit current)
Example:
At 145 kV with kpp = 1.5 the rated transient recovery voltage will be 249 kV
Rated out-of-phase The rated out-of-phase breaking current is the maximum out-of-phase breaking
making and breaking current the circuit breaker shall be capable of breaking.
current The standard value of the rated out-of-phase breaking current is 25% of the rated
short-circuit breaking current.
Out-of-phase The power frequency recovery voltage (rms) for out-of-phase conditions can be calcu-
lated as:
Where:
Ur = Rated voltage (kV)
kpp = first-pole-to-clear-factor (out-of-phase) or out-of-phase voltage factor
kaf = Amplitude factor (According to IEC: 1.25)
Example:
At 245 kV with kpp = 2.0, the out-of-phase transient recovery voltage will be 500 kV
The applied voltage before making is not affected by the earthing of the system. The
maximum applied voltage during out-of-phase conditions is always 2.0 times the
single-phase voltage.
Other characteristics for the short-line fault are the peak factor and the RRRV factor.
These have been standardized to the following values:
Application
- no-load line switching
- no-load cable switching
- capacitor bank switching
Standard values for capacitive voltage factors for normal service conditions are as
follows:
When different capacitive voltage factors apply from different applications, the highest
value should be referred to.
The voltage factor can be used to calculate the single-phase recovery voltage peak:
Where:
Ur = Rated voltage
kc = capacitive voltage factor
Example:
What is the peak recovery voltage for a 245 kV breaker when switching a no-load line
with earthed neutral?
The voltage factor is 1.2 due to earthed neutral system.
Explanations
System and Switching Conditions
Capacitive switching There are two different capacitive switching classes:
class
Class C1: Circuit breaker with low probability of restrike during capacitive switching.
Class C2: Circuit breaker with very low probability of restrike during capacitive switching.
A circuit breaker intended for Class C2 can of course also be used for Class C1.
Rated capacitive The rated capacitive inrush current (peak value) is only applicable for circuit breakers
inrush current and intended for switching of (mainly back-to-back) capacitor banks.
inrush frequency
The inrush current is characterized by a very high inrush current and inrush frequency.
Values may vary due to different configurations of capacitor banks, current limiting
inductance etc.
Standardized value of inrush current is 20 kA (peak value) and with an inrush current
frequency of 4.25 kHz.
Time constant The time constant of the system is equal to the ratio between inductance and resistance
in the network (L/R) and is expressed in ms. Standard value is 45 ms. The time constant
will affect the required DC component.
If a required X/R-ratio has been given, the time constant in ms can easily be calculated
by dividing the X/R-ratio with (2 x π x f), where f is the rated frequency.
Example:
X/R = 14 corresponds to a time constant of 45 ms at 50 Hz
X/R = 17 corresponds to a time constant of 45 ms at 60 Hz
Ambient Conditions
Minimum ambient The minimum ambient (air) temperature specifies the lowest temperature at which the
temperature circuit breaker shall be able to operate, at specified ratings.
The minimum ambient temperature affects the choice of gas pressure and/or gas mixture.
Maximum ambient The maximum ambient (air) temperature specifies the highest temperature at which the
temperature circuit breaker shall be able to operate, at specified ratings.
The maximum ambient temperature can affect the continuous current carrying capability.
NOTE!
Creepage distance voltage used to be phase to phase voltage.
To avoid confusion check which voltage reference that is used.
Pollution level Environmental conditions, with respect to pollution, are sometimes categorized in pollution
levels. The pollution levels are described in IEC 60815. During 2008 the former levels I, II,
III and IV was replaced with the five levels a, b, c, d, and e.
There is a relation between each pollution level and a corresponding minimum nominal
specific creepage distance. Since 2008 IEC 60815 states that the phase - ground voltage
shall be used for description of creepage distances instead of phase - phase voltage as in
the old versions of the standard. As a reference the old values are also given below.
Ice class If applicable, outdoor switchgear may be assigned to withstand a specified ice coating.
Three classes exist in IEC:
- 1 mm of ice coating
- 10 mm of ice coating
- 20 mm of ice coating
Wind load The specified wind loads for circuit breakers intended for outdoor normal conditions are
based on a wind speed of 34 m/s, (IEC).
Explanations
Design
Single- or three-pole For single-pole operation (1-pole operation), each individual pole of the circuit
operation breaker is operated by its own operating mechanism. This makes single-
phase as well as three-phase auto-reclosing possible.
For three-pole operation, (ganged operation) all three poles are operated by
a common operating mechanism. The three poles are mechanically linked
together for three-phase auto-reclosing.
(Two-pole operation applies only for special applications, i.e. railway systems.)
Trip-free A circuit breaker which can perform a complete opening operation, even if
circuit breaker the trip command is activated during a closing operation and with the closing
command maintained.
The resistor blocks will close the circuit approximately 8-12 ms before the
arcing contacts.
Pre-insertion resistors are mainly used at higher system voltages (≥362 kV).
b) CO - t’’ - CO
Where:
t’’ = 15 s for circuit breakers not intended for rapid auto-reclosing
Mechanical endurance There are two different mechanical endurance classes:
class
Class M1: Circuit breaker with normal mechanical endurance
(2,000 operations).
A circuit breaker intended for Class M2 can of course also be used for Class M1.
Terminal load The conductors connected to the circuit breaker terminals, as well as ice and
wind loads, cause the resultant static terminal loads.
Standard values for static terminal loads are given by the standards.
The rated static terminal loads of the equipment are normally verified by load
calculations.
Design
Pressure Gas pressures can be expressed in several units, such as MPa, bar, P.s.i etc.
Alarm pressure
The alarm pressure is given at the reference temperature of +20 °C and may
be expressed in relative or absolute terms. The alarm pressure is the pressure
at which a monitoring (alarm) signal indicates that replenishment is necessary
in a relatively short time.
Maximum pressure
The maximum pressure is given at the reference temperature of +20 °C and
may be expressed in relative or absolute terms. The maximum pressure is the
pressure at which the circuit breaker is carrying its normal current at maximum
ambient temperature.
Grading capacitors Grading capacitors are sometimes used on circuit breakers of multi-break
design (two or more identical making/breaking units connected in series) to
obtain uniform distribution of the voltage stresses across the open gaps.
The grading capacitor is connected in parallel with each and every making/
breaking unit and has a standard value of 1600 pF/capacitor.
Where:
- Cgr is the capacitance of each grading capacitor.
- n is the number of making/breaking units connected in series.
Parallel capacitor Parallel capacitors are used to increase the short-circuit capability of circuit
breakers.
The additional capacitance increases the time delay for the initial transient
recovery voltage and has therefore an impact mainly on the short-line fault
performance.
Explanations
Time Quantities
Opening time The opening time is the interval of time from energizing of the opening release (e.g. opening
coil) for a circuit breaker being in closed position and the instant when the (arcing) contacts
have separated in all poles.
Closing time The closing time is the interval of time from energizing of the closing release (e.g. closing
coil) for a circuit breaker being in open position and the instant when the (arcing) contacts
touch in all poles.
Rated break time The rated (maximum) break time (interrupting time) is the time interval between energizing
the trip circuit and when the arc is extinguished in all poles.
The break time is expressed in ms or cycles (20 ms = 1 cycle at 50 Hz).
In IEC, the break-time is based on the results of the terminal fault test duties with
symmetrical current.
Compensation is made for single-phase testing and for reduced control voltages.
Dead time The dead time (during auto-reclosing) is the interval of time between final arc extinction in
all poles in the opening operation and the first re-establishment of current in any pole in the
subsequent closing operation.
IEC and ANSI/IEEE specify a dead time of 300 ms.
Arcing time Interval of time between the instant of the first initiation of an arc and the instant of final arc
extinction in all poles.
Pre-arcing time Interval of time between the initiation of current flow in the first pole during a closing opera-
tion and the instant when the contacts touch in all poles for three-phase conditions and the
instant when the contacts touch in the arcing pole for single-phase conditions.
Reclosing time The reclosing time is the interval of time between the energizing of the opening release (e.g.
opening coil) and the instant when the contacts touch in all poles during a reclosing cycle.
If the differences in operating times (closing and opening time respectively) between poles
are small and can be neglected, the following approximative formula can be applied:
Reclosing time = Opening time + Arcing time + Dead time + Pre-arcing time
Close-Open time The close-open time is the interval of time between the instant of contact touch in the first
pole during a closing operation and the instant when the (arcing) contacts have separated in
all poles during the following opening operation.
The opening release (e.g. opening coil) shall have been energized at the instant when the
contacts touch during closing (CO-operation without any intentional time delay; pre-tripped
CO-operation).
NOTE: The close-open time is not equal to Closing time + Opening time.
Open-Close time The open-close time (during auto-reclosing) is the interval of time between the instant of
contact separation in all poles and the instant when the contacts touch in the first pole in
the subsequent closing operation.
If the differences in operating times (closing and opening time respectively) between poles
are small and can be neglected, the following approximative formula can be applied:
Open-Close time = Arcing time + Dead time + Pre-arcing time
Make time Interval of time between energizing the closing circuit, the circuit breaker being in the open
position, and the instant when the current begins to flow in the first pole.
Make-Break time The make-break time is the interval of time between the initiation of current flow in the first
pole during a closing operation an the end of the arcing time during the subsequent open-
ing operation.
The make-break time is based on an operation where the opening release (e.g. opening
coil) shall have been energized at the instant when the contacts touch during closing (CO-
operation without any intentional time delay a.k.a pre-tripped CO-operation).
If the differences in operating times (closing and opening time respectively) between poles
are small and can be neglected, the following approximative formula can be applied:
Make-break time = Pre-arcing time + Close-open time + Arcing time
Open position
Current flow
Break time
Final arc extinction in all poles
Closed position
Contact movement
Open position
Current flow
Pre-arcing time
Closing time
Explanations
Operation and Control
Operating Mechanism - Control Cubicle
Control voltage Control voltage is a DC supply used for the control circuits such as:
Close circuit and trip circuits etc.
The operating mechanism, including the control circuit, is designed for a rated control vol-
tage but must additionally have operational capability throughout a specific voltage range
to accommodate variations in supply voltage. The following required voltage ranges are
required according to IEC:
The motor and the motor circuit are designed for a rated voltage but must additionally have
operational capability throughout a specific voltage range to accommodate variations in
supply voltage. The following required voltage range is required according to IEC:
NO-contact NO-contact (normally open contact) is an open contact in the same situation.
Could also be called: Make contact or a-contact.
NOC-contact (normally open-closed contact) is a closed contact that opens and an open
contact that closes with a common backside when changing position.
Could also be called: Change-over contact.
Trip / Close switch The trip / close switch is used for control operations, when the local / remote
(/ disconnected) switch is in local position.
Local / Remote / The local / remote / disconnected selector switch is used to switch between remote opera-
Disconnected selector ting and local operating (via the open / close switch). It also has a disconnected position
switch where operation is not possible. However a protection trip by-pass can be supplied that
makes it possible to trip the circuit breaker remotely even in disconnected position.
Additional close coils can be supplied as option. Also the second trip coil can be of the
double type and additional trip circuit can be used.
Hand / Motor switch The hand / motor switch disconnects the motor circuit during hand cranking.
The hand / motor switch, either manual or automatic, has the following functions:
- Motor position; connects the motor-to-motor supply.
- Hand position; short-circuit the motor to be used as a generator brake.
Explanations
Operation and Control – ABB Options
Gas supervision
Another option is trip at low SF6-pressure. This option gives a trip order via the
Trip at low SF6 gas- supervision interlocking relays at the same time blocking occurs.
All type tests, except the mechanical tests, are carried out at this blocking
pressure.
Panel light Panel light can as an option be fitted on the control panel.
The panel lamp is automatically switched on when the panel door is opened.
Socket outlet Socket outlet can be fitted inside the cubicle.
CEE 7/4 – French/Belgium std. with Round 2-pole plug with inverted
earth-pole.
GPO – Australia
TCS – TCS – Trip Circuit Supervision is mainly used to check the connection
Trip Circuit between the protection trip relay (control room) and the operating mechanism
Supervision and secondly the trip coil(s) inside the operating mechanism(s).
The TCS is a device that can be fitted in parallel with the protection trip relay(s)
and sends a low (< 50 mA) testing current through the trip circuit(s).
To be able to monitor the trip circuits when the circuit breaker is in open pos-
ition (when the auxiliary contact in the trip circuit is open), there is a parallel
wiring to this contact. There are two normal ways to do this:
1. A resistor in parallel with this contact, with resistance value given by the
supplier of the TCS device.
Note! Used only when protective tripping should override the selector switch.
Position indicating As an option we can supply green/red-indicating LED-lamps connected to the
lamps auxiliary switch for circuit breaker position indication inside the cubicle.
The relay can be an auxiliary relay or with a time delay relay depending on
alarm delaying possibility in the bay control unit.
The alarm delay must be at least as long as the spring charging time, normally
15 s.
Voltage supervision The circuits can be equipped with voltage supervision relay(s).
This could be a zero-voltage relay (a standard auxiliary relay -not adjustable) or
voltage supervision relays (with adjustable setting for voltage and hysteresis).
Heater supervision The heating circuit can be equipped with a current supervision relay (with
adjustable setting for current and hysteresis) or an indicating lamp in series
with the continuously connected heater.
Capacitor tripping Trip circuits can be equipped with capacitor tripping devices.
Used to automatically trip the circuit breaker at loss of, or at low operating
voltage.
The capacitor tripping device is always used together with a voltage supervi-
sion relay (adjustable setting for voltage and hysteresis) that controls the trip-
ping voltage level (one capacitor device / trip coil is required).
Seismic Conditions
Seismic stress There are many zones in the world where earthquakes may occur, and where
circuit breakers should be designed to withstand the corresponding stresses.
When an earthquake occurs, the acceleration and amplitude of the motion of
the ground will vary in a statistical manner. The stress conditions are normally
most severe in the horizontal direction. The type of soil (sand, clay, rock, etc)
has a strong influence on the actual local severity of an earthquake and the
damage it may inflict.
For technical purposes earthquake stresses are normally defined by the maxi-
mum value of the horizontal acceleration. IEC has standardized three values of
maximum horizontal acceleration 2, 3, and 5 m/s2, corresponding to 0.2, 0.3,
and 0.5 g.
IEEE, which is more relevant (more severe) has corresponding standardized
values, 0.25 g and 0.5 g respectively for moderate and heavy seismic action.
Resulting stress on When a HV circuit breaker is subjected to an earthquake, the motion of
circuit breakers the ground will induce oscillations in the circuit breaker with corresponding
mechanical stress. The mechanical stress will normally be most severe at the
lower end of the support column.
The circuit breaker will have one or more natural oscillation frequencies,
eigenfrequencies, where the predominant one is typically a few Hz. Since the
frequency of typical earthquake oscillations is also of the order of a few Hz, the
actual stress on the breaker may be is amplified due to mechanical resonance.
The degree of amplification depends on the eigenfrequency (natural oscilla-
tion frequency) and damping of the circuit breaker, and may be deduced from
response spectra, published e.g. by IEC.
Earthquake dampers An earthquake damper will increase the damping of the natural oscillation of
the circuit breaker. In this way the amplification of earthquake stresses due to
resonance is significantly decreased, and the maximum mechanical stress on
the circuit breaker significantly reduced.
Verification of seismic The seismic capability of a circuit breaker may be verified by a direct test,
capability where a complete circuit breaker, or pole, is subjected to simulated earth-
quake stress on a shaker table.
S
ES R|
OT E
. OMT
US
#
1
6
2 7
3 8
4 9
10
11
1. Upper current carrier | 2. Stationary arcing contact | 3. Moving arcing contact | 4. Puffer volume | 5. Lower
current carrier | 6. Nozzle | 7. Stationary main contact | 8. Moving main contact | 9. Puffer cylinder | 10. Refill
valve | 11. Stationary piston
In its normal position, the circuit breaker con- arcing contacts. As the arc flows, it to some
tacts are closed and current is conducted degree blocks the flow of SF6 gas through
from the upper current carrier to the lower the nozzle. Thus, the gas pressure in the
current carrier via the main contacts and the puffer volume continues to increase. When
puffer cylinder. the current waveform crosses zero, the arc
becomes relatively weak. At this point, the
On opening, the moving part of the main pressurized SF6 gas flows from the puffer
and arcing contacts, as well as the puffer volume through the nozzle extinguishing the
cylinder and nozzle, are pulled toward the arc.
open position. It is important to note that the
moving contacts, nozzle and puffer cylinder In the open position, there is sufficient
form one moving assembly. distance between the stationary and moving
contacts to withstand rated dielectric levels.
As the moving assembly is drawn toward
the open position, the refill valve is forced On closing, the refill valve opens so that
closed and SF6 gas begins to be com- SF6 gas can be drawn into the puffer volume.
pressed between the moving puffer cylinder
and the stationary piston. The first contacts Note that the SF6 gas pressure required
to part are the main contacts. Parting the for interruption is built up by mechanical
main contacts well before the arcing con- means. Thus, circuit breakers using puffer
tacts ensures that any arc drawn will be interrupters require operating mecha-
between the arcing contacts and contained nisms with sufficient energy to overcome
by the nozzle. the pressure build up in the puffer volume
required to interrupt rated short circuit
When the arcing contacts part, an arc is current while at the same time maintaining
drawn between the moving and stationary the contact speed required to withstand
recovery voltage.
1
8
2 9
3 10
4 11
5 12
6 13
14
13
1. Upper current carrier | 2. Stationary arcing contact | 3. Moving arcing contact | 4. Auto-Puffer™ volume |
5. Puffer volume | 6. Refill valve | 7. Stationary piston | 8. Nozzle | 9. Stationary main contact | 10. Moving main
contact | 11. Auto-puffer™ valve | 12. Puffer cylinder | 13. Over-pressure relief valve | 14. Lower current carrier
When interrupting high currents (e.g. rated Gas pressure inside the Auto-Puffer™
short-circuit current), Auto-Puffer™ interrup- volume continues to increase until it is high
ters show the advantage they were designed enough to force the Auto-Puffer™ valve to
to provide. the closed position. All SF6 gas required for
interruption is now trapped in the fixed Auto-
At opening, the operation of an Auto- Puffer™ volume and any further increase in
Puffer™ interrupter at high current begins the gas pressure in that volume is due solely to
same way as a puffer interrupter. It is not until heating from the arc. At about the same time,
after arcing begins that a difference in the the gas pressure in the puffer volume reaches
operation principle is seen between the high a level sufficient to push the overpressure relief
and low current interrupting cases. valve open. Since the gas in the puffer volume
escapes through the overpressure valve, there
When the arcing contacts part, an arc is is no need for a high operating energy to over-
drawn between the moving and stationary come the compression of SF6 gas while at
arcing contacts. As the arc flows, it to some the same time maintaining the contact speed
degree blocks the flow of SF6 gas through necessary to withstand recovery voltage.
the nozzle. The arc drawn is extremely hot
and radiates a lot of heat and begins to heat When the current waveform crosses zero,
the SF6 gas in the interrupting gas volume. the arc becomes relatively weak. At this point,
Thus, the pressure inside the Auto-Puffer™ the pressurized SF6 gas flows from the Auto-
and puffer volumes increases due to the rise Puffer™ volume through the nozzle extin-
in temperature as well as due to the com- guishing the arc.
pression of gas between the puffer cylinder
and stationary piston. At closing, the refill valve opens so that gas
can be drawn into the puffer and Auto-
Puffer™ volumes.
ABB produced the world’s first SF6 circuit The design of the LTB is a well-proven
breakers with arc-assisted interrupters in the technology (over 25,000 units are in service).
mid-1980’s - Auto-Puffer™.
The Auto-Puffer™ principle is described in Design features
chapter C-1. LTB is available for single- or three-pole
operation.
For circuit breakers with one breaking ele-
ment per pole, both modes of operation are
possible. For two- or four-chamber circuit
breakers only single-pole operation applies.
The energy required for interrupting short cir- The three poles of the circuit breaker can
cuit currents is partly taken from the arc itself, be mounted on individual pole supports or
significantly reducing the energy required in the case of LTB D on a common support
from the operating mechanism. frame (pole beam).
Lower operating energy inherently reduces
mechanical stresses, on the circuit breaker Operating mechanism
itself as well as on the foundation, and in- BLK is used for:
creases circuit breaker reliability.
LTB D 72.5 - 170 kV
For many years, ABB has used operating LTB E 72.5 - 245 kV singe-pole operation
mechanisms with energy mechanically stored FSA1 is used for:
in springs. This solution offers considerable LTB D 72.5 - 170 kV
advantages in that the energy in the tensio-
ned springs is always available. BLG is used for:
Our spring operating mechanisms BLK, BLG LTB E 72.5 - 245 kV three-pole operation
and FSA1 are described in separate chapters LTB E 362 - 800 kV single-pole operation
in this Buyers Guide.
Motor Drive™ is used for:
In the year 2001 ABB introduced Motor
Drive, a digital servomotor system capable LTB D 72.5 - 170 kV
Current switching capability sion, without the need of extra protection. For
All LTB circuit breakers are capable of inter- use in extreme trying environments LTB can
rupting short-circuit currents in a maximum be delivered with a protective painting.
of 40 ms. For the LTB D with FSA1 the
maximum break time is 60 ms. We can also The support structure and protective tubes
guarantee restrike free interruption of capaci- for the pull rods are made of hot-dipped gal-
tive currents due to optimized contact design vanized steel.
and movement.
For inductive current switching the over- Seismic strength
voltages are low as a result of optimum All LTB circuit breakers have a mechanically
quenching at current zero. robust construction due to optimized pole
and support structure, designed to withstand
Dielectric strength seismic accelerations up to 3 m/s2 , (0.3 g)
LTB has high dielectric strength even at without extra precautions.
atmospheric SF6 pressure, due to optimized
contact gap. With reinforced support structure, insula-
tors or earthquake dampers or combinations
Controlled switching thereof, the circuit breakers can withstand
As option LTB circuit breakers can be used seismic accelerations considerably higher
for controlled switching by applying our con- than 5 m/s2 , (0.5 g).
trolling device type Switchsync™.
For further information please see chapter Q-1 Read more about “Seismic Withstand
“Controlled Switching”. Capability” in chapter S-1.
The HPL circuit breaker is operated by the The design corresponds with the demands
motor charged spring operating mechanism in the standards IEC and ANSI. Special
type BLG which is described in separate design solutions to meet other standards
chapters in this Buyer’s Guide. and/or specifications are also available.
Applications
BLK spring operating mechanisms are used
for the following types of ABB live tank circuit
breakers:
LTB D
LTB E1 (single-pole operated)
Panels Tools
Behind the front door there is a panel that A compartment for tools is located on the
may be equipped differently, depending on backside of the rear door.
customer specific requirements. As a stan-
dard, the following equipment is included on Central Control Cubicle (CCC)
the control panel: or Master-slave
• Casing with instruction manual and final For local three-pole operation of a single-pole
drawings operated circuit breaker a Central Control
• Local open / close switch Cubicle (CCC) can be used. The CCC can
• Local / remote / disconnect selector switch be delivered by ABB or arranged by the
• Electro-mechanical operations counter customer.
– non-resettable As an alternative to the CCC we can also
• MCB (Miniature Circuit Breaker) for motor- provide a “Master-slave” solution, which elim-
and AC auxiliary circuits inates the need for the CCC. Master-slave
means that the function and the components
There is easy access to relays and contac- in the CCC have instead been incorporated
tors, which are placed on the rear side of the in one of the three operating mechanisms.
hinged control panel. This saves time for installation and cabling
work.
Behind the rear door of the operating
mechanism housing there is an interface We are open for discussions how to arrange
panel containing all necessary terminal the two alternatives.
blocks for customer connections. Standard
terminal blocks are compression type in
which a bare wire is compressed between
two metallic plates in the terminal.
Closed position
In the normal service position of
the circuit breaker the contacts are
closed and the opening and closing
springs are charged.
In this position the circuit breaker is
always ready to perform an opening
operation or a complete auto-
reclosing O - 0.3s - CO.
Opening operation
To open the circuit breaker, the
opening latch (1) is released by 1
the tripping coil, and the opening
spring*) (A) of the circuit breaker car-
ries out the operation. The motion 2
of the contact system is retarded by
a damping device (2). With a spring
operated circuit breaker the opening
operation is extremely reliable as the
operation is only dependent on the
functioning of the opening latch and
the opening spring.
Closing operation
Releasing of the closing latch (4)
means an immediate response to 1 2 3
close the circuit breaker. The driver
lever (2) brings the eccentric guided
closing lever (3) to the closed posi-
tion. At the same time the opening
spring (A) is charged. At the end
of the stroke the closing lever (3)
connected to the circuit breaker is
hooked up by the opening latch (1)
in the closed position. Due to the
eccentric guided lever (3) the driver
lever (2) is declutched and contin-
ues to the resting position.
4
A
Applications
The BLG spring operating mechanisms are
used for the following types of circuit breaker:
HPL B
LTB E1 (three-pole operated)
LTB E2
LTB E4
Design features
The closing springs in the mechanism gener-
ate the required driving force to close the
breaker and charge the opening spring.
In addition, capacitor bank and reactor The principle of the operating mechanism
switching applications, which impose added can be briefly described as follows:
requirements on operational endurance, are an endless chain links a cam disc and a set
becoming more common. of springs. The chain, which is in two loops
and runs over a motor-driven sprocket,
In an international investigation it was transmits energy when the springs are being
shown that eighty percent (80%) of all failures charged and drives the cam disc around
in high voltage circuit breakers originated when the circuit breaker is to be closed.
in the operating mechanism. Therefore, to During its rotation the cam disc actuates a
achieve highest operational reliability, circuit link that converts the rotating motion into a
breakers should be equipped with highly reli- linear motion.
able operating mechanisms.
The trip and closing latches are identical,
With over 50,000 BLG operating mecha- fast acting and vibration proof.
nisms delivered, ABB is confident that the
BLG housing
• Corrosion resistant housing of painted
aluminum of 2 mm thickness.
• Front and back doors equipped with door-
stops and provisions for padlock on door
handles.
• Insulated doors and walls for low energy
consumption and low noise level. Central Control Cubicle (CCC)
When the circuit breaker is single-pole opera-
Panels ted a Central Control Cubicle (CCC) is used
Below the front door there is a panel, with a when the circuit breaker is locally three-pole
transparent shutter, that may be equipped operated. The CCC will be delivered by ABB
differently, depending on customer specific or arranged by the customer, from case to
requirements. As a standard, the following case. We are open for discussions how to
equipment is included on the control panel: arrange the solution.
Closed position
In the normal service position of the circuit
breaker (B), the contacts are in closed posi-
tion, with closing- (5) and opening spring (A)
charged.
The breaker is kept in the closed position
by the opening latch (1), which takes up the
force from the charged opening spring.
The mechanism is now ready to open upon
an opening command and can carry out a
complete fast auto re-closing
(O - 0.3 s - CO) cycle.
Opening operation
When the breaker is being opened, the latch
(1) is released by the tripping coil.
The opening spring (A) pulls the breaker (B)
towards the open position. The operating
lever (2) moves to the right and finally rests
against the cam disc (3).
The motion of the contact system is
damped towards the end of the stroke by an
oil-filled damping device (4).
Closing operation
When the breaker is being closed, the clos-
ing latch (6) is released by the closing coil.
The sprocket (7) is locked to prevent rota-
tion where upon the operating energy in the
closing springs is transferred via section (8)
of the endless chain to the sprocket (11)
belonging to the cam disc (3).
The cam disc then pushes the operating
lever (2) towards the left where it is locked in
its end position by the tripping latch (1).
The last part of the rotation of the cam disc
is damped by the damping device (9) and
a locking latch on the sprocket (11) again
takes up the initial position against the clos-
ing latch (6).
Applications
The FSA1 spring operating mechanisms are
used for the following types of circuit breaker:
ED
LTB D1
Design features
The operating mechanism consists primary
of two tension springs.
FSA1 Design
3 1
6
2
1 1
9
2
10
11 15
8
3 12
13
14
7 16
4
6
17
A B
Contact
position
Approx. 0.5 mm
Closed
Contact separation
Open
Time (ms)
Operating principle
5 2 1
4 3
S
ES R|
OT E
. OMT
US
#
SF6 gas
Gas for filling up to rated pressure can be de-
livered in bottles, each containing 40 kg gas.
The quantity required for each type of LTB
varies from one circuit breaker type to an- Disposal
other. This information is given in the tender. The disposal of wasted parts should be
The pressurizing equipment can be de- carried out in accordance with local legal
livered on request, and is described under provisions.
“Erection and Commissioning”. The SF6 gas should not be released into
the athmosphere when the circuit breaker is
Brackets and primary connections disposed.
As optional equipment, LTB 72.5 - 170 D1/B The SF6 gas can be recycled.
can be delivered with cantilever support
brackets for current transformer IMB, and The porcelain can, after it has been
primary connections between the circuit crushed, be used as fill.
breaker and the current transformers moun- The metals used in the circuit breaker can
ted on the brackets. be recycled.
SF6
LTB 72.5D1/B
LTB 145D1/B
LTB 170D1/B
LTB 72.5E1
LTB 170E1
LTB 245E1
LTB 420E2
LTB 550E2
Number of breaks per pole 1 1 1 1 1 1 2 2
Rated voltage kV 72.5 145 170 72.5 170 245 362 550
Rated frequency Hz 60 60 60 60 60 60 60 60
Power frequency
withstand voltage 1)
- To earth (Dry/Wet) kV 160/140 310/275 365/315 160/140 365/315 425/350 555/- 860/-
- Across open pole (Dry/Wet) kV 160/140 310/275 365/315 160/140 365/315 425/350 555/- 860/-
Lightning Impulse
Withstand Voltage
- Across open pole kV 350 650 750 350 750 900 1300 1800
- To earth (2 μs) kV 452 838 968 452 968 1160 1680 2320
- Across open pole (2 μs) kV 452 838 968 452 968 1160 1680 2320
Switching Impulse
Withstand Voltage
Rated continuous current A 3000 3000 3000 4000 4000 4000 4000 4000
First-pole-to-clear factor 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3
Rated closing and latching current kA 104 104 104 104 104 104 104 104
Closing time ms < 40 2) < 40 2) < 40 2) < 55 < 55 < 55 < 70 < 70
Opening time ms 22 2) 22 2) 22 2) 17 17 17 18 18
Interrupting time ms 40 2) 40 2) 40 2) 40 40 40 40 40
Dead time ms 300 300 300 300 300 300 300 300
LTB 72.5D1/B
LTB 145D1/B
LTB 170D1/B
LTB 72.5E1
LTB 170E1
LTB 245E1
LTB 420E2
LTB 550E2
LTB 800E4
Number of breaks per
1 1 1 1 1 1 2 2 4
pole
Rated voltage kV 72.5 145 170 72.5 170 245 420 550 800
Power frequency
withstand level 1)
- To earth and between
kV 140 275 325 140 325 460 520 620 830
phases
- Across open pole kV 140 275 325 140 325 460 610 800 1150
Rated normal current A 3150 3150 3150 4000 4000 4000 4000 4000 4000
Making current peak kA 100/104 100/104 100/104 125 104 125 104 125 104 125 104 125 104 125
Duration of short
s 3 3 3 3 3 3 3 3 3
circuit
Closing time ms < 40 2) < 40 2) < 40 2) < 55 < 55 < 55 < 70 < 70 < 65
Opening time ms 22 2) 22 2) 22 2) 17 17 17 18 18 20
Break time ms 40 2) 40 2) 40 2) 40 40 40 40 40 40
Dead time ms 300 300 300 300 300 300 300 300 300
Rated operating
- O-0.3s-CO-3min-CO or CO-15s-CO
sequence
1)
Up to and including 245 kV, power frequency withstand voltage ratings apply for both wet and dry conditions
2)
With BLK operating mechanism
Dimensions — LTB D
LTB D1/B Two-column stand,
Three-pole operation
Rated voltage: 72.5 - 170 kV
Dimensions (mm)
Rated F
A B C D E F
voltage E E
72.5 kV 4647 1164 670 3283 1050 3230 267
145 kV 5197 1164 1220 3833 1750 4630
170 kV 5808 1475 1520 4133 1750 4630 B
Rated
Height to lowest part of insulator **
voltage
72.5-170 kV 1123 2503* 2945 3528
*) Standard
**) Other dimensions can be provided
Dimensions (mm) F
Rated E E
A B C D E F
voltage 267
72.5 kV 4647 1164 670 3283 1750 4380
145 kV 5197 1164 1220 3833 1750 4380 B
170 kV 5808 1475 1520 4133 1750 4380
Rated 783
Height to lowest part of insulator ***
voltage
72.5-170 kV 1123** 2503* 2945 3528
*) Standard
**) Central control cabinet must be mounted separately
***) Other dimensions can be provided
Dimensions — LTB D
LTB D1/B Two-column stand,
Single-pole operation (FSA mechanism)
Rated voltage: 72.5 - 170 kV
Dimensions (mm) F
Rated E E 267
A B C D E F
voltage
72.5 kV 4647 1164 670 3280 1750 4189
B
145 kV 5197 1164 1220 3830 1750 4189
170 kV 5808 1475 1520 4130 1750 4189
Rated D
Phase distance
voltage
72.5 kV 1500 1750* 2000 2500 2501
2140
2000
707
145 kV - 1750* 2000 2500 580
1162 574
170 kV - 1750* 2000 2500
*) Standard 756
Dimensions (mm) B
Rated
A B C D E F
voltage
72.5 kV 4647 1164 670 3280 1750 4174 C
145 kV 5197 1164 1220 3830 1750 4174 A
Rated
Phase distance
1218
voltage
692
72.5 kV 1500 1750* 2000 2500
145 kV - 1750* 2000 2500 300
2530
)
* Standard
Dimensions between stands. Centre to centre (mm)
Rated Phase distance Stand distance
Height to lowest part of insulator **
voltage 1500 2530
72.5-145 kV 2501* 2946 3529 1750 2530
*) Standard 2000 2530
**) Other dimensions can be provided 2500 2530
Dimensions — LTB D
LTB D1/B Three-column stand,
Three-pole operation
Rated voltage: 72.5 - 170 kV
Dimensions (mm)
Rated F
A B C D E F
voltage E E
267
72.5 kV 4647 1164 670 3283 1050 3266
145 kV 5197 1164 1220 3833 1750 4666
B
170 kV 5808 1475 1520 4133 1750 4666
Rated
Height to lowest part of insulator **
voltage
72.5-170 kV 800 2503* 2950 3203
*) Standard
**) Other dimensions can be provided
Dimensions (mm)
Rated
A B C D E F
voltage
72.5 kV 4647 1164 670 3283 1750 4380
145 kV 5197 1164 1220 3833 1750 4380
170 kV 5808 1475 1520 4133 1750 4380
Rated
Height to lowest part of insulator ***
voltage
72.5-170 kV 800** 2503* 2950 3203
*) Standard
**) Central control cabinet must be mounted separately
***) Other dimensions can be provided
Dimensions — LTB E
LTB E1
Three-pole operation
Rated voltage: 72.5 - 245 kV
Dimensions (mm)
Rated
A B C D E F
voltage
72.5 kV 4790 1292 655 3244 1100 3590
170 kV 5400 1292 1265 3854 2500 6390
245 kV 6703 1914 1955 4544 3500 8390
Rated
Height to lowest part of insulator
voltage
72.5-245 kV 1950 2508* 2992 3642 4142
*) Standard
LTB E1
Single-pole operation
Rated voltage: 72.5 - 245 kV
Dimensions (mm)
Rated
A B C D E* F
voltage
72.5 kV 4790 1292 655 3244 2500 6298
170 kV 5400 1292 1265 3854 2500 6298
245 kV 6703 1914 1955 4544 3500 8298
*) Recommended phase distances
Dimensions — LTB E
LTB 420E2
Single-pole operation
Rated voltage: 362 - 420 kV
All dimensions in mm
LTB 550E2
Single-pole operation
Rated voltage: 550 kV
All dimensions in mm
Dimensions — LTB E
LTB 800E4
Single-pole operation
Rated voltage: 800 kV
All dimensions in mm
10860
1600 pF
5870 6070
11001
10642
3847
2086
m kg m kg m kg
4.09 x 0.57 x 1.0 / 150 /
LTB 72.5 D1/B 3.26 x 1.78 x 0.72 1130 / 710 2.17 x 0.90 x 0.53 370
0.77 x 0.55 x 1.26 170
4.09 x 0.57 x 1.0 / 150 /
LTB 145 D1/B 3.26 x 1.78 x 0.72 1250 / 740 2.17 x 0.90 x 0.53 370
0.77 x 0.55 x 1.26 170
S
ES R|
OT E
. OMT
US
#
40 40
D=14.5(13x) 44.5
22.25
23 28.5
40 44.5
125
40
For detailed information please see special • One special control valve, for connection to
chapter T-1 regarding “Quality Control and the gas bottle, and a 20 m gas-filled hose
Testing”. with connectors.
S
ES R|
OT E
. OMT
US
#
HPL 72.5B1
HPL 170B1
HPL 245B1
HPL 420B2
HPL 550B2
HPL 800B4
Number of breaks per pole 1 1 1 2 2 4
- Across open pole (Dry/Wet) kV 160/140 365/315 425/350 555/- 860/- 960/-
Lightning Impulse
Withstand Level (LIWL)
- Across open pole (2 μs) kV 452 968 1160 1680 2320 2640
Switching Impulse
Withstand Level (SIWL)
Break time ms 33 33 33 33 33 33
HPL 72.5B1
HPL 170B1
HPL 245B1
HPL 300B1
HPL 420B2
HPL 550B2
HPL 800B4
Number of breaks per pole 1 1 1 1 2 2 4
Power frequency
withstand level 1)
- To earth and between phases kV 140 325 460 380 520 620 830
- Across open pole kV 140 325 460 435 610 800 1150
Lightning Impulse
Withstand Level (LIWL)
-To earth and between phases kV 325 750 1050 1050 1425 1550 2100
Switching Impulse
Withstand Level (SIWL)
Rated normal current A 4000 4000 4000 4000 4000 4000 4000
Making current peak kA 158/164 158/164 158/164 158/164 158/164 158/164 158/164
Break time ms 33 33 33 33 33 33 33
1)
Up to and including 245 kV, power frequency withstand voltage ratings apply for both wet and dry conditions
2)
Short-circuit current ratings up to 80 kA available on request
Dimensions — HPL B
HPL B1
Three-pole operation
Rated voltage: 72.5 - 300 kV
Dimensions (mm)
Rated
A B C D E F
voltage
72.5 kV 5213 1724 655 3270 1100 3600
170 kV 6063 1724 1505 4120 2500 6400
245 kV 6703 1914 1955 4570 3500 8400
300 kV 7163 2124 2205 4820 3500 8400
Rated
Height to lowest part of insulator
voltage
72.5-300 kV 1950 2508* 2992 3642 4142
*) Standard
HPL B1
Single-pole operation
Rated voltage: 72.5 - 300 kV
Dimensions (mm) F
Rated E E
A B C D E* F 420
voltage
72.5 kV 5213 1724 655 3270 2500 6400
170 kV 6063 1724 1505 4120 2500 6400
B
245 kV 6703 1914 1955 4570 3500 8400
300 kV 7163 2124 2205 4820 3500 8400
*) Recommended phase distances
C
A
Rated
Height to lowest part of insulator
voltage 2508
72.5-300 kV 1950 2508* 2992 3642 4142
*) Standard 752
Dimensions — HPL B
HPL 420B2
Single-pole operation
Rated voltage: 362 - 420 kV
All dimensions in mm
HPL 550B2
Single-pole operation
Rated voltage: 550 kV
(Without grading capacitors)
All dimensions in mm
5288 680
Available dimensions for heights to lowest part
of insulator (mm) 1914
Rated
Height to lowest part of insulator
voltage
550 kV 1950 2508* 2992 3642 4142
*) Standard
4135
8043
7571
2366 2508
752
Dimensions — HPL B
HPL 800B4
Single-pole operation
Rated voltage: 800 kV
All dimensions in mm
10100
795 795
1724
11001 5870
10642
3847
2086
Electrical Functions
The principle function of the mechanism’s Heater circuits
electrical components is shown in the The operating mechanism is provided with
elementary diagram on next page. an anti-condensation heater.
To ensure reliable operation at low tem-
Closing circuit peratures the mechanism is provided with a
The closing coil (Y3) can be activated electri- thermostat-controlled heater unit (BT1, E2).
cally by means of local or remote control. Alternatively, in climatic conditions with
When the circuit breaker is in closed position, high humidity, the mechanism can be pro-
the closing circuit is interrupted by the auxil- vided with moisture detector.
iary contact (BG).
Terminal blocks
Tripping circuits The terminal blocks are the user’s interface
The mechanism is provided with two inde- to the control circuits and connect the inter-
pendent trip coils (Y1 and Y2). The mecha- nal wiring.
nism can be operated electrically through lo- Standard terminal blocks are compression
cal or remote control. With the circuit breaker type in which a bare wire end is compressed
in the open position, the tripping circuits are between two metallic plates in the terminal.
interrupted by the auxiliary contact (BG).
Circuits for supply to motor and AC
Interlocks auxiliaries are normally connected to 6 mm2
The contact on the density switch (BD) through-terminals. (Entrelec M6/8)
actuates the auxiliary relays (K9, K10), which
block the operating impulse if the density of The signal circuits are connected to 4 mm2
the SF6 gas is too low. The antipumping relay through-terminals. (Entrelec M4/6)
(K3) blocks any remaining closing impulse
after the breaker has completed a closing As options the 6 mm2 terminals can be of the
operation. disconnectable type.
The density of the SF6 gas and condition (Entrelec M6/8.STA)
of the operating mechanism is monitored
electrically, given the following (remote) indi- All terminals can be protected with a trans-
cations: parent cover.
• Topping up of SF6 gas is recommended
(alarm level) Internal wiring
• Density of the SF6 gas is too low The cabling in the operating mechanism is
(blocking level) normally carried out with PVC-insulated
• Indication of charged spring 1.5 mm2 cables.
Electrical functions
NOTE! CCC = Central Control Cubicle is only applicable on single-pole operated circuit breakers.
CLOSE TRIP 1 TRIP 2
S1
S4
BD
BW2 BW1 BD
K3 BG
K12
K3
K9 K10
BG
K13
BG BG Y7 BG
Y3 Y1 Q1 Y2
CONTROL CIRCUITS
SIGNALS MOTOR
N = Neutral
L = Live
Circuit diagram shows three operating mechanisms BLK with one control cubicle.
Technical Data
Motor
Universal motor*) for 110 - 125 or 220 - 250V, AC or DC
Rated Starting current Normal Current
voltage peak value at DC
(max) (approximately)
V A A
110 60 ** 16
220 30 ** 8
*) Please note that the motor contactor is either AC or DC type.
**) Depending on power source.
Operating coils
Operating Rated Power consumption
coils voltage (approximately)
V (DC) W
110 - 125
Closing 200
220 - 250
110 - 125
Tripping 200
220 - 250
Auxiliary contacts
Rated Rated Making Breaking
voltage current current current
DC AC
L/R = 40 ms Cos ϕ = 0.95
V A A A A
110 25 20 4 25
220 25 10 2 25
The operating mechanism normally includes 8 NO and 8 NC spare
auxiliary contacts.
Heating elements
Rated Power consumption
voltage Continuously Thermostatically
connected controlled
BLK CCC BLK/CCC
V W W W
110 - 127 70 140 140
220 - 254 70 140 140
The voltage range for motor, control and auxiliaries fulfills the
requirements according to IEC and ANSI C37 standards.
Design Data
BLK CCC
Dimensions (mm) 640 x 770 x 880 850 x 1015 x 497
Weight (kg) 205 195
Material of housing Aluminium
Thickness (mm) 2
Color Grey, RAL 7032
Temperature range (°C) -50 to +40
Degree of protection As per IEC 60529: IP55
Supply, control, motor and AC circuits through 6 mm2 block.
Terminal blocks
Signal circuits through 4 mm2 block
Cable entry flange (mm) Size FL 33: 102 x 306
Earthing clamp For conductors with maximum 13 mm diameter
Internal cable 1.5 mm2 PVC insulated cable
Front View
Lifting
Beams
Spring
Indication
Counter
See fig. 2
Bottom View
See fig. 2
Lifting Beams
See fig. 3
Design Data
Optional equipment Mechanical life tests have been performed
• Manual mechanical trip push-button - In- with 10,000 operations.
side or outside cubicle Before delivery each operating mecha-
• Additional auxiliary contacts - 6 NO + 6 NC nism together with the corresponding circuit
• Trip circuit supervision breaker has to pass routine tests according
• Internal light with door switch to current standards.
• Socket outlet For each circuit breaker together with its
• Position indicating lights operating mechanism a routine test report is
• Extra heater with MCB - Moisture detector issued showing the actual test result.
control
• Provision for key interlock (Castell, Fortress Recommended spare parts for
or Kirk) BLK
• Extra closing coil Applicable for circuit breakers for frequent
• Lockable operating switches switching duty, e.g. switching capacitor- or
• Protective cover for terminal block reactor-banks.
• Catchgear with closing coil (or separate coil)
Tests • Catchgear with tripping coils (or separate
The BLK mechanism has together with the coil)
corresponding circuit breaker, passed type • Heater
tests in accordance with applicable IEC and • Motor contactor
ANSI standards. • Auxiliary relays
Storage
The operating mechanism shall preferably be
stored indoors in a dry building. When stored
outdoors, the box should be opened to pro-
mote the exchange of air and the internal heater
should be used to prevent condensation.
Electrical Functions
The principle function of the mech- Heater circuits
anism’s electrical components is The operating mechanism is provided with
shown in the elementary diagram on an anti-condensation heater.
next page.
To ensure reliable operation at low tem-
peratures the mechanism is provided with a
Closing circuit thermostat-controlled heater unit (BT1, E2).
The closing coil (Y3) can be activated electri- Alternatively, in climatic conditions with
cally by means of local or remote control. high humidity, the mechanism can be pro-
When the circuit breaker is in closed posi- vided with moisture detector.
tion, the closing circuit is interrupted by the
auxiliary contact (BG). Terminal blocks
The terminal blocks are the user’s interface to
Tripping circuits the control circuits and connect the internal
The mechanism is provided with two inde- wiring.
pendent trip coils (Y1 and Y2). The mecha- Standard terminal blocks are compression
nism can be operated electrically through lo- type in which a bare wire end is compressed
cal or remote control. With the circuit breaker between two metallic plates in the terminal.
in the open position, the tripping circuits are Circuits for supply to contol, motor and AC
interrupted by the auxiliary contact (BG). auxiliaries are normally connected to 6 mm2
disconnectable terminals. (Entrelec M6/8.STA)
Interlocks
The contact on the density switch (BD) The signal circuits are connected to 4 mm2
actuates the auxiliary relays (K9, K10), which through-terminals. (Entrelec M4/6)
block the operating impulse if the density of
the SF6 gas is too low. The antipumping relay All terminals can be protected with a trans-
(K3) blocks any remaining closing impulse parent cover.
after the breaker has completed a closing
operation. Internal wiring
The density of the SF6 gas and condition The cabling in the operating mechanism
of the operating mechanism is monitored is normally carried out with PVC-insulated
electrically, given the following (remote) indi- cables.
cations: The dimensions are 2.5 mm2 for motor-
• Topping up of SF6 gas is recommended circuits and 1.5 mm2 for control- and
(alarm level) auxiliary-circuits.
• Density of the SF6 gas is too low
(blocking level) As an option flameproof, halogen free
• Direct-on-line motor starter switched off cable can be provided.
• Indication of charged springs
Electrical Functions
K3 BG
K9
K3 K10
BW
BG BG BG
Y3 Y1 Y2
Q1
K25
M.1 M
Y7 Y7 N = Neutral
L = Live
Technical Data
Motor
Universal motor*) for 110 - 125 or 220 - 250V, AC or DC
Rated Starting current Normal current
voltage peak value at DC
(max) (approximately)
V A A
110 20 - 45 ** 12 - 30 ***
220 10 - 30 ** 6 - 15 ***
*
)
Please note that the motor contactor is either AC or DC type.
**) Depending on power source.
Peak value during first 0.1 s is in general 3 times charge current.
***) Depending on spring setup.
Operating coils
Operating Rated Power consumption
coils voltage (approximately)
V (DC) W
110 - 125
Closing 200
220 - 250
110 - 125
Tripping 200
220 - 250
Auxiliary contacts
Rated Rated Making Breaking
voltage current current current
DC AC
L/R = 40 ms Cos ϕ = 0.95
V A A A A
110 25 20 4 25
220 25 10 2 25
Heating elements
Rated Power consumption -40 °C
voltage Continuosly Thermostatically
connected controlled
V (AC) W W
110 - 127 70 140 *
220 - 254 70 140 *
*) 2 x 140 W for -55 ºC
The voltage range for motor, control and auxiliaries fulfills the
requirements according to IEC and ANSI C37 standards.
Design Data
BLG
Front View SIDE Side
VIEWView
845
96 14x20
16.5x30
136
102.5
102
1522
450
28
231 59
353
Bottom View 760
Design Data
Optional equipment Before delivery each operating mechanism
• Manual mechanical trip push-button - together with the corresponding circuit
Inside or outside cubicle breaker has to pass routine tests according
• Additional auxiliary contacts - 6 NO + 6 NC to current standards.
• Trip circuit supervision For each circuit breaker together with its
• Internal light with door switch operating mechanism a routine test report is
• Socket outlet issued showing the actual test result.
• Position indicating lights
• Extra heater - Moisture detector control Recommended spare parts for
• Provision for key interlock (Castell, Fortress BLG
or Kirk) Applicable for circuit breakers for frequent
• Extra closing coil switching duty, e.g. switching capacitor- or
• Lockable operating switches reactor-banks.
• Protective cover for terminal block • Catchgear with closing coil (or separate coil)
• Catchgear with tripping coils (or separate coil)
Tests • Heater
The BLG mechanism has together with the • Motor with driving unit
corresponding circuit breaker, passed type • Motor contactor
tests in accordance with applicable IEC and • Auxiliary relays
ANSI standards.
Mechanical life tests have been performed
with 10,000 operations.
Instructions Maintenance
With each delivery of circuit breakers, there is The maintenance requirements are small, as
an extensive product manual that will guide FSA1 is designed for a service life of more
the user how to handle the apparatus during than 30 years.
its lifetime. Instructions, product manual, Normally it is sufficient with ocular inspection
circuit diagram and other documents are every 1-2 years.
placed in a compartment inside the front
door of the operating mechanism. Preventive inspection is recommended after
15 years or 5,000 operations.
Transport
FSA1 is packed assembled on polebeam or A more detailed check is recommended after
in separate box. Both alternatives in sea 30 years of service or 10,000 operations.
worthy wooden boxes for transport.
Overhaul and repair work must be per-
Arrival inspection - unpacking formed by authorized personnel only.
Please check the contents and packaging
with regard to transport damage immediately The instructions in the manual for operation
on arrival. In the event of any material miss- and maintenance should be observed. This
ing or damage to the goods, contact ABB for ensures a continued problem-free operation.
advice, before further handling of the goods
takes place. Disposal
Any damage should be documented (photo- The disposal should be carried out in accor-
graphed). dance with local legal provisions.
The metals used in FSA1 can be recycled.
If the FSA1 is packed separately the operat-
ing mechanism must be lifted using the lifting
eyes on top of the cabinet. Slings must not
be placed around the cabinet when lifting.
Electrical Functions
The principle function of the mech- Heater circuits
anism’s electrical components is The operating mechanism is provided with
shown in the elementary diagram on an anti-condensation heater.
next page.
To ensure reliable operation at low tem-
peratures the mechanism is provided with a
Central control cubicle, CCC thermostat-controlled heater unit (BT1, E2).
Local operation and connections from the
control room are made at the central con- Terminal blocks
trol cubicle, CCC. The single-pole operated The terminal blocks are the user’s interface to
LTB D with FSA1 has a CCC that is integra- the control circuits and connect the internal
ted with the B-phase operating mechanism. wiring.
This solution is sometimes referred to as Standard terminal blocks are compression
master-slave solution. The cabling from the type in which a bare wire end is compressed
CCC out to the operating mechanisms are between two metallic plates in the terminal.
as standard assembled and tested together Circuits for supply to motor and AC auxilia-
with the circuit breaker in the factory. This ries are normally connected to 6 mm2 dis-
gives an optimized solution, that saves time connectable terminals. (Entrelec M6/8.STA)
for cabling and installation work at site.
The signal circuits are connected to 4 mm2
Closing circuit through-terminals. (Entrelec M4/6)
The closing coil (Y3) can be activated electri-
cally by means of local or remote control. All terminals can be protected with a trans-
When the circuit breaker is in closed posi- parent cover.
tion, the closing circuit is interrupted by the
auxiliary contact (BG). Internal wiring
The cabling in the operating mechanism
Tripping circuits is normally carried out with PVC-insulated
The mechanism is provided with two inde- 1.5 mm2 cables.
pendent trip coils (Y1 and Y2). The mecha-
nism can be operated electrically through lo- As an option flameproof, halogen free cable
cal or remote control. With the circuit breaker can be provided.
in the open position, the tripping circuits are
interrupted by the auxiliary contact (BG).
Interlocks
The contact on the density switch (BD)
actuates the auxiliary relays (K9, K10, K11),
which block the operating impulse if the den-
sity of the SF6 gas is too low. The antipump-
ing relay (K3) blocks any remaining closing
impulse after the breaker has completed a
closing operation.
The density of the SF6 gas and condition of
the operating mechanism is monitored elec-
trically, given the following (remote) indica-
tions:
• Topping up of SF6 gas is recommended
(alarm level)
• Density of the SF6 gas is too low
(blocking level)
• Direct-on-line motor starter switched off Combined CCC and operating mechansim for
• Indication of charged springs single-pole operation with FSA1
Electrical Functions
BD Density switch Signal contact of density switch in trip and close circuit
BG Auxiliary contact Interrupting contact, close and trip circuit
BT1 Thermostat AC auxiliary circuit
BW Limit switch Signal contact
E1, E2 Heater AC auxiliary circuit
F1.A-C Miniature circuit breaker (MCB) Direct on-line motor starter. Motor circuit
F2 Miniature circuit breaker (MCB) AC auxiliary circuit
K3 Anti-pumping relay Close circuit
K9, K10 Interlocking relay, trip Trip circuit
K11 Interlocking relay, close Close circuit
K25 Auxiliary relay Gas supervision, Alarm signal
M1 Motor Motor circuit
S1 Control switch Close and trip circuit
S3 Selector switch Close circuit
S4 Selector switch Close and trip circuit
Y1, Y2 Tripping coil Trip circuit
Y3 Closing coil Close circuit
Circuit diagrams shows operating mechanism when circuit breaker is in “off” position, not
pressurised, closing springs uncharged, no power supply connected and selector switch in
position LOCAL.
F2
F1
BT1
E1/E2
BW1
M M M
-/~ -/~ -/~
Electrical Functions
C+ + -
BG
S1
BW
S4
S1
K11
K3
S3
R LD
S4
(S3)
BW1
(A) B (C)
K9 K10 K11 K25
BG1
Y3
F1.A F1.B F1.C F2
(A) B (C)
BD1 BD1
S1
S4
S4
K25
K11
K10
K9
BG1 BG1
Y2
Y1
(A) B (C)
(A) B (C)
Technical Data
Motor
Universal motor for 110 - 125 or 220 - 250V, AC or DC
Rated Starting current Normal current
voltage peak value at DC
(max) (approximately)
V A A
110 20 * 8 **
220 10 * 4.5 **
*) Depending on power source.
**) Depending on spring setup.
Operating coils
Operating Rated Power consumption
coils voltage (approximately)
V (DC) W
110 - 125
Closing 500
220 - 250
110 - 125
Tripping 500
220 - 250
Auxiliary contacts
Rated Rated Making Breaking
voltage current current current
DC AC
L/R = 40 ms Cos ϕ = 0.95
V A A A A
110 25 20 4 25
220 25 10 2 25
Heating elements
Rated Power consumption
voltage Continuosly Thermostatically
connected controlled
V (AC) W W
110-127 70 140
220-254 70 140
The voltage range for motor, control and auxiliaries fulfills the
requirements according to IEC and ANSI C37 standards.
Design Data
Dimensions (mm)
Single-pole operated Master: 770 x 575 x 1473, Slave: 595 x 453 x 1023
Three-pole operated 701 x 605 x 1022
Weight (kg)
Single-pole operated Master: 177, Slave 142
Three-pole operated 150
Material of housing Aluminium
Thickness (mm) 2
Color Grey, RAL 7035
Temperature range (°C) -50 to +40 (Other on request)
Degree of protection As per IEC 60529: IP55
Supply, motor and AC circuits, disconnectable 6 mm2 block.
Terminal blocks
Signal circuits through 4 mm2 block.
Cable connection
Single-pole operated master 2 x (218 x 76)
Three-pole operated 2 x (180 x 80)
Earthing clamp For conductors with maximum 13 mm diameter
Internal cable 1.5 mm2 PVC-insulated cable.
80
1448
(Master)
25 96 96
15
680 42 455
764
Bottom View
770
595 453
110 320 75 234
80
76 (2x)
218 (2x)
1023
918
25
547 10
375
Bottom View
605
182 320 75 234
80
19
1022
917
25
35 20
636 477
Bottom View
701
684
180 (2x)
80 (2x)
555
• Only one (1) moving part in the drive • Low operation forces
• Low stable power consumption • Simple installation without adjustment
• Extremely low noise level • Advanced self-monitoring system
Technical Data
Power supply Heating element
Input Rated voltage (V) 1)
Power consumption
110 - 250 V DC (70% — 110%) Rated voltage Thermostatically controlled
1 and 2
220 - 240 V AC (70% — 110%) (V, AC/DC) Placed in Control cubicle
1)
There is one supply which has priority (supply 1) which will be used if it is 110 - 230 2 x 100 W (at 20°C)
present, the change to secondary supply (supply 2) is automatically done without
interruption.
Test voltage 1 min. 50 Hz
Maximum power required at rated supply voltage Circuit Voltage (kV)
During startup of On-line without During and Voltage supply 2
the system operations immediately
following a single Control circuits 2
operation Outputs 2
< 10s Heating element 2
< 100 ms, 550 W
< 100 W < 400 W
< 60 s, 350 W Operating times
Opening times 22 ms
Control circuits
Closing times 45 ms
Control circuit Rated voltage Current or power
O - 0.3 s - CO - 3 min - CO
(V DC) Rated operating sequence
CO - 15 s - CO
110 160 mA during the
Close input
220 on request first 3 ms, then 3 mA Dimensions
110 160 mA during the Control cubicle
Trip input
220 on request first 3 ms, then 3 mA
Dimension (mm) 885 x 1345 x 787
110 160 mA during the
Others Weight (kg) 190
220 on request first 3 ms, then 3 mA
Thickness 2 mm aluminium
Outputs Color Grey (RAL 7032)
Output Nom. rated Breaking Max. Temperature range -50 °C to +70 °C
current capacity Breaking
Resistive load current Degree of protection As per IEC 60529: IP55
(A) (V DC) (A) Supply, control and AC-circuits
Indication 110 0.45 Terminal blocks isolatable 6 mm2 block.
16 Signal circuits through 4 mm2 block.
closed position 250 0.35
Indication open 110 0.45 Cable-entry flange Size FL33, two flanges
16 (mm) 2 x (102 x 306)
position 250 0.35
Indication For conductor with
110 0.45 Earthing clamp
circuit breaker 16 max. 13 mm diameter
250 0.35
fault Internal cable 1.5 mm2 PVC insulated cable
110 0.45
Others 16
250 0.35 Testing
The motor drive has successfully passed the following
Serial communication port type tests
Output Connector type Compatible Mechanical, High/Low temperature
optical fibre and power according IEC and ANSI
62.5/125 µm EMC according IEC and EN
Fibre output ST
nom. 820 nm
Mechanical life tests have been performed with 10,000 operations.
Before delivery each motor drive has to pass routine tests con-
forming to current standards. For each circuit breaker a routine
test report is issued showing the actual test result.
Composite Insulators
ABB has developed a full range of high Color
voltage equipment including surge The (SIR) insulators for the circuit breakers
arresters, instrument transformers and are delivered in light gray color.
circuit breakers with high performance
Applications
and robust composite insulation as an Composite insulators are used for the follow-
alternative to porcelain. Use of com- ing types of ABB live tank circuit breakers:
posite insulators provides new pos-
sibilities for substation designers to LTB 72.5 - 800 kV
improve safety and availability. HPL 72.5 - 800 kV
Switching of Capacitor banks and with a time separation of 1/6 cycle (3.3 ms at
Harmonic filters 50 Hz or 2.8 ms at 60 Hz).
SwitchsyncTM circuit breaker controllers for
shunt capacitor banks and harmonic filters For capacitor banks with ungrounded neu-
are normally used for control of closing tral, two poles should close simultaneously
operations. at phase - phase voltage zero, and the last
one 1/4 cycle later (5 ms at 50 Hz or 4.2 ms
A discharged capacitor is similar to a mo- at 60 Hz).
mentary short-circuit when connected to a
Required time staggering for grounded shunt
power source. If energized when the source
capacitor bank
voltage is high, the connection results in volt-
age and current transients that may cause + 6.7 ms
serious problems. Depending on the network + 3.3 ms
configuration, the voltage surge may cause 0 ms
dielectric breakdown somewhere in the high
voltage network, and low voltage equipment
may suffer insulation damage or malfunc-
tion. With back-to-back capacitor banks,
the inrush current may have high frequency
and high amplitude. In extreme cases, it may
threaten the mechanical integrity of both the
capacitor bank and circuit breaker. Control- 0 ms
ling the circuit breaker to energize a capaci- 0 ms
tive load at zero voltage across the contacts
will eliminate harmful transients. + 5 ms
Figure 3 shows by means of an example how Required time staggering for ungrounded
efficiently controlled switching eliminates the shunt capacitor bank
harmful switching transients related to ener-
Figure 4.
gizing of a capacitor bank.
Examples of making sequences for a 50 Hz
shunt capacitor bank. The minor time devia-
tions from voltage zero across contacts, have
been disregarded.
In a normal three-phase situation, the three Opening of capacitor bank circuit breakers
circuit breaker poles should close at different generally does not lead to any significant
time instants. The time differences depend switching transients. The major reason is
on the application. that the circuit breakers are designed to have
very low risk of restrikes upon interruption of
For capacitor banks with grounded neutral, capacitive current. However, in special cases
the three poles should close in succession
All controllers have provisions for adaptive input to compensate for systematic variations in operating time of
the circuit breaker. In addition, Switchsync™ F236, T183, and L183 have provisions for two external, predic-
tive inputs (e.g. temperature variation, control voltage). These functions make it possible to achieve added
precision in the timing of the controlled circuit breaker. They also have a data memory that stores information
on switching times, thus permitting condition monitoring of the circuit breaker. Sensors for compensation
purposes and communication software for all controllers except E-models are accessories that are ordered
separately.
Type designation
The type designation of a Switchsync™ con-
troller gives information about its functionality.
The letter is a generation and application
identification, while the subsequent numbers
provide the following information:
Figure 10. Switchsync™ F236 and E113 controllers
More information
Further information about controlled switch-
ing applications and Switchsync™ control-
lers is found in “Controlled Switching, Buyer’s
Guide/Appplication Guide”.
Catalogue publication 1HSM 9543 22-01en.
The OLM2 monitor is a measuring data ac- The following parameters may be monitored:
quisition unit optimized for on-line analysis of operating times, coil currents, contact travel
high-voltage circuit breakers. The electronic (giving information about speed, overtravel
circuit is fitted into an EMC shielded aluminum and damping), motor current including spring
profile housing. The aluminum housing has charging time, SF6-density. Phase currents can
screw terminals for all external connections. be measured as an option to determine the
contact erosion.
The OLM2 units have a limited data storage
capacity. To fully use the flexibility of the OLM Design
System, a data storage device (server com- An OLM2 unit consists of a signal processor
puter) is required at the substation level. with programmable logic. Most internal func-
Communication to and from the monitoring tions can be modified by firmware or software
units within a substation is done using an changes, which means that it can easily be
OLM-bus (a modified RS 485 bus), using a adapted to any type of equipment. The OLM2
twisted pair shielded cable suitable for RS units have their own internal watchdog with
485. Another option is using optic fiber, this alarm function.
requires optical modems at both ends.
The software provided together with the OLM
From the server computer in the substation to consists of three parts:
the location where detailed analysis is per- • OLM Installer, used for installation of the
formed, data can be transmitted using any individual units
existing communication means supported by • OLM Server, used for communication with
Windows®. External systems, such as SCADA the individual OLM2 units on a bus and the
can easily make use of the data obtained server computer (usually a PC) in the substa-
through the OLM. tion;
• OLM Explorer, the data analysis and super-
Data acquisition starts when an OLM2 is trig- vision tool. The OLM Explorer software also
gered by either a coil input (trip or close), an hosts a server engine that communicates
input to the motor of the operating mechanism with server computers.
or an alarm. For each operation of the circuit
breaker a complete image of the recorded
parameters is stored into the unit, including lo-
cal time and temperature (ambient and inside
operating mechanism). The stored data is then
transferred to the server computer and is then
accessible for remote analysis using the OLM
Explorer software. With this software a de-
tailed analysis of all circuit breaker parameters
is possible including trend analysis.
Example of the presentation of the motor current
Monitored data
OLM2-unit: From the function categories the following
Internal temperature parameters are derived and supervised:
Power supply voltage and current Operating times
Coil circuit and operating currents Operating speeds
Motor circuit, operation current and time Coil armature time
Operating times Coil peak current
Time between operations Damping time
Monitoring equipment functions (watchdog) Overtravel and rebound
Storage capacity OLM2-unit: Counters recording the number of operations
Last 32 alarm status records and number of motor operations;
Last 8 contact status records Motor peak current and spring charging time;
Last 16 motor operation records Internal temperature of the operating mechanism;
Monitored function categories Ambient temperature;
through OLM Explorer: Power supply voltages and currents
Status signals (circuit breaker open or closed) (OLM2 unit and heaters);
Closing operation SF6 density, with trend analysis;
Opening operation Contact wear (optional);
Close-open operation Contact stroke and contact position.
Motor operation
The software is delivered with the OLM System and it contains a feature for automatic update of the
software free of charge.
S
ES R|
OT E
. OMT
US
#
tude of the motion of the ground will vary in breaker, and is given by the response spec-
a statistical manner. The stress conditions tra, specified by IEC 62271-300 or IEEE 693.
are normally most severe in the horizontal Sometimes also other response spectra are
direction. The type of soil (sand, clay, rock, used, e.g. from Endesa or Edelca.
etc) has a strong influence on the actual local For the same maximum ground accelera-
severity of an earthquake and the damage it tion, the requirements of IEEE 693 are more
may inflict. stringent than those of IEC 62271-300. The
For technical purposes earthquake stresses major reason is that IEEE applies a safety
are normally defined by the maximum value factor 2 for the mechanical strength of the
of the horizontal acceleration. insulators, while IEC uses a factor 1. In ad-
IEC 62271-300 specifies three values of dition the IEEE response spectra are more
maximum horizontal acceleration, 2, 3, and severe than those of IEC.
5 m/s2, corresponding to 0.2, 0.3, and 0.5 g,
while IEEE 693 specifies 2.5 and 5 m/s2, Seismic capability of LTB and HPL
corresponding to 0.25 and 0.5 g. circuit breakers
All standard versions of HPL- and LTB-circuit
Resulting stress on circuit breakers breakers can withstand seismic accelerations
When a HV circuit breaker is subjected to below 0.3 g in accordance with IEC 62271-
an earthquake, the motion of the ground will 300 and below 0.25 g in accordance with
induce oscillations in the circuit breaker with IEEE 693 (see page J-2 and K-2). In order
corresponding mechanical stress. The me- to withstand higher earthquake stresses the
chanical stress will normally be most severe circuit breakers may be provided with rein-
at the lower end of the support column. forced support structures and/or reinforced
The circuit breaker will have one or more insulators. In addition, and in order to handle
natural oscillation frequencies, eigenfrequen- the highest stresses, earthquake dampers
cies, where the predominant one is typically may be applied on large circuit breakers.
APPLICATION
Line
Transformer
Reactor banks
Capacitor banks
Other service duty
Number of operations per year
SYSTEM PARAMETERS
Rated voltage
Rated frequency
Rated normal current
Maximum breaking current
LIWL (Lightning impulse 1.2/50 μs)
SIWL (Switching impulse 25/2500 μs, for
Um ≥300 kV)
Power frequency withstand voltage
Grounded / Ungrounded neutral
AMBIENT CONDITIONS
Ambient temperature (max - min)
Altitude (m.a.s.l.)
Earthquake withstand requirements
ACCESSORIES
SF6 gas for pressurizing
Gas filling equipment
Controlled Switching (Switchsync™)
Condition monitoring (OLM)
Test equipment
- SA10
- Programma
Tools
Spare parts
NOTE! For information regarding the parameters asked for see chapter B-1 “Explanation”.
ABB AB
High Voltage Products
SE-771 80 LUDVIKA, Sweden
Phone +46 240 78 20 00
Fax +46 240 78 36 50
E-mail: [email protected]
Internet: http://www.abb.com