Hitachi TroubleshootingGuide
Hitachi TroubleshootingGuide
Hitachi TroubleshootingGuide
May 2011
INITIAL TROUBLESHOOTING FLOW CHART
Does the timer lamp on the indoor unit blink? See IDU Fault Chart.
No Yes
Set to room temperature 16°C in cooling Remove the terminal cover and check the voltage
mode or to 32°C in heating mode, and between terminal (C) and terminal (D)
press the start/stop button. Does the
operation lamp on the indoor unit start to
light or blink?
Yes No
Terminal C Terminal D
Press temp switch on (+35V) (0V)
IDU. Does lamp blink? No
Yes
Yes No
No Yes
No
See ODU Fault Chart.
Check the refrigerating cycle. Check outdoor electrical parts. Check indoor electrical parts.
2
IDU FAULT CHART
TIMER LAMP DETAILS MAIN CHECK POINT
1. Heat exchanger thermistor disconnected. (Heating Mode only)
2. Reversing valve coil defective
Reversing valve defective 3. Reversing valve jammed
(Read every 3 mins - requires 3 consecutive trips)
1 time
Outdoor unit forced operation Activation of service / Test run switch on ODU
2 times
1. Communication Wire
2. Outdoor PCB
Communication Error 3. Indoor PCB
3 times
4 times
1. IDU Room temperature thermistor
2. IDU Heat exchanger thermistor
Thermistor fault
9 times
When over current is detected at the DC fan motor of the indoor unit
1. Fan motor locked / faulty
Indoor fan fault 2. Indoor PCB faulty
10 times
Program data corruped or lost (possible power spike)
1. Power reset
Data reading error 2. Change main PCB
13 times
NOTE:
If the communication circuit is faulty when power is supplied, the self-diagnosis will not display.
If the indoor unit does not operate at all check the connecting cable to the outdoor unit.
LEGEND
OFF ON FLASHING
3
ODU FAULT CHART
ODU FAULT CHART
SELF DIAGNOSIS
LD301
LD302
LD303
DETAIL MAIN CHECK POINT
NAME
DURING OPERATION
DURING STOP
Stopped by thermistor or
Normal Stop No malfunction
controller.
1. Re-try operation
Microprocessor rebooted
Reset stop 2. Power P.W.B
(Normal after power reset)
3. Main P.W.B.
1 time
1. Power P.C.B.
Compressor current draw
Peak current cut 2. Main P.W.B.
beyond maximum limit.
3. Compressor
2 times
2. Main P.W.B.
rotation not detected.
3. Compressor
3 times
4
1. Leak of refrigerant
Compressor Acceleration Compressor not acelerating 2. Power P.C.B. fault
failure more than min. speed. 3. Compressor fault
8 times
1. C, D cable reversed
installation
No communication between
Communication Error 2. Cable disconnected
indoor and outdoor units
3. Outdoor P.C.B.
9 times 4. Indoor P.C.B.
1. Reactor
Inverter active circuit
PAM active converter defective 2. Power P.C.B.
abnormal
3. Main P.W.B
15 times
NOTE:
Do not disconnect anything until smoothing capacitors discharged.
5
ODU SELF CHECK MODE
When ODU fault lamp blinks 2,3,4,5,14 and 15 times, follow the below to determine
whether the PCB’s or compressor are faulty.
6
TEST RUN MODE
(In some cases operation will only start after 1 minute after pressing the TEST SWITCH due to
initializing of the expansion valve.)
Press the test switch again for about 1 second or more to stop the test run operation.
NB: Can also be used to pump unit down if appropriate valves are closed.