PHILIPPINE ELECTRICAL CODE 2017 – ARTICLE 1.3 ELECTRICAL PLANS Technical Articles
AND SPECIFICATIONS Steel Pole Design
Pinoy Inhinyero
1. Electrical plans and drawings shall be drawn on drawing sheets of the 72,212 hits
2. In cases such as projects of large magnitude, exemption in the use of the Philippine Electrical
standard drawing sheets may be granted by the office of the local building Code (PEC) 2017
Edition
official.
3. For a dwelling unit having a floor area of not more than 50 square meters What is Ruling Span?
with a total load not exceeding 3680 VA, a drawing sheet of size 297 mm x
420 mm (A3 size) is permitted. Philippine Electrical
Code
1.3.1.2 Drawing Scale.
Sample Calculation of
(D) Electrical Layout.
(1) Plan for Power. Layout and wiring plans for power on the oor plans
drawn to scale, shall show:
(2) Plan for Lighting and Receptacle Outlets. Layout and wiring plans for
general lighting and receptacle outlets on oor plans drawn to scale, shall
show:
(3) Plan for Fire Alarm Circuits. Layout and wiring plans of re alarm
station, re alarm bell, re alarm control panel, and other shall be drawn
to scale and show:
(3) Other Loads.
FPN No. 1: This analysis is not required for dwelling units but required for
service equipment and other electrical equipment n part of the individual
dwelling units of residential condominium and individual detached
dwelling units.
FPN No. 3: IEEE std 1584-2002, Guide for Performing Flash Hazard
Calculations provides guidelines for arc- ash hazard analysis.
Installation details;
Conductor supports, separators, and attachments where required by this
Code; and
Dimensions and description or specifications.
(D) Low energy power and low voltage power installation shall show:
Specification of equipment,
Wiring of lighting and remote-control systems,
One-line diagram(s) of entire installation with voltage indicated,
Computations on size of wires, busbar, transformer, fuses, switches and
breaker, and
Class of insulation or insulators.