M700 Addressable Call Points

Data Sheet

The M700 series with integral isolator, are call points designed Both break glass, supplied, and re-settable operating elements
to provide a manual alarm interface to NOTIFIER’s fire alarm (PS230) can be used in the standard unit. Operation of the re-
control panel. settable element, as well as being indicated by the units LED, is
also indicated by a yellow strip on the element which becomes
Installation efficiency, flexibility and compliance with the latest visible when activated. With the addition of a hinged transparent
standards are at the heart of the call point range. cover (PS200) the element may be protected against accidental
operation and may be further protected by using a cover seal
(PS056) which requires breaking in order to operate the unit.
Features
• Unique ‘Plug & Play’ installation concept The call points use one of 99 possible addresses which is
• Integral loop isolation simply ‘dialled in’ using the two rotary decade switches on the
rear of the unit.
• Model available protected to IP67
• Re-settable operating element option A specialist test key may be inserted into the bottom of the unit
• Analogue addressable communications to lower the glass and release the micro‑switch and thus a full
functional test is achieved.
• Semi-Flush or surface mounting
• Fully compliant with EN54, Part 11 Installation
• Backward compatibility
• Integral LED The call points are suitable for semi-flush mounting as standard,
for indoor use. This uses a single‑gang electrical knock-out box
in conjunction with a terminal tray (ETT‑P) for isolated screen
The unique ‘plug and play’ concept is designed specifically to continuity connection. However if surface mounting is required,
reduce installation time by using a terminal block which can be then a matching single terminal back box is also available
wired during the initial installation cabling with a link (P102) to (SR1T).
provide continuity for testing. During the commissioning phase,
the links are removed and the terminal block is simply inserted
into the connector at the back of the unit. No re-termination is Mounting hardware and installation instructions are provided
required. with each module.

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability ISO9001
can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. Design, Manufacture and
Supply to Quality Manage-
For more information, contact: ment Systems Certified to
NOTIFIER. Caburn House, Brooks Road, Lewes, East Sussex, BN7 2BY. United Kingdom ISO9001:1994
Phone: +44 (0) 1273 897 000 300 Fax: +44 (0) 1273 376 894

Page 1 of 4 - 990-091_1215 www.notifierfiresystems.co.uk


Addressable Manual Call Point M700KACI-FG
The M700KACI-FG with integral isolator, is a call point designed to provide a manual alarm interface to
NOTIFIER’s fire alarm control panel.

Installation efficiency, flexibility and compliance with the latest standards are at the heart of the call point range.
The unique ‘plug and play’ concept is designed specifically to reduce installation time by using a terminal block
which can be wired during the initial installation cabling with a link (P102) to provide continuity for testing.
During the commissioning phase, the links are removed and the terminal block is simply inserted into the
connector at the back of the unit. No re-termination is required.

Specifications
Addressable Manual Call Point
M700KACI-FG (Glass) & M700KACI-FF (flexible Element)
Mechanical Specification Electrical Specification
• Dimensions:
• Current Consumption
Semi-flush mounting:
Quiescent: 360µA
Height: 93 mm
Alarm Current: 6mA
Width: 89 mm
Depth: 27.5 mm • Operating Voltage: 15 V to 30VDC maximum
Surface mounting:
Height: 93 mm Environmental Specifications
Width: 89 mm • Operating temperature -30°C to +70°C
Depth: 59.5 mm
• Relative humidity: 0% to 95%, non-condensing
• Weight:
Flush 110 g • Ingress Protection (IP) Rating: IP24D
Surface 130 g

89mm
93mm

27.5mm 32mm

Page 2 of 4 - 990-091_1215 www.notifierfiresystems.co.uk


Addressable Waterproof Call Point M700WCP
This IP67 rated call point is available with integral isolator and designed to provide a manual alarm interface to
Notifier fire alarm control panels where additional protection against the environment is necessary.

Installation efficiency, flexibility and compliance with the latest standards are at the heart of the call point range.

The unique ‘plug and play’ concept is designed specifically to reduce installation time by using a terminal block
which can be wired during the initial installation cabling with a link (P102) to provide loop continuity for testing.
During the commissioning phase, the links are removed and the terminal block is simply inserted into the
connector at the back of the unit. No re-termination is required.

Specifications
Addressable Waterproof Call Point M700WCP-R/I/SG
Mechanical Specification Electrical Specification
• Dimensions: • Quiescent (with isolator) 360μA
Height: 93 mm • Alarm Current: 6mA
Width: 97.5 mm
• Operating Voltage: 15 V to 30VDC maximum
Depth: 71 mm
• Weight: 400 g (incl packaging) Environmental Specifications
• Mounting hole centres: 60mm • Operating temperature: -30°C to +70°C
• Storage temperature: -30°C to +70°C
• Relative humidity: 0% to 95%, non-condensing
• Ingress Protection (IP) Rating: IP67

Page 2 of 4 - 990-091_1215 www.notifierfiresystems.co.uk


Product Range at a Glance
Part Number

Addressable call point with in built isolator. Glass included. Requires SR1T for surface mounting, terminal
M700KACI-FG
tray ETT-P and single gang back box for semi flush mounting.

Addressable call point with in built isolator. Flexible element included. Requires SR1T for surface mount-
M700KACI-FF
ing, terminal tray ETT-P and single gang back box for semi flush mounting.

Intelligent water resistant call point with isolator. Supplied with glass M700WCP-R/I/SG

Semi-flush mounting call point terminal tray. ETT-P

Surface mounting call point back box. SR1T

Transparent hinged cover. PS200

Call point cover seal (anti-tamper). Pack of 5. PS056

Pack of 10 EN54 Pt.11 glasses.


KG1/N10/GL1293

Pack of 10 resettable elements.


PS230

Pack of 10 continuity links. P102

Charles Avenue T: +44 (0) 116 246 2255


Burgess Hill F: +44 (0) 116 246 2210
Page 4 of 4 - 990-091_1215 W. Sussex E: [email protected]