Tilf Out 2 Tilf Out 2
Tilf Out 2 Tilf Out 2
Tilf Out 2 Tilf Out 2
GB10963.1,IEC60898-1
Compliant certification
CCC,CE
Major function
Technical parameters
Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A,;
Rated voltage: 240V ~ (1P, 1P+N), 415V ~ (2 ~ 4P, 3P+N);
Frequency: 50/60Hz;
Electromagnetic release type: B, C, D;
Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P;
Mechanical life: 20000 cycles;
Electrical life: 10000 cycles;
Rated short-circuit breaking capacity: 10000A;
Short-circuit breaking capacity: 7500A;
Rated impulse withstand voltage: 4kV;
Power consumption on each pole of the circuit breaker: see Table 1.
Table 1
1~10 2
16~32 3.5
40~63 5
0
72 -1.20
3P+N, 4P
0
54 -1.20 0
3P 77.8 -1.20 (Multipolar)
0
0
36 -0.62 76.8 -1.20
1P+N, 2P (Unipolar)
0
18 -0.43 42.5±0.31
1P
tilf out
2
34.5±0.5
45±0.31
-1.20
0
1 lift
80
65.5±0.37
Modular DIN Rail Products
Identifier description
Trademark
Product model
CE
Indication window
Open/Close position
indicator
Technical parameters
Standard
Modular DIN Rail Products
Product overview
Accessories
A variety of additional features can be achieved with wide range of accessories when used with circuit breaker, such as alerts, shunt trip, under
-voltage protection, etc. Usually the Max number of accessories assembled on the circuit breaker is three. Accessories with independent tripping
function should be assembled first, such as shunt trip, and under-voltage trip, Followed by other accessories , such as auxiliary contacts, alarm
auxiliary contacts.
Accessories that can be assembled with NXC-63 series (IEC/EN 60947-5)
AX-X1 AL-X1
SHT-X1 OVT-X1
UVT-X1 OUVT-X1