General Specification
Power Supply AC220~240V, 47~63Hz, Access to PCB by transformer;
Power Consumption
Measure Range -50~125°C Resolution +/-0.2°C @ 25°C

Working Cond. -20 ~ 70°C ≦85% no condensation


20W max.
Storage Cond. -35 ~85°C ≦85% no condensation

Switch on/off Single relay load: Inductive load ≦100W (Current=0.5A);resistive load ≦
8pcs relays
output 400W(current=2A). Single common relay total load ≦ 1KW (current=5A)

Switch on/off 9pcs passive


Prohibit access external power and total access load resistance ≦2kΩ
input signal relays

Motor Output 2pcs interfaces for stepper motor, 12Vdc, Coil current ≦ 0.4A

Analog Input 9pcs NTC temperature sensor (10K 3950); 2pcs currect detecting interfaces (FJ300)

Spare lists in the package Application:


1 PCB board - - 1PC Low temperature air source heat pump (EVI)

2 Panel - - 1PC Common air source heat pump

3 Communication Cable- - 1pc Air cooled water chiller

4 Transformer 220Vac-- 1pc Water source/geothermal heat pump

5 Fixtures -- 4 fixing feet Water cooled water chiller

6 NTC temperature sensor--7pcs or 9pcs

7 Instrument transformer-- 1pc


If you have more technical questions, please
Optional parts email to [email protected] or call +86
1 WIFI module 21 60719608

2 GPRS module

Wiring:
1. Before wiring, It must cut off main power supply; Pohibit electric live operation
2. Please correct wiring following wiring diagram to avoid damage the board
3. When wiring, please following strong and weak separation principle, Keep distance between
the board and the contactor more than 50mm, in order to avoid strong electromagnetic
interference; Please make the shield according to the rules if there have frequency inverter
devices around.
4. Don’t sink temperature sensor into water long time to avoid temperature resolution

5. Please select pure copper & low resistant wire if it need extend temperature sensor wire at
the site. Longer wire,thicker wire. NO hand twist connection, prefer connection with wire nuts.

1
BOWA SOLUTION

Key Parameters Settings


1 Press " Add" to be parameter setting status

2 Long press " Enter" to show parameters when in parameter setting status
Press “Add” and “Sub” keys synchronously + enter password (default 1234) to be engineering setting
3 status
Press “Add” and “Sub” keys synchronously + enter password (default 12345) to be manufacturer
4 setting status

Manufacturer check and confirm


0 = 风冷 Air source
1 机型Source 0 (默认值, default)
1 = 水冷 Water Source
2 模块数 Module quantity When Module Quantity should be setup "1", it become valid and need
reset.
3 主路电子膨胀阀 Main EEV 3 modes (Stop, manual and auto) is optional
4 增焓电子膨胀阀 EVI EEV Usually manual is for debugging

If use this function, please set parameter "run"


电气保护参数
Electric Protection If don't use and only show current, please set parameter into "show"
Parameter
5 compressor rated current = max. run current X 1.2
(含板载三相电检测
incl. Onbard 3-phase If no phase protect relay, please keep normal open
detector)
If no 3phase power supply, please set into " stop"

Water outlet Min. Temp System will stop when water temperature is less than the setting
6
Water outlet Max. Temp System will stop when water temperature is higher than the setting

用户参数设定 User Settings


工作模式 1 制冷 Cooling
1 1 (default 默认值)
Working Mode 2 制热 Heating
制冷设定温度
2 min...100.0 min= (制冷下限) 12'C (Default 默认值)
Cooling Temperature
制热设定温度
3 0.0... max max = (制热上限) 40’C (default默认值)
Heating Temperature
掉电记忆开关机 使用 Run 不用(默认值)
4
Power-foff memory switch 不用 Stop Stop (Default)

端子说明及常规参数说明 Terminals & Normal Parameters List


序号 名称 默认值 类型及说明 备注
NOs. Name Default Setting Type & description Remark
变压器 线路板电源
JP1 AC220V - DC11V
Transformer PCB power supply
输入公共端 回路必须条件
JP2
Common Input For Close Circuit

2
BOWA SOLUTION
压机低压 常闭 压缩比控制防止过载
JP3
Low Pressure switch Normal Close Compressing Ratio
压机高压 常闭 Control to avoid
JP4 overload
High Pressure Switch Normal Close
压机过载 常闭
JP5 热继电器/电机保护器
Compressor overload Normal Close
Thermal relay or
风机过载 常闭 motor protector
JP6
Fan motor overload Normal Close
常开
水量开关 常闭 监测水流量变化
JP7 常闭
Flow Switch Normal Close Monitoring flow rate
Normal Open
热继电器/电机保护器 Normal Close
水泵过载 常闭
JP8 Thermal relay or
Water Pump Overlad Normal Close motor protector

电源异常时切断供电回
相序保护 常闭 路 When power
JP9
Phase protector Normal Close supply is abnormal,
turn off it to protect

远程开关 常开 额外控制接入口
JP10
Remote Switches Normal Open Extra more interface
备用
JP11
Standby
开关量输入
由控制板板内提供电源,不可接入外部电源。直接接开关量信号线到板上信号端和公共端即可
Switches input
It use onboard power supply and prohibit access external power. Wiring common input and signal input directly.

序号 名称 参数 默认值 Default
NOs. Name Parameters (设置范围 Setting Range)
4°C
最低温度 Min. Temp
(-30~100°C)

使用 Run
防冻使用 Anti-freeze usage
出水温度 (不适用使用 Stop/Run)
Water 40minutes
JP12 防冻周期 Anti-freeze cycle
Outlet (2~300minutes)
Temp. 6°C
防冻温度 Anti-freeze Temperature
(-20~20°C)

55°C
最高温度 Max. Temp
(0~100°C)

和出水最小温差 9°C
回水温度
Min. Temp. Diff. with Outlet Water (5~50°C)
JP13 Water Inlet
和出水最大温差 4°C
Temp.
Max. Temp. Diff. with Outlet Water (5~50°C)
环境温度 增焓阀开启环温 5°C
JP14
Ambient Ambient temp. to switch on/off EVI valve (-30~30°C)
Temp. 最大除霜比例 50%
Max. defrost ratio (0~100%)

除霜周期1 50minutes
Defrost peroid 1 (1~300min)

3
BOWA SOLUTION
除霜周期2 30minutes
Defrost peroid 2 (1~300min)
最长除霜时间 300s
Max. defrosting time (20~1200s)
进除霜翅温 -2°C
Fins Temp. to start defrosting (-20~2°C)

除霜环翅温差 8°C
翅片温度 Temp. Difference between Ambinent and fins (2~20°C)
JP15
Fins Temp. 结束除霜翅温 14°C
Fins temp. to exit defrosting (5~20°C)

退出除霜开风机时间 10s
Delay to power off fan motor when exit defrosting (1~30s)
低压除霜使用 Stop
Defrost in low pressure (stop/run)
除霜停机时间 30s
Comp. stop time during defrosting (0~300s)
允许除霜出水温度 25°C
Defrosted Water temp. (0~40°C)

最长除霜周期 18minutes
Max. defrost Cycle (1~600min)
排气温度保护(制冷) 95°C
Discharge Protecting Temp.(Cooling) (60~125°C)
排气温度保护(制热) 108°C
Discharge Protecting Temp.(heating) (60~125'C) 排气温度高于此值,报警停机。
设置大于125°C,表示不使用该报
排气温度过高 122°C
警;
Discharge overheat Temp. (60~126°C)
When discharge temp. is higher
喷液响应温度 95°C than the setting, it will alarm
Liquid injection response Temp. (30~125°C) and stop compressor. If setting
排气温度
喷液冷却退出温差 6°C 125'C, it will stop such function.
Discharge
JP16 Liquid injection off Temp. Diff. (1~50°C)
Temp.
(60~125°C) 开增焓阀排气温度 70°C
Dis.Temp to switch on/off EVI (50~125°C)
排气温度过低 25°C
Discharge underlow Temp. (0~100°C)
压缩机开机5分钟检测排气温度过低
排气温度过低检测延时 5minutes
Delay 5minutes to detect discharge
Disc.underlow Temp. detecting delay (0~100min) underlow temp after compressor on

排气温度过低检测延时 30s
Disc.underlow Temp. alarm delay (0~1200s)
吸气温度 用于过热度测算和设定
JP17
Suction Temp. For Superheat Setting
阀前温度 热泵状态下过热度测算设定
JP18
Liquid temp. before EEV For Superhat Setting in heat pump
备用
JP19
Standby
备用
JP20
Standby

4
BOWA SOLUTION

使用Usage 0 0=不用 Stop; 1=显示 Display; 2=报警 Alarm

电流过低 1A
压缩机电流 Low Current (0~30A)
compressor
电流过低延时 30s
Current
Low Current delay (5~300s)
JP21 额定电流 20A 实际电流>(额定电流)*1.2时,才开始报警;电流超出越多,报警越快
Rated Current (0~36A) Alarm when real current > rated current*1.2 or more

GND
水泵电流
使用Usage 0 0=不用 Stop; 1=显示 Display; 2=报警 Alarm
Water
pump 额定电流 20A 实际电流>(额定电流)*1.2时,才开始报警;电流超出越多,报警越快
Current Rated Current (0~36A) Alarm when real current > rated current*1.2 or more

使用Usage 0 0=不用 Stop; 1=手动 Manual; 2=自动 Auto

励磁方式 0 (default) 0 = 1-2 phase Excitation


Excitation Method 1 1 = 2-2 phase Excitation
励磁速度 (pps) 0 = 31pps; 1 = 62pps; 2 = 83pps; 3 = 100pps;
Excitation Speed 4 =125pps; 5 = 166pps; 6 = 250pps
主路电子膨 总步数 Pulse 500 (0 ~ 9000)
JP22 胀阀
Main EEV 过热度 Superheat 5'C (-10'C ~ +30'C)
初始开度
60%
Initial Opening
初始开度维持时间
10 seconds (0 ~ 300)
Initial Hold-up Time
除霜开度
65%
Opening when defrosting
JP23 增焓电子膨胀阀 EVI EEV
JP24 使用 Run 通常不接相序保护器时才使用; 故障代码和"JP22-3 电源故障“相同;
板载三相电检测
JP25 (不使用/使用 Usually run without phase protector and same error code " JP22-
Onbard 3-phase detector 3" as power error
JP26 Stop/ Run)

通常指的时电磁阀
JP27 增焓阀/喷液阀 EVI / liquid injection
Usually it is Solenoid Valve
避免带液启动
JP28 曲轴加热/故障指示 Crankcase heater
Avoid liquid shock
JP29 凝水盘加热 Condensed water pan heater
如管道加热器
JP30 辅助加热 Auxiliary heater
For example, tube heater
开机延时 15s 0~200秒之间延时设置
Start Delay (0~200s) 0 ~ 200s delay is optional
使用;压机停机后延时60秒停水泵;
水泵 使用 可选
继电器输出 Run:delay 60s to stop water pump after
JP31 Water Run Optional
a)只提供开关(干触 compressor stop
Pump
点),需外接220VAC电 停用:只要开机状态,水泵一直工作
停用 默认 源; Stop: water pump keep working when
Stop default b.)每个触点容量<2A, compressor is on
公共触点容量<4A;

5
BOWA SOLUTION
制冷低速时翅温
公共触点容量<4A;
20°C 翅片温度不使用时, 风机强制高速;风机
Fins Temp. at Low 独立时, 根据"风机低速翅温"确定风机开/
Speed in cooling (1~60°C)
停, 此时风机高速无效;风机共用时, 根据
制冷高速时翅温 Switches Output “风机高速翅温”和"风机低速翅温“分成3挡,
25°C 输出分别为: 2风机, 1个风机和风机停止运
Fins Temp. at high a.) Only switch
Speed in cooling (1~60°C) 行.
风机 on/off output &
JP32 Stop fins temp, fan will run at high
Fan motor 制热低速时翅温 need connect speed forcibly; Fan works indepently,
11°C
Fins Temp. at Low external power it is switch on/off by "fins temp at low
Speed in heating (-5~30°C)
supply; speed ", and "fins temp at high speed" is
制热高速时翅温 invalid; When fan is shared, there has 3
5°C b.) Each relay load is
Fins Temp. at high level by fins temp, output:2fans, 1fan
(-5~30°C) <2A and common or stop.
Speed in heating
output is <4A
常开: 制冷((除霜)断电, 制热时通电
常开/常闭 常开 常闭:制冷(除霜)通电,制热时断电
四通阀 NO: Power Off in cooling, on in heating
NO/NC Normal Open
4-Way NC: Power On in cooling, Off in heating
JP33
Reversed
负值:先开压缩机,再开四通阀
Valve 开机延时 -3s
Negative: Start Comp. firstly, then
Start Delay (-10~10s) start 4-way valve
压缩机
JP34
Compress
or
输出公共端
JP35
Common
Output

文本屏接口
JP36 HM503 default
Text
screen
文本/触摸 HM501 可选 三者选其一
JP37 屏接口 HM502 Optional It must choose only one
Text/touch
扩展通讯口 可选
JP38 Extended SK043
Optional
communicati

6
BOWA SOLUTION

工程参数 Engineering Parameter


出温 Outlet Temperture 回温 (默认值)
控制对象 回温 Inlet Tempeature Inlet Temperture (Default)
1
Control Object 出温补偿 Outlet Temp.Compensation 0'C (默认值 Default)
回温补偿 Inlet Temp. Compensation -30 ~ 30'C
远程开关类型 拨动 Toggle 拨动 (默认值)
2
Remote Switch Type 脉冲 Pulse Toggle (Default)
系统探头位置 机组 In the unit 机组 (默认值)
3
System Sensor Location 工程 In the engineering In the unit (Default)
系统水流量开关位置 机组(默认值) In the unit (default) 模块个数设置为1时才有效。设置
4
Flow Switch location 工程 In the engineering 后需重新上电。When Modular
上位机监控地址 1 (默认值 Default) Quantity should be setup "1", it
5 become valid and need reset.
Upper monitor address (0...512)

制造商参数设定 Manufacturer Setting


机型 0 = 风冷 Air source
1
Source
0...1 0 (默认值, default)
1 = 水冷 Water Source
模式 0 = 单冷 Single Cooling; 1 = 单热 Single Heating;
2
Mode
0...2 2 = 热泵冷水机(默认) heat pump water chiller(default)
切换对象 冷媒 Refrigerant 冷媒(默认值)
3
Shift Object 水路 Water Refrigerant (default)
JP27输出自定义 0 = 增焓阀 EVI valve
4
JP27 output csutom 1 = 喷液阀 Liquid Injection Valve
JP28输出自定义 2 = 曲轴加热 Crankcase heater
5
JP28 output csutom 3 = 故障指示灯
压缩机类型 定速(默认值) Constant Speed (Default)
6
Compressor Type 变速 Variable Speed
变频器类型
7 CVTE (默认值 default); 正弦 Sine;
Inverter
0=Pansonic 5KD (Default) ; 1=Mistubish LNB42; 2=Landa TD200; 3=GMCC ATF235; 4=
压缩机型号
8 Highly WHP156; 5 = Highly WHP115; 6=GMCC ATF310; 7=Landa TF310; 8=Landa D20Z;
Compressor Model 9=Landa F310; 10=Custom

压缩机最低转速
9 15...60 rps 35 (default)
Comp. Min. Speed
压缩机最高转速
10 45...120 rps 80 (default)
Comp. Max. Speed
回油间隔
11 0...500 minutes 180 (default)
Oil Return Cycle
回油时间
12 0...20 minutes 3 (default)
Oil Return Hold-up Time

If you have more technical questions, please email to [email protected] or call +86 21 60719608