4004R Gas Release Panel

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Release Control Fire Alarm Systems

UL, ULC, CSFM Listed; FM Approved; 4004R Suppression Releasing Panel for Automatic
MEA (NYC) Acceptance* Extinguishing, Deluge and Preaction Sprinkler Control

Features Agent discharge path

Fire alarm control panel designed specifically for


suppression release operation with: Actuator
Agent
Actuator
• Four initiating device circuits (IDCs) circuit
source

• Two notification appliance circuits (NACs) Coil


• Two releasing appliance circuits (RACs)
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED INSTALLATION INSTRUCTIONS 574-437 REV YEL
NAC+ MAINTAIN 1/4" SEPARATION

supervisory
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-
BLK SIMPLEX TIME RECORDER CO. GARDNER MA. USA

module
• Two special purpose monitor inputs (SPMs) that accept
manual release request and manual abort request for
Agent Release systems, and waterflow and supervisory NORMAL

Maintenance Switch
0

DISC./

for Preaction or Deluge systems


1
DISABLE

FIRE SUPPRESSION
DISCONNECT / DISABLE

• Three auxiliary relays with selectable functions


• Easily selected activity timing options SPM 1
FIRE SUPPRESSION
RAC 1 RAC 2
SYSTEM ABORT

Suppression release operation includes: PUSH AND HOLD


NAC 1
• Automatic extinguishing release
SPM 2
• Deluge and preaction sprinkler system release Alarm

Trouble

Alarm
Zone 1

Zone 2
Manual Release

Zone 5 Trouble

Manual Release

• Dual or single hazard area protection


IDC 1 Trouble

Alarm

Trouble

Alarm
Zone 3
Zone 6 Trouble

NAC 1 Trouble

NAC 2 Trouble

RAC 1 Trouble
CAUTION
DISCONNECT

Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER
Alarm Silenced Agent Released BEFORE
SERVICING
Supervisory Earth Fault

• Combined agent release and preaction operation**


System Trouble Abort Active

AC Power Relay Disconnect

• IDCs are selectable for cross-zoning or for activation NAC 2


IDCs 2, 3, and 4
from a single detection input
• Short circuit RAC supervision 4004R Suppression Release Panel
• Compatible with Listed/Approved valves and actuators
4004R Suppression Release Panel
Audible Escalation of Events: One-Line System Reference Drawing
• Single Audible Appliance Tone: Stage 1 activates
Temporal or 20 bpm March Time pattern; Stage 2 Introduction (Continued)
activates 120 bpm March Time pattern to indicate Flexible I/O Capabilities. Four IDCs allow for either
release timer active; Release activates On Steady to four separately monitored zones or two, cross-zoned
indicate release timer expired and actuator is activated connections. Two SPMs allow dedicated manual inputs for
• Dual Audible Appliance Control** (Single Hazard): release or abort; for waterflow and supervisory, or
RAC 2 provides a third NAC for dedicated Stage 1 Bell release/abort and pressure, depending on system type. Two
control; NACs 1 & 2 indicate release as On Steady releasing appliance circuits (RACs) supervise to the
Operator interface provides: actuator coils and activate the actuators when required. The
• Status LEDs per circuit for Alarm, Trouble, and two NACs and the three panel auxiliary relays provide
Supervisory (where appropriate) status condition information.
• Acknowledge, Alarm Silence, and System Reset Easy Program Selections. The operator panel has a
• Operating mode selection and timer selections when in program mode that allows selection of panel operation
programming mode type and detailed operating selections using an easily
Related system components: selected sequential programming operation.
• Coil supervision module 2081-9046, one per RAC History Log. The last 50 events are stored in
• Maintenance Switch, one per RAC non-volatile memory. This information is accessed by
• Abort Switch connecting a technician’s computer to the service port
which is also used to set the date and time.
Listed to
• UL Standard 864 and ULC Standard S527 Panel Feature Description
Introduction Operator Panel. The operator panel has alarm and
trouble status indicating LEDs for each input and output,
Dedicated for Suppression Release. 4004R visible through the locking cabinet door (refer to diagram
Suppression Release Panels provide conventional fire alarm on page 4). Unlocking the door provides access to the
control circuits and are equipped with the features required Acknowledge, Alarm Silence, and System Reset
for a wide variety of single or dual hazard suppression release pushbutton switches.
applications. Capabilities include automatic extinguishing
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
agent release and deluge and preaction sprinkler control. Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7165-0026:314 for allowable values and/or conditions concerning material presented in
** Requires Software Revision 4.01 or higher. this document. Additional listings may be applicable; contact your local Simplex® product
supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are
the property of Tyco Fire Protection Products Westminster.

S4004-0002-9 7/2018
Panel Feature Description (Continued) Two Class B Releasing Appliance Circuits (RACs). Rated
2 A each, these circuits are dedicated to operating release
(Refer to specifications on page 6 for more information.) control actuators. RAC cutout timing is selectable as no
Four Class B IDCs provide coverage for either two cutout, 45 seconds, or 1, 3, 3.5, 4, 5, 6, 7, 21, 25, 34, 44,
cross-zoned areas or four separately zoned areas. IDCs are or 64 minutes. For bell/horn/strobe single hazard
capable of supporting up to 30 Simplex current-limited applications, RAC 2 functions as a third NAC (NAC 3).
smoke detectors or electronic heat detectors (see list on Auxiliary Power Output. Two sets of output terminals are
page 2) as well as manual stations and other compatible provided, one for continuous operation and the other for
contact closure initiating devices. IDCs are capable of resettable operation, rated for 750 mA combined.
Class A operation with an optional adapter module and can Resettable terminals are provided for 4-wire smoke
be programmed as Style C (short or open initiates a trouble) detector power.
for use with current limited devices only. Single hazard agent Standard Panel Auxiliary Relay Outputs. Three relay
release applications monitor pressure switches with IDC 3 outputs are available, selectable as normally open or
and tamper switches with IDC 4. normally closed, rated 2 A @ 30 VDC, 0.35 p.f. inductive:
Two Class B Special Purpose Monitoring Circuits (SPMs)
Aux Relay 1 (Trouble) is energized when Normal and is
are dedicated for manual release or abort, waterflow and de-energized with a common Trouble condition.
supervisory, or release/abort and pressure, depending on
system type. Inputs are normally open switches. An abort Aux Relays 2 and 3 respond differently depending on the
switch stops release while activated and upon deactivation, system type and whether single or dual hazard. Typical
the release operation occurs after a selectable time delay. functions are:
Manual release inputs override abort switches and activate For Single Hazard Operation, Aux Relay 2 is the
the release after selectable delays of from 0 to 30 seconds in common Alarm relay. Aux Relay 3 can be selected to
5 second increments. For Dual Hazard applications, current indicate pre-discharge (release time delay started),
limited abort operation is required. SPMs are programmable common supervisory, waterflow, or pressure switch relay,
as Style C and capable of Class A operation with the optional depending on the system type.
adapter module. For Dual Hazard Operation, Aux Relay 2 is for Hazard
Two Class B NACs are provided for reverse polarity, Area 1 common Alarm; Aux Relay 3 is for Hazard Area 2
notification appliance operation, each rated 2 A. Class A common Alarm.
operation is available with the optional adapter module. Power Supply and Battery Charger. During alarm, the
NAC operation is selectable per application. Synchronized power supply provides 3 A at 25.5 VDC, filtered and
strobe operation requires a separate 4905 Series Strobe regulated. The temperature compensated battery charger
Synchronization Module (see product selection below), and provides 27.5 VDC for charging batteries up to 12.7 Ah,
a continuous, steady-on (non-coded) input from the NAC. suitable for up to 90 hour standby and 10 minutes of alarm.
A 4081 Series external battery cabinet with charger can be
used for more battery backup (see battery selection below).
Product Selection
Release Control Panels
Model Color Listings Description
4004-9301 Beige UL, ULC, CSFM, & FM Basic Releasing Panel; operates with AC input of: 120/220/230/240 VAC,
50/60 Hz (auto-select); includes: four IDCs, two NACs, two SPMs, two RACs,
UL, ULC, CSFM, FM, & 3 auxiliary relays, 3 A power supply with battery charger, and NEMA 1/IP30 rated
4004-9302 Red
MEA (NYC) cabinet and door
Expansion Modules
Model Description Reference
Auxiliary Relay Module; four dual contact relays selectable as N.O. or N.C.; rated 7 A Select
4004-9860 Two maximum
@ 120 VAC resistive, 5 A @ 30 VDC, 0.35 p.f. inductive; unsupervised contacts as
4004-9864 Two Circuit Class A Adapter Module for IDCs, SPMs, or NACs Four maximum required

System Batteries
Model Description Reference
2081-9272 6.2 Ah battery, 12 V These batteries can be mounted in the 4004R cabinet; select one battery model
2081-9274 10 Ah battery, 12 V per system standby requirements; two batteries are required; for more capacity
2081-9288 12.7 Ah battery, 12 V see data sheet S4081-0001 for a compatible external battery cabinet with charger

Release Control Systems Accessories (refer to additional information listed on page 3)


Model Description
2081-9046 Coil Supervision Module, one required per RAC; refer to pages 6 and 7 for detail
Abort Supervision Module; encapsulated 560Ω, 1/2 W resistor; for Dual Hazard SPM; allows non-current limited
2081-9048
Abort and Manual Release stations to be on same circuit; refer to pages 6 and 7 for detail
4081 Series End-of-Line Resistor Harnesses; refer to data sheet S4081-0003
2099 Series Manual Stations for Releasing Applications; refer to data sheet S2099-0010
Strobe synchronization modules; 4905-9914 for Class B, 4905-9922 for Class A; see data sheet S4905-0003 for
4905-Series
details

2 S4004-0002-9 7/2018
Reference Information, Compatible Simplex Detectors and other System Components
Model Type Data Sheet
4098-9601 Standard detector
Photoelectric smoke detectors for 2-wire and 4-wire S4098-0015
4098-9605 Reduced sensitivity detector
bases
4098-9602 Combination smoke and heat detector S4098-0017
4098 Series Ionization Smoke Detectors; 2-wire and 4-wire models S4098-0018
4098-9612 135° F (57°C)
Fixed heat detector
4098-9614 200° F (93°C)
Electronic heat detectors for 2-wire and 4-wire bases S4098-0014
4098-9613 135° F (57°C) Fixed with rate-of-rise
4098-9615 200° F (93°C) heat detector

2099-9149 Standard Manual Release Station with selectable release labels;


S2099-0010
2099-9152 Style C, with 560 Ω internal resistor double action push, N.O. contact
Maintenance Switches, flush or surface mount; indicator lamps require 24 VDC wiring
2080-Series S2080-0010
Abort Switches, surface or flush mount; available standard or with 1.2 kΩ, 1 W resistor

Expansion Modules and Accessories


Auxiliary Relay Module 4004-9860 provides four Dual Circuit Class A Adapter Module 4004-9864.
additional relays. Dual hazard applications will require This module converts two Class B circuits to Class A
two modules for auxiliary relay operation. Each relay operation. It consumes no additional current and is
module has a manual disconnect switch that controls compatible with IDCs, SPMs, and NACs. Up to four
relays 2 through 4. (Trouble Relay 1 is not controlled.) modules may be mounted within the 4004R cabinet.
Relay outputs are required to be connected to a 15 A Abort Switches. For manual abort requests, these abort
maximum circuit breaker. (Relay specifications are switches are available with or without a built-in 1.2 kΩ, 1
detailed on page 6.) W resistor and are mounted on single-gang stainless steel
Auxiliary Relay Module Operation: plates. Abort switches are connected to the SPM inputs
Relay 1 activates on a common trouble associated with per system requirements.
its hazard or a system trouble. Activity abort occurs while the switch is pushed and
Relay 2 activates on a common alarm associated with its continues after releasing the switch for the selected Abort
hazard. Release Time Delay. (See drawing below.)
Relay 3, selected for original operation, activates for Maintenance Switch. Proper service of release appliance
pressure switch, waterflow switch, or release timer as circuits requires the ability to securely disconnect the
required per application type (hazard specific), or release circuit during installation and maintenance. Simplex
activates with the second zone for cross-zoned systems maintenance switches are controlled by keyswitch and
(hazard specific). “Original” operation allows direct panel initiate a supervisory condition when in disconnect/disable
replacement if required. position. Models with lamp are on a double-gang plate and
Relay 3, selected for enhanced operation, (software 4.01 are powered from separate 24 VDC wiring. Mounting is on
or higher), activates to indicate pre-discharge, stainless steel plates and models are available as either
supervisory, or waterflow (application specific). surface or flush mount. (See drawing below.)
Relay 4 activates when the hazard specific RAC activates For additional Maintenance and Abort Switch information
or with pressure switch input (application specific). refer to data sheet S2080-0010.

FIRE SUPPRESSION
SYSTEM ABORT
NORMAL

DISC./
1
DISABLE

FIRE SUPPRESSION
PUSH AND HOLD
DISCONNECT / DISABLE

Abort Switch Maintenance Switch


3 S4004-0002-9 7/2018
Programming Modes and Selection Choices
Sequence Select one of 13 Application Modes (numbered 1 through 13 in italics)
Cross-Zoned 1 Combined Release
Single Hazard
Either Zone 2 (RACs activate together)
Agent Release
Cross-Zoned 3 Independent Release (RACs are
Dual Hazard
Either Zone 4 separate)
Cross-Zoned 5 Combined Release
Single Hazard
Either Zone 6 (RACs activate together)
Preaction/Deluge
1 Cross-Zoned 7 Independent Release (RACs are
Dual Hazard
Either Zone 8 separate)
Agent Release; Single Hazard Cross-Zoned 9 NYC Abort (not UL listed)
Agent Release & Preaction; Cross-Zoned 10 RAC 2 provides Preaction Control;
Single Hazard Either Zone 11 RAC 1 is Agent Release Control
Agent Release, Bell/Horn/Strobe; Cross-Zoned 12 RAC 2 operates as NAC 3 for Stage 1 Bell Control
Single Hazard Either Zone 13 (separate sound from release alarm)

Sequence Programming Mode Description Description


Select Relay Operation for Select “Original” operation mode or “Enhanced" mode (refer to Auxiliary Relay 3
2
Application Modes 1-9 information on page 3 for details)
3 IDC and SPM Circuit Style Class B/Class A or Style C
4 Automatic Release Time Delay Selectable in 5 second increments from 0 to 60 seconds (default is 60 seconds)
5 RAC Cutout Timer No cutout, 45 seconds, or 1, 3, 3.5, 4, 5, 6, 7, 21, 25, 34, 44, or 64 minutes
6 Manual Release Time Delay 0, 5, 10, 15, 20, 25, or 30 seconds
UL Standard 864 listed Immediate or 10 seconds remaining
Abort Release Time Delay Not UL Standard 864 IRI abort (cross-zoned systems only), NYC abort, or
7
listed original release delay
8 NAC Coding (where selectable) Temporal pattern or 20 beats per minute (first cross-zone alarm)
Standard No inhibit or one minute inhibit selected as: both on until silence, NAC 1 on until
Operation reset and NAC 2 on until silence, or both on until reset;
NAC Operation NOTE: For Halon 1301, Halon 1211, or clean agent release, a pre-discharge NAC
9 Pre-Discharge
must be configured to warn of impending discharge, the release timer selects the
Operation
duration of the pre-discharged signal
10 Supervisory Latching Latching or non-latching
LED and tone-alert only, or with: NAC 2 also on; Aux Relay 3 also on; or both
11 Supervisory Notification
NAC 2 and Aux Relay 3 also on

Operator Panel Function Reference


LABEL INSERT selectable for
Preaction/Deluge, Agent Release, or
Alarm
Combination Agent Release/Preaction
RUN MODE: LEDs provide Zone 1 Deluge, UL or ULC versions (UL Agent
Alarm (red) and Trouble (yellow) Trouble Zone 5 Trouble
Release version shown for reference)
status per IDC zone; Zone 4
Alarm Manual Release
yellow LED indicates supervisory
status if still flashing after ACK Trouble
Zone 2 Zone 6 Trouble
RUN MODE: red LEDs indicate Manual
Release activated (for Agent Release
Alarm NAC 1 Trouble
Applications); yellow LEDs indicate
PROGRAM MODE: Top ten
LEDs indicate Programming Trouble
Zone 3 NAC 2 Trouble
Trouble for SPMs (Zones 5 and 6) and
NACs, for RACs, yellow LED indicates
Mode Category supervisory if still flashing after ACK
Alarm RAC 1
Zone 4 RAC 2 PROGRAM MODE:
Alarm Silenced yellow LED
Top nine LEDs provide
indicates that audible Agent Released
Alarm Silenced Programming Selection
notification appliances are
silenced prior to system reset Supervisory Earth Fault
Agent Released red LED
indicates RACs are activated
Supervisory and System System Trouble Abort Active
Trouble yellow LEDs; for UL Earth Fault yellow LED indicates
AC Power Relay Disconnect
systems, indication of disabled presence of an earth fault
or disconnected RAC
ALARM SYSTEM
Abort Active yellow LED tracks
ACK
SILENCE RESET state of Abort Switch
AC Power green LED is on
with normal power status Relay Disconnect yellow LED
indicates that expansion relays
have been disabled for service
ACK acknowledges status during RUN mode
ALARM SILENCE SYSTEM RESET restores the system to normal during RUN
and accepts selection during PROGRAM mode;
silences audible alarms mode and toggles the selection during PROGRAM mode
press and hold for 5 sec to perform LAMP TEST

4 S4004-0002-9 7/2018
Release Control System Reference Release Control System Requirements
Automatic Extinguishing Release Systems 1. Actuators are connected as two-wire, Class B
automatically activate actuators for the release of a fire notification/releasing circuits with only one 24 VDC
extinguishing agent (dry chemical, water spray, foam, actuator per circuit to ensure supervision. Where
CO2, Clean Agent, etc.) in response to fire detection applicable, two 12 VDC actuators in series or one 12
device input. VDC actuator per circuit may be used (refer to the
Automatic Extinguishing Release Systems with actuator manufacturer's installation documentation for
Separate Bell Control (single hazard) (SW rev. 4.01 additional details and requirements).
or higher). RAC 2 operates as a bell control NAC. When 2. Coil Supervision Module, model 2081-9046, must be
cross-zoned, stage 1 alarm activates the bell until the wired electrically before the actuator and located in the
release timer starts. When not cross-zoned, stage 1 alarm actuator wiring junction box. (See diagram on page 7.)
activates the bell until expiration of the release timer. In 3. For UL Listed Automatic Extinguishing Release valves
both cross-zoned and non cross-zoned applications, and actuators, refer to list on page 7.
NAC2 may be programmed to indicate either a tamper 4. For FM Approved Automatic Extinguishing Release,
switch supervisory condition or the start of the release secondary standby must be a minimum of 24 hours with
timer using a cadence pattern operation. 5 minutes of alarm. Actuators must be electrically
compatible.
UL and FM Extinguishing Release System Panels
5. For FM Approved Deluge and Preaction Sprinkler
must have a minimum of 24 hours of standby power.
operation: IDCs must be Class A, wired to
Initiating devices must be Listed/Approved for the Listed/Approved devices; secondary standby capacity
application, and may be wired either Class A or B.
must be a minimum of 90 hours with 10 minutes of
Actuators must be electrically compatible with the control
alarm; and the specified compatible Automatic Water
panel circuits and power supplies, and are wired Class B to Control Valves/Actuator must be used. (See list on
provide coil supervision. (See details in next section.)
page 8.)
Deluge and Preaction Sprinkler Systems 6. Power supply loading and wiring distances must be per
automatically activate water control valves in response to Installation Instructions 579-354.
fire detection device input. 7. Battery standby must be selected for proper actuator
Deluge Sprinkler Systems employ open sprinkler heads operation and may require a minimum voltage of
and provide water flow when the fire detection system 23 VDC depending on the actuator. Detailed battery
activates a common automatic water control valve. They are calculation reference information is contained in
used to deliver water simultaneously through all of the open Installation Instructions 579-354.
sprinkler heads. This type of system is applicable where the 8. Maintenance Switches, one per RAC, are required per
immediate application of large quantities of water over large NFPA 72, the National Fire Alarm and Signaling Code,
areas is the proper fire response. to allow the system to be tested or serviced without
Preaction Sprinkler Systems are similar to deluge actuating the fire suppression systems. Their use may not
systems except that normally closed sprinkler heads are used be allowed in some jurisdictions, always confirm local
and supervisory air pressure is maintained in the pipe. requirements. When used, Simplex Maintenance
Operation requires both an activated sprinkler head and an Switches are required to ensure that operation initiates a
activated fire alarm initiating device. supervisory condition.
Additional System Device Information
Combined Agent Release and Preaction Systems
provides agent release and preaction control. (Available 1. Simplex Abort Switches are available when abort
with software revision 4.01 or higher.) For applications operation is required. When used, wire on Special
where agent release may not be sufficient for fire control, Purpose Monitoring Circuits (SPMs) as Class A or
sprinklers are put in preaction mode to allow waterflow to Class B; Simplex model Abort Switches are required.
continue the fire response. (Preaction is assumed, selected 2. Manual Release Stations are used for direct activation of
deluge could be provided, determined by the sprinkler the release actuators with the appropriate time delay
installation, panel operation is the same.) implemented by the fire alarm control panel.
UL requirements for Fire Alarm Systems Listed for 3. See pages 2 and 3 for additional reference information.
Automatic Release or Deluge and Preaction Sprinkler
Additional Information
Systems are the same as described above for Automatic
Extinguishing Release Systems. This data sheet is a summary of the extensive operating
FM Approved requirements for Fire Alarm Systems for features and options available with the 4004R Release
Automatic Release of Deluge and Preaction Sprinkler Control Panel. Complete details are covered in the 4004R
Systems require operation of specific compatible FM Installation, Programming, and Operating Instructions
Approved Automatic Water Control Valves, a minimum manual (publication 579-354) shipped with each 4004R.
secondary power capacity of 90 hours, and all circuits for Compatible system devices are listed on page 3. For general
the automatic release initiating devices must be capable of information, refer to Factory Mutual Research Corporation
operation during a single open circuit fault condition (FMRC) “FMRC Approval Guide,” FM Approval standard
(Class A). “Deluge Systems and Preaction Systems.”

PLEASE NOTE: Proper operation of release control systems requires that the system design, installation, and maintenance be
performed correctly and in accordance with all applicable local and national codes, and equipment manufacturer’s
instructions. No liability for total system operation is assumed or implied.
5 S4004-0002-9 7/2018
Specifications (Refer to diagram on page 7 and Instructions 579-354 for additional information)
Power Ratings
Voltage Ratings 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
AC Input
Current Ratings 2 A maximum @ 120 VAC input; 1 A maximum @ 240 VAC input
Power Supply Output 3 A maximum available for external loads
Temperature compensated, capable of recharging batteries required for 90 hour
Battery Charger
standby and 10 minute alarm (contingent on auxiliary power load)
Standby Current 100 mA; with IDCs fully loaded, tone-alert silenced, trouble LED on, charger off
Alarm Current 264 mA + external loads; (2 zones in alarm & 2 internal relays, NACs and RACs on)
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum; see NAC ratings for details)
Supervisory 3 mA maximum; 3.3 kΩ end-of-line resistor per circuit
Alarm Current 75 mA maximum
Initiating Device
Circuits (IDCs) Output Voltage 28 VDC maximum
Each IDC supports up to 30 detectors (smoke or electronic heat) and manual
Capacity
stations as required; wiring distance is limited to 50 Ω maximum
For Manual Release, Abort Switches, or Supervisory functions only; not for
Application
detectors; wiring distance is limited to 50 Ω maximum
Special Purpose For Dual Hazard Dual Hazard Application Abort Switches require a current limiting resistor of 1.2 kΩ,
Monitoring Circuits Applications 1 W, or an external Abort Supervision Module per SPM
(SPMs) Supervisory 6 mA; 3.3 kΩ end-of-line resistor per circuit
Activated 75 mA maximum
Output Voltage 28 VDC maximum
Special Application appliance rating = 2 A maximum on a NAC
NOTE: Special Application appliance rating = full 3 A power supply rating
Alarm Current
Regulated 24 DC appliance power = 1.5 A maximum on a circuit
Notification
Appliance Circuits NOTE: Regulated 24 DC strobe load = 1.35 A maximum total for power supply
(NACs) Output Voltage Alarm = 26 VDC max.; supervisory = 29 VDC maximum; 10 kΩ end-of-line resistor
Requires NAC dedicated to strobe control with non-coded output; use an external
Synchronized
Synch Module (4905-9914, Class A, or 4905-9922, Class B, see data sheet
Strobe Operation
S4905-0003 for details); up to 33 strobes can be synchronized per 4004R
Special Application Simplex 4901 Series horns, 4904 and 4906 Series strobes, 4903 Series 4-wire
Notification Appliances horn/strobes; refer to Installation Instructions 579-354 for additional details
Appliance
Reference Regulated 24 DC Power for other appliances listed to UL Standard 1971 or UL Standard 464; use
Appliances associated external synchronization modules where required
Output Current 2 A maximum per circuit
Release Appliance
Circuits (RACs) Activated = 26 VDC maximum; non-alarm = 29 VDC maximum;
Output Voltage
10 kΩ end-of-line resistor
Auxiliary Power Output; for Special Two outputs are available, continuous operation or resettable operation; combined
Application loads only output is 750 mA maximum; output voltage = 19.25 to 27 VDC
Auxiliary Relay Outputs Contacts rated 2 A @ 30 VDC, 0.35 p.f., inductive, selectable as N.O. or N.C. by
(Trouble, Aux Relay 2, Aux Relay 3) jumper
Wiring Connections for Above and AC Input Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
Auxiliary Module Ratings
Two circuits per module, rated same as circuits; not applicable to RACs (no
Class A Adapter Module 4004-9684
additional current required)
Relay Type Four relays with two outputs per relay; individually selectable as N.O. or N.C.
AC Ratings 7 A @ 120 VAC, resistive
Auxiliary Relay Module
DC Ratings 5 A @ 30 VDC, 0.35 power factor, inductive
4004-9860
Module Current 12 mA standby; 70 mA with all four relays energized; @ 24 VDC
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
2081-9046 Coil Supervision Module and 2081-9048 Abort Supervision Module (see page 7 for additional details)
Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Coil Supervision Module Current Rating 2 A maximum; internally fused at 3 A, non-replaceable
Abort Supervision Module Resistance 560 Ω, 1/2 W
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum

6 S4004-0002-9 7/2018
s4004R System Connection Reference
Listed/approved actuator or Deluge
A and Preaction Automatic Water
Control Valve; one if 24 VDC (or 2 in
series if 12 VDC) per RAC

Actuator wiring Coil Supervision Module


junction box Yel Blk 2081-9046
+ Out - COIL SUPERVISIONMODULE( 2 AMP) 2081- 9046
RED YEL

+ In - NAC+
INSTALLATIONINSTRUCTIONS574- 437 REV
MAINTAIN1/4 " SEPARATION
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S
LIMITED( YEL/BLK) W IRING
DATECODE: 519- 958
BLK

Abort Supervision Module 2081-9048 Red Blk NAC-


BLK S IM P L E X T IM E R E C OR D E R C O.GA R D N E R MA .U S A

(for dual hazard mode with non-current


limited devices on the SPM)
Maintenance Disconnect Switch
ABORT SUPERVISION MODULE 2081-9048
RED YEL
INSTALLATION INSTRUCTIONS 579-465 REV OUT +
IN+
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
FM (RED/BLK) AND NONPOWER

IN-
DATE CODE:
LIMITED (YEL/BLK) WIRING
OUT -
BLK
NORMAL

1
DISC./
DISABLE
24 VDC for Maintenance Disconnect
BLK SIMPLEX TIME RECORDER CO. WESTMINSTER MA 01441 USA

FIRE SUPPRESSION
DISCONNECT / DISABLE status indicator (if required)

RAC 2
Abort Switches Manual Release Optional 4905-9914 or
(as required) Stations RAC 1 4905-9922 Strobe
Synchronization Module
FIRE SUPPRESSION FIRE SUPPRESSION
SYSTEM ABORT SYSTEM ABORT

PUSH AND HOLD PUSH AND HOLD


Typical strobe only NAC
MANUAL MANUAL
RELEASE RELEASE

SPM 1 SPM 2
Alarm

Trouble

Alarm

Trouble
Zone 1

Zone 2
Manual Release

Zone 5 Trouble

Manual Release

Zone 6 Trouble
NAC 1
CAUTION

4-Wire
Alarm NAC 1 Trouble DISCONNECT

Trouble
Zone 3 NAC 2 Trouble

Alarm RAC 1 Trouble

IDC 1 Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER

Horn/Strobe
Alarm Silenced Agent Released BEFORE
SERVICING

Typical horn only NAC


Supervisory Earth Fault

System Trouble Abort Active

AC Power Relay Disconnect

Manual fire NAC 2


alarm station
Compatible IDCs 2, 3, and 4
detection devices
4004R Suppression Release Panel
GENERAL WIRING NOTE:
Wiring shown is for reference only, refer to installation instructions for detailed wiring information.

7 S4004-0002-9 7/2018
Compatible UL Listed Valves and Actuators

Manufacturer Model Number Electrical Ratings


AUTOMAN II-C Assembly (solenoid 17728; coil 25924) 24 VDC, 750 mA
AUTOMAN II-C Explosion-Proof Releasing Device 24 VDC, 750 mA
(solenoid 31492; coil 31438)
24 VDC, 750 mA
AUTOMAN II-C Assembly (solenoid 68739; coil 25924)
ANSUL Solenoid Electric Actuator (solenoid 73111; coil 73097) 24VDC, 1 A
*CV90 HF Electric Actuator 73327 24 VDC, 570 mA
LP CO2 w/ASCO solenoid 422934 24VDC, 442 mA
LP CO2 double action 24 VDC solenoid 430948 24VDC, 438 mA
LP CO2 3-way selector valve solenoid 433419 24VDC, 438 mA
Electric Actuator 24 VDC solenoid 570537 24VDC, 250 mA
Solenoid Electric Actuator (uses solenoid: Flow Control
609500/671S)
Solenoid Coupling Assembly 21006401 (uses solenoid:
Flow Control 609500/671S)
LPG Solenoid Coupling Assembly 21006402 (uses solenoid: 24 VDC, 542 mA
Flow Control 609500/671S)
LPG128/145/190/230-50/55 FM-200 valves (uses
solenoid: Flow Control 609500/671S)
LPG128-90UL iFLOW and FM-200 valve (uses
solenoid: Flow Control 609500/671S)
8210A107 (097617-005D coil) 24 VDC, 750 mA
8210G207 (238310 coil) 24 VDC, 440 mA
8211A107 (097617-005D coil) 24 VDC, 750 mA
8262H182 (238910 coil) 24 VDC, 483 mA
ASCO EF8210G001MBMO 24 VDC, 450 mA
HV2628571 (23810 coil) 24 VDC, 442 mA
HV2648581 (23810 coil) 24 VDC, 442 mA
R8210A107 (097617-005D coil) 24 VDC, 700 mA
T8210A107 (097617-005D coil) 24 VDC, 700 mA
304.205.010 – Electrical Actuator Suppression Diode 24 VDC, 250 mA
Hygood (TSP)
304.209.001 – Electrical Actuator Bridge Rectifier 24 VDC, 250 mA
ECH Electrical Control Head (551201) 24 VDC, 1700 mA
PyroChem Explosion-Proof Electric Actuator (570147) 24 VDC, 396 mA
Removable Electric Actuator (570209) 24 VDC, 200 mA
71395SN2ENJ1N0H111C2 (Skinner coil H111C2) 24 VDC, 420 mA
73212BN4TN00N0C111C2 (Skinner coil C111C2) 24 VDC, 420 mA
Skinner 73212BN4TNLVN0C322C2 (Skinner coil C322C2) 24 VDC, 830 mA
73218BN4UNLVN0H111C2 (Skinner coil H111C2) 24 VDC, 410 mA
73218BN4UNLVN0C111C2 (Skinner coil C111C2) 24 VDC, 410 mA
Star Sprinkler D deluge valve, with solenoid 5550 Refer to manufacturer’s documentation
Minimax MX1230 without diode 24 VDC, 420 mA
Burkert 5282 2/2-Way Solenoid Valve 24 VDC, 333 mA
Versa CGS-4292-NB3-S20000 24 VDC, 438 mA
Model TSP 304205030 24 VDC, 0.5A
Tyco Safety Products
Model TSP 304700001 24 VDC, 830mA
Masteco Model MSC-01 24 VDC, 1.7 A

* For 24 VDC, 450 mA activation requires one actuator connected in series with a 73866 (21.5 ohm, 23 watt) in-line resistor shipping assembly
ordered separately. For additional information refer to the manufacturer’s technical documentation.

8 S4004-0002-9 7/2018
Compatible
Compatible FM
FM Approved
Approved Water
Water Co
Control Valves

4004R Control Panels are assigned to FM Release Control Panel Group 3. Group 3 FM Approved Release Control Panels are
compatible with all FM Approved Solenoid Valves rated at 22 Watts or less. For verification of agency listings and power
requirements refer to the solenoid valve manufacturer’s technical documentation.

Mounting Reference Information

Box width 14-5/8" (372 mm)

Knockouts are (Top and side views are


located on top shown with door installed)
and sides
Box depth
4-1/4" (108 mm)

11-1/4" (286 mm)

Aux.
Class A adapter boards
relay
module 1 Door thickness
Relay Relay
Disc 1 Disc 2

5/8" (16 mm)


Aux.
relay
13-1/2" Main board module 2
16"
(343 mm) (406 mm)

AC input

Battery Area
No conduit or wiring in this area

13-1/4" (337 mm)


(Front view module placement reference showing NOTE: For semi-flush mounting, cabinet
mounting hole dimensions, optional Class A must extend 1-1/2" (38 mm)
adapter modules, and optional relay modules) minimum from wall surface
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4004-0002-9 7/2018


www.simplex-fire.com
© 2018 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.