AERCO Boiler Benchmark 3.0
AERCO Boiler Benchmark 3.0
AERCO Boiler Benchmark 3.0
No.
GF-116
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
Installation, Operation
& Maintenance Instructions
Benchmark 3.0LN
Series
Gas Fired
Low NOx
Boiler System
Condensing, Modulating
Forced Draft, Hot Water Boiler
3,000,000 BTU/H Input
1-800-526-0288
FOREWORD A
i
CONTENTS
ii
CONTENTS
APPENDICES
WARRANTIES W-1
iii
FOREWORD
Foreword
The AERCO Benchmark 3.0LN Boiler is a modulating unit. It represents a true industry advance
that meets the needs of today's energy and environmental concerns. Designed for application
in any closed loop hydronic system, the Benchmark's modulating capability relates energy input
directly to fluctuating system loads. The Benchmark 3.0, with its 15:1 turn down ratio and
condensing capability, provides extremely high efficiencies and makes it ideally suited for
modern low temperature, as well as, conventional heating systems.
The Benchmark 3.0 operates at inputs ranging from 200,000 BTU/hr. to 3,000,000 BTU/hr. The
output of the boiler is a function of the unit’s firing rate and return water temperature. Output
ranges from 198,000 BTU/hr. to 2,900,000 BTU/hr., depending on operating conditions.
When installed and operated in accordance with this Instruction Manual, the Benchmark 3.0
Boiler complies with the NOx emission standards outlined in:
Whether used in singular or modular arrangements, the Benchmark 3.0 offers the maximum
flexibility in venting with minimum installation space requirements. The Benchmark's advanced
electronics are available in several selectable modes of operation offering the most efficient
operating methods and energy management system integration.
For service or parts, contact your local sales representative or AERCO INTERNATIONAL.
NAME:
ORGANIZATION:
ADDRESS:
TELEPHONE:
A
SAFETY PRECAUTIONS
1-1
SAFETY PRECAUTIONS
1-2
SAFETY PRECAUTIONS
a. In the event that the side wall horizontally vented gas fueled equipment is installed in
a crawl space or an attic, the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of
completion of installation, the owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an alarm shall be installed.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the
most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential
purposes.
(e) A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled
equipment and all the venting instructions, parts lists and/or design instructions for the venting system
shall remain with the appliance or equipment at the completion of the installation.
_______________________________ [End of Extracted Information From 248 CMR 5.08 (2)]
1-3
INSTALLATION
CHAPTER 2 INSTALLATION
2-1
INSTALLATION
WARNING Remove the four (4) lag screws securing the unit
KEEP THE UNIT AREA CLEAR AND to the shipping skid. Lift the unit off the shipping
FREE FROM ALL COMBUSTIBLE skid and position it on the 4 inch to 6 inch
MATERIALS AND FLAMMABLE housekeeping concrete pad (required) in the
desired location.
VAPORS OR LIQUIDS.
BURNER
ASSEMBLY
CAUTION
While packaged in the shipping LIFTING LIFTING
container, the boiler must be moved TAB 1 TAB 2
by pallet jack or forklift from the
FRONT ONLY. LIFTING
TAB 3
OUTLET
FLANGE
SHELL DRAIN
VALVE
INSULATED
FLEX HOSE 2" GAS INLET
(SEE IMPORTANT CONNECTION
NOTE BELOW)
EXHAUST
MANIFOLD
REAR VIEW
PARTIAL TOP VIEW - REAR
Figure 2-4
Figure 2-3 Supply and Return Locations
Location of Threaded Support Rod
2.6 CONDENSATE DRAINS
IMPORTANT The Benchmark 3.0 Boiler is designed to
THE INSULATED FLEX HOSE condense water vapor from the flue products.
SHOWN IN FIGURE 2-3 MUST BE Therefore, the installation must have provisions
LEVEL OR SLOPING UPWARD AS for suitable condensate drainage or collection.
IT EXITS THE BOILER. FAILURE TO Two condensate drain connections are provided
PROPERLY POSITION THIS HOSE on the rear of the unit as shown in Figure 2-5.
MAY CAUSE INEFFECTIVE AIR One drain connection is located on the exhaust
ELIMINATION RESULTING IN ELE- manifold and the other is located on the
VATED TEMPERATURES THAT connecting manifold.
COULD COMPROMISE THE TOP
The drain at the bottom of the exhaust manifold
HEAD GASKET. also includes a condensate trap containing a
2.4.4 Removal of Strap and Packing float assembly. When condensate collects in the
exhaust manifold, the float rises, thereby
Material From Heat Exchanger
allowing it to discharge through the drain
Prior to connecting the external gas supply or opening. The drain pipe located on the
electrical power to the unit. the strap and connecting manifold must be connected to a
packing material must be removed from the top second condensate trap which is packed
of the primary heat exchanger. This material is separately within the unit’s shipping container.
located in the area of the ignitor-injector and
staged ignition solenoid on the burner assembly
2-3
INSTALLATION
The procedures to install and connect both of 2.6.2 Connecting Manifold Condensate
the condensate drains are provided in Drain
paragraphs 2.6.1 and 2.6.2.
The connecting manifold drain pipe shown in
Figure 2-5, View B – B must be connected to a
separate condensate drain trap external to the
unit. This condensate trap (part no. 24060) is
supplied with the unit along with a trap adapter
EXHAUST
MANIFOLD and a 3/4” NPT x 5” long nipple. Refer to Figure
A 2-6 and install the trap as follows:
NOTE
CONDENSATE
The condensate trap described in the
TRAP following steps can be installed on the
DRAIN
A floor behind the unit as shown in Figure 2-
6. Ensure that the condensate trap inlet is
SHELL DRAIN level with or below the connecting
VALVE
manifold drain pipe. Ensure that the outlet
B hose from the trap slopes away (down)
CONNECTING
MANIFOLD
from the trap.
2-4
INSTALLATION
2-5
INSTALLATION
TERMINAL BLOCK
NATURAL
GAS
SUPPLY
2" MANUAL
SHUTOFF
VALVE
Figure 2-7
Manual Gas Shut-Off Valve Location 2.8.1 Electrical Power Requirements
The AERCO Benchmark 3.0 Boiler is available
in two different AC power configurations:
2.7.4 IRI Gas Train Kit
The IRI gas train is an optional gas train • 208 VAC/3-Phase/60 @20 amps
configuration which is required in some areas for
• 460 VAC/3-Phase/60 Hz @ 15 amps
code compliance or for insurance purposes.
The IRI gas train is factory pre-piped and wired. Each of the power configurations utilize a Power
See Appendix F, Drawing AP-A-803 for details. Box with a terminal block that matches the
configuration ordered. The two different terminal
2.8 AC ELECTRICAL POWER WIRING block configurations are shown in Figure 2-9. A
The AERCO Benchmark 3.0 Electrical Power wiring diagram showing the required AC power
Wiring Guide, GF-3060, must be consulted prior connections is provided on the front cover of the
to connecting any AC power wiring to the unit. Power Box.
External AC power connections are made to the
unit inside the Power Box on the front panel of Each Benchmark 3.0 Boiler must be connected
the unit. Remove the front door of the unit to to a dedicated electrical circuit. NO OTHER
access the Power Box mounted directly above DEVICES SHOULD BE ON THE SAME
the Control Box. Loosen the four Power Box ELECTRICAL CIRCUIT AS THE BENCHMARK
cover screws and remove cover to access the BOILER. A means for disconnecting AC power
AC terminal connections inside the Power Box from the unit (such as a service switch) must be
(Figure 2-8). installed near the unit for normal operation and
maintenance. All electrical connections should
NOTE be made in accordance with the National
Electrical Code and/or with any applicable local
All electrical conduit and hardware must codes.
be installed so that it does not interfere
with the removal of any unit covers, inhibit For electrical power wiring diagrams, see the
service/maintenance, or prevent access AERCO Benchmark 3.0 Electrical Power Wiring
between the unit and walls or another Guide, (GF-3060).
unit.
2-6
INSTALLATION
NEU
L3 L3
L2 L2
L1 L1
Figure 2-9
AC Terminal Block Configurations
2-7
INSTALLATION
OUTDOOR SENSOR IN
REMOTE INTL'K IN
SENSOR COMMON
(AIR) AUX SENSOR IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED NOT USED
NC
COM FAULT RELAY
NO 120 VAC, 5A, RES
+ NC
ANALOG IN- COM AUX RELAY
+ NO 120 VAC, 5A, RES
B.M.S. (PWM) IN -
+ RELAY CONTACTS:
mA OUT
- 120 VAC, 30 VDC
+ 5 AMPS RESISTIVE
RS-485
G
COMM.
- DANGER
NOT USED 120 VAC USED
0 – 10V IN THIS BOX
AGND
2.9.1 Constant Setpoint Mode utilize either pulse width modulation (PWM)
signaling, or RS485 Modbus signaling. For PWM
The Constant Setpoint Mode is used when it is signaling, connections are made from the
desired to have a fixed setpoint that does not AERCO Boiler Management System to the
deviate. No wiring connections, other than AC B.M.S. (PWM) IN terminals on the I/O Box
electrical power connections, are required for terminal strip. For RS485 Modus signaling,
this mode. However, if desired, fault monitoring connections are made from the BMS to the
or enable/disable interlock wiring can be utilized RS485 COMM terminals on the I/O Box terminal
(see paragraphs 2.9.9.1 and 2.9.10). strip. Polarity must be maintained and the shield
must be connected only at the AERCO BMS.
2.9.2 Indoor/Outdoor Reset Mode
The boiler end of the shield must be left floating.
This mode of operation increases supply water For additional instructions, refer to Chapter 5,
temperature as outdoor temperatures decrease. paragraph 5.6 in this manual. Also, refer to GF-
An outside air temperature sensor (AERCO Part 108M (BMS Model 168) and GF-124 (BMS II
No. 122790) is required. The sensor MUST BE Model 5R5-384), BMS -Operations Guides.
wired to the I/O Box wiring terminals (see Figure
2-11). Refer to paragraph 2.10.1 for additional
information on outside air temperature sensor 2.9.4 Remote Setpoint and Direct Drive
installation. Modes
2.9.3 Boiler Management System Mode The Benchmark 3.0 Boiler can accept several
types of signal formats from an Energy
NOTE Management System (EMS), Building
BMS Model 168 can utilize either pulse Automation System (BAS) or other source, to
width modulation (PWM) or RS485 control either the setpoint (Remote Setpoint
Modbus signaling to the Boiler. BMS II Mode) or firing rate (Direct Drive Mode) of the
Model 5R5-384 can utilize only RS485 Boiler. These formats are:
signaling to the Boiler. • 4 to 20 mA/1 to 5 VDC
When using an AERCO Boiler Management • 0 to 20 mA/0 to 5 VDC
System (BMS), the field wiring is connected • PWM – (Pulse Width Modulated signal. See
between the BMS Panel and each Boiler’s I/O para. 2.10.4)
Box terminal strip (Figure 2-11). Twisted
shielded pair wire from 18 to 22 AWG must be • Network (RS485 Modbus. See para. 2.10.8)
utilized for the connections. The BMS Mode can
2-8
INSTALLATION
While it is possible to control a boiler or boilers SENSOR IN and SENSOR COMMON terminals
using one of the previously described modes of in the I/O Box (see Figures 2-10 and 2-11). Wire
operation, it may not be the method best suited the sensor using a twisted shielded pair wire
for the application. Prior to selecting one of from 18 to 22 AWG. There is no polarity to
these modes of operation, it is recommended observe when terminating these wires. The
that you consult with your local AERCO shield is to be connected only to the terminals
representative or the factory for the mode of labeled SHIELD in the I/O Box. The sensor end
operation that will work best with your of the shield must be left free and ungrounded.
application. For more information on wiring the
4 to 20 mA / 1to 5VDC or the 0 to 20 mA / 0 to 5 When mounting the sensor, it must be located
VDC, see paragraph 2.9.3. on the North side of the building where an
average outside air temperature is expected.
The sensor must be shielded from direct sunlight
2.9.5 Combination Mode as well as impingement by the elements. If a
shield is used, it must allow for free air
NOTE circulation.
Only BMS Model 168 can be utilized for
the Combination Mode, not the BMS II 2.10.2 AIR SENSOR IN
(Model 5R5-384). The AIR SENSOR IN is connected to the AUX
SENSOR IN and SENSOR COMMON terminals
With a Combination Mode unit, field wiring is on the I/O board. The AIR SENSOR measures
between the unit’s I/O Box wiring terminals, the the temperature of the air input to the Air/Fuel
CCP (Combination Control Panel), and the BMS Valve. This temperature reading is one of the
Model 168 (Boiler Management System). The components used to calculate the rotational
wiring must be accomplished using twisted- speed of the blower used in the combustion
shielded pair wire from 18 to 22 AWG. Polarity Calibration process (Chapter 4).
must be maintained. For further instructions and
wiring diagrams, refer to the GF-108 Boiler The AUX SENSOR IN terminals can be used to
Management System Operations Guide and the add an additional temperature sensor for
CCP-1 data sheet. monitoring purposes. This input is always
enabled and is a view-only input that can be
2.10 I/O BOX CONNECTIONS seen in the Operating Menu. The sensor must
The types of input and output signals and be wired to the AUX SENSOR IN and SENSOR
devices to be connected to the I/O Box terminals COMMON terminals and must be similar to
shown in Figure 2-11 are described in the AERCO BALCO wire sensor Part No. 12449. A
following paragraphs. resistance chart for this sensor is provided in
Appendix C.
CAUTION
DO NOT make any connections to the 2.10.3 ANALOG IN
I/O Box terminals labeled “NOT The ANALOG IN + and – terminals are used
USED”. Attempting to do so may when an external signal is used to drive the
firing rate (Direct Drive Mode) or change the
cause equipment damage.
setpoint (Remote Setpoint Mode) of the Boiler.
2.10.1 OUTDOOR SENSOR IN Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA
An outdoor air temperature sensor (AERCO Part / 0 to 5 VDC signal may be used to vary the
No. 122790) will be required primarily for the setpoint or firing rate. The factory default setting
Indoor/Outdoor reset mode of operation. It can is for 4 to 20 mA / 1 to 5 VDC, however this may
also be used with another mode if it is desired to be changed to 0 to 20 mA / 0 to 5 VDC using the
use the outdoor sensor enable/disable feature. Configuration Menu described in Chapter 3. If
This feature allows the boiler to be enabled or voltage rather than current is selected as the
disabled based on the outdoor air temperature. drive signal, a DIP switch must be set on the
PMC Board located inside the Control Box.
The factory default for the outdoor sensor is Contact the AERCO factory for information on
DISABLED. To enable the sensor and/or select setting DIP switches.
an enable/disable outdoor temperature, see the
Configuration menu in Chapter 3. All of the supplied signals must be floating
(ungrounded) signals. Connections between the
The outdoor sensor may be wired up to 200 feet signal source and the Boiler’s I/O Box must be
from the boiler. It is connected to the OUTDOOR made using twisted shielded pair wire from 18 to
2-9
INSTALLATION
2-10
INSTALLATION
2-11
INSTALLATION
2.13.2 Combustion Air From Inside the 2.13.4 Temporary Combustion Air
Building Filtering During Construction
When combustion air is provided from within the When the AERCO Benchmark 3.0 Boiler is used
building, it must be supplied through two to provide heat temporarily during ongoing
permanent openings in an interior wall. Each building construction, accumulated drywall dust,
opening must have a free area of not less than sawdust and similar particles can accumulate in
one square inch per 1000 BTU/H of total boiler the unit’s combustion air intake filter and block
input. The free area must take into account any combustion air flow. In these situations, AERCO
restrictions such as louvers. recommends that a disposable air intake filter be
installed, temporarily, above the boiler
2.13.3 Sealed Combustion combustion air inlet.
The AERCO Benchmark 3.0 Boiler is UL listed
for 100%-sealed combustion. For sealed AERCO recommends that the temporary air filter
combustion installations, the screen on the air be cut from a McMaster-Carr part no. 2122K315
inlet duct of the unit must be removed. The inlet Polyester Air Filter Roll Tackfield, 1/2” thick, 16”
air ductwork must then be attached directly to wide, or equivalent. Cover the Benchmark 3.0
the unit’s air inlet. air inlet with the blue side of the filter material
facing outward to hold the dust on the outside
In a sealed combustion air application, the surface. Maximize the surface area of the filter
combustion air ducting pressure losses must be covering the 8" diameter opening by creating a
taken into account when calculating the total dome out of the filter material.
maximum allowable venting run. See the
AERCO Benchmark Venting and Combustion During construction, check the filter for dust
Air Guide, GF-2050. When using the boiler in a accumulation and replace it when the
sealed combustion air configuration, each unit accumulation becomes noticeable.
must have a minimum 8-inch diameter
connection at the unit.
2-12
CONTROL PANEL OPERATING PROCEDURES
3.1 INTRODUCTION
The information in this Chapter provides a guide
to the operation of the Benchmark 3.0 Boiler
using the Control Panel mounted on the front of
the unit. It is imperative that the initial startup of
this unit be performed by factory trained
personnel. Operation prior to initial startup by
factory trained personnel will void the equipment 2
warranty. In addition, the following WARNINGS
and CAUTIONS must be observed at all times.
CAUTION 1
3
All of the installation procedures in
Chapter 2 must be completed before
attempting to start the unit. 4
12
WARNING 5
WARNING 8
DO NOT ATTEMPT TO DRY FIRE
THE BOILER. STARTING THE UNIT
WITHOUT A FULL WATER LEVEL
9
CAN SERIOUSLY DAMAGE THE
UNIT AND MAY RESULT IN INJURY
TO PERSONNEL OR PROPERTY
DAMAGE. THIS SITUATION WILL
VOID ANY WARRANTY.
3-1
CONTROL PANEL OPERATING PROCEDURES
3-2
CONTROL PANEL OPERATING PROCEDURES
3-3
CONTROL PANEL OPERATING PROCEDURES
available menu options in the Top-Down
3.3 CONTROL PANEL MENUS sequence. Pressing the ▼ arrow key will
The Control Panel incorporates an extensive display the options in the Bottom-Up
menu structure which permits the operator to set sequence. The menu options will wrap-
up, and configure the unit. The menu structure around after the first or last available option
consists of five major menu categories which are is reached.
applicable to this manual. These categories are
shown in Figure 3-2. Each of the menus shown, 6. To change the value or setting of a
contain options which permit operating displayed menu option, press the CHANGE
parameters to be viewed or changed. The key. The displayed option will begin to flash.
menus are protected by a password levels to Press the ▲ or ▼ arrow key to scroll
prevent unauthorized use. through the available menu option choices
for the option to be changed. The menu
Prior to entering the correct password, the option choices do not wrap around.
options contained in the Operation, Setup, 7. To select and store a changed menu item,
Configuration and Tuning Menu categories can press the ENTER key.
be viewed. However, with the exception of
Internal Setpoint Temperature (Configuration
Menu), none of the viewable menu options can
be changed.
3-4
CONTROL PANEL OPERATING PROCEDURES
NOTE 3.5 SETUP MENU
The following paragraphs provide brief The Setup Menu (Table 3-3) permits the
descriptions of the options contained in each operator to enter the unit password (159) which
menu. Refer to Appendix A for detailed is required to change the menu options. To
descriptions of each menu option. Refer to prevent unauthorized use, the password will
Appendix B for listings and descriptions of time-out after 1 hour. Therefore, the correct
displayed startup, status and error password must be reentered when required. In
messages. addition to permitting password entries, the
Setup Menu is also used to enter date and time,
units of temperature measurements and entries
3.4 OPERATING MENU required for external communication and control
The Operating Menu displays a number of key of the unit via the RS-232 port. A view-only
operating parameters for the unit as listed in software version display is also provided to
Table 3-2. This menu is “Read-Only” and does indicate the current Control Box software
not allow personnel to change or adjust any version.
displayed items. Since this menu is “Read-Only”,
it can be viewed at any time without entering a NOTE
password. Pressing the ▲ arrow key to display The Outdoor Temp display item shown with
the menu items in the order listed (Top-Down). an asterisk in Table 3-2 will not be displayed
Pressing the ▼ arrow key will display the menu unless the Outdoor Sensor function has
items in reverse order (Bottom-Up). been enabled in the Configuration Menu
(Table 3-4).
3-5
CONTROL PANEL OPERATING PROCEDURES
3-6
CONTROL PANEL OPERATING PROCEDURES
*CAUTION:
1. DO NOT CHANGE the Analog Output Menu Item from its Default setting (Valve
Position 0-10V).
3-7
CONTROL PANEL OPERATING PROCEDURES
3.9 START SEQUENCE If all of the above switches are closed, the
When the Control Box ON/OFF switch is set to READY light above the ON/OFF switch will light
the ON position, it checks all pre-purge safety and the unit will be in the Standby mode.
switches to ensure they are closed. These
switches include: When there is a demand for heat, the following
events will occur:
• Safety Shut-Off Valve Proof of Closure
(POC) switch
NOTE
• Low Water Level switch
If any of the Pre-Purge safety device
• High Water Temperature switch switches are open, the appropriate fault
• High Gas Pressure switch message will be displayed. Also, the
• Low Gas Pressure switch appropriate fault messages will be displayed
throughout the start sequence, if the
• Blower Proof switch
required conditions are not observed.
3-8
CONTROL PANEL OPERATING PROCEDURES
1. The DEMAND LED status indicator will light. Valve (Figure 3-6) will read between 25
and 35 to indicate that the valve is in
2. The unit checks to ensure that the Proof of
the low-fire position.
Closure (POC) switch in the downstream
Safety Shut-Off Valve (SSOV) is closed. (b) The igniter relay is activated and
See Figure 3-3 for SSOV location. provides ignition spark.
(c) The gas Safety Shut-Off Valve (SSOV)
is energized (opened) allowing gas to
flow into the Air/Fuel Valve.
Figure 3-3.
SSOV Location
3-9
CONTROL PANEL OPERATING PROCEDURES
3-10
INITIAL START-UP
4-1
INITIAL START-UP
4.2.3 Accessing the Vent Probe Port 3. Set the control panel ON/OFF switch to the
OFF position.
The unit contains NPT plugs on both the left and
right side of the exhaust manifold at the rear of 4. Turn on external AC power to the unit. The
the unit as shown in Figure 4-2. display will show LOSS OF POWER and the
time and date.
5. Set the unit to the Manual Mode by pressing
the AUTO/MAN key. A flashing Manual
Valve Position message will be displayed
showing the present air/fuel valve % open
position. Also, the MANUAL LED will light.
6. Adjust the air/fuel valve position to 0% by
pressing the ▼ arrow key.
7. Ensure that the leak detection ball valve
downstream of the SSOV is open.
8. Set the ON/OFF switch to the ON position.
9. Change the valve position to 29% using the
▲ arrow key. The unit should begin its start
sequence and fire.
Figure 4-2
Analyzer Probe Hole Location
4-2
INITIAL START-UP
Figure 4-3
Regulator Adjustment Screw Location
Figure 4-4
Iris Air Damper Location/Adjustment
4-3
INITIAL START-UP
NOTE NOTE
The remaining combustion calibration steps are The remaining steps basically repeat the
performed using the Combustion Cal Menu procedures in steps 18 through 25 for air/fuel
included in the C-More Control System. The valve positions of 50%, 40%, 30% and 14%
combustion calibration control functions will be open. However, since oxygen levels vary, these
used to adjust the oxygen level (%) at air/fuel steps are repeated in their entirety. When
valve positions of 80%, 60%, 45%, 30% and performing these steps, also ensure that the
16% as described in the following steps. These carbon monoxide (CO) and nitrogen oxide (NOx)
steps assume that the inlet air temperature is readings do not exceed the values shown for
within the range of 50°F to 100°F. each valve position.
4-4
INITIAL START-UP
37. Press the ▼ arrow key until CAL Voltage arrow keys. This will adjust the output
40% is displayed. voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
38. Press the CHANGE key. CAL Voltage 40%
increases the oxygen level and pressing the
will begin to flash.
▼ arrow key decreases the oxygen level.
39. The oxygen level at the 40% valve position
49. Once the oxygen level is within the specified
should be as shown below. Also, ensure that
range at 30%, press the ENTER key to store
the carbon monoxide (CO) and nitrogen
the selected blower output voltage for the
oxide (NOx) readings do not exceed the
30% valve position.
values shown.
50. Press the ▲ arrow key until SET Valve
Combustion Oxygen Level at Position appears on the C-MORE display.
40% Valve Position 51. Press the CHANGE key. SET Valve Position
Oxygen % Carbon will begin to flash.
± 0.2 Monoxide NOx 52. Press the ▼ arrow key until the SET Valve
7.8 % <50 ppm <20 ppm Position reads 14%, then press the ENTER
key.
40. If the oxygen level is not within the specified
range, adjust the level using the ▲ and ▼ 53. Press the ▼ arrow key until CAL Voltage
arrow keys. This will adjust the output 14% is displayed.
voltage to the blower motor as indicated on 54. Press the CHANGE key. CAL Voltage 14%
the display. Pressing the ▲ arrow key will begin to flash.
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level. 55. The oxygen level at the 14% Valve Position
should be as shown below. Also, ensure that
41. Once the oxygen level is within the specified the carbon monoxide (CO) and nitrogen
range at 40%, press the ENTER key to store oxide (NOx) readings do not exceed the
the selected blower output voltage for the values shown.
40% valve position.
Combustion Oxygen Level at
42. Press the ▲ arrow key until SET Valve
Position appears on the C-MORE display. 14% Valve Position
43. Press the CHANGE key. SET Valve Position Oxygen % Carbon
will begin to flash. ± 0.2 Monoxide NOx
8.5 % <50 ppm <30 ppm
44. Press the ▼ arrow key until the SET Valve
Position reads 30%, then press the ENTER
56. If the oxygen level is not within the specified
key. range, adjust the level using the ▲ and ▼
45. Press the ▼ arrow key until CAL Voltage arrow keys. This will adjust the output
30% is displayed. voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
46. Press the CHANGE key. CAL Voltage 30% increases the oxygen level and pressing the
will begin to flash. ▼ arrow key decreases the oxygen level.
47. The oxygen level at the 30% Valve Position 57. Once the oxygen level is within the specified
should be as shown below. Also, ensure that range at 14%, press the ENTER key to store
the carbon monoxide (CO) and nitrogen the selected blower output voltage for 14%
oxide (NOx) readings do not exceed the Valve Position.
values shown.
4-5
INITIAL START-UP
4-6
MODE OF OPERATION
5-1
MODE OF OPERATION
5-2
MODE OF OPERATION
If the Network setting is selected for RS485 5.5 DIRECT DRIVE MODES
Modbus operation, a valid Comm Address must The unit’s air/fuel valve position (% open) can be
be entered in the Setup Menu. Refer to Modbus changed by a remote signal which is typically
Communication Manual GF-114 for additional sent from an Energy Management System
information. (EMS) or from a Building Automation System
(BAS). The Direct Drive mode can be driven by
While it is possible to change the settings of a current or voltage signal within the following
temperature related functions, the unit is factory ranges:
preset with settings that work well in most
applications. It is suggested that an AERCO 4-20 mA/1-5 Vdc
representative be contacted, prior to changing
any temperature related function settings. For 0-20 mA/0-5 Vdc
descriptions of temperature-related functions
and their factory defaults, refer to Appendices A The factory default setting for the Direct Drive
and E. mode is 4-20 mA/1-5 Vdc. With this setting, a 4
to 20 mA signal, sent by an EMS or BAS is used
to change the unit’s valve position from 0% to
5.4.1 Remote Setpoint Field Wiring 100%. A 4 mA/1V signal is equal to a 0% valve
The only wiring connections necessary for the position, while a 20 mA /5V signal is equal to a
Remote Setpoint mode are connection of the 100% valve position. When a 0-20 mA/0-5 Vdc
remote signal leads from the source to the unit’s signal is used, zero is equal to a 0% valve
I/O Box. The I/O Box is located on the front position.
panel of the boiler. For either a 4-20mA/0-5V or
a 0-20mA/0-5V setting, the connections are In addition to the current and voltage signals
made at the ANALOG IN terminals in the I/O described above, the Direct Drive mode can also
Box. For a Network setting, the connections are driven by a RS485 Modbus Network signal from
made at the RS-485 COMM terminals in the I/O an EMS or BAS.
Box. The signal must be floating, (ungrounded)
at the I/O Box and the wire used must be a two When in a Direct Drive mode, the unit is a slave
to the EMS or BAS and does not have a role in
wire shielded pair from 18 to 22 AWG. Polarity
temperature control. Direct Drive can be used to
must be observed. The source end of the shield
drive single, or multiple units.
must be connected at the source. When driving
multiple units, each unit’s wiring must conform to
the above. NOTE
If a voltage, rather than current signal is
5.4.2 Remote Setpoint Startup used to control the remote setpoint, a DIP
Since this mode of operation is factory preset switch adjustment must be made on the
and the setpoint is being externally controlled, CPU Board located in the Control Box
no startup instructions are necessary. In this Assembly. Contact your local AERCO
mode, the REMOTE LED will light when the representative for details.
external signal is present.
To enable the Direct Drive Mode, the following
To operate the unit in the Manual mode, press menu setting must be made in the Configuration
the AUTO/MAN switch. The REMOTE LED will Menu:
go off and the MANUAL LED will light.
MENU OPTION SETTING
To change back to the Remote Setpoint mode, Boiler Mode Direct Drive
simply press the AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL Remote Signal 4-20mA/1-5V,
LED will go off.
0-20mA/0-5V, or
Network
5-3
MODE OF OPERATION
If the Network setting is selected for RS485 header. The BMS can control up to 40 boilers; 8
Modbus operation, a valid Comm Address must via pulse width modulation (PWM) and up to 32
be entered in the Setup Menu. Refer to Modbus via Modbus (RS485) network communication.
Communication Manual GF-114 for additional For BMS programming, operation, and Header
information. Sensor installation details, see GF-108M (BMS
Model 168) and GF-124 (BMS II Model 5R5-
5.5.1 Direct Drive Field Wiring 384), BMS Operations Guides. For operation via
an RS485 Modbus network, refer to Modbus
The only wiring connections necessary for Direct Communication Manual GF-114.
Drive mode are connection of the remote signal
leads from the source to the unit’s I/O Box. For To enable the BMS Mode, the following menu
either a 4-20mA/0-5V or a 0-20mA/0-5V setting, settings must be made in the Configuration
the connections are made at the ANALOG IN Menu:
terminals in the I/O Box. For a Network setting,
the connections are made at the RS-485 COMM MENU OPTION SETTING
terminals in the I/O Box. The signal must be
Boiler Mode Direct Drive
floating, (ungrounded) at the I/O Box and the
wire used must be a two wire shielded pair from Remote Signal BMS (PWM Input)
18 to 22 AWG. Polarity must be observed. The or
source end of the shield must be connected at Network (RS485)
the source. When driving multiple units, each
unit’s wiring must conform to the above. Refer to paragraph 3.3 for instructions on
changing menu options.
5.5.2 Direct Drive Startup
Since this mode of operation is factory preset
5.6.1 BMS External Field Wiring
and the valve position is being externally Wiring connections for BMS control using PWM
controlled, no startup instructions are necessary. signaling are made between connector JP2 on
In this mode, the REMOTE LED will light when the BMS panel (boilers 1 through 8), and the
the signal is present. B.M.S. (PWM) IN terminals in the I/O Box on the
front of the boilers. Refer to the wiring diagram
To operate the unit in manual mode, press the provided on the cover of the I/O Box.
AUTO/MAN switch. The REMOTE LED will go
off and the MANUAL LED will light. Wiring connections for RS485 Modbus control
are made between connector JP11 on the BMS
To change back to the Direct Drive mode, simply (boilers 9 through 40) and the RS485 COMM
press the AUTO/MAN switch. The REMOTE terminals in the I/O Box on the front of the
LED will again light and the MANUAL LED will boilers.
go off.
Wire the units using shielded twisted pair wire
between 18 and 22 AWG. Observe the proper
5.6 BOILER MANAGEMENT SYSTEM
polarity for the B.M.S. (PWM) IN and/or RS485
(BMS) COMM wiring connections. Shields should be
NOTE terminated only at the BMS and the boiler end
must be left floating. Each unit’s wiring must
BMS Model 168 can utilize either pulse
conform to the above.
width modulation (PWM) or RS485
Modbus signaling to the Boiler. BMS II
Model 5R5-384 can utilize only RS485 5.6.2 BMS Setup and Startup
signaling to the Boiler. This mode of operation is factory preset and the
AERCO BMS controls the firing rate (air/fuel
The BMS mode of operation is used in valve % open position). There are no setup
conjunction with an AERCO Boiler Management instructions for each individual unit.
System. The BMS mode is used when it is
desired to operate multiple units in the most To operate the unit in manual mode, press the
efficient manner possible. For this mode of AUTO/MAN switch. The REMOTE LED will go
operation, a BMS Header Sensor must be off and the MANUAL LED will light
installed between 2 and 10 feet downstream of
the LAST boiler in the boiler plant's supply water
5-4
MODE OF OPERATION
To change back to the BMS mode, simply press Combination Control Panel see the AERCO
the AUTO/MAN switch. The REMOTE LED will CCP-1 literature.
again light and the MANUAL LED will go off.
5.7.1 Combination Control System Field
5.7 COMBINATION CONTROL SYSTEM Wiring
(CCS) Wiring for this system is between the BMS
NOTE Model 168 panel, the CCP and the B.M.S.
Only BMS Model 168 can be utilized for (PWM) IN terminals in the I/O Box. Wire the
the Combination Mode, not the BMS II units using a shielded twisted pair of 18 to 22
(Model 5R5-384). AWG wire. When wiring multiple units, each
unit’s wiring must conform to the above. For a
A Combination Control System (CCS) is one complete CCP system-wiring diagram see the
that uses multiple boilers to cover both space- AERCO CCP-1 literature.
heating and domestic hot water needs. An
AERCO Boiler Management System (BMS) 5.7.2 Combination Control System Setup
Model 168 and a Combination Control Panel and Startup
(CCP) are necessary to configure this system.
Typically, an adequate number of boilers are Setup for the Combination Mode requires entries
installed to cover the space-heating load on the to be made in the Configuration Menu for boiler
design day, however one or more units are used mode, remote signal type and setpoint. The
for the domestic hot water load. setpoint is adjustable from 40°F to 240°F.
The theory behind this type of system is that the Enter the following settings in the Configuration
maximum space-heating load and the maximum Menu:
domestic hot water load do not occur simul- MENU OPTION SETTING
taneously.+ Therefore, boilers used for the
domestic hot water are capable of switching Boiler Mode Combination
between constant setpoint and BMS modes of
operation. These boilers are the combination Remote Signal BMS (PWM Input)
units and are referred to as the combo boilers. Internal Setpt 40°F to 240°F
The combo boilers heat water to a constant
setpoint temperature. That water is then Refer to paragraph 3.3 for instructions on
circulated through a heat exchanger in a changing menu options.
domestic hot water storage tank.
While it is possible to change other temperature-
When the space-heating load is such that all the related functions for combination mode, thes
space-heating boilers are at the 100% valve functions are preset to their factory default
position, the BMS will then ask the Combination values. These default settings work well in most
Control Panel for the domestic boilers to applications. It is suggested that AERCO be
become space-heating boilers. Provided the contacted prior to changing settings other than
domestic hot water load is satisfied, the combo the unit’s setpoint. For a complete listing of
(hot water) boilers will then become space- temperature related function defaults, see
heating boilers. If the domestic hot water load is Appendix E.
not satisfied, the combo boiler(s) remain on the
domestic hot water load. If the combo boilers To set the unit to the manual mode, press the
switch over to space heating, but there is a call AUTO/MAN switch. The MANUAL LED will
for domestic hot water, the CCP switches the light.
combo units back to the domestic load.
To set the unit back to the auto mode, press the
When the combo units are satisfying the AUTO/MAN switch. The MANUAL LED will go
domestic load they are in constant setpoint off and the REMOTE LED will light.
mode of operation. When the combo units
When the boiler is switched to BMS mode, the
switch over to space heating, their mode of
AERCO BMS controls the valve position. There
operation changes to the BMS mode. For more
are no setup requirements to the boiler(s) in this
information concerning the operation of the
mode.
5-5
SAFETY DEVICE TESTING
6.1 TESTING OF SAFETY DEVICES 4. Place the unit in Manual Mode and adjust the
air/fuel valve position (% open) between 25
Periodic safety device testing is required to and 30%.
ensure that the control system and safety
devices are operating properly. The Benchmark 5. While the unit is firing, slowly close the
3.0LN control system comprehensively monitors external manual gas shut-off valve.
all combustion-related safety devices before, 6. The unit should shut down and display a
during and after the start sequence. The LOW GAS PRESSURE fault message at
following tests check to ensure that the system approximately 2.6” W.C. The FAULT indi-
is operating as designed. cator should also start flashing.
Operating controls and safety devices should be
tested on a regular basis or following service or 1/8" NPT PLUG
replacement. All testing must conform to local (INSTALL MANOMETER HERE
FOR HIGH GAS PRESSURE
codes such as ASME CSD-1. FAULT TEST)
LEAK DETECTION
HIGH GAS BALL VALVE
NOTE PRESSURE
SWITCH
MANUAL and AUTO modes of operation
are required to perform the following
tests. For a complete explanation of these TO
AIR/FUEL
modes, see Chapter 3. VALVE
6.2 LOW GAS PRESSURE FAULT TEST 7. Fully open the external manual gas shut-off
Refer to Figure 6-1 and ensure that the leak valve and press the CLEAR button on the
detection ball valve located at the high gas Control Box.
pressure switch is closed.
8. The fault message should clear and the
1. Remove the 1/8 “ plug from the ball valve at FAULT indicator should go off. The unit
the low gas pressure switch shown in the should restart.
lower portion of Figure 6-1. 9. Upon test completion, close the ball valve
2. Install a 0 – 16 “ W.C. manometer or a W.C. and remove the manometer. Replace the 1/8
gauge where the 1/8" plug was removed. “ plug removed in step 1.
6-1
SAFETY DEVICE TESTING
1. Remove the 1/8 “ plug from the leak 7. Close the drain and pressure relief valve
detection ball valve shown in the upper used in draining the unit.
portion of Figure 6-1. 8. Open the water shut-off valve in the return
piping to the unit.
2. Install a 0 – 16” W.C. manometer (or W.C.
gauge) where the 1/8” plug was removed. 9. Open the water supply shut-off valve to the
unit to refill.
3. Slowly open the leak detection ball valve
10. After the shell is full, press the LOW WATER
4. Start the unit in Manual mode at a valve LEVEL RESET button to reset the low water
position (firing rate) between 25 and 30%. cutoff.
11. Press the CLEAR button to reset the FAULT
5. Slowly increase the gas pressure using the
LED and clear the displayed error message.
adjustment screw on the SSOV Actuator
(see Figure 4-3). 12. Set the ON/OFF switch to the ON position.
The unit is now ready for operation.
6. The unit should shut down and display a
HIGH GAS PRESSURE fault message
when the gas pressure exceeds 2.6” W.C. 6.5 WATER TEMPERATURE FAULT
The FAULT indicator should also start TEST
flashing.
A high water temperature fault is simulated by
7. Reduce the gas pressure back to 1.8” W.C. adjusting the automatic over-temperature switch.
This switch is accessible from the left side of the
8. Press the CLEAR button on the Control Box unit as shown in Figure 6-2.
to clear the fault.
1. Start the unit in the normal operating mode.
9. The fault message should clear and the Allow the unit to stabilize at its setpoint.
FAULT indicator should go off. The unit
should restart. Lower the adjustable over-temperature switch
setting to match the displayed OUTLET
10. Upon test completion, close the ball valve TEMPERATURE.
and remove the manometer. Replace the Once the adjustable over-temperature switch
1/8“ plug removed in step 1. setting is approximately at, or just below, the
actual outlet water temperature, the unit
should shut down. The FAULT indicator
6.4 LOW WATER LEVEL FAULT TEST should start flashing and a HIGH WATER
To simulate a low water level fault: TEMP SWITCH OPEN fault message should
be displayed. It should not be possible to
1. Set the ON/OFF switch to the OFF position restart the unit.
2. Close the water shut-off valves in the supply Reset the adjustable over-temperature switch to
and return piping to the unit. its original setting.
3. Slowly open the drain valve on the rear of the The unit should start once the adjustable
unit. If necessary the unit’s relief valve may temperature limit switch setting is above the
be opened to aid in draining. actual outlet water temperature.
4. Continue draining the unit until a LOW
WATER LEVEL fault message is displayed
and the FAULT indicator flashes.
5. Place the unit in the Manual Mode and raise
the valve position above 30%.
6-2
SAFETY DEVICE TESTING
RESET BUTTON FOR MANUAL that a device such as a pump, gas booster, or
RESET TEMPERATURE LIMIT
SWITCH louver is operational.
HIGH LIMIT
2. Start the unit in the Manual Mode and set the
valve position between 25% and 30%.
3. If there is a jumper across the REMOTE
INTL’K IN terminals, remove one side of the
ADJUSTABLE jumper. If the interlock is being controlled by
TEMPERATURE
LIMIT SWITCH an external device, either open the interlock
via the external device or disconnect one of
the wires leading to the external device.
6-3
SAFETY DEVICE TESTING
3. Close the manual gas shutoff valve located (a) The unit will execute a shutdown purge
between the Safety Shut-Off Valve (SSOV) cycle for a period of 15 seconds and
and the Air/Fuel Valve (see Figure 6-3). display WAIT FAULT PURGE.
(b) The unit will execute a 30 second re-
AIR
INLET BLOWER PROOF ignition delay and display WAIT RETRY
BLOCKED SWITCH
INLET PAUSE.
SWITCH BLOWER
(c) The unit will then execute a standard
ignition sequence and display WAIT
IGNITION RETRY.
P/O FRAME
4. Set the ON/OFF switch to the ON position to 2. Start the unit in the Manual Mode at a valve
start the unit. position between 25% and 30%.
5. The unit should shut down after reaching the 3. The unit should shut down and execute an
Ignition cycle and display FLAME LOSS IGNITION RETRY cycle by performing the
DURING IGN. following steps:
6. Open the valve previously closed in step 3 (a) The unit will execute a 30 second re-
and press the CLEAR button. ignition delay and display WAIT RETRY
PAUSE.
7. Restart the unit and allow it to prove flame.
(b) The unit will then execute a standard
8. Once flame is proven, close the manual gas ignition sequence and display WAIT
valve located between the SSOV and the IGNITION RETRY.
Air/Fuel Valve.
4. The unit should perform two IGNITION
The unit should shut down and execute an RETRY cycles and then shut down on the
IGNITION RETRY cycle by performing the third successive ignition attempt. The unit will
following steps: display AIRFLOW FAULT DURING PURGE.
6-4
SAFETY DEVICE TESTING
6.9 SSOV PROOF OF CLOSURE SWITCH 6.10 PURGE SWITCH OPEN DURING
The SSOV shown in Figure 6-1 contains a proof PURGE
of closure switch. The proof of closure switch The Purge Switch (and Ignition Switch) is
circuit is checked as follows: located on the Air/Fuel Valve. To check the
switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF
position. 1. Set the unit’s ON/OFF switch to the OFF
2. Place the unit in Manual Mode and set the position. Place the unit in manual mode and
valve position between 25% and 30% set the valve position between 25% and
30%.
3. Refer to Figure 6-1 and locate the SSOV.
2. Remove the Air/Fuel Valve cover by rotating
4. Remove the cover from the SSOV by the cover counterclockwise to unlock it and
loosening the screw shown in Figure 6-4. Lift then lift up (see Figure 6-5).
off the cover to access the terminal wiring
connections. 3. Remove one of the two wires (#171 or #172)
from the Purge Switch (Figure 6-6).
6-5
SAFETY DEVICE TESTING
17
16
position.
2
170
171
2. Place the unit in Manual Mode and set the
valve position between 25% and 30%. IGNITION PURGE
POSITION POSITION
3. Remove the Air/Fuel Valve cover (Figure SWITCH SWITCH
6-5) by rotating the cover counterclockwise to
unlock and lift up to remove. Figure 6-6
4. Remove one of the two wires (#169 or #170) Air/Fuel Valve Purge and Ignition Switch
from the Ignition Switch (Figure 6-6). Locations
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and 6.12 SAFETY PRESSURE RELIEF
then shut down and display IGN SWITCH
VALVE TEST
OPEN DURING IGNITION.
Test the safety Pressure Relief Valve in
7. Replace the wire on the Ignition Switch and accordance with ASME Boiler and Pressure
press the CLEAR button. The unit should Vessel Code, Section VI.
restart.
Figure 6-5
Air/Fuel Valve Cover Location
6-6
MAINTENANCE
CHAPTER 7 MAINTENANCE
NOTE
The 24-Month Waterside/Fireside Inspec-
tion Kit also includes the items contained STAGED
IGNITION
in the Annual Maintenance Kit. Therefore, ASSY
only Kit Part No. 58025-04 is required
when performing the waterside/fireside
inspections.
IGNITOR- FLAME DETECTOR
INJECTOR & GASKET (SECURED
WITH 2 SCREWS)
Appendix K contains recommended spare parts
Figure 7-1.
lists for maintenance of the boiler.
Burner Assembly – Top View
TO AVOID PERSONAL INJURY, 1. Set the ON/OFF switch on the control panel,
PRIOR TO SERVICING: to the OFF position. Disconnect AC power
• DISCONNECT THE AC SUPPLY BY from the unit
TURNING OFF THE SERVICE 2. Remove the top and side panels from the
SWITCH AND AC SUPPLY CIRCUIT unit.
BREAKER. 3. Disconnect the cable from the ignitor-injector.
• SHUT OFF THE GAS SUPPLY AT
4. Using a 7/16” open-end wrench, disconnect
THE MANUAL SHUT-OFF VALVE
the compression nut securing the gas injector
PROVIDED WITH THE UNIT tube of the ignitor-injector to the elbow of the
• ALLOW THE UNIT TO COOL TO A staged ignition assembly. Disconnect the
SAFE WATER TEMPERATURE TO staged ignition assembly from the ignitor-
PREVENT BURNING OR SCALDING injector.
7-1
MAINTENANCE
BURNER
HOUSING
5. Next, loosen and remove the ignitor-injector HOUSING
CENTERLINE
from the burner housing using a 1" open-end IGNITOR-
wrench. INJECTOR
7-2
MAINTENANCE
7-3
MAINTENANCE
BURNER
HOUSING
3/8-16 STAGED STAGED IGNITION
NUTS (8) IGNITION ASSEMBLY
ASSEMBLY
FLAME
DETECTOR
GROUNDING
SCREW
IGNITOR-
INJECTOR
BURNER GASKET
BURNER
HOUSING
BURNER
BURNER GASKET
1/4-20
SCREWS
(6)
Figure 7-3
Burner Disassembly Diagram - Top View Figure 7-4
Burner Assembly - Exploded View
NOTE
The burner housing is heavy, weighing 7.7 CONDENSATE DRAIN TRAPS
approximately 25 pounds.
The Benchmark 3.0 Boiler contains two
11. Refer to the exploded view in Figure 7-4. condensate traps as shown in Chapter 2, Figure
Remove the burner housing from burner 2-5. One trap is located external to the unit and
flange by pulling straight up. attached to the drain pipe from the connecting
manifold. The other trap is an integral part of the
12. Remove the grounding screw. exhaust manifold. These traps should be
inspected and, if necessary, cleaned to ensure
13. Remove the burner by pulling straight up.
proper operation. Follow the procedures in
14. Remove and replace the burner gaskets. paragraphs 7.7.1 and 7.7.2.
15. Beginning with the burner removed in step
13, reinstall all the components in the reverse 7.7.1 Connecting Manifold Condensate
order that they were removed. Trap
To inspect and clean the condensate trap (part
16. Make sure to align the burner housing with
no. 24060) attached to the connecting manifold,
the blower and the heat exchanger top head.
proceed as follows:
17. Check to ensure that the grounding screw is
reinstalled. Also, ensure that conductive, 1. Loosen the thumbscrew securing the trap
high-temperature, anti-seize compound is adaptor (Figure 2-6) to the condensate drain
applied to the threads of the ground screw pipe on the connecting manifold.
and the ignitor-injector. Torque the ignitor-
2. Remove the nipples and connections on the
injector to 80 to 90 in-lbs. However, if the
inlet and outlet sides of the condensate trap
burner housing was replaced during
shown in Figure 7-5.
inspection, torque to 180 in-lbs, then loosen
and re-tighten to 80 to 90 in-lbs.
7-4
MAINTENANCE
FLOAT CONDENSATE
TRAP
INLET
ORIFICE
GASKET DRAIN
3/4 NPT
PORT HOSE
3/4 NPT CLAMP
PORT
1" I.D.
OUTLET HOSE
Figure 7-5
External Condensate Trap
7-5
MAINTENANCE
7-6
TROUBLESHOOTING
8.1 INTRODUCTION
This troubleshooting guide is intended to aid When a fault occurs in the Benchmark Boiler,
service/maintenance personnel in isolating the proceed as follows to isolate and correct the
cause of a fault in a Benchmark 3.0 Boiler. The fault:
troubleshooting procedures contained herein are
presented in tabular form on the following pages.
These tables are comprised of three columns 1. Observe the fault messages displayed in the
labeled: Fault Indication, Probable Cause and Control Box display.
Corrective Action. The numbered items in the
Probable Cause and Corrective Action columns 2. Refer to the Fault Indication column in
correspond to each other. For example, Troubleshooting Table 8-1 which follows and
Probable Cause No. 1 corresponds to Corrective locate the Fault that best describes the
Action No. 1, etc. existing conditions.
8-1
APPENDIX B
TABLE 8-1. BOILER TROUBLESHOOTING
8-2
TROUBLESHOOTING
3. Blocked airflow switch 3. Remove the airflow switch and inspect for signs of blockage,
clean or replace as necessary.
4. Defective airflow switch 4. Measure the airflow switch for continuity with the combustion
blower running. If there is an erratic resistance reading or the
resistance reading is greater than zero ohms, replace the switch.
5. Combustion oscillations 5. Run unit to full fire. If the unit rumbles or runs rough, perform
combustion calibration.
6. PROBABLE CAUSES from 3 to 12 6. PROBABLE CAUSES from 3 to 12 for AIRFLOW FAULT
for AIRFLOW FAULT DURING DURING IGNITION applies for this fault
IGNITION applies for this fault
8-3
TROUBLESHOOTING
DIRECT DRIVE 1. Direct drive signal is not present: 1. Check I/O Box to ensure signal is hooked up.
SIGNAL FAULT Not yet installed. Hook up if not installed.
Wrong polarity. If installed, check polarity.
Signal defective at source. Measure signal level.
Broken or loose wiring. Check continuity of wiring between source and boiler.
2. Signal is not isolated (floating). 2. Check signal at source to ensure it is isolated.
3. Control Box signal type selection 3. Check DIP switch on PMC board to ensure it is set correctly for
switches not set for correct signal the type of signal being sent. Check control signal type set in
type (voltage or current). Configuration Menu.
FLAME LOSS 1. Burner Ground Screw not installed 1. Inspect and install/retighten Burner Ground Screw.
DURING IGN or loose.
2. Worn flame detector 2. Remove and inspect the flame detector for signs of wear.
Replace if necessary.
3. No spark from Spark Plug 3. Close the internal gas valve in the boiler. Install and arc a spark
igniter outside the unit.
4. Defective Ignition Transformer 4. If there is no spark, check for 120VAC at the primary side of the
ignition transformer during the ignition cycle.
5. Defective Ignition/Stepper (IGST) 5. If 120VAC is not present, the IGST Board in the Control Box
Board may be defective. Refer fault to qualified service personnel.
6. Defective SSOV 6. While externally arcing the spark igniter, observe the
open/close indicator in the Safety Shut-Off Valve to ensure it is
opening. If the valve does not open, check for 120VAC at the
valve’s input terminals. If 120VAC is not present, the IGST
board in the Control Box may be defective. Refer fault to
qualified service personnel.
8-4
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
8-5
TROUBLESHOOTING
3. Defective High Gas Pressure Switch 3. Remove the leads from the high gas pressure switch and
measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does not
show continuity.
4. Gas pressure snubber not installed. 4. See Figure 8-1. Ensure that the gas pressure snubber is installed
at the high gas pressure switch.
HIGH WATER TEMP 1. Faulty Water temperature switch. 1. Test the temperature switch to insure it trips at its actual water
SWITCH OPEN temperature setting.
2. Incorrect PID settings. 2. Check PID settings against Menu Default settings in the
Appendix. If the settings have been changed, record the current
readings then reset them to the default values.
3. Faulty shell temperature sensor. 3. Using the resistance charts in the Appendix C, Measure the
resistance of Shell sensor and BTU sensor at a known water
temperature.
4. Unit in Manual mode 4. If unit is in Manual Mode switch to Auto Mode.
5. Unit setpoint is greater than Over 5. Check setpoint of unit and setpoint of Temperature Switch;
Temperature Switch setpoint. Ensure that the temperature switch is set higher than the unit’s
setpoint.
6. Boiler Management System PID or 6. Check the BMS for changes to PID default values, correct as
other settings not correctly setup. necessary.
7. No interlock to boiler or BMS to 7. If system pump is controlled by Energy Management System
disable boiler(s) in event that system other than BMS or pumps are individually controlled by boiler,
pumps have failed. check to see if there are flow switches interlocked to the BMS or
boiler.
8. System flow rate changes are 8. If the system is a variable flow system, monitor system flow
occurring faster than boilers can changes to ensure that the rate of flow change is not faster than
respond. what the boilers can respond to.
8-6
TROUBLESHOOTING
8-7
TROUBLESHOOTING
8-8
TROUBLESHOOTING
8-9
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
8-10
TROUBLESHOOTING
8-11
TROUBLESHOOTING
Figure 8-2
Staged Ignition Solenoid Location
Figure 8-1
High Pressure Gas Switch & Snubber Locations
Figure 8-3
Damping Orifice Location
8-12
RS232 COMMUNICATION
9-1
RS232 COMMUNICATION
(c) Menu changes will be stored in non- 9.4.2 Operation Time Log
volatile memory.
The Operation Time Log consists of a string of
9. To redisplay the menu and view the option ASCII records stored in non-volatile memory
which was just changed in step 5, enter D within the C-More Control Panel. Events such
and press <Rtn>. as power-up, ignition and turn-off are time
10. To display the Fault (F) Log, Sensor (S) Log stamped. Data logged while the unit is running
or Time (T) Line Log, press F, S or T are run-length encoded. Data is logged or the
followed by <Rtn>. Refer to paragraph 9.4 for run-length incremented every 30 seconds. For a
descriptions and samples of these data logs. new run record to be logged, the fire rate or
flame strength must change by more than 5%,
11. To log off and terminate the RS232 com- or the run mode must change. At steady-state,
munication link, press L followed by <Rtn>. the run-length is allowed to reach a maximum of
30 minutes before the record is logged. This
9.4 DATA LOGGING means that no more than 30 minutes of data can
be lost if the unit loses power. Table 9-2 shows
During operation, the C-More Control Panel a sample Operation Time Log for a boiler:
continuously monitors and logs data associated
with operational events, faults and sensor The Operation Time Log can only be accessed
readings associated with the boiler or water through the RS232 interface using a laptop or
heater system. Descriptions of these data logs other terminal device. Ten operation time
are provided in the following paragraphs. The records are displayed for each T command
basic procedure for accessing each data log is entry. The operation time log can be cleared
described in paragraph 9.3, step 7. ONLY by factory authorized personnel using the
Clear Log option in the Factory menu.
9.4.1 Fault Log
The C-More Control Panel logs the last 10 faults NOTE:
(0 – 9) starting with the most recent (#0). They The Sensor (S) Log can store up to 1200
can be viewed in the front panel display or via records. Therefore, to view the most
the RS232 port. The Fault Log cannot be recently logged record, enter “S” followed
cleared. If the Fault Log already contains 10 by 0 (zero) and then press Enter (i.e. S0
faults, the earliest fault is overwritten when a <Enter>). To view earlier records in
new fault occurs. A sample Fault Log display is reverse chronological order, enter S and
shown in Table 9-1. press Enter. To go back 200 or 700
records, enter S200 or S700, etc. and
NOTE: press Enter.
The Operation Time (T) Log can store
thousands of records. Therefore, to view 9.4.3 Sensor Log
the most recently logged record, enter “T”
The sensor values can be logged at a different
followed by 0 (zero) and press Enter
rate if needed by setting the Sensor Log Interval
(i.e. T0 <Enter>). To view earlier records
in the Diagnostics Menu. The log interval can
in reverse chronological order, enter T
vary from once every minute to once every day.
and press Enter. To go back 200 or 1000
Table 9-3 shows a sample Sensor Log every 5
records, enter T200 or T1000, etc. and
minutes for a boiler running in Constant Setpoint
press Enter.
mode.
9-2
RS232 COMMUNICATION
Setpt Outlet Outdr FFWD Aux Inlet Exhst CO O2 Flow Date Time
130 181 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:51pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:46pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:41pm
130 179 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:36pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:31pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:26pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:21pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:16pm
130 179 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:11pm
130 180 OPEN OPEN OPEN OPEN OPEN 0 .0 0 1/15/02 5:06pm
9-3
APPENDIX A
A-1
APPENDIX A
A-2
APPENDIX A
A-3
APPENDIX A
A-4
APPENDIX A
A-5
APPENDIX B
MESSAGE DESCRIPTION
DEMAND DELAY Displayed if Demand Delay is active.
XX sec
DISABLED Displayed if ON/OFF switch is set to OFF. The display also
HH:MM pm, pm shows the time (am or pm) and date that the unit was
MM/DD/YY disabled.
FLAME PROVEN Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
of flame strength.
IGNITION TRIAL Displayed during ignition trial of startup sequence. The
XX sec duration of cycle counts up in seconds.
PURGING Displayed during the purge cycle during startup. The
XX sec duration of the purge cycle counts up in seconds.
STANDBY Displayed when ON/OFF switch is in the ON position, but
there is no demand for heat. The time and date are also
displayed.
WAIT Prompts the operator to wait.
WARMUP Displayed for 2 minutes during the initial warm-up only.
XX sec
B-1
APPENDIX B
B-2
APPENDIX B
B-3
APPENDIX C
C-1
APPENDIX D
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
50F 50 50 50 50 50 50 50 50 50 50
45F 53 54 55 56 57 58 59 60 60 62
40F 56 58 60 62 64 66 68 70 72 74
35F 59 62 65 68 71 74 77 80 83 86
30F 62 66 70 74 78 82 86 90 94 98
25F 65 70 75 80 85 90 95 100 105 110
20F 68 74 80 86 92 98 104 110 116 122
15F 71 78 85 92 99 106 113 120 127 134
10F 74 82 90 98 106 114 122 130 138 146
5F 77 86 95 104 113 122 131 140 149 158
0F 80 90 100 110 120 130 140 150 160 170
-5F 83 94 105 116 127 138 149 160 171 182
-10F 86 98 110 122 134 146 158 170 182 194
-15F 89 102 115 128 141 154 167 180 193 206
-20F 92 106 120 134 148 162 176 190 204 218
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
60F 60 60 60 60 60 60 60 60 60 60
55F 63 64 65 66 67 68 69 70 71 72
50F 66 68 70 72 74 76 78 80 82 84
45F 69 72 75 78 81 84 87 90 93 96
40F 72 76 80 84 88 92 96 100 104 108
35F 75 80 85 90 95 100 105 110 115 120
30F 78 84 90 96 102 108 114 120 126 132
25F 81 88 95 102 109 116 123 130 137 144
20F 84 92 100 108 116 124 132 140 148 156
15F 87 96 105 114 123 132 141 150 159 168
10F 90 100 110 120 130 140 150 160 170 180
5F 93 104 115 126 137 148 159 170 181 192
0F 96 108 120 132 144 156 168 180 192 204
-5F 99 112 125 138 151 164 177 190 203 216
-10F 102 116 130 144 158 172 186 200 214
-15F 105 120 135 150 165 180 195 210
-20F 108 124 140 156 172 188 204
D-1
APPENDIX D
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
65 65 65 65 65 65 65 65 65 65 65
60 68 69 70 71 72 73 74 75 76 77
55 71 73 75 77 79 81 83 85 87 89
50 74 77 80 83 86 89 92 95 98 101
45 77 81 85 89 93 97 101 105 109 113
40 80 85 90 95 100 105 110 115 120 125
35 83 89 95 101 107 113 119 125 131 137
30 86 93 100 107 114 121 128 135 142 149
25 89 97 105 113 121 129 137 145 153 161
20 92 101 110 119 128 137 146 155 164 173
15 95 105 115 125 135 145 155 165 175 185
10 98 109 120 131 142 153 164 175 186 197
5 101 113 125 137 149 161 173 185 197 209
0 104 117 130 143 156 169 182 195 208
-5 107 121 135 149 163 177 191 205 219
-10 110 125 140 155 170 185 200 215
-15 113 129 145 161 177 193 209
-20 116 133 150 167 201 218
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
70F 70 70 70 70 70 70 70 70 70 70
65F 73 74 75 76 77 78 79 80 81 82
60F 76 78 80 82 84 86 88 90 92 94
55F 79 82 85 88 91 94 97 100 103 106
50F 82 86 90 94 98 102 106 110 114 118
45F 85 90 95 100 105 110 115 120 125 130
40F 88 94 100 106 112 118 124 130 136 142
35F 91 98 105 112 119 126 133 140 147 154
30F 94 102 110 118 126 134 142 150 158 166
25F 97 106 115 124 133 142 151 160 169 178
20F 100 110 120 130 140 150 160 170 180 190
15F 103 114 125 136 147 158 169 180 191 202
10F 106 118 130 142 154 166 178 190 202 214
5F 109 122 135 148 161 174 187 200 213
0F 112 126 140 154 168 182 196 210
-5F 115 130 145 160 175 190 205
-10F 118 134 150 166 182 198 214
-15F 121 138 155 172 189 206
-20F 124 142 160 178 196 214
D-2
APPENDIX D
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
75F 75 75 75 75 75 75 75 75 75 75
70F 78 79 80 81 82 83 84 85 86 87
65F 81 83 85 87 89 91 93 95 97 99
60F 84 87 90 93 96 99 102 105 108 111
55F 87 91 95 99 103 107 111 115 119 123
50F 90 95 100 105 110 115 120 125 130 135
45F 93 99 105 111 117 123 129 135 141 17
40F 96 103 110 117 124 131 138 145 152 159
35F 99 107 115 123 131 139 147 155 163 171
30F 102 111 120 129 138 147 156 165 174 183
25F 105 115 125 135 145 155 165 175 185 195
20F 108 119 130 141 152 163 174 185 196 207
15F 111 123 135 147 159 171 183 195 207 219
10F 114 127 140 153 166 179 192 205 218
5F 117 131 145 159 173 187 201 215
0F 120 135 150 165 180 195 210
-5F 123 139 155 171 187 203 219
-10F 126 143 160 177 194 211
-15F 129 147 165 183 201 219
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
80F 80 80 80 80 80 80 80 80 80 80
75F 83 84 85 86 87 88 89 90 91 92
70F 86 88 90 92 94 96 98 100 102 104
65F 89 92 95 98 101 104 107 110 113 116
60F 92 96 100 104 108 112 116 120 124 128
55F 95 100 105 110 115 120 125 130 135 140
50F 98 104 110 116 122 128 134 140 146 152
45F 101 108 115 122 129 136 143 150 157 164
40F 104 112 120 128 136 144 152 160 168 176
35F 107 116 125 134 143 152 161 170 179 188
30F 110 120 130 140 150 160 170 180 190 200
25F 113 124 135 146 157 168 174 190 201 212
20F 116 128 140 152 164 176 188 200 212
15F 119 132 145 158 171 184 197 210
10F 122 136 150 164 178 192 206
5F 125 140 155 170 185 200 215
0F 128 144 160 176 192 208
-5F 131 148 165 182 199 216
-10F 134 152 170 188 206
D-3
APPENDIX D
RESET RATIO
Air 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Temp
90F 90 90 90 90 90 90 90 90 90 90
85F 93 94 95 96 97 98 99 100 101 102
80F 96 98 100 102 104 106 108 110 112 114
75F 99 102 105 108 111 114 117 120 123 126
70F 102 106 110 114 118 122 126 130 134 138
65F 105 110 115 120 125 130 135 140 145 150
60F 108 114 120 126 132 138 144 150 156 162
55F 111 118 125 132 139 146 153 160 167 174
50F 114 122 130 138 146 154 162 170 178 186
45F 117 126 135 144 153 162 171 180 189 198
40F 120 130 140 150 160 170 180 190 200 210
35F 123 134 145 156 167 178 189 200
30F 126 138 150 162 174 186 198 210
25F 129 142 155 168 181 194 207
20F 132 146 160 174 188 202 216
15F 135 150 165 180 195 210
10F 138 154 170 186 202 218
5F 141 158 175 192 209
0F 144 162 180 198 216
D-4
APPENDIX E
E-1
APPENDIX E
E-2
HEAT EXCHANGERS & COMBUSTION CHAMBER DESIGN STANDARDS LIFTING LUGS
MAX. WORKING MAXIMUM TEST PRESS. HT'G SURFACE MIN. RELIEF VA. 7 15/16 3/4" ELECTRICAL
PRESS. (PSIG) TEMP. (°F) (PSIG) SQ.FT. CAPACITY MBH (20.1) CONDUIT CONNECTION
160 210 240 178 3000
14 5/16
ASME B & PV CODE: SECTION IV STAMP H (PRIMARY H.X.)
(36.4)
SECTION VIII STAMP U (SECONDARY H.X.) 28
8" EXHAUST (71.1)
OUTLET 15
7 7/16 (38.0)
(18.9)
33
8" AIR INLET 6 7/8 (84.7)
(17.4) 64 (162.6) 23
(58.4)
DOOR SWING
78 (198.1)
38
(96.7)
THIS AREA TO BE
ACCESSIBLE FOR 18
PRESS. RELIEF VALVE MAINTENANCE. (45.7)
4"-150# FLG'D 2 5/8
HOT WATER OUTLET CONN. (SEE NOTE 3) (6.6)
PRESS./TEMP. GAUGE CONTROL
PANEL
DISPLAY
69 5/8
54 5/16
(176.9)
(137.0) 4"-150# FLG'D
BMK3.0 LN DIM. DIM. DIM. COLD WATER
MODEL "A" "B" "C" INLET CONN.
CONDENSATE PORT
25 5/16
(64.3) 79
NAT. GAS 28 15/16 (201.4)
N/A FOR IRI 2" NPT NATURAL GAS 5 7/8
ONLY (73.5)
GAS TRAIN INLET CONN. (14.9)
OPTION 42 1/8
DUAL-FUEL (107.0) 1" NPT GAS
25 7/16 15 7/16 VENT CONN.
WITH FM N/A 36 11/16
GAS TRAIN
(64.6) (39.2) FOR "IRI" GAS
(93.2)
TRAIN OPTION" ONLY
DUAL-FUEL
25 7/16 16 3/16 12 1/16 "A" "C" "B"
WITH IRI 13.5
GAS TRAIN
(64.6) (41.1) (30.6)
(34.3)
5 1/4
(13.3) 12 3/4 2" NPT PROPANE GAS
INLET CONN. CONDENSATE PORT NORTHVALE, NJ 07647
(32.4) 1-1/2" NPT
AERCO
FOR DUAL-FUEL
23 3/16 (58.8) DRAIN CONN. OPTION ONLY
4" CONCRETE PAD - SET BENCHMARK 3 MIL. LOW NOx BTU
23 5/8 (60.0)
UNIT FLUSH AT REAR GAS FIRED BOILER
NOTES:
DIMENSIONAL DRAWINGS
1) ALL DIMENSIONS SHOWN ARE IN INCHES (CENTIMETERS).
2) RELIEF VALVE, TRIDICATOR & CONDENSATE TRAP ARE INCLUDED SEPARATELY IN SHIPMENT. DWN.BY CZ DATE072606 REV.
SCALE SIZE A
3) FIELD PIPING TO THE BOILER MUST ENSURE THAT THE HOT WATER OUTLET CONNECTION FLEXIBLE PIPING AP-A-811 E
CHKD. APPD.
(LOCATED INSIDE THE BOILER) IS LEVEL OR SLOPING UP AS IT EXITS THE BOILER. REV.DATE
F-1
APPENDIX F
F-2
ANCHOR HOLE 4 X Ø.75 (Ø1.91) THRU HOLES
4 PL
APPENDIX F
23
26
FRONT (66.0) (58.4) 28 REAR
(71.1)
1 1/2
9 36 7/8
(3.8)
(22.9) (93.7)
62
(157.5)
64
(162.6)
INTERNATIONAL, INC.
AERCO NORTHVALE, NJ 07647
24"
78" 18"
56"
101"
79"
43" 24"
(SEE NOTE)
24"
REAR FRONT
F-3
APPENDIX F
F-4
SIDE VIEW TOP VIEW
APPENDIX F
78" 18"
24"
43" 24"
101" 28"
(SEE NOTE)
79"
24"
REAR FRONT
INSTALLATION CLEARANCES
1) THIS APPLIANCE MAY BE INSTALLED ON COMBUSTIBLE FLOORING
2) MINIMUM CLEARANCES TO ADJACENT CONSTRUCTION ARE AS FOLLOWS:
PRESSURE SNUBBER
P/N: 99017 TO AIR/FUEL VALVE
ASSEMBLY
F-5
APPENDIX F
F-6
HIGH GAS PRESS. 1/8" NPT PLUG
SWITCH (INSTALL
BOILER BOUNDARY P/N: 61002-3 MANOMETER HERE)
SAFETY SHUT-OFF
VALVE ACTUATOR w/ GAS
PRESSURE ADJUSTMENT
FULL PORT P/N 64048
BALL VALVE
2" NPT
P/N: 123540
2"-SCH.40 PIPE
1"-SCH.40 PIPE
13
3 INTERNATIONAL, INC.
AERCO NORTHVALE, NJ 07647
2
BENCHMARK 3.0 LOW NOx
BURNER ACCESSORIES
DWN.BY CZ DATE 072606 REV.
SCALE SIZE
CHKD. APPD. PL-A-151 D
REV. DATE
F-7
APPENDIX F
APPENDIX F
BMK3.0LN STAGED
8 24227 1
IGNITION ASSY.
HEAT EXCHANGER
ITEM PART NO. QTY DESCRIPTION
PRIMARY HEAT EXCH.
11 80018 1
UPPER INSULATION
PRIMARY HEAT EXCH.
12 80019 1
LOWER INSULATION
13 80020 1 SECONDARY HEAT EXCH.
INSULATION
14 28030 1 PRIMARY HEAT EXCH.
15 28029 1 SECONDARY HEAT EXCH.
BLOWER
ITEM PART NO. QTY DESCRIPTION
16 24045 1 BLOWER ASSEMBLY
17 123815 1 IRIS AIR DAMPER
18 123681 1 8"x6" REDUCING COUPLING
19 33028 1 BLOWER BRACKET
20 124245 4 5/16 DAMPENER
21 81057 1 BLOWER GASKET
22 96006 1 6" 90 DEG ELBOW
23 96009 1 6" DIAM. x 4" LG DUCT W/PORT
24 96008 1 6" DIAM. x 4" LG DUCT
25 123990 1 REDUCER OFFSET COVER AERCO INTERNATIONAL,
NORTHVALE, NJ
INC.
07647
26 123583 1 CLAMP HOSE SAE #96 BENCHMARK 3.0 LOW NOx
BOILER PARTS LIST
DRAWN BY SJD PL - A - 150
DATE 2/18/09 (SHEET 1 OF 7)
H
F-8
APPENDIX F
46 1
64068 VFD
47 93230 1 ORIFICE SNUBBER
(4) 48 124310 1 460V TRANSFORMER SHEET METAL / PANEL ASSEMBLY
(4) 49 124380 1 500 VAC, 4 AMP FUSE ITEM PART NO QTY DESCRIPTION
(4) 50 58009 1 460V Terminal Cover Kit 80 37004 1 LEFT REAR PANEL
DRIVE REACTOR TO VFD 81 37003 1 RIGHT REAR PANEL
(1) 51 63060 1
WIRING HARNESS
82 49028 2 TOP RAIL
(4) 52 79002 1 460V TRANSFORMER LABEL
83 201233 1 MOUNTING PANEL
53 61024 1 AIR TEMP SENSOR
FRONT PANEL
84 201113 1
ENCLOSURE
55 GP- 122569 1 IGNITION CABLE ASSY. 85 201120 1 FRONT DOOR ASSY.
56 63016 1 BMK3.0LN SHELL HARNESS 86 GP-122620 4 HANDLE
57 124320 1 BLOWER HARNESS 87 30022 2 TOP PANEL
88 37002 4 SIDE PANEL
89 74004 1 BMK3.0LN LOGO
58
OTHER PARTS
F-9
APPENDIX F
1
2
11
13
15 14
12
3 53 2 6 8
25 61 92
18
24
17 9
10
55
39
23 40 BLOWER PROOF SWITCH
41
38
44
22
26
47
16
DETAIL A
SCALE 1 : 10
AERCO INTERNATIONAL,
NORTHVALE, NJ
INC.
07647
5
BENCHMARK 3.0 LOW NOx
BOILER PARTS LIST
DRAWN BY SJD PL - A - 150
DATE 2/18/09 (SHEET 3 OF 7)
H
F-10
APPENDIX F
31 67 34 30 28
20
19
B
71
4
B SECTION B-B
SCALE 1 : 18
36
70
34 32 29 33 34
21 27 7
35 62
63 AERCO INTERNATIONAL,
NORTHVALE, NJ
INC.
07647
BENCHMARK 3.0 LOW NOx
BOILER PARTS LIST
DRAWN BY SJD PL - A - 150
DATE 2/18/09 (SHEET 4 OF 7)
H
F-11
APPENDIX F
59
37 46
DETAIL B:
43 TERMINAL COVER
ARE HIDEN
B
45
42 48
C
52 50
SEE 49
DETAIL C DETAIL C:
FUEL SELECTOR SWITCH
(DUAL FUEL ONLY)
78
76 77 79
65
90
56
64
57
AERCO INTERNATIONAL,
NORTHVALE, NJ
INC.
07647
BENCHMARK 3.0 LOW NOx
BOILER PARTS LIST
DRAWN BY SJD PL - A - 150
DATE 2/18/09 (SHEET 5 OF 7)
H
F-12
APPENDIX F
82
83
80 81
AERCO INTERNATIONAL,
NORTHVALE, NJ
INC.
07647
BENCHMARK 3.0 LOW NOx
BOILER PARTS LIST
DRAWN BY SJD PL - A - 150
84 H
DATE 2/18/09 (SHEET 6 OF 7)
F-13
APPENDIX F
F-14
LEGEND
AUTOMATIC Y STRAINER
CHECK SYSTEM AIR VENT
HEATING VALVE RELIEF ISOLATION VALVE
PUMP
SYSTEM (TYP.) VALVE (TYP.) UNION
SUPPLY BALANCING VALVE
P&T
PRESSURE &
AIR TEMPERATURE GAUGE
WATER SEPARATOR AT MAXIMUM BTU/HR INPUT,
SUPPLY MAINTAIN MINIMUM NATURAL GAS PRESSURE AT
3.5" W.C. (FM GAS TRAIN)/4.0" W.C. (IRI GAS TRAIN)
MAX GAS PRESSURE = 2.0 PSIG.
(SEE NOTE 6)
PRESSURE
REDUCING
FILL VALVE P&T
Diagram 1
(SEE NOTE 8)
MAINTAIN A REGULATED
3.5" W.C. (NAT. GAS, FM/
LINE 4.0" W.C. (NAT. GAS, IRI/GAS
SIZE PRESSURE AT MAX BTU/HR INPUT
BYPASS
(TO BOILER)
BACKFLOW PREVENTER GAS SUPPLY
DIAPHRAGM TYPE
EXPANSION TANK
* 2" MANUAL
HEATING SHUTOFF
1-1/2" NPT SYSTEM VALVE
DRAIN CONN. RETURN DRIP TRAP
GAS SUPPLY
* CONDENSATE DRAIN TRAP * 2" MANUAL
SHUTOFF DRIP TRAP
VALVE
(SEE NOTE 7)
NOTES:
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN
FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A
HEIGHT 18'' ABOVE FLOOR.
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE
BE 6'' AWAY FROM SIDE PANELS. INTERNATIONAL, INC.
AERCO NORTHVALE, NJ 07647
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED BENCHMARK 3 MIL. BTU LOW NOx
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG. GAS FIRED BOILER
SINGLE UNIT INSTALLATION
7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN.
8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE, DWN.BY SD DATE 061506 REV.
SCALE
SEE DIAGRAM 1 APPD. MC DATE
SD-A-681 C
G-1
APPENDIX G
HEATING CHECK RELIEF
G-2
SYSTEM VALVE VALVE (TYP.)
AUTOMATIC
SUPPLY (TYP.) SYSTEM AIR VENT AT MAXIMUM BTU/HR INPUT, LEGEND
PUMP MAINTAIN MINIMUM NATURAL GAS
AIR PRESSURE AT 3.5" W.C. (FM GAS Y STRAINER
WATER SEPARATOR TRAIN)/4.0" W.C. (IRI GAS TRAIN) ISOLATION VALVE
SUPPLY MAX GAS PRESSURE = 2.0 PSIG. UNION
(SEE NOTE 6) BALANCING VALVE
P&T
PRESSURE &
APPENDIX G
TEMPERATURE GAUGE
PRESSURE
REDUCING
FILL VALVE P&T
LINE
SIZE
BYPASS
BACKFLOW PREVENTER
P&T
Diagram 1
(SEE NOTE 8)
DIAPHRAGM TYPE
MAINTAIN A REGULATED EXPANSION TANK
4" W.C. GAS PRESSURE
AT MAX BTU/HR INPUT
1-1/2" NPT
DRAIN CONN.
(TO BOILER) * 2" MANUAL
SHUTOFF
GAS SUPPLY
VALVE
NOTES:
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN
FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A
HEIGHT 18'' ABOVE FLOOR.
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE
BE 6'' AWAY FROM SIDE PANELS. INTERNATIONAL, INC.
AERCO NORTHVALE, NJ 07647
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED BENCHMARK 3 MIL. BTU LOW NOx
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG. GAS FIRED BOILER
7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN. MULTIPLE UNIT INSTALLATION
8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE. DWN.BY SD DATE 061506 REV.
SCALE
SEE DIAGRAM 1 APPD. MC DATE
SD-A-682 C
APPENDIX G
G-3
G-4
HEATING CHECK LEGEND
SYSTEM VALVE Y STRAINER
AUTOMATIC
SUPPLY (TYP.) SYSTEM AIR VENT ISOLATION VALVE
PUMP
RELIEF UNION
AIR
VALVE (TYP.) BALANCING VALVE
WATER SEPARATOR
SUPPLY P&T
PRESSURE &
TEMPERATURE GAUGE
APPENDIX G
PRESSURE
REDUCING AT MAXIMUM BTU/HR INPUT,
FILL VALVE MAINTAIN MINIMUM NATURAL GAS PRESSURE AT
P&T 3.5" W.C. (FM GAS TRAIN)/4.0" W.C. (IRI GAS TRAIN)
MAX GAS PRESSURE = 2.0 PSIG.
(SEE NOTE 6)
P&T
LINE
SIZE
BYPASS
BACKFLOW PREVENTER
DIAPHRAGM TYPE
EXPANSION TANK
P&T
Diagram 1
(SEE NOTE 8)
P&T
MAINTAIN A REGULATED
4" W.C. GAS PRESSURE
AT MAX BTU/HR INPUT 1-1/2" NPT
DRAIN CONN.
* CONDENSATE DRAIN TRAP
(TO BOILER) * 2" MANUAL
SHUTOFF
GAS SUPPLY
(SEE NOTE 7) VALVE
DRIP TRAP
* 2" MANUAL
SHUTOFF
VALVE HEATING
SYSTEM
DRIP TRAP RETURN
GAS SUPPLY
NOTES:
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN
FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A
HEIGHT 18'' ABOVE FLOOR.
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE INTERNATIONAL, INC.
BE 6'' AWAY FROM SIDE PANELS. AERCO NORTHVALE, NJ 07647
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED. BENCHMARK 3 MIL. BTU LOW NOx
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED GAS FIRED BOILER MULT. INSTALLATION
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG. WITH ZERO SIDE CLEARANCE
7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN. SD
DWN.BY DATE 072606 REV.
8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE. SCALE
APPD. DATE
SD-A-691 C
SEE DIAGRAM 1
APPENDIX G
G-5
APPENDIX H
141 193 136 135 138 190 172 170 168 166 164 162 152 150 148 146
173 171 169 167 165 163 161 133 134
191 194 137 155 154 192 140 195 153 151 149 147 145
IGNITION
TRANSFORMER
141
FLAME ROD
1 149 148
352
CLOSURE SWITCH
SHUTOFF VALVE
153 151
351
321
SHELL
WHT
GRN
RED
2 10K TEMP.
IGNITOR
PROOF OF
SENSOR
SAFETY
NC C
1K
3
POSITION
POSITION
STEPPING G
IGNITION
A H N
SWITCH
SWITCH
MOTOR
PURGE
142
5K B
147
154 146
53
AIR/FUEL VALVE C 152 150 145
FUSE
MANUAL RESET AUTO RESET 200
201 364
OVER TEMPERATURE SWITCHES TO I/O BOX
FUSE
AIR TEMP
SENSOR
363
207 24 VAC 202
209 XFMR
208 204
TO I/O BOX
0-10V
6 PIN CONNECTOR AGND
201 GND 260
FUSE BLOCK
190 202 NEU 203
204 20 AMP
191 203 263 333
T1 T2 T3 T4 T5 T6
BLOWER
L3 263 333 333 303
208 VAC L3 L1 U MOTOR
192 206 20 AMP
3O L2 262 262 332 332 332 302
193 209 60 HZ L2 L2 V
200 20 AMP
194 208 L1 261 261 331 331 331 301
L3 W
195 260 142
L1
GND BLOCK A1 A2 B1 B2 C1 C2 PE PE
206 330 375 300
321 330 GND
TO CONTROL BOX
ENCLOSURE { 320 366 DRIVE
POWER BOX VFD
REACTOR
SOLENOID 350 375
WIRING SCHEMATIC, BMK 3.0 LN
208 VAC, 3 PHASE
H-1
1
OUTDOOR AIR SENSOR IN
FROM AIR 2
SENSOR COMMON IN
TEMP SENSOR 3
AUX SENSOR IN
4
+
CO SENSOR IN 5
-
6
+
FLOW SENSOR IN 7
-
8
+
OXYGEN SENSOR IN 9
-
10
SENSOR EXCIT. (12 VDC)
11
+
ANALOG IN 12
-
13
+
BMS (PWM) IN 14
-
15
SHIELD 16
1
+
ANALOG OUT 2
-
1
+
2
RS-485 IN GND
3
-
1
A
IN 2
B
3
0-10V
TO VFD 4
AGND
NOT USED 7
6
N.O.
AUX 5
C
RELAY N.C. 4
N.O. 3
FAULT 2
C
RELAY N.C. 1
7
NOT USED 6
IN
DELAYED INTLK 5
OUT
4
IN
EXHAUST TEMP 3
OUT
2
IN
1
REMOTE INTLK OUT
H-2
APPENDIX H
APPENDIX H
141 193 136 135 138 190 172 170 168 166 164 162 152 150 148 146 133 134
191 194 137 155 154 192 140 195 173 171 169 167 165 163 161 153 151 149 147 145
IGNITION
AIR
TEMP.
SENSOR
GND
1 149 148
FLAME ROD
SHELL
352
351
153 151
321
SHUTOFF VALVE
BLOCKED AIR INLET SW.
TEMP.
YEL
CLOSURE SWITCH
HIGH GAS PRESS. SW.
2 10K SENSOR
IGNITOR
WHT
GRN
RED
BLU
SAFETY
BLK
PROOF OF
NC C
POSITION
MOTOR
142
POSITION
IGNITION
SWITCH
SWITCH
PURGE
5K B
147
146
154 53
C 152 150 145
AIR/FUEL VALVE
SHIELD
363 TO I/O BOX
AIR TEMP
364 SENSOR
137 209 136
375 375
SOLENOID 350
H-3
1
OUTDOOR AIR SENSOR IN
FROM AIR 2
SENSOR COMMON IN
TEMP SENSOR 3
AUX SENSOR IN
4
+
CO SENSOR IN 5
-
6
+
FLOW SENSOR IN 7
-
8
+
OXYGEN SENSOR IN 9
-
10
SENSOR EXCIT. (12 VDC)
11
+
ANALOG IN 12
-
13
+
BMS (PWM) IN 14
-
15
SHIELD 16
1
+
ANALOG OUT 2
-
1
+
2
RS-485 IN GND
3
-
1
A
IN 2
B
3
0-10V
TO VFD 4
AGND
NOT USED 7
6
N.O.
AUX 5
C
RELAY N.C. 4
N.O. 3
FAULT 2
C
RELAY N.C. 1
7
NOT USED 6
IN
DELAYED INTLK 5
OUT
4
IN
EXHAUST TEMP 3
OUT
2
IN
1
REMOTE INTLK OUT
H-4
APPENDIX H
APPENDIX H
H-5
APPENDIX H
232 234 236 238 240 242 244 246 250 252 254 220 215 213 211
231 233 235 237 239 241 243 245 247 251 253 226 221 219 216 214 212
J3 J2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
J1
LS4
LS3
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
1
2
1
2
3
1
2
3
4
LS2 LS1
AGND
A
B
OUTDOOR AIR SENSOR IN
SENSOR COMMON IN
0-10V
AUX SENSOR IN
7
6
5
4
3
2
1
7
6
5
4
3
2
1
RS-485 IN GND
+
+
-
-
SHIELD
ANALOG OUT
SENSOR EXCIT. (12 VDC)
ANALOG IN
OUT
BMS (PWM) IN
IN
FLOW SENSOR IN
CO SENSOR IN
OXYGEN SENSOR IN
OUT
OUT
N.O.
N.O.
N.C.
N.C.
C
IN
IN
IN
NOT USED
DELAYED INTLK
REMOTE INTLK
EXHAUST TEMP
NOT USED
RELAY
FAULT
RELAY
AUX
TO VFD
AUX SENSOR IN
FROM AIR
SENSOR
TEMP
INPUT/OUTPUT BOX
H-6
APPENDIX H
H-7
1
OUTDOOR AIR SENSOR IN
FROM AIR 2
SENSOR COMMON IN
TEMP SENSOR 3
AUX SENSOR IN
4
+
CO SENSOR IN 5
-
6
+
FLOW SENSOR IN 7
-
8
+
OXYGEN SENSOR IN 9
-
10
SENSOR EXCIT. (12 VDC)
11
+
ANALOG IN 12
-
13
+
BMS (PWM) IN 14
-
15
SHIELD 16
1
+
ANALOG OUT 2
-
1
+
2
RS-485 IN GND
3
-
1
A
IN 2
B
3
0-10V
TO VFD 4
AGND
NOT USED 7
6
N.O.
AUX 5
C
RELAY N.C. 4
N.O. 3
FAULT 2
C
RELAY N.C. 1
7
NOT USED 6
IN
DELAYED INTLK 5
OUT
4
IN
EXHAUST TEMP 3
OUT
2
IN
1
REMOTE INTLK OUT
H-8
APPENDIX H
APPENDIX I
RECOMMENDED PERIODIC TESTING CHECK LIST
WARNING
NOTE: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as
designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property
damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive
maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.
Accomplished
Item Frequency By Remarks
Refer to indicated paragraphs of this manual for detailed procedures
Gauges, monitors and Visual inspection and record readings in operator
Daily Operator
indicators log
Instrument and Visual check against factory recommended
Daily Operator
equipment settings specifications
Weekly Operator Verify factory settings
Semi- Service
Firing Rate Control Verify factory settings
Annually Technician
Service Check with combustion calibration test
Annually
Technician equipment. See paragraph 7.4 and Chapter 4.
Flue, vent, stack or Visually inspection condition and check for
Monthly Operator
intake air duct obstructions
Igniter Weekly Operator See paragraph 7.2
Air/Fuel Valve position Weekly Operator Check position indicator dial (paragraph 3.8)
Service Check for leakage in accordance with the SSOV
SSOV Leakage test Annually
Technician manufacturer’s (Siemens) recommendations.
Close manual gas shutoff valve and check safety
Flame failure Weekly Operator
shutdown. See paragraph 6.7
Check flame strength using the Control Panel
Flame signal strength Weekly Operator
Operating Menu. See paragraph 3.4.
Low water level cut off
Weekly Operator See paragraph 6.4
and alarm
Perform a slow drain test in accordance with
Semi-
Slow drain test Operator ASME Boiler and Pressure Vessel Code,
Annually
Section IV.
High water temperature Service
Annually See paragraph 6.4
safety control test Technician
Operating controls Annually Operator See paragraph 3.2
Low air flow Monthly Operator See paragraph 6.6
High and low gas
Monthly Operator See paragraphs 6.2 and 6.3
pressure interlocks
Air/Fuel Valve purge Service
Annually See paragraph 6.10
position switch Technician
Air/Fuel Valve ignition Service
Annually See paragraph 6.11
position switch Technician
Check per A.S.M.E. Boiler and Pressure Vessel
Safety valves As required Operator
Code, Section IV
Inspect burner Semi- Service See paragraph 7.6
components Annually Technician
I-1
APPENDIX J
J-1
APPENDIX J
P6
P5
P4
P3
P2
P1
J-2
APPENDIX K
NOTE
Refer to the Parts List Illustrations in Appendix F for the
locations of the recommended and optional spare parts
listed in the following Tables.
NOTE:
1. If boiler is installed in the State of Kentucky, contact your local AERCO Sales
Representative for Temperature Switch rated for 200°F max.
K-1
Standard Warranty:
Benchmark Gas-Fired Hydronic Boiler
International, Inc.
The pressure vessel/heat exchanger shall carry a 10-year prorated, limited warranty from shipment
against any failure due to condensate corrosion, thermal stress, mechanical defects or workmanship.
Operation of the boiler using contaminated air will void the warranty. The pressure vessel/heat
exchanger shall not be warranted from failure due to scaling, liming, corrosion, or erosion due to water
or installation conditions. AERCO will repair, rebuild or exchange, at its option the heat
exchanger/combustion chamber according to the following schedule:
AERCO labeled control panels are conditionally warranted against failure for (2) two years from
shipment.
AERCO shall accept no responsibility if such item has been improperly installed, operated, or
maintained or if the buyer has permitted any unauthorized modification, adjustment, and/or repairs to
the item.
The warranty as set forth on the back page of the Operations & Maintenance Manual is in lieu of and
not in addition to any other express or implied warranties in any documents, or under any law. No
salesman or other representative of AERCO has any authority to expand warranties beyond the face of
the said warranty and purchaser shall not rely on any oral statement except as stated in the said
warranty. An Officer of AERCO must do any modifications to this warranty in writing. AERCO
MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR
PURPOSE OR ANY OTHER EXPRESS OR IMPLIED WARRANTIES. AERCO disclaims all
responsibility for any special, incidental or consequential damages. Any claim relating to the product
must be filed with AERCO not later than 14 days after the event-giving rise to such claim. Any claims
relating to this product shall be limited to the sale price of the product at the time of sale. The sale of
the product is specifically conditioned upon acceptance of these terms.
CONDITIONS OF WARRANTY
Should an AERCO gas-fired Hydronic boiler fail for any of the above reasons within the specified time
period from the date of original shipment(s), AERCO shall, at its option, modify, repair or exchange
the defective item. AERCO shall have the option of having the item returned, FOB its factory, or to
make field replacements at the point of installation. In no event shall AERCO be held liable for
replacement labor charges or for freight or handling charges.
AERCO shall accept no responsibility if such item has been improperly installed, operated, or
maintained or if the buyer has permitted any unauthorized modification, adjustment, and/or repairs to
the item. The use of replacement parts not manufactured or sold by AERCO will void any warranty,
express or limited.
In order to process a warranty claim a formal purchase order number is required prior to shipment of
any warranty item. In addition, the returned item must include a Returned Goods Authorization (RGA)
label, attached to the shipping carton, which identifies the item’s return address, register number and
factory authorized RGA number.
Warranty coverage for all components and equipment mentioned in said warranty are not valid unless
the Hydronic boiler is started up by a factory certified SST (Service, Start-Up and Troubleshooting)
Technician and an AERCO start-up sheet is completed.
This warranty coverage is only applicable within the United States and Canada. All other geographical
areas carry a standard warranty of 18 months from date of shipment or 12 months from startup,
whichever comes first.