Earthing Transformer: Engineering Department

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

EARTHING

TRANSFORMER

December 2017

Engineering Department

WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Regd. Office: VidyutBhawan, Block – DJ, Sector-II, Bidhannagar, Kolkata – 700091.


CIN: U40101WB2007SGC113474; Website: www.wbsetcl.in

WBSETCL / TECH SPEC/ Rev.-3 Page 1 of 12 Earthing Transformer


Technical Specification of Earthing Transformer

1. SCOPE :

This specification is intended to cover the design, engineering, manufacture, testing at


manufacturer’s works of 3 ph, Copper wound, oil immersed 33KV Earthing transformers for
efficient and trouble free operation as specified herein. The neutral of the earthing
transformer shall be solidly earthed to provide earthed neutral in the 33 KV systems. The
Earthing Transformer shall have impedance to restrict earth fault current.

The earthing transformer covered by this specification shall be complete in all respect. Any
material or accessories which may not specifically mentioned here but which is usual and
necessary for satisfactory and trouble free operation and maintenance of the transformer
shall be supplied without any extra charge.

2. STANDARDS :

The equipment to be furnished under this specification, shall unless otherwise stated, be
designed, constructed and tested in accordance with the latest revisions of the following Indian
Standards:

IS:3151 Specification for Earthing Transformer

IS 2026 Specification for Power Transformer

IS 2099 Bushing for alternating voltage above 1000V.

IS 6600 Guide for loading of oil immersed transformer

IS 335 Specification of new insulating oil

OTHERS CBIP Manual on Transformers

3. I) DEVIATION :

Normally the offer should be as per Technical Specification without any deviation.

II) MODIFICATION :

If any modification felt necessary to improve performance, efficiency and utility of equipment,
the same must be mentioned in the 'Modification schedule' with reasons duly supported by
documentary evidences and advantages. Such modifications suggested may or may not be
accepted, but the same must be submitted along with Pre-Bid Queries. The modifications not
mentioned in Schedule will not be considered.

WBSETCL / TECH SPEC/ Rev.-3 Page 2 of 12 Earthing Transformer


4. BRIEF DESCRIPTION OF THE TRANSFORMER :

(a) 33KV Earthing Transformer, ONAN Cooled, 3 ph, oil-immersed, class A insulated, fitted with
outdoor type bushings on HV side. Neutral of HV bushings shall be earthed for non-
effectively earthed 33 KV system. Earthing transformer shall consist of a single winding in
which case this winding shall be connected inter-star (zigzag) in accordance with the
relevant IS group.
(b) INTERPHASE CONNECTION:HV :Inter-star (Zigzag) with neutral brought out through
Bushing for solid earth connection.

5. GENERAL DESIGN CRITERIA :

(a) The transformer will be installed at outdoor. All equipment accessories and wiring shall be
provided with tropical finish to prevent fungus growth.
(b) If not specifically mentioned in BOQ, the transformer shall be capable of withstanding a fault
current of 874 Amps at rated voltage and frequency through the neutral for a time duration
of 30 seconds without using neutral grounding resistor and without exceeding the
temperature of 250 0 C for copper.
(c) The earthing transformer shall be capable of withstanding the mechanical and thermal
stresses caused by the rated short time current flowing in the windings under fault
conditions.This shall be determined by tests as per relevant IS and the results furnished
along with the bid.
(d) The maximum flux density in any part of the core and yokes, at normal voltage and
frequency of each transformer shall be consistent with the material used. The maximum flux
density shall be 1.7 Tesla.
(e) The thermal ability to withstand short circuit shall be proved by calculation and shall be
furnished along with the drawings.
(f) The transformer shall be free from annoying hum or vibration. The design shall be such as
not to cause undesirable interference with radio or communication circuit.
(g) TYPE & RATING :
i) The Earthing Transformer shall be of 33 KV, 3-phase, 50 c/s Copper wound, oil-
immersed, interconnected Star (Zig-Zag) winding. The earthing transformer shall have
100% impedance to allow rated fault current at rated system voltage in the event of
occurrence of a solid single phase to ground fault. The fault MVA rating of the earthing
transformer shall be 50 MVA for duration of 30 seconds, if not specifically mentioned in
BOQ.

ii) The rating and other guaranteed particulars of the earthing transformer shall be
as per specific technical parameters of this specification, submitted G.T.P. and
relevant ISS.

6. TERMINAL BUSHING :

The terminals shall be brought out through outdoor type bushings on HV side conforming to IS:
2099 and provided with suitable Bi-metallic terminal connectors for suitable dia. ACSR
conductors for phases and suitable size copper flat for neutral.
The bushing shall have high factors of safety against leakage to ground and shall be so located
as to provide adequate electrical clearances between bushings and grounded parts. Bushings of
identical voltage rating shall be interchangeable. All bushings shall be equipped with suitable
terminals of approved type and size. The insulation class of the high voltage neutral bushing
shall be properly coordinated with the insulation class of the neutral of the high voltage winding.

WBSETCL / TECH SPEC/ Rev.-3 Page 3 of 12 Earthing Transformer


Each bushing shall be so coordinated with the transformer insulation that all flash-over will occur
outside the tank.
All porcelain used in bushings shall be homogeneous and free from cavities or other flaws. The
glazing shall be uniform in colour and free from blisters, burns and other defects.
All bushings shall be porcelain shed type. The neutral bushings shall be insulated for 33 KV.
Bushings shall conform to IS: 3347, IS: 2099 and IEC: 137. Main terminals shall be solder less.
The spacing between the bushings must be adequate to prevent flashover between phases
under all conditions of operation.
All bushings shall be suitable for heavily polluted atmosphere.

7. CORE :

i) The material circuit of the earthing transformer shall be constructed from high quality,
low loss and high permeability cold rolled grain oriented silicon steel laminations
especially suitable for transformer core.
ii) The prime core materials are only to be used. Bidders should furnish following
document as applicable as a proof towards use of prime Core material to be submitted
before the stage inspection :
 Invoice of supplier
 Mill’s test certificate
 Packing List
 Bill of landing
 Bill of entry certificate by Custom.
 Description of material, electrical analysis, physical inspection, certificate for
surface defects, thickness and width of the materials

iii) All transformers shall be subjected to routine test and no load loss measurement as per
relevant IS as mentioned in the Clause “: TEST AT FACTORY AND TEST REPORTS”.
iv) Core materials should be directly procured from either the manufacturer or their
accredited marketing organisation of repute and not through any agent.
v) Inter-laminar insulation shall be coated over laminations during manufacturing process.
vi) The legs and yokes of cores shall have similar section to minimise heating and noise.
Necessary cooling ducts shall be provided for heat dissipation.
vii) The whole core shall be electrically connected by copper strip of not less than 6.25
sq.mm cross section to the tank inside for being earthed to drain off any electrostatic
potential that may build up.
viii) Each core bolt and part of the core clamping frame work shall be insulated from the core
lamination. The core shall be tested to withstand a voltage of 2500 volts AC for a
duration of one minute.
ix) Only No-load losses are to be specified. The tolerance on specified No-load losses will be
subject to limits specified in IS:2026. Transformer losses shall be taken into account
during tender evaluation. Capitalization of losses at rated voltage & frequency shall be
guaranteed with tolerance limit as specified in IS:2026.
x) Capitalization value of iron loss per KW-Rs. Rs. 4,95,943/-.
xi) If losses after test are found beyond the guaranteed value declared in the bid offer with
tolerance limits then penalty will be imposed for the excess losses for the corresponding
guaranteed value by applying the above stated values. For fraction of a KW, the penalty
shall be applied pro-rata, but no bonus will be applied or vice-versa. No changes in
guaranteed figure will be allowed after tender opening.

WBSETCL / TECH SPEC/ Rev.-3 Page 4 of 12 Earthing Transformer


8. WINDING :

Earthing Transformer with single inter-star connected windings shall consist of two distinct
sections, each representing one half of each inter-star winding and shall be rated for one-
third of the line voltage.

The winding shall be made of paper insulated continuous and smooth electrolytic copper
conductor and shall be so designed that all the coil assemblies of identical voltage rating shall
be interchangeable and field repairs to the winding can be made without special equipment.
The insulation of the coils and assembly of windings shall be insoluble, non-catalytic,
chemically inactive in the hot transformer oil & shall not be adversely affected under the
operating conditions.

The insulation of the windings shall withstand the impulse and power frequency test voltages
as specified in technical parameters.

Windings shall be designed to withstand the Electromechanical stresses exerted during the
short circuit conditions as per IS:2026.

Liberal ducts shall be provided for oil circulation and prevention of any hot spot
temperature in the winding that may affect the life of the transformers. All leads and
connections shall be mechanically strong, heavily insulated and rigidly clamped, so as to
withstand stresses due to terminal short circuit.

9. TANK :

Tank shall be of welded construction and fabricated from good quality sheet steel of
adequate thickness. The thickness of top, bottom and side plates shall be stated by the bidder.
The tank shall be so shaped as to reduce welding to a minimum. All seams shall be double
welded for absolute oil tightness.

Bushing turret covers, access-holes covers, pockets of thermometer shall be so


designed to prevent any ingress of water. The conservator shall be liberally dimensioned so
that oil level remains above the bushing top at the lowest ambient temperature and no-load,
and the oil shall not spill into the breather pipe, or the exterior as waste. The conservator shall
be provided with a window type oil gauge. The tank shall withstand specified pressure and
vacuum tests without any deformation in excess of the permissible deflections.

10. INSULATING OIL :

The transformer oil shall be duly filled in with required quantity for first filling and to
supply 10% extra . The oil shall conform to IS:335. The transformer should be filled in with
oil having dielectric strength 60 KV (rms) minimum after filtration .The oil in the transformer
being supplied shall be provided with test result conforming to IS:335.

11. COOLING EQUIPMENTS :

Transformer shall be suitable for 100% continuous maximum current rating with ONAN
Cooling within the specified maximum temperature rise of 50 oC by oil & 55oC rise by winding .
The transformer if required, shall be fitted with radiators of tubular construction. Thickness of
radiator tubes should not be less than 2.5 mm and material should be mild steel.

WBSETCL / TECH SPEC/ Rev.-3 Page 5 of 12 Earthing Transformer


12. CURRENT TRANSFORMER FOR E/F PROTECTION

Outdoor type current transformer conforming to IS-2705 having ratio 200-100/1A (11KV class)
& 1000-800/1A (33KV class) (if not specifically mentioned) of PS class shall be provided by the
manufacturer for 33 KV neutral bushing.

13. FITTINGS & ACCESSORIES :

The Earthing Transformer shall be complete with necessary fittings and accessories, but not
limited to the following:

i) Conservator with filling hole, cap and drain valve having flanged terminal.
ii) Conservator and supporting bracket for mounting on transformer tank.
iii) Isolation valve for the conservator.
iv) Magnetic oil level gauge with low oil level alarm contacts.
v) Silica gel breather with oil seal and connecting pipe for non-inert gas
sealed transformer .
vi) Pressure relief pipe, double diaphragm type, complete with port-hole type oil
gauge for indication of the puncture of lower diaphragm and necessary air
equalizer connection between the conservator and the pressure relief pipe.
vii) Access holes/Inspection holes with bolted covers for access to inner ends of
bushing.
viii) Lifting eyes for cover, core and winding and lifting lugs for the complete
transformer.
ix) Air release plugs on top of cover and bushing turrets.
x) Upper & Bottom filter valve and Drain valve flanged with oil sampling device.
xi) Jacking pads with hauling holes.
xii) Flat roller wheels.
xiii) Two nos. tank earthing terminal.
xiv) Buchholz (gas) relay, double float type with one set of alarm contacts and one
set of trip contacts and a testing cock. The contacts shall be wired up to terminal
cabinet with insulted cables.
xv) Dial type thermometer for oil temperature indication complete with two sets of
alarm and trip contact.
xvi) Pocket for inserting alcohol thermometer for oil temperature with necessary
thermometer.
xvii) Rating plate and Diagram plate.
xviii) Rigid type terminal connectors on the HV bushing.
xix) Insulating oil required for first filling.
xx) Other attachment/accessories required to complete the equipment for
satisfactory operation.

14. PAINTING :

All steel surfaces shall be cleaned by sand blasting or chemical process as required to produce
a smooth surface, free of scale, grease and rust. Steel surface in contact with insulating oil shall
be painted with heat resistant oil insoluble insulating varnish. External surfaces shall be given
a coat of high quality red or yellow chromate primer and finished with gray colour (IS:631)
with two coats of synthetic enamel paints. Paints shall be carefully selected to withstand tropical
heat, rain etc. The paint shall not scale off or crinkle or be removed by abrasion due to normal
handling. Sufficient quantity of touch up paint shall be furnished by application at site.

WBSETCL / TECH SPEC/ Rev.-3 Page 6 of 12 Earthing Transformer


15. AUXILIARY SUPPLY :

The auxiliary supply available for the equipment are :

i) 220 V D.C±10% .
ii)400 V ± 10%, 3 phase , 4 wire , 50 c/s AC.

16. EQUIPMENT FOUNDATION AND STEEL STRUCTURE :

i) The earthing transformers shall be furnished complete with base frame, anchor/
foundation bolts and hardwares
ii) The equipment shall be designed for mounting on concrete base.

17. CONTRACT DRAWINGS AND MANUALS :

In the event of placement of P.O. six (6) copies of following drawings, GTP & leaflets
shall be furnished for approval :

(a) Dimensional general arrangement drawing transformer showing constructional features


and dispositions of various fittings and accessories.
(b) Technical leaflets on transformer and accessories explaining the functions and special
features.
(c) Type test certificates on similar transformers.
(d) Transport/shipping dimensions with weights.
(e) Dimensional general arrangement and sectional view with plan and elevation of bushing
with technical parameters.
(f) Foundation and anchor details including dead-load and impact load with direction.
(g) Assembly drawing for erection at site with part numbers and schedule of materials.
(h) Electrical schematic and wiring diagram.
(i) Any other relevant drawings and data necessary for erection, operation and maintenance.
(j) Instruction manuals and data sheets for each piece of equipment. The manuals shall
clearly indicate the installation methods, checkups and tests to be carried out for covering
the equipment and maintenance procedure.
(k) Rating and diagram plate of the transformer.

After approval four (4) sets of approved drawings and maintenance manual/catalogue of all
equipment both in hard and soft copy shall be submitted for our record and distribution to site.

18. TEST AT FACTORY AND TEST REPORTS :

All routine tests are to be carried out on each transformer as per relevant IS. Those routine test
reports are to be submitted along with inspection offer.
After completion of the manufacture, the following routine tests shall be carried out at
manufacturer’s works on each Transformer in presence of representative from WBSETCL. The
contractor shall give at least 15 (fifteen) days advance notice intimating the actual date of
inspection and details of all tests that are to be carried out.

WBSETCL / TECH SPEC/ Rev.-3 Page 7 of 12 Earthing Transformer


i) Measurement of Zero-sequence impedance
ii) Measurement of no-load loss and no load current.
iii) Measurement of winding resistance.
iv) Measurement of insulation resistance.
v) Induced voltage withstand test.
vi) Separate source voltage withstand test.

Any other test not specified above but required to be carried out as per relevant IS & IEC shall
be within the scope of contractor.

Rejection and retesting shall be guided by relevant IS.

Porcelain bushing, Bushing current transformers, winding temperature indicating device, Dial
Thermometers, Buchholz relays, Insulating oil and other accessories to be supplied by the
manufacturer shall be tested by the manufacturer in accordance with the relevant I.S.
Publication. Three (3) copies of test reports of each of the component shall be furnished along
with the test certificate of the main equipment.

19. GUARANTEE :

Electrical characteristics shall be guaranteed by the bidder. In case of failure of materials to


meet the guarantee, WBSETCL shall have right to reject the material. Guaranteed Technical
Particulars are to be submitted by successful bidder during detailed engineering along with
submitted drawings/documents. However format for submission of GTP shall be handed over to
intending bidders at the time of sale of tender documents.

20. TEST REPORTS & TYPE TESTS :

Only type tested Earthing transformer are to be offered conforming to our technical
specification, and relevant IS and IEC. Earthing transformer offered should be similar with ones
on which type testing has been carried out as per relevant IS and IEC. Three sets of complete
type test reports carried out in Govt. recognized Test House or Laboratory /NABL accreditated
laboratory shall have to be submitted by successful bidder positively along with submission of
drawing during detail engineering.

Successful Bidder may require producing original copies of type test report at the time of detail
engineering if asked by WBSETCL.

Each type test report shall comply the following information with test result

a. Compete identification, date and serial number.


b. Method of application, Where applied, duration and interpretation of each test.
c. Relevant drawings as documented with test report.

WBSETCL / TECH SPEC/ Rev.-3 Page 8 of 12 Earthing Transformer


SPECIFIC TECHNICAL PARAMETERS

SNO DESCRIPTION TECHNICAL PARAMETERS


i) Service Outdoor

ii) Type 33KV, 50Hz., Oil filled, Copper wound


natural air cooled (ONAN), 3ph, Earthing
transformer, CLASS-A insulation for winding.

iii) Zero sequence Impedance (Ohm) per As per design


phase. (tolerance +20%, - 0%)

iv) Maximum permissible neutral current for 874 or as specified in BOQ


single phase to ground fault (amps) for 30
secs.

v) Basic Insulation level


(a) Winding 170 KVp
(b) Bushing 170 KVp

vi) Power frequency withstand voltage


Dry one minute
(i) HV Winding 70 KV (rms.)
(ii) HV Bushing 70 KV (rms.)

vii) Temperature rise over ambient (500C) for


continuous rating
(a) Winding, by resistance 550C
(b) Oil by thermometer 500C
(c) Core As permitted by adjacent winding

viii) Flux density 17000 Lines/sq.cm (max.). In the event of


over voltage to the extent of 12.5%, the
core shall not get saturated

ix) Whether uniformly insulated or graded Uniformly Insulated

WBSETCL / TECH SPEC/ Rev.-3 Page 9 of 12 Earthing Transformer


GUARANTEED TECHNICAL PARTICULARS FOR 33KV EARTHING TRANSFORMER

(To be filled in and signed by the Bidder)

1. Name of the Manufacturer and Address :

2. Type and Designation :

3. Conforming Standard :

4. Continuous Maximum Rating (KVA) :

5. Vector Group :

6. Rated temperature rise over specified average


ambient (50oC air) at rated output :

a) Of oil by thermometer (oC) :

b) of winding by resistance (oC) :

7. No load voltage ratio :

8. Exciting current referred to H.V. and


50 C/S at :

a) 90% rated voltage (Amps.) :

b) 100% rated voltage (Amps.) :

c) 110% rated voltage (Amps.) :

9. Power factor for excitation current at


100% rated voltage , 50 C/S :

10. Iron losses at 50 C/S and :

a) 90% rated voltage (KW) :

b) 100% rated voltage (KW) :

c) 110% rated voltage (KW) :

11. Copper losses (at 750C) (KW) :

12. Total losses (KW) :

WBSETCL / TECH SPEC/ Rev.-3 Page 10 of 12 Earthing Transformer


13. Reactance voltage (at 75oC) at full load :

a) HV (%) :

b) LV (%) :
(All values shall be referred to rated KVA)

14. Impedance voltage (at 75oC) at full load

a) HV (%) :

b) LV (%) :
(All values shall be referred to rated KVA)

15. Resistance per phase (at 20oC)

a) HV (Ohm) :

b) LV (Ohm) :

16. Zero sequence Impedence (Ohm) per phase :

17. Maximum permissible neutral current for


single phase to ground fault (amps) for
30 seconds :

18. 1.2/50 micro second Impulse withstand


voltage (KVp) :

a) Winding :

b) Bushing :

19. 1 min. Power frequency withstand voltage


on Bushing (KVrms) :

a) Dry :

b) Wet :

20. Core :

a) Material & grade :

b) Thickness of stampings :

c) Type :

d) Flux density in the core at rated

WBSETCL / TECH SPEC/ Rev.-3 Page 11 of 12 Earthing Transformer


Voltage and 50 Hz. :

e) Flux density at 110 percent voltage


and 50 Hz. :

21. 1 min. Power frequency withstand


voltage (Dry) on winding (KVrms) :

22. Untanking height of core and coils (mm) :

23. a) Weight in Kg of the following :

i) Transformer in oil :

ii) Core & coils :

iii) Tank and fittings :

iv) Oil :

v) Shipping weight of heaviest package :

b) Quantity of oil in litres :

24. Dimensions of the Transformer (mm) :

a) Length :

b) Width :

c) Height from plinth level :

25. Width of Rail gauge suitable :


for rollers of Tr.

26. Whether the similar equipment is type tested :


compliance to the technical specification
(Yes/No). If Yes, furnish details.

27. Confirm compliance to specification w.r.t.


i) Transformer Oil (Yes/No) :
ii) Bushings (Yes/No) :

WBSETCL / TECH SPEC/ Rev.-3 Page 12 of 12 Earthing Transformer