4004R Gas Release Panel
4004R Gas Release Panel
4004R Gas Release Panel
UL, ULC, CSFM Listed; FM Approved; 4004R Suppression Releasing Panel for Automatic
MEA (NYC) Acceptance* Extinguishing, Deluge and Preaction Sprinkler Control
supervisory
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-
BLK SIMPLEX TIME RECORDER CO. GARDNER MA. USA
module
• Two special purpose monitor inputs (SPMs) that accept
manual release request and manual abort request for
Agent Release systems, and waterflow and supervisory NORMAL
Maintenance Switch
0
DISC./
FIRE SUPPRESSION
DISCONNECT / DISABLE
Trouble
Alarm
Zone 1
Zone 2
Manual Release
Zone 5 Trouble
Manual Release
Alarm
Trouble
Alarm
Zone 3
Zone 6 Trouble
NAC 1 Trouble
NAC 2 Trouble
RAC 1 Trouble
CAUTION
DISCONNECT
Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER
Alarm Silenced Agent Released BEFORE
SERVICING
Supervisory Earth Fault
S4004-0002-9 7/2018
Panel Feature Description (Continued) Two Class B Releasing Appliance Circuits (RACs). Rated
2 A each, these circuits are dedicated to operating release
(Refer to specifications on page 6 for more information.) control actuators. RAC cutout timing is selectable as no
Four Class B IDCs provide coverage for either two cutout, 45 seconds, or 1, 3, 3.5, 4, 5, 6, 7, 21, 25, 34, 44,
cross-zoned areas or four separately zoned areas. IDCs are or 64 minutes. For bell/horn/strobe single hazard
capable of supporting up to 30 Simplex current-limited applications, RAC 2 functions as a third NAC (NAC 3).
smoke detectors or electronic heat detectors (see list on Auxiliary Power Output. Two sets of output terminals are
page 2) as well as manual stations and other compatible provided, one for continuous operation and the other for
contact closure initiating devices. IDCs are capable of resettable operation, rated for 750 mA combined.
Class A operation with an optional adapter module and can Resettable terminals are provided for 4-wire smoke
be programmed as Style C (short or open initiates a trouble) detector power.
for use with current limited devices only. Single hazard agent Standard Panel Auxiliary Relay Outputs. Three relay
release applications monitor pressure switches with IDC 3 outputs are available, selectable as normally open or
and tamper switches with IDC 4. normally closed, rated 2 A @ 30 VDC, 0.35 p.f. inductive:
Two Class B Special Purpose Monitoring Circuits (SPMs)
Aux Relay 1 (Trouble) is energized when Normal and is
are dedicated for manual release or abort, waterflow and de-energized with a common Trouble condition.
supervisory, or release/abort and pressure, depending on
system type. Inputs are normally open switches. An abort Aux Relays 2 and 3 respond differently depending on the
switch stops release while activated and upon deactivation, system type and whether single or dual hazard. Typical
the release operation occurs after a selectable time delay. functions are:
Manual release inputs override abort switches and activate For Single Hazard Operation, Aux Relay 2 is the
the release after selectable delays of from 0 to 30 seconds in common Alarm relay. Aux Relay 3 can be selected to
5 second increments. For Dual Hazard applications, current indicate pre-discharge (release time delay started),
limited abort operation is required. SPMs are programmable common supervisory, waterflow, or pressure switch relay,
as Style C and capable of Class A operation with the optional depending on the system type.
adapter module. For Dual Hazard Operation, Aux Relay 2 is for Hazard
Two Class B NACs are provided for reverse polarity, Area 1 common Alarm; Aux Relay 3 is for Hazard Area 2
notification appliance operation, each rated 2 A. Class A common Alarm.
operation is available with the optional adapter module. Power Supply and Battery Charger. During alarm, the
NAC operation is selectable per application. Synchronized power supply provides 3 A at 25.5 VDC, filtered and
strobe operation requires a separate 4905 Series Strobe regulated. The temperature compensated battery charger
Synchronization Module (see product selection below), and provides 27.5 VDC for charging batteries up to 12.7 Ah,
a continuous, steady-on (non-coded) input from the NAC. suitable for up to 90 hour standby and 10 minutes of alarm.
A 4081 Series external battery cabinet with charger can be
used for more battery backup (see battery selection below).
Product Selection
Release Control Panels
Model Color Listings Description
4004-9301 Beige UL, ULC, CSFM, & FM Basic Releasing Panel; operates with AC input of: 120/220/230/240 VAC,
50/60 Hz (auto-select); includes: four IDCs, two NACs, two SPMs, two RACs,
UL, ULC, CSFM, FM, & 3 auxiliary relays, 3 A power supply with battery charger, and NEMA 1/IP30 rated
4004-9302 Red
MEA (NYC) cabinet and door
Expansion Modules
Model Description Reference
Auxiliary Relay Module; four dual contact relays selectable as N.O. or N.C.; rated 7 A Select
4004-9860 Two maximum
@ 120 VAC resistive, 5 A @ 30 VDC, 0.35 p.f. inductive; unsupervised contacts as
4004-9864 Two Circuit Class A Adapter Module for IDCs, SPMs, or NACs Four maximum required
System Batteries
Model Description Reference
2081-9272 6.2 Ah battery, 12 V These batteries can be mounted in the 4004R cabinet; select one battery model
2081-9274 10 Ah battery, 12 V per system standby requirements; two batteries are required; for more capacity
2081-9288 12.7 Ah battery, 12 V see data sheet S4081-0001 for a compatible external battery cabinet with charger
2 S4004-0002-9 7/2018
Reference Information, Compatible Simplex Detectors and other System Components
Model Type Data Sheet
4098-9601 Standard detector
Photoelectric smoke detectors for 2-wire and 4-wire S4098-0015
4098-9605 Reduced sensitivity detector
bases
4098-9602 Combination smoke and heat detector S4098-0017
4098 Series Ionization Smoke Detectors; 2-wire and 4-wire models S4098-0018
4098-9612 135° F (57°C)
Fixed heat detector
4098-9614 200° F (93°C)
Electronic heat detectors for 2-wire and 4-wire bases S4098-0014
4098-9613 135° F (57°C) Fixed with rate-of-rise
4098-9615 200° F (93°C) heat detector
FIRE SUPPRESSION
SYSTEM ABORT
NORMAL
DISC./
1
DISABLE
FIRE SUPPRESSION
PUSH AND HOLD
DISCONNECT / DISABLE
4 S4004-0002-9 7/2018
Release Control System Reference Release Control System Requirements
Automatic Extinguishing Release Systems 1. Actuators are connected as two-wire, Class B
automatically activate actuators for the release of a fire notification/releasing circuits with only one 24 VDC
extinguishing agent (dry chemical, water spray, foam, actuator per circuit to ensure supervision. Where
CO2, Clean Agent, etc.) in response to fire detection applicable, two 12 VDC actuators in series or one 12
device input. VDC actuator per circuit may be used (refer to the
Automatic Extinguishing Release Systems with actuator manufacturer's installation documentation for
Separate Bell Control (single hazard) (SW rev. 4.01 additional details and requirements).
or higher). RAC 2 operates as a bell control NAC. When 2. Coil Supervision Module, model 2081-9046, must be
cross-zoned, stage 1 alarm activates the bell until the wired electrically before the actuator and located in the
release timer starts. When not cross-zoned, stage 1 alarm actuator wiring junction box. (See diagram on page 7.)
activates the bell until expiration of the release timer. In 3. For UL Listed Automatic Extinguishing Release valves
both cross-zoned and non cross-zoned applications, and actuators, refer to list on page 7.
NAC2 may be programmed to indicate either a tamper 4. For FM Approved Automatic Extinguishing Release,
switch supervisory condition or the start of the release secondary standby must be a minimum of 24 hours with
timer using a cadence pattern operation. 5 minutes of alarm. Actuators must be electrically
compatible.
UL and FM Extinguishing Release System Panels
5. For FM Approved Deluge and Preaction Sprinkler
must have a minimum of 24 hours of standby power.
operation: IDCs must be Class A, wired to
Initiating devices must be Listed/Approved for the Listed/Approved devices; secondary standby capacity
application, and may be wired either Class A or B.
must be a minimum of 90 hours with 10 minutes of
Actuators must be electrically compatible with the control
alarm; and the specified compatible Automatic Water
panel circuits and power supplies, and are wired Class B to Control Valves/Actuator must be used. (See list on
provide coil supervision. (See details in next section.)
page 8.)
Deluge and Preaction Sprinkler Systems 6. Power supply loading and wiring distances must be per
automatically activate water control valves in response to Installation Instructions 579-354.
fire detection device input. 7. Battery standby must be selected for proper actuator
Deluge Sprinkler Systems employ open sprinkler heads operation and may require a minimum voltage of
and provide water flow when the fire detection system 23 VDC depending on the actuator. Detailed battery
activates a common automatic water control valve. They are calculation reference information is contained in
used to deliver water simultaneously through all of the open Installation Instructions 579-354.
sprinkler heads. This type of system is applicable where the 8. Maintenance Switches, one per RAC, are required per
immediate application of large quantities of water over large NFPA 72, the National Fire Alarm and Signaling Code,
areas is the proper fire response. to allow the system to be tested or serviced without
Preaction Sprinkler Systems are similar to deluge actuating the fire suppression systems. Their use may not
systems except that normally closed sprinkler heads are used be allowed in some jurisdictions, always confirm local
and supervisory air pressure is maintained in the pipe. requirements. When used, Simplex Maintenance
Operation requires both an activated sprinkler head and an Switches are required to ensure that operation initiates a
activated fire alarm initiating device. supervisory condition.
Additional System Device Information
Combined Agent Release and Preaction Systems
provides agent release and preaction control. (Available 1. Simplex Abort Switches are available when abort
with software revision 4.01 or higher.) For applications operation is required. When used, wire on Special
where agent release may not be sufficient for fire control, Purpose Monitoring Circuits (SPMs) as Class A or
sprinklers are put in preaction mode to allow waterflow to Class B; Simplex model Abort Switches are required.
continue the fire response. (Preaction is assumed, selected 2. Manual Release Stations are used for direct activation of
deluge could be provided, determined by the sprinkler the release actuators with the appropriate time delay
installation, panel operation is the same.) implemented by the fire alarm control panel.
UL requirements for Fire Alarm Systems Listed for 3. See pages 2 and 3 for additional reference information.
Automatic Release or Deluge and Preaction Sprinkler
Additional Information
Systems are the same as described above for Automatic
Extinguishing Release Systems. This data sheet is a summary of the extensive operating
FM Approved requirements for Fire Alarm Systems for features and options available with the 4004R Release
Automatic Release of Deluge and Preaction Sprinkler Control Panel. Complete details are covered in the 4004R
Systems require operation of specific compatible FM Installation, Programming, and Operating Instructions
Approved Automatic Water Control Valves, a minimum manual (publication 579-354) shipped with each 4004R.
secondary power capacity of 90 hours, and all circuits for Compatible system devices are listed on page 3. For general
the automatic release initiating devices must be capable of information, refer to Factory Mutual Research Corporation
operation during a single open circuit fault condition (FMRC) “FMRC Approval Guide,” FM Approval standard
(Class A). “Deluge Systems and Preaction Systems.”
PLEASE NOTE: Proper operation of release control systems requires that the system design, installation, and maintenance be
performed correctly and in accordance with all applicable local and national codes, and equipment manufacturer’s
instructions. No liability for total system operation is assumed or implied.
5 S4004-0002-9 7/2018
Specifications (Refer to diagram on page 7 and Instructions 579-354 for additional information)
Power Ratings
Voltage Ratings 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
AC Input
Current Ratings 2 A maximum @ 120 VAC input; 1 A maximum @ 240 VAC input
Power Supply Output 3 A maximum available for external loads
Temperature compensated, capable of recharging batteries required for 90 hour
Battery Charger
standby and 10 minute alarm (contingent on auxiliary power load)
Standby Current 100 mA; with IDCs fully loaded, tone-alert silenced, trouble LED on, charger off
Alarm Current 264 mA + external loads; (2 zones in alarm & 2 internal relays, NACs and RACs on)
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum; see NAC ratings for details)
Supervisory 3 mA maximum; 3.3 kΩ end-of-line resistor per circuit
Alarm Current 75 mA maximum
Initiating Device
Circuits (IDCs) Output Voltage 28 VDC maximum
Each IDC supports up to 30 detectors (smoke or electronic heat) and manual
Capacity
stations as required; wiring distance is limited to 50 Ω maximum
For Manual Release, Abort Switches, or Supervisory functions only; not for
Application
detectors; wiring distance is limited to 50 Ω maximum
Special Purpose For Dual Hazard Dual Hazard Application Abort Switches require a current limiting resistor of 1.2 kΩ,
Monitoring Circuits Applications 1 W, or an external Abort Supervision Module per SPM
(SPMs) Supervisory 6 mA; 3.3 kΩ end-of-line resistor per circuit
Activated 75 mA maximum
Output Voltage 28 VDC maximum
Special Application appliance rating = 2 A maximum on a NAC
NOTE: Special Application appliance rating = full 3 A power supply rating
Alarm Current
Regulated 24 DC appliance power = 1.5 A maximum on a circuit
Notification
Appliance Circuits NOTE: Regulated 24 DC strobe load = 1.35 A maximum total for power supply
(NACs) Output Voltage Alarm = 26 VDC max.; supervisory = 29 VDC maximum; 10 kΩ end-of-line resistor
Requires NAC dedicated to strobe control with non-coded output; use an external
Synchronized
Synch Module (4905-9914, Class A, or 4905-9922, Class B, see data sheet
Strobe Operation
S4905-0003 for details); up to 33 strobes can be synchronized per 4004R
Special Application Simplex 4901 Series horns, 4904 and 4906 Series strobes, 4903 Series 4-wire
Notification Appliances horn/strobes; refer to Installation Instructions 579-354 for additional details
Appliance
Reference Regulated 24 DC Power for other appliances listed to UL Standard 1971 or UL Standard 464; use
Appliances associated external synchronization modules where required
Output Current 2 A maximum per circuit
Release Appliance
Circuits (RACs) Activated = 26 VDC maximum; non-alarm = 29 VDC maximum;
Output Voltage
10 kΩ end-of-line resistor
Auxiliary Power Output; for Special Two outputs are available, continuous operation or resettable operation; combined
Application loads only output is 750 mA maximum; output voltage = 19.25 to 27 VDC
Auxiliary Relay Outputs Contacts rated 2 A @ 30 VDC, 0.35 p.f., inductive, selectable as N.O. or N.C. by
(Trouble, Aux Relay 2, Aux Relay 3) jumper
Wiring Connections for Above and AC Input Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
Auxiliary Module Ratings
Two circuits per module, rated same as circuits; not applicable to RACs (no
Class A Adapter Module 4004-9684
additional current required)
Relay Type Four relays with two outputs per relay; individually selectable as N.O. or N.C.
AC Ratings 7 A @ 120 VAC, resistive
Auxiliary Relay Module
DC Ratings 5 A @ 30 VDC, 0.35 power factor, inductive
4004-9860
Module Current 12 mA standby; 70 mA with all four relays energized; @ 24 VDC
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
2081-9046 Coil Supervision Module and 2081-9048 Abort Supervision Module (see page 7 for additional details)
Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Coil Supervision Module Current Rating 2 A maximum; internally fused at 3 A, non-replaceable
Abort Supervision Module Resistance 560 Ω, 1/2 W
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
6 S4004-0002-9 7/2018
s4004R System Connection Reference
Listed/approved actuator or Deluge
A and Preaction Automatic Water
Control Valve; one if 24 VDC (or 2 in
series if 12 VDC) per RAC
+ In - NAC+
INSTALLATIONINSTRUCTIONS574- 437 REV
MAINTAIN1/4 " SEPARATION
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S
LIMITED( YEL/BLK) W IRING
DATECODE: 519- 958
BLK
IN-
DATE CODE:
LIMITED (YEL/BLK) WIRING
OUT -
BLK
NORMAL
1
DISC./
DISABLE
24 VDC for Maintenance Disconnect
BLK SIMPLEX TIME RECORDER CO. WESTMINSTER MA 01441 USA
FIRE SUPPRESSION
DISCONNECT / DISABLE status indicator (if required)
RAC 2
Abort Switches Manual Release Optional 4905-9914 or
(as required) Stations RAC 1 4905-9922 Strobe
Synchronization Module
FIRE SUPPRESSION FIRE SUPPRESSION
SYSTEM ABORT SYSTEM ABORT
SPM 1 SPM 2
Alarm
Trouble
Alarm
Trouble
Zone 1
Zone 2
Manual Release
Zone 5 Trouble
Manual Release
Zone 6 Trouble
NAC 1
CAUTION
4-Wire
Alarm NAC 1 Trouble DISCONNECT
Trouble
Zone 3 NAC 2 Trouble
IDC 1 Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER
Horn/Strobe
Alarm Silenced Agent Released BEFORE
SERVICING
7 S4004-0002-9 7/2018
Compatible UL Listed Valves and Actuators
* For 24 VDC, 450 mA activation requires one actuator connected in series with a 73866 (21.5 ohm, 23 watt) in-line resistor shipping assembly
ordered separately. For additional information refer to the manufacturer’s technical documentation.
8 S4004-0002-9 7/2018
Compatible
Compatible FM
FM Approved
Approved Water
Water Co
Control Valves
4004R Control Panels are assigned to FM Release Control Panel Group 3. Group 3 FM Approved Release Control Panels are
compatible with all FM Approved Solenoid Valves rated at 22 Watts or less. For verification of agency listings and power
requirements refer to the solenoid valve manufacturer’s technical documentation.
Aux.
Class A adapter boards
relay
module 1 Door thickness
Relay Relay
Disc 1 Disc 2
AC input
Battery Area
No conduit or wiring in this area
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and