IOM - YAH-D - Ceiling Mounted FCU
IOM - YAH-D - Ceiling Mounted FCU
IOM - YAH-D - Ceiling Mounted FCU
Main Parameters
Notes:
1. The unit weight listed in table above is shipment weight, based on weight of unit with additional 20%
considered.
TRANSPORTATION & INSTALLATION
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Air Handling Unit
Unit Dimensions
Airflow K
Model
3
m /h Return Fresh
A B C D E F G H J 6 L M N P Q
air air
Rows
4 Rows 4 Rows
YAH1.5B 1500 860 850 417 410 259 228 - 73 53 66 66 110 400 144 319 710 320
YAH02B 2000 860 935 417 410 259 228 - 73 53 66 66 110 400 144 319 795 320
YAH03B 3000 860 1360 417 470 259 228 184 73 53 66 66 110 400 144 319 1220 320
YAH04B 4000 860 1600 417 520 259 228 184 73 53 66 66 110 400 144 319 1460 320
YAH05B 5000 940 1500 508 580 232 262 184 107 63 66 66 110 400 144 420 1360 411
YAH06B 6000 940 1750 508 551 232 262 184 107 63 66 88 110 400 144 420 1610 411
YAH08B 8000 980 2250 508 705 298 262 244 107 63 66 88 110 400 144 420 2110 411
YAH10B 10000 1100 1850 736 690 471 404 - 112 77 83 110 138 441 145 641 1710 639
YAH12B 12000 1150 2150 736 690 373 404 294 112 77 83 110 138 441 145 641 2010 639
YAH15B 15000 1170 2625 736 793 373 40 294 112 77 83 110 138 441 145 641 2485 639
Note: G column expressed with “-” indicates the unit with only one air inlet.
TRANSPORTATION & INSTALLATION
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Air Handling Unit
Note:
1. The coil connecting pipes uses the male thread of which the corresponding diameter in imperial unit
are shown below:
34mm —— 1″
42mm —— 1-1/4″
48mm —— 1-1/2″
60mm —— 2″
76mm —— 2-1/2″
89mm —— 3″
2. Condensate water pipe uses the male thread of 34mm in diameter.
Main Components
The main components of the YORK YAH ceiling air handling unit include:
Main Fittings:
Blower: SYT series double-suction forward centrifugal fan with V-belts transmission.
Motors: IE3 efficiency three-phase asynchronous motor, with class F insulation and IP55 protection rate.
Heat exchanger coil: Cooling/ Heating, 3Rows/4Rows + Heating 1Row/2rows.
Filter: Nylon Filter
Optional Fittings:
Filter: Aluminium Mesh filter, Washable synthetic fiber filter class G3 & G4.
TRANSPORTATION & INSTALLATION
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Air Handling Unit
ELECTRICAL CONNECTION
1. The electrical wiring can be configured by users with reference to Figure 1 or Figure 2, which is not provided with
the standard unit. The wires should be tightened.
2. All electrical connections should meet the local electrical installation standard.
3. The grounding point provided in the unit should be connected to the ground terminal of the unit control box.
4. Check whether every power supply is in accordance to the rating voltage on unit name plate and the power
distribution should adopt a proper fuse.
5. Check whether the protection devices against short circuit, overload and phase loss have been allocated along with
power input connection.
FAN PART
1. Switch off the master switch before carry out an internal inspection to the fan.
2. Check whether the electrical connected components of the unit is in accordance to circuit diagrams.
3. Check the motor’s rating plate and observe whether the rated voltage, phase and circuit are in accrdance with the
power supply recorded in field.
4. Before the fan starts operate, check for foreign matter in the fan housing, then rotate the fan blade manually and
check for any collision and friction to the housing; listen for any abnormal noise produced from bearing. If there is
no abnormity only the fan can be turn on.
5. After the power is switched on, first turn on the fan and check for correct rotate direction. If not, turn off the fan
and change the power phase sequence, then connect it with the power supply formally.
6. Check the motor operating current with ammeter and compare the obtained current value with data indicated in the
motor rating plate.
Maintenance and Repairing
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Fan Coil Unit
MOTOR
It is possible to store the rotation equipment for a certain period of time. Even if the storage time and condition meet the
specifications, a series of electrical and mechanical checks are still necessary.
For the motor of 7.5KW or above, it should be equipped with a voltage dropping starter, avoiding the
over-starting-current.
STORAGE CONDITIONS
The motor should be stored in a dry environment, in which if the humidity exceeds 90%, the motor insulation device are
subject to prompt damage; when the humidity is up to 100%, the insulation device will lose its function completely.
Ambient Temperature
The ambient air temperature changes with the seasons but will not be greater than 40℃.
Four-Point
Inspection
Method
Warning: Over-tightened or loose belt will influence the performance of fan operation.
Maintenance and Repairing
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Fan Coil Unit
Belt Adjustment
1. Before the starting and operation of your unit, check the tension of the belt.
2. After one-week operation, the belt will be expanded slightly. In this case, readjust the tensile force applied to the
belt and make it comply with the specifications listed in the belt Tension Indicator.
3. After 30-day operation of the unit, check the tension of the belt again.
4. After 3-months operation of the unit, make a complete inspection.
Mechanical Inspection
When in contact with air, the grease used to lubricate the bearing will suffer from oxidation or even deterioration.
Applying oxidized lubricating grease shall further shorten the life cycle of motor bearing.
Storage Time
If the motor is lubricated just before it operates, a more effective lubricating effect can be obtained.
Fan Part
1. Before repair the internal part of the fan, switch off the control switch.
2. Check the V-belt and its tension regularly. If it is found that the tensile force applied to the belt is not enough,
retighten it. For correct tension data, refer to the Belt Tension Indicator.
3. Check the alignment of motor, fan V-belt and pulley.
4. Check whether the interior flexible parts are fixed firmly.
5. Check whether the motor can operate freely.
6. Refer to the maintenance instruction provided by the motor supplier.
7. Check if the fan are able to rotate smoothly, check the temperature of bearing.
8. Clean the fan blade regularly.
Fan Bearing
The double suction forward fan used in the YAH unit is designed with sealed bearing and normal service life is 75,000
working hours at least.
Due to continuous improvement and development, we reserve the right of changing the technical specification and
dimension without notice in advance.
Maintenance and Repairing
Installation, Operation and Maintenance Manual of the YAH-D Series Ceiling Fan Coil Unit
MOTOR
Any maintenance should be carried out in comply according to the motor instruction manual. This manual only provide
partial of technical information.
Replacement of Motor
Replace the motor from one side of the unit or after the top or side frame panel is removed.
Failure Analysis
www.johnsoncontrols.com
YAH-D-01IOM(YMM)(1215)
While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press,
we are constantly striving for improvement and therefore please confirm with your local distribution office