Loop Impedance - B1
Loop Impedance - B1
Loop Impedance - B1
Phase-Earth Phase-Neutral
Socket PEFC PSC Room
Reference Impedance Prospective Impedance Prospective Reference Remarks
(ohm) earth fault (ohm) Short circuit
Current (A) current (A)
AD-LG-DB01-
0.42 565 0.49 484 PLT-1-LG-02 PASS
B1
AD-LG-DB01-
0.33 712 0.33 712 PLT-1-LG-22 PASS
R1
SIGNATURE
NAME SHAHUL MUNIR MOHAMED
DATE 21-12-2019 21-12-2019
Client: Contractor:
MAINTENANCE TEST REPORT
Date 21/12/2019 Page: 2 of 5
Location BASEMENT-1
Equipment Power Socket
Feeder Description
Phase-Earth Phase-Neutral
Socket PEFC PSC Room
Reference Impedance Prospective Impedance Prospective Reference Remarks
(ohm) earth fault (ohm) Short circuit
Current (A) current (A)
AD-LG-DB01-
0.29 828 0.28 840 PLT-1-LG-03 PASS
R1
AD-LG-DB01-
0.35 679 0.79 301 PLT-1-PG-02 PASS
B7
DOOR NO PASS
BB-01-R7 0.22 1100 0.28 843
2426
EB-LG-DB03-
0.46 516 0.59 402 ADM-1-LG-03 PASS
Y3
LG-DB03-R6 0.56 422 0.72 328 Corridor PASS
EB-LG-DB03-
0.44 540 0.42 565 ADM-1-LG-04 PASS
Y6
EB-LG-DB03-
0.57 414 0.72 328 ADM-1-LG-04 PASS
R,Y,B-7
EB-LG-DB03-
0.52 456 0.73 325 ADM-1-LG-04 PASS
R,Y,B-7
AD-LG-DB01-
0.53 442 0.53 442 PLT-1-LG-23 PASS
R4
AD-LG-DB01-
0.64 367 0.64 366 PLT-1-LG-23 PASS
R6
AB-LG-DB01- DOOR NO
0.64 370 0.65 364 PASS
Y3 2147
AD-LG-DB01-
0.55 427 0.57 412 T01-1-LG-01 PASS
R4
SIGNATURE
NAME SHAHUL MUNIR MOHAMED
DATE 21-12-2019 21-12-2019
Client: Contractor:
MAINTENANCE TEST REPORT
Date 21/12/2019 Page: 3 of 5
Location BASEMENT-1
Equipment Power Socket
Feeder Description
Phase-Earth Phase-Neutral
Socket PEFC PSC Room
Reference Impedance Prospective Impedance Prospective Reference Remarks
(ohm) earth fault (ohm) Short circuit
Current (A) current (A)
AD-LG-DB01-
0.36 626 0.38 365 ST0-1-LG-C01 PASS
B1
EB-LG-DB05-
0.62 384 0.97 245 ST0-4LG-12 PASS
Y9
EB-LG-DB05-
0.53 448 0.52 456 ST0-1-LG-12 PASS
B6
EB-LG-DB05-
0.54 440 0.70 340 ST0-1-LG-12 PASS
Y6
EB-LG-DB05-
0.54 439 0.54 449 PLT-4-LG-08 PASS
B7
EB-LG-DB05-
0.46 514 0.51 464 Corridor PASS
R9
EB-LG-DB05-
0.68 348 0.68 438 PLT-1-LG-16 PASS
R1
BC-LG-DB05-
0.42 562 0.44 537 PLT-1-LG-14 PASS
R3
EB-LG-DB05-
0.40 591 0.26 910 PLT-1-LG-13 PASS
R3
EB-LG-DB03-
0.55 433 0.59 403 ST0-1-LG-10 PASS
B4
SIGNATURE
NAME SHAHUL MUNIR MOHAMED
DATE 21-12-2019 21-12-2019
Client: Contractor:
MAINTENANCE TEST REPORT
Date 21/12/2019 Page: 4 of 5
Location BASEMENT-1
Equipment Power Socket
Feeder Description
Phase-Earth Phase-Neutral
Socket PEFC PSC Room
Reference Impedance Prospective Impedance Prospective Reference Remarks
(ohm) earth fault (ohm) Short circuit
Current (A) current (A)
B1-DB11-B2 0.84 282 0.57 416 PLT-2-B1-34 PASS
SDO-2-B1-
B1-DB11-R7 0.47 500 0.70 236 PASS
03
B1-DB11-B5 0.32 742 0.37 641 PLT-2-B1-43 PASS
SIGNATURE
NAME SHAHUL MUNIR MOHAMED
DATE 21-12-2019 21-12-2019
Client: Contractor:
MAINTENANCE TEST REPORT
Date 21/12/2019 Page: 5 of 5
Location BASEMENT-1
Equipment Power Socket
Feeder Description
Phase-Earth Phase-Neutral
Socket PEFC PSC Room
Impedanc
Reference Impedance Prospective Prospective Reference Remarks
e
(ohm) earth fault Short circuit
(ohm)
Current (A) current(A)
B1-DB01-Y5 0.52 455 0.51 464 PLT-2-B1-C06 PASS
Instrument Name Instrument Make Type Serial No. Cal. Due. Date
Multi-function meter Fluke 5522A 2597902 24-07-2020
SIGNATURE
NAME SHAHUL MUNIR MOHAMED
DATE 21-12-2019 21-12-2019