NA3 - Service Manual
NA3 - Service Manual
NA3 - Service Manual
service manual
1
2
DIGITAL-TO-ANALOGUE
METER WITH A MULTICOLOUR
BARGRAPH
+ SERIAL INTERFACE
NA3 TYPE
CONTENTS Page
1. APPLICATION..............................................................................................5
2. SET OF THE METER...................................................................................6
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY...................................6
4. INSTALLATION.............................................................................................7
5. SERVICING................................................................................................10
6. RS-485 INTERFACE..................................................................................26
7. TECHNICAL DATA......................................................................................43
8. BEFORE A FAILURE HAS BEEN DECLARED..........................................47
9. EXAMPLES OF NA3 METER PROGRAMMING........................................48
10. ORDERING PROCEDURE........................................................................51
3
4
1. APPLICATION
NA3 series meters with a multicoloured bargraph have an universal input destined
to measure temperature, resistance, voltage from shunts, standard signals, d.c.
voltage and d.c. current.
NA3 meters can optionally have a continuous analogue output, relays, OC type
(Open Collector) and digital RS-485 outputs.
They can find application in various industrial fields, e.g. food industry, intermediate
pumping stations, sewage treatment plants, chemical industry, weather stations,
breweries.
The NA3 meter is made in the version:
with a 4-digit LED readout field (digit height: 7 mm) and a multicolour
bargraph.
The type choice is made in the execution code.
They are programmed by means of the keyboard and through RS-485. Meters only
with the bargraph can be programmed through RS-485.
5
2. SET OF THE NA3 METER
We deliver in the set:
- NA3 meter..................................................... 1 pc.
- user’s guide................................................... 1 pc.
- plug with screw terminals.............................. 1 pc
- holders to fix the indicator in the panel.......... 2 pcs
When unpacking the meter, please check whether the type and execution code
on the data plate correspond to the order.
CAUTION!
Designates a general useful note. If you observe it, handling of the
meter is made easier. One must take note of this when the instrument is
working inconsistently to the expectations.
Possible consequences if disregarded !
In the security scope the NA3 meter meets the requirements of the EEC
Low-Voltage directive (EN 61010 -1 issued by CENELEC).
6
4. INSTALLATION
4.1. Fitting
Prepare a ( 22.2+0.5 x 92+0.5) mm hole in the panel. The thickness of the material from
which the panel is made should be in the range 1...15 mm.
The meter has screw terminal strips which enable the connection of 2.5 mm2 cross-
section external conductors.
Meter dimensions are shown on the fig. 2.
5
24
96 110
max 115
7
Resistance Resistance Thermocouple
thermometer in thermometer in or
two-wire system three-wire system 0... 60 mV voltage
RS-485
RS-485 + 1 relay + 1 OC type output 2 relays
(open collector)
8
A B GND PC Computer
NA3 meter
5 3 GND 2
2 RxD 3 DB9
4
1 TxD 5
3
PD51
2
supply B
1 A
10
9
...
PC Computer
with RS-485 card
NA3 meter
B 6
5 1
A
DB9
4 GND
5
9
3
2
supply
1
9
5. SERVICING
After connecting external signals and switching the meter on, its name
and also the current version of the program, e.g. are displayed.
After ca 3 seconds, the meter is transiting automatically into the working mode
in which it carries out the measurement and the display of the measured value
on the display and the bargraph. Depending on alarm and bargraph parameter
settings, alarm thresholds are also displayed on the bargraph. The meter blanks
automatically insignificant zeros.
0 10 20 30 40 50 60 70 80 90 100
NA3
Escape key
Acceptation
Increasing value key key
Key functions:
- acceptation key
- entry into the programming mode (hold down during ca 3 seconds),
- entry into the chosen parameter level,
- entry into the changing mode of the parameter value,
- acceptation of the changed parameter value.
10
- Key to increase the value
- display of the minimal value (first pressure), maximal (second pressure),
return to measurement (third pressure),
- mowing on the preview menu or programming matrix,
- change of the chosen parameter value - increasing of the value.
- Escape key
- entry into the menu of parameter preview (hold down ca 3 seconds),
- exit from the preview menu or programming matrix,
- escape from the parameter change.
The pressure and hold down the key during 3 seconds causes the entry
into the programming mode. The programming mode is protected by the
safety code.
The pressure and hold down the key during 3 seconds causes the entry
into the preview menu. One must move on the preview menu by means of the
key. In this menu, only all programmed parameters, except servicing
parameters, are accessible to readout. The exit from the preview menu is operated
by means of the key.
In the preview menu, it is also possible to review recorded resl values. The
pressure of the key on the resl parameter causes the entry into the
preview menu of recorded values. The number of the recorded result is displayed
alternately with the value e.g. The moving on recorded values
takes place by means of the key. The hold down of this key longer than ca
2 seconds will cause the acceleration of the review. The pressure of the key
in any time will cause the display of the number of recorded results. The exit from
the review of recorded values is operated by means of the key.
The algorithm of the meter servicing is presented on the fig. 5.
11
12
Fig 5. Servicing algorithm of the NA3 meter.
Incorrectly introduced safety code
The appearance of the following symbols and inscriptions on the display means:
It is possible to change meter parameters:
- from the meter keyboard ...................................................................... - p. 5.1
- through RS-485..................................................................................... - p.6.
13
Item Main menu Parameters of the selected level
14
1
Input Math. Kind of Decim. Measur. Input Param. Param. Param. Param.
type functions compens. points time individ. of ind. of ind. of ind. of ind.
charact. charact. charact. charact. charact.
15
Programmable parameters of NA3 meter Table 1
Symbol
on the Parameter description Range of changes
display
0... 60 mV
Standart signals:
3U - voltage up to 3 V
0U - voltage up to 10 V
nnal - current up to 5 mA
nnaH - current up to 20 mA
High signals:
200U - voltage up to 200 V
600U - voltage up to 600 V
2a - current up to 2 A
5a - current up to 5 A
16
Kind of compensation of sensor auto - automatic compensation
Con working conditions changes: (in case of resistance thermometers and
- In case of a resistance thermometer resistance measurement it requires a
and resistance measurement it 3-wire line.)
concerns the compensation of the
0.0...60.0C - value of the reference
resistance changes of the conductor
temperature for thermocouples.
linking the sensor with the meter,
- In case of a thermocouple it concerns 0.0...40.0 - resistance of two conduc-
the compensation of reference tors for resistance thermometers and
junction temperature changes. resistance measurement.
The automatic compensation does The writing of a value beyond the interval
not operate in case of a resistance of manual compensation will cause the
measurement up to 4 k, Pt1000 automatic compensation switching
and Pt100
decimal point
lower or upper exceeding.
Where:
I_H1 i I_H2 - measured value
d_Y1 i d_Y2 - expec-
ted value on
the display.
Fig.9 shows the way of the individual
17
typb Bargraph type 0neC - „ one colour „ bargraph,
:ntr - „ interval „ bargraph,
sect - „ sector” bargraph,
p:nt - „ point bargraph,
tren -”trend” bargraph.
Fig. 10 explains bargraph types. .
g - green,
rg - red + green
other colours are accessible only in
Bargraph Parameters
18
H_0f - manually switched off. Till
the time of the alarm type change,
the alarm output is being permanently
switched off.
one must give the time in seconds Introduction of 0.0 causes the ope-
after which the alarm will operate after ration at the moment of the alarm
its occurrence. occurrence.
al1 al2 al3
b - blue,
rb - red + blue,
gb - green + blue,
rgb - red + green + blue,
Fig. 10 explains the idea of CurL and
CurH... parameters
19
:nd0 Switching off or on of the individual
linear user’s characteristic - („indivi-
0n - characteristic switched on,
dual characteristic of the analog 0ff - characteristic switched off .
output”). When the characteristic is switched
off, the meter operates at the maximal
range depending on input and range
output.
where:
d_H1 and d_H2 - displayed value
Output parameters
20
set Manufacturer’s parameters.
Manufacturer’s parameters are
The pressure of the key
causes the writing of manufacturer’s
presented in the table 2. parameters.
Clrl Erasing of the minimal value. The pressure of the key causes
the erasing of the minimal value.
ClrH Erasing of the maximal value. The pressure of the key causes
the erasing of the maximal value.
date
Recording parameters
21
Fig. 8. Alarm types: a, b - normal, c - switched off, d - switched on
22
a)
b)
23
Type of Examplary settings of the bargraph and the alarm, ex. 1
Notes
bargraph Curl=G (green)
Curl= r (red) CurH= rG (red + green )
0neC
Value under the
value prl
:ntr Value between
prlandprH
Value over
prH
sect
p:nt
Value without
changes in time
Value decre-
ases
NOTE!
– In case of the meter working with a resistance thermometer in a two-wire system,
the choice of the automatic compensation of conductor resistance changes will
cause a meter defective work.
– The automatic compensation is switched off when choosing Pt1000, Pt500
sensors and at measuring the resistance up to 4 k Connect the signal only in
the two-wire system.
– In case of switching the display individual characteristic on, the result on the
display is lineally converted in accordance with the introduced I_H1, I_H2, d_Y1
and d_Y2 parameters.
– In case of switching the analogue output individual characteristic on, the measu-
rement result is lineally converted in accordance with the introduced d_H1, d_H2,
O_Y1 and O_Y2 parameters.
24
– The meter checks currently the value of the introduced parameter. In case when
the introduced value exceeds the upper or lower change range given in the
table 1, the meter will not make the parameter record.
– In case of the Input type change, a simultaneous change of the decimal point
follows, optimally for the given input.
– After the supply decay, the current time is reset.
– The switching of the record off follows in following cases: switching the record off
from the programming matrix, change of the input kind, change of Go_r , change
of IntE, setting Cnt=0, memory filling up and when the meter is switched to the
network on again.
– In case of the Intr or Sect bargraph type, the setting of Curl and Curh markers
(from one alarm) is possible. The others are automatically erased.
– Max. and min. values are erased in case of following changes: input type,
individual characteristic (on, off), entry of standard parameters.
25
6. RS-485 INTERFACE
NA3 programmable digital meters have a serial link of RS-485 standard to commu-
nicate in computer systems and with other devices fulfilling the master function. The
MODBUS asynchronous character communication protocol has been implemented
on the serial link. The transmission protocol describes information exchange pro-
cedures between devices through the serial link.
26
The configuration of serial link parameters is described in the further part of this ser-
vice manual. It consists on the settlement of the baud rate (Baud parameter), device
address (Adr parameter), and the type of the information unit (Tryb parameter)
Note: Each meter connected to the communication network must:
have a unique address, different from addresses of other devices connected to
the network
the identical baud rate and the type of the information unit.
Note:
In NA3 meters the answer response frame to the function 17 is as follows:
Device Number Device Device Field depending on Check-
Function
address of bytes identifier state the type of device sum
X 11 08 X FF XXXXXX
27
Response:
Check-
Device Number Value from the register Value from the register sum
Function
address of bytes 1DBD (7613) 1DBE (7614) CRC
01 03 08 3F 80 00 00 40 00 00 00 42 8B
Response:
Register Register Check-
Device Value from the register
Function address address sum
address 1DBD (7613)
Hi Lo CRC
01 06 1D BD 3F 80 00 00 85 AD
Request:
Register Number of Check-
Function
Device Number Value for the register Value for the register
address registers sum
address of bytes 1DBD (7613) 1DBE (7614)
Hi Lo Hi Lo CRC
01 10 1D BD 00 02 08 3F 80 00 00 40 00 00 00 03 09
Response:
Register Register Number of Number of Check-
Device
Function address address registers registers sum
address
Hi Lo Hi Lo (CRC)
01 10 1D BD 00 02 D7 80
28
Report identifying devices (code 11h) in RTU mode.
Example: the read-out.of data identifying the device for NA3 meter with a univer-
sal input
Request:
Device Checksum
Function
address (CRC)
01 11 C0 2C
Response:
Device Number Device Device Field depending on Check-
Function
address of bytes identifier state the type of device sum
01 11 08 80 FF 00XXXXX
29
No. of the software
version - software version implemented in the meter
- X X_ _ _ _4 - byte variable of float type
Checksum - 2 bytes in case of work in RTU mode
- 1 byte in case of work in ASCII mode
Example:
Work in RTU mode, e.g.: Mode = RTU 8N2 (value 0x02 in case of readout/record
through the interface).
NA3 meter with an universal input (NA3-XXXU)
Execution with a voltage analogue output: 00,
No. of the software version: 1.00,
Device address set on: Adr = 0 x 01,
30
6.5. Registers for recording and readout
NA3 meter
as 32-bit registers from the
successive 16-bit registers
enclosing the same data
Readout (r)
Writing (w)
Symbol Range Description
7600 area
registers
Channel
7202 7601 w/r 0...1 No occurs
number
7204 7602 Output type w/r 0...20 Input type
Value
0 Pt100 RTD
1 Pt500 RTD
2 Pt1000 RTD
3 J thermocouple
4 K thermocouple
5 N thermocouple
6 E thermocouple
7 R thermocouple
8 S thermocouple
9 T thermocouple
10 R. meas. up to 400
11 R. meas. up to 4 k
12 Volt. meas. 0... 60 mV
13 Volt. meas. 0... 3 V
14 Volt. meas. 0...10 V
15 Current meas. 0... 5 mA
16 Current meas. 0... 20 mA
17 Volt. meas. 0... 200 V
18 Volt. meas. 0... 600 V
19 Current meas. 0...2 A
20 Current meas. 0...5 A
31
7206 7603 LoIn w/r -1999... 9999 No occurs
7208 7604 HiIn w/r -1999... 9999 No occurs
7210 7605 Function w/r 0... 2 Arithmetical function
Value
0 Switched off
1 Squaring
2 Extraction of roots
Value
0 One-colour (OnEC)
1 Change of colour after
exceeding the alarm threshold
(the colour change the whole
bargraph) (Intr)
32
2 Change of colour after
exceeding the alarm threshold
(Three-segment change of
colour) (SEct)
3 One-coloured bargraph, alarm
markers in another colour
(PInt)
4 Increasing/decreasing trend
(trEn)
7232 7616 Colour w/r 0... 7 Bargraph colour
Value
0 Bargraph off (OFF)
1 Red (r)
2 Green (G)
3 Red + Green (rG)
Other values are only accessible in meters
with RGB diodes
4 Blue (b)
5 Red + Blue (rb)
6 Green + blue (Gb)
7 Red + Green + Blue (rGb)
Brl „Magnifier „on the bargraph. Lower
7234 7617 w/r -1999... 9999
threshold
Brh „Magnifier „on the bargraph. Upper
7236 7618 w/r -1999... 9999
threshold
Alarm
7238 7619 number w/r 0... 2 Choice of alarm number
33
7248 7624 Alarm delay w/r 0... 999.9 Alarm delay <Alarm No>
Alarm
7250 7625 support w/r 0... 1 Alarm signalling support <Alarm No>
Value
0 Support switched off
1 Support switched on
Value
0 Characteristic switched off
1 Characteristic switched on
34
7260 7630 X1 LED w/r - 1999... 9999 Parameters of the analogue output
characteristic
7262 7631 Y1 Out w/r - 1999... 9999 Parameters of the analogue output
characteristic
7264 7632 X2 LED w/r - 1999... 9999 Parameters of the analogue output
characteristic
7266 7633 Y2 Out w/r - 1999... 9999 Parameters of the analogue output
characteristic
7268 7634 Baud rate w/r 0... 2 Baud rate of the RS-485 interface
Value
0 2400 bit/s
1 4800 bit/s
2 9600 bit/s
Working
7270 7635 mode w/r 1... 7 Working mode of the MODBUS protocol
Value
1 ASCII 8N1
2 ASCII 7E1
3 ASCII 7O1
4 RTU 8N2
5 RTU 8E2
6 RTU 8O2
7 RTU 8N1
7272 7636 Address w/r 0... 247 Choice of the device address
7274 7637 Test w/r 0... 1 Test of the display
Value
0 Lack of operation
1 Test
7276 7638 Hour w/r 0... 23.5959 Current time
This parameter occurs with four
places after the decimal point in format
gg,mmss, where:
gg - means hours,
mm - means minutes,
ss - means seconds
In case when introducing and incorrect
time, the indicator will correct it auto-
matically.
7278 7639 Recording w/r 0... 1 Registration of measured value
Value
0 Registration switched off
1 Registration switched on
35
7280 7640 Interval w/r 0... 99.5959 Time interval of the recording
Recording
7282 7642 time w/r 0... 23.5959 Time of the recording start
Value
0 Lack of operation
1 Erasing
Erasing of
7292 7646 maximum w/r 0... 1 Erasing of the maximal value
Channel 1
Value
0 Lack of operation
1 Erasing
Erasing of
7294 7647 minimum w/r 0... 1 No occurs
Channel 2
Erasing of
7296 7648 minimum w/r 0... 1 No occurs
Channel 2
36
Year of the
7320 7660 memorised w/r 1970... 2038 Year of memorised value in memory
value
Month of the
7322 7661 memorised w/r 1... 12 Month of memorised value in memory
value
Day of the
7324 7662 memorised w/r 1... 31 Day of memorised value in memory
value
Time of the
7326 7663 memorised w/r 0... 23.5959 Time of memorised value in memory
value
This parameter occurs with four
places after the decimal point in format
gg,mmss, where:
gg - means hours,
mm - means minutes,
ss - means seconds
In case when introducing and incorrect
time, the meter will correct it automa-
tically.
Index of the
7328 7664 memorised w/r 1... 750 Number of memorised value in memory
value
7230 7665 Status w/r 0... 8 Operation status on the buffer
Value
0 Lack of operation
1 Searching acc. date and time
(registers nr 7660...7663 and
7320...7326)
2 Searching acc. time (registers
nr 7663 and 7326)
3 Searching acc. index (registers
nr 7664 and 7328)
4 Load next values into the buffer
(registers7672...7691and
7344...7382)
5 Load previous values into the
buffer (registers7672...7691
and 7344...7382)
6 Go to the first memorised value
in memory.
37
7 Go to the last memorised value
in memory.
8 Erase the memory
Number of
7332 7666 the memori- r 0... 750 Number of memorised value in memory,
sed value placed in the first buffer register
Value
0 Memory is empty
1... 750 Number of the memorised
value
Number of
7334 7667 recorded r 0... 750 Number of recorded buffer registers
registers
Value
0 Buffer is empty
1... 750 Number of recorded registers
7336 7668 Year r 1970... 2038 Year for the value in the first register
7338 7669 Month r 1... 12 Month for the value in the first register
7340 7670 Day r 1... 31 Day for the value in the first register
7342 7671 Time r 0... 23.5959 Time for the value in the first register
This parameter occurs with four places
after the decimal point in format gg,mmss,
where:
gg - means hours,
mm - means minutes,
ss - means seconds
7672... Buffer Memorised values, read out from the
7344...7382 r –
7691 memory
20 registers , including 20 memorised
values.
1) In case of registers not occurring in the given meter series, their value
38
6.6. Registers only for readout
NA3 meter
successive 16-bite registers.
The value is placed into two
Readout (r)
Writing (w)
from the area 7500.
1) In case of registers no occurring in the given meter series, their values is 1E+20
Note !
– At the moment of exceeding the upper or lower range, „displayed value”, „mini-
mum”, „maximum” parameters are set on the value 1E+20.
– For the parameter Cnt=0 (Measurement switching off and display of the
current time), „minimum”, „maximum” and „displayed value” parameters are set
on the value 1E+20.
39
Description of the Status 1 register
X X X X X X X X X X X X X X X X
bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
MSB LSB
0 - Lack of error
1 - Signalling of compensation error
Bit-7...5 Position of the decimal point
000 - lack
001 - 000.0
010 - 00.00
011 - 0.000
100 - Auto
Bit-4 Signalling of the upper range exceeding
0 - normal work
1 - range exceeding
Bit-3 Signalling of the lower range exceeding
0 - normal work
1 - range exceeding
Bit-2 Individual characteristic
40
0 - individual characteristic switched off
1 - individual characteristic switched on
Bit-1...0 Kind of output (voltage, current)
00 - lack of analogue output
01 - current
10 - voltage
Bit-15. No used
Alarm 3 state
Alarm 2 state
Alarm 1 state
Working
Baud rate
mode and
information
unit
X X X X X X X X X X X X X X X X
bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
MSB LSB
41
1 - on
Bit-5 State of alarm 1
0 - off
1 - on
Bit-4...2 Working mode and information unit
000 - interface switched off
001 - 8N1 - ASCII
010 - 7E1 - ASCII
011 - 7O1 - ASCII
100 - 8N2 - RTU
101 - 8E1 - RTU
110 - 8O1 - RTU
111 - 8N1 - RTU
Bit-1...0 Baud rate
00 - 2400 bit/s
01 - 4800 bit/s
10 - 9600 bit/s
42
7. TECHNICAL DATA
INPUTS:
NA3-XXXU
Range
Input resistance:
- for voltage inputs > 4 M
- for inputs (5 mA and 20 mA) <4
- for inputs (2 A and 5 A) 10 m 10%
Intensity of current flowing through the resistance thermometer: < 170 A
Resistance of conductors linking the resistance thermometer with the meter:
< 20 /1 wire
Thermocouple characteristics acc. EN 60584-1.
Resistance thermometer characteristics acc. IEC 751 + A1+A2.
43
OUTPUTS:
– Analogue output galvanically isolated, with a resolution = 0,025% of the
range
- current programmable: 0/4..20mA load resistance 500
- or voltage programmable: 0..10V load resistance 500
- output response time 100 ms
- output error 0.2 % of the range
- additional error due to ambient
temperature changes: (0.1% of the range /10K)
– Relay output
Relays (1 or 2); voltageless make contacts - maximal load:
voltage 250 V a.c., 150 V d.c.,
current 5 A 30 V d.c., 250 V a.c.,
resistance load 1250 VA, 150 W.
Programmable alarm thresholds;
Three types of alarms;
Hysteresis defined by means of the lower and upper alarm threshold;
Signalling of alarm operation on the bargraph or by means of alarm diodes.
– Digital output:
interface: RS-485,
transmission protocol: MODBUS,
ASCII: 8N1, 7E1, 7O1,
RTU: 8N2, 8E1, 8O1, 8N1,
baud rate: 2400, 4800, 9600 baud
maximal response time to the
request frame: 300 ms.
Memory parameters:
- meter memory (record) 750 samples
- min. record interval 1 sec;
Basic error: 0.2% 1 digit
44
Additional errors in nominal working conditions when measuring the
temperature:
- compensation of reference junction
temperature changes 0.2 % of range
- compensation of wire resistance
changes 0.2 % of range
Additional error from ambient
temperature changes (0.1 % of range/10K)
Averaging time min 500 ms, temperature measurement
min 200 ms, other ranges
Rated operation conditions:
- supply voltage depending on the
execution code 95...230...253 V a.c./d.c.
20...24...40 V a.c./d.c.
- supply a.c. voltage frequency 40...50/60...440 Hz
- ambient temperature - 10...23...55C
- storage temperature - 25...+85C
- relative humidity < 95% (no condensation)
- time of preliminary indicator heating 10 min
Sustained overload:
- thermocouples, resistance
thermometers 1%
- measurement of voltage, current
and resistance 10 %
Momentary overload (3 s):
- sensor inputs and voltage 60 mV 30 V
- voltage input >= 3 V 10 Un (< 1000 V)
- current input 10 In
Readout field (depending on execution): 4 seven-segment LED display,
NA3-F digit height: 7 mm
indication range: -1999...9999
bargraph length: 82 mm
- 45 segments in three-colour execution
- 25 segments in seven-colour
execution
45
Bargraph resolution programmable
Bargraph accuracy 0.5 segment
Servicing: three keys:
Ensured protection degree (EN 60529):
- through the casing IP 40
- from terminal side IP 20
Dimensions: 96 x 24 x 125 mm (with terminals)
Weight: < 0.3 kg
Power consumption < 8 VA
Resistance against supply decay acc. EN 61000-6-2:2002
Electromagnetic compatibility:
- immunity EN 61000-6-2:2002
- emission EN 61000-6-4:2002
- additional error from
electromagnetic risks < 0.5%
Safety requirements according EN 61010-1:
- installation category III
- pollution degree 2
- phase-to-earth max. working voltage:
input 600 V
supply 300 V
relays 300 V
analogue output 50 V
RS-485 50 V
46
8. BEFORE A FAILURE WILL BE DECLARED
In case of incorrect symptoms please to acquaint with the table below.
SYMPTOMS PROCEDURE
1. Lack of indications on the display. The Check the connection of the feeder cable.
bargraph indicates nothing.
2. The time is displayed on the display, The number of measurements Cnt = 0 has been
e.g. H_12 alternately with 34:43. introduced. The meter is working in the SLEEP
mode. It displays the current hour.
Check the correctness of the input signal connec-
3. Marks or tion. See the service manual. Check also the setting
are displayed on the display. of parameters D_P and Ind.
4. A signal inconsistent with our expec- One must check if the load resistance of the ana-
tations occurs on the meter analogue logue output is in accordance with technical data.
output. Check if the individual characteristic is not switched
on. In case of necessity make changes of individual
characteristic parameters or introduce manufacturer
parameters Set.
5. Lack of possibility to enter into the The programming mode is protected by a password.
programming mode. The inscription When the user forgets which password has been
Err is displayed. introduced, he should contact by phone the manu-
facturer or the nearest authorised workshop.
6. Lack of certainty if all segments of the Enter into the programming matrix and switch the
display or bargraph are efficient. display and bargraph tSt test on.
Character fields are lighted successively from 0000
to 9999. In the same time the bargraph is lighted
with successive colours. If some of segments are not
lighted or diodes have different colours, one must
submit these defects to the nearest workshop.
7. During the operation in the pro- Enter into the programming matrix and accept the
gramming mode, parameter values SEt parameter. The meter will introduce values in
inconsistent with the range of changes accordance with the table 2.
given in the table 1, appear on the
display.
47
8. A result inconsistent with our expecta- Check if the individual characteristic is not switched
tions appears on the display. on. In case of necessity enter into the programming
matrix and accept the SEt parameter. The meter will
introduce parameters in accordance with the table 2.
9. The bargraph does not work in accor- Check bargraph parameters. In case of a further
dance with our expectations. incorrect operation, enter into the programming
matrix and accept the parameter SEt.
Switch the display and bargraph tSt test on.
10. Despite the exceeding of the alarm Check the delay of alarm operation introduced into
threshold the alarm relay does not the meter. In case of need, correct dLY parameters.
switch on.
11. The meter, instead of displaying the The meter is working in the preview mode or in the
measurement result, displays the programming mode. Press the escape key .
parameter symbol and its value.
12. Despite of the introduced delay in the The lasting alarm state was shorter than the
alarm operation, e.g. 30 seconds, the programmed, that means that during the lasting time,
alarm after this time did not operate. the alarm withdrawal state occurred. In such a case,
the meter begins to count down the time from the
beginning.
13. The meter does not establish the Check if interface conductors (A, B, GND) were
communication with the computer correctly connected. Then, check in the program-
through the RS-485 interface. ming matrix the setting of the interface (bAud, trYb,
Adr). These parameters must be the same as in the
used software.
48
transit on the I_H2 parameter and introduce the value 20.00
transit on the d_Y2 parameter and introduce the value 100
49
Example 5 Programming of an analogue output
If we want to programme so that to the displayed value 0.00 mA for the channel
2 will correspond the value 4.00 on the analogue output, whereas to the value
20.00 mA , the value 20.00 mA, one must:
enter into the programming mode, choose the IndO parameter and switch the
individual characteristic On
choose the d_H1 parameter and introduce the value 0.00
transit on the O_Y1 parameter and introduce the value 4.00
transit on the d_H2 parameter and introduce the value 20.00
transit on the O_Y2 parameter and introduce the value 20.00
50
10. ORDERING PROCEDURE
Execution codes of NA3 meter (seeTable 5).
Table 5.
NA3 - X X X X X X X X XX X
Meter version:
with a bargraph and F
digital display
Bargraph colour:
3-colour (R, G, R+G) T
7-colour (R, G, B,
M
R+G, R+B, G+B, R+G+B)
Display colour:
red R
green G
Input signal:
universal input U
Analog output:
lack 0
0/4...20 mA 1
0...10 V 2
Additional output:
lack 0
RS-485 digital output + 1 relay 1
RS-485 digital output + 1 output of OC type 2
2 relays 3
2 outputs of OC type 4
Supply voltage:
95...253 V a.c./d.c. 1
20...40 V a.c./d.c. 2
on order* X
Kind of terminals:
screwed plug-in sockets 0
Version:
standard 00
custom-made* XX
Acceptance tests:
without extra requirements 8
with an extra quality inspection certificate 7
*after agreeing with the manufacturer
acc. to customer’s request X
51
Ordering example:
The code: NA3 - F T R U 0 1 1 0 00 8 means:
NA3 - meter of NA3 type
F - with bargraph and digital display
T - 3-colour display
R - red display colour
U - universal input
0 - lack of analog output
1 - additional outpout : RS-485 + 1 relay
1 - supply voltage: 95...253 V a.c./d.c
0 - screwed plug-in socket
00 - standard version
0 - without extra requirements
52
53
54
55
LUMEL S.A.
ul. Sulechowska 1, 65-022 Zielona Góra, POLAND
tel.: +48 68 45 75 100, fax +48 68 45 75 508
www.lumel.com.pl
Export department:
tel.: (+48 68) 45 75 139, 45 75 233, 45 75 321, 45 75 386
NA3-09A/2
56