Protection Test Report
Protection Test Report
Protection Test Report
2. Equipment details:
Make GE
Type / Model no T60
SI. No. ABHC12000599
RATING 25MVA
VECTOR GROUP YNyn0
HV SIDE-1 CT Ratio 150/1 A
LV SIDE CT Ratio 2500/1 A
PT Ratio 132kV/√3:110V/√3
3. General Inspection : OK
4. Measurements:
INJECTED MEASURED PRIMARY CURRENT VALUES(A)
PHASE SECONDARY
CURRENT(A) HV SIDE LV SIDE
R-N 1∟0° 0.149∟0° 2502∟0° -
Y-N 1∟-120° 0.150∟-120° 2500∟-120° -
B-N 1∟1200° 0.149∟120° 2501∟120° -
HV SIDE-1 LV SIDE
REF
PICKUP CURRENT(A) PICKUP CURRENT(A)
0.168 0.202
3-PH 0.168 0.202
0.168 0.202
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
HV SIDE-1 LV SIDE
REF
PICKUP CURRENT(A) PICKUP CURRENT(A)
0.251 0.300
1-PH 0.250 0.301
0.251 0.300
STABILITY TEST
INJECTED CURRENTS(A) MEASURED VALUES STATUS
Ref
HV SIDE-1 LV SIDE Id Ir
R ph 0.728∟0° 0.874∟180° 0 0.873 RELAY STABLE
Y ph 0.728∟240° 0.874∟60° 0 0.873
B ph 0.728∟120° 0.874∟300° 0 0.873
TRIP TEST:
TIME STATUS
INJECTED CURRENTS(A) MEASURED VALUES
(ms)
Ref
HV SIDE-1 LV SIDE Id Ir
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
SLOPE TEST:
TIME STATUS
INJECTED CURRENTS(A) MEASURED VALUES
(ms)
Ref
HV SIDE-1 LV SIDE Id Ir
R ph 0.167∟0° 0 0.200 0.200 30.4 TRIP
Y ph 0.167∟240° 0 0.200 0.200
B ph 0.167∟120° 0 0.200 0.200
SLPOE:1 SETTING:m1=30%
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
SLOPE=(0.374-0.2)/(1.248-0.636)=28.40 percent…
SLPOE:2 SETTING:m2=80%
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
SLOPE=(10.461-8.725)/(13.083-11.350)=79.85percent…
6. INSTANTANEOUS DIFFERENTIAL:
TIME STATUS
INJECTED CURRENTS(A) MEASURED VALUES
(ms)
Ref
HV SIDE-1 LV SIDE Id Ir
R ph 4.166∟0° 0 4.998 4.998 29.9 TRIP
Y ph 4.166∟240° 0 4.998 4.998
B ph 4.166∟120° 0 4.998 4.998
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
7. HARMONICS TEST:4
8.SEF PROTECTION:
GROUND IOC
Note: SEF (stand by earth fault protection function disable as per the GAIL recommend)
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
2. Equipment details:
Make GE
Type / Model no F650
SI. No. 81.551.704 HW05
CT Ratio 150/1 A
PT RATIO 132KV/√3:110/√3V
3. General Inspection : OK
4.CURRENT Measurements:
1. PHASE CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
2. REF CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
5. voltage measurements:
PH TOC HIGH:
Stage-1 SET CURRENT=0.73A TMS-0.08 Sec Characteristic: IEC A CURVE
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
NEUTRAL TOC:
Stage-1
I=0.2A TMS: 0.08Sec Characteristic: IDMT
70.50°-0°-260.50° 75.50°-180°-255.50°
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
9.BREAKER FAIL:
Stage-1
BREAKER FAIL LOW SET : 2 AMPS.
SET TIME : 0.2 SEC
LBB INITIATION: F CARD INPUT F01
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
2. Equipment details:
Make GE
Type / Model no F650
SI. No. 81.551.703 HW:05
CT Ratio 150/1 A
PT RATIO 132KV/√3:110/√3V
3. General Inspection : OK
4. CURRENT Measurements:
1. PHASE CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
5.voltage measurements:
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
PH TOC HIGH:
Stage-1 SET CURRENT=0.73A TMS-0.08 Sec Characteristic: IEC A CURVE
Set Pick-up Operating Time (sec) at multiple of PS
Phase TMS (Amps) 2xIs 5xIs 10xIs
Current(A)
R 0.73 0.08 0.744 0.835 0.369 0.250
Y 0.73 0.08 0.749 0.837 0.361 0.251
B 0.73 0.08 0.748 0.839 0.359 0.247
Expected Operating Time (Sec) 0.802 0.342 0.238
NEUTRAL TOC
Stage-1 I=0.2A TMS: 0.15Sec Characteristic: IDMT
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
70.50°-0°-260.50° 75.50°-0°-255.50°
8.BREAKER FAIL:
Stage-1
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
9. PT FUSE FAIL:
PT FUSE FAIL CONDITIONS WERE CHECKED BY CUT ANY 1 PHASE VOLTAGE AS WELL AS
ANY 2 PHASE VOLTAGE.CORRESPONDING LEDS WERE CHECKED WHILE FUSE FAIL OPERATION.
NOTE:
IF ALL THE 3 PHASES ARE CUT OFF MEANS RELAY WILL SENSE IT IS A DEAD BUS.
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
2. Equipment details:
Make GE
Type / Model no F650
SI. No. 81.556.591 HW05
CT Ratio 150/1 A
PT RATIO 132KV/√3:110V/√3
3. General Inspection : OK
4. CURRENT Measurements:
1. PHASE CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
5. voltage measurements:
PH TOC HIGH:
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
NEUTRAL TOC:
8. BREAKER FAIL:
Stage-1
BREAKER FAIL LOW SET : 2 AMPS.
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
2. Equipment details:
Make GE
Type / Model no F650
SI. No. 81.540.901 HW:05
CT Ratio 2500/1 A
PT RATIO 6.6kV/√3:110/√3V
3. General Inspection : OK
4. CURRENT Measurements:
1. PHASE CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
5. VOLTAGE measurements:
MEASURED MEASURED
INJECTED VOLTAGE RELAY PT
VOLTAGE(PH-PH) VOLTAGE (PH-N)
PHASE VOLTS MODULE
KV KV
RN 63.51∟0° 6.580 ∟-329.9° 3.807 ∟0° A5-A6
PH TOC HIGH: 50
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
PH IOC HIGH: 51
NEUTRAL TOC:
Stage-1
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
8. SEF:
ISG:
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
2. Equipment details:
Make GE
Type / Model no F650
SI. No. 81.603.001.HW:202
CT Ratio 2500/1 A
3. General Inspection : OK
4. CURRENT Measurements:
1. REF CT
INJECTED MEASURED
Ref
CURRENT CURRENT RELAY CT
MODULE
PHASE AMPS KAMPS
SWL EIL/GAIL
Sign Sign
Name Name
Date Date
STERLING AND WILSON LIMITED ANNEXURE-B
5. REF:
Injected
SET CURRENT SET TIME Operated time
Ref Current
(Amps) (Sec) (sec)
(Amps)
ISG 0.1 0.0 0.15 0.030
SWL EIL/GAIL
Sign Sign
Name Name
Date Date