Automatic Mains Failure: Mcpherson Controls
Automatic Mains Failure: Mcpherson Controls
Automatic Mains Failure: Mcpherson Controls
McPherson
Controls
TM
McPherson Controls
www.mcphersoncontrols.com
TABLE OF CONTENTS
Section Page
ATTENTION ........................................................................................................................................... 3
PROJECT BACKGROUND.................................................................................................................... 3
INTRODUCTION .................................................................................................................................... 3
AMF-10 MONITORING AND PROTECTION FUNCTION ...................................................................... 3
2. OPERATION ...................................................................................................................................... 7
2.1 Summary....................................................................................................................................... 7
2.2 Auto Mode Of Operation................................................................................................................ 7
2.3 Off Mode Of Operation .................................................................................................................. 8
2.4 Manual Mode Of Operation ........................................................................................................... 8
2.5 Test Mode Of Operation ................................................................................................................ 8
5. SPECIFICATION .............................................................................................................................. 14
______________________________________________________________________________________
2
AMF-10 Automatic Mains Failure Module
The customer can program the AMF-10 module ● Battery over and under voltage monitoring
directly from the front panel without using a ● Low fuel level monitoring
computer. Any new settings are recorded into the
internal (EEPROM) and protected from erasure AMF-10 has 2 extra inputs for the customer to use
even without battery. and set-up, like fuel overflow, radiator water levels,
etc.
The AMF-10 has 4 settings; Automatic (AUTO) -
Manual (MANU) - Testing (TEST) and Shutdown
(OFF) in addition to this four buttons the front panel
has a 4 digital, 7 segment numerical displays
showing all the alternating Volts, Amps and Hertz,
Battery Volts and engine running Hours readings
and the programming interface for changing all the
engine, ATS and generator parameters.
Normal Power Manual Transfer the Switch from Emergency to Normal Position
Connect to Load (ON MANUAL MODE ONLY)
Emergency Power Manual Transfer the Switch from Normal to Emergency Position
Connect to Load (ON MANUAL MODE ONLY)
______________________________________________________________________________________
4
AMF-10 Automatic Mains Failure Module
Harness Fixture
______________________________________________________________________________________
5
AMF-10 Automatic Mains Failure Module
L 12 L 23 L 31 AMF-10
Volt Batt
Amp
Freq Hour
______________________________________________________________________________________
6
AMF-10 Automatic Mains Failure Module
In AUTO mode, the START - STOP - MAIN - GEN After engine starts, the AMF-10 enters a 30sec
buttons do not operate. They work only when the grace period, delaying any shutdowns, and giving
controller is in Manual operation. See paragraph the generator time to reach normal engine speed,
2.5. together with oil pressure, AC voltage and other
operating parameter, the screen displays [Ac.XX]
Press the AUTO button and notice the LED after confirming that everything is running OK.
lights-up confirming that you are in AUTO. In AUTO
mode the ATS (Automatic Transfer Switch) and But if the genset does not run normally before the
genset are directly controlled by the AMF-10. 30sec grace period is up, the module shutdown the
generator displaying the reason for stopping the
The operation sequence in AUTO is as follows; genset on the front panel.
when the AMF-10 detects any unusually voltage or
no voltages or a missing phase coming from the Now if the generator stabilizes and reaches its rated
normal (city grid), it automatically initiates the output, The AMF-10 starts the TDNE (Time Delay
generator start sequences Normal to Emergency) countdown, showing [nE.XX]
on the front screen. (Remember that each entered
First activating the engine Preheat, and at the same value is equals to 5sec delay, the preset TDNE
time displaying the Pre-Heat countdown in countdown is 10sec, See page 12). When the
seconds[PH.XX]on the front screen. countdown stops, the module sends a signal to the
transfer switch to change-over from normal to
Second, after the preheat times out, the starter
emergency (standby generator) power. If the
motor begin to start and the screen displays the
transfer switch fails to do this in 15sec, the AMF-10
starter motor running time [St.XX] The starter motor
runs for 6 sec. (the user can change the running flashes emergency on LED and display FAIL on the
time of the starter motor for up to 30 seconds) If the screen, after the problem is resolved, press the
engine fails to start the first time, the AMF-10 SET/Failure reset button to remove the warning
returns to Preheat and tries again. The AMF-10 tries signal.
3 times (the user can also change how many times
the engine tries to start - up to 9 times).
______________________________________________________________________________________
7
AMF-10 Automatic Mains Failure Module
As soon as Normal power returns, the AMF-10 Shutdown immediately to prevent further damage to
verifies this and begins the TDEN (Time Delay the genset. Once the generator completely stops,
Normal to Emergency) countdown showing [En.XX] the reason for the failure is displayed on the front
on the screen. Again each entered value equals panel, helping maintenance locate the problem. To
5sec, the factory preset TDEN countdown is 10sec erase the failure signal, press the [SET / FAILURE
(see page 12). When the countdown stops, the Reset]key or switch to OFF position.
module sends a signal to the transfer switch to
change-over from emergency to normal power. On OFF mode, the operator can press the Increase
/ Selection [︽] button, to get other readings for
Finally the engine executes TDEC. (Time Delay battery voltage and Operating hours. These
Engine Cool down) The screen display readings are switched from one to the other every
[CL.XX]Again each entered value equals to 5sec; 2sec.
the preset TDEC count down is 60sec (see page
12). 2.4 Manual Mode of Operation
On MANUAL, the operator can manually start and
ATTENTION!! stop the generator and activate the transfer switch
When the generator is on Engine Cool-down to go from Normal to Emergency solely by using the
the AMF-10 protection system remains in START – STOP - MAINS- GENERATOR buttons on
effect and if any failure occurs, the module front of the AMF-10
bypasses the countdown and shutdown
[START]Manual Engine Start
generator immediately.
[STOP]Manual Engine Stop
[MAIN]Manually change over to Normal Power
[GEN]Manually change over to (Stand by) Power
After Engine Cool down, the AMF-10 cuts the
Engine fuel by using either one of two different The Engine Start, Shutdown and transfer switch
methods (either Energize to Stop or Energize to changeover sequence under MANU mode is the
Start), the AMF-10 display[SP.XX]on the front same as the AUTO mode, reference from Section
screen. 2.2 (page 7).
In AUTO mode, AMF-10 allows the operator to use 2.5 Test Mode of Operation
a remote signal to test the generator with or Without
LOAD (programmable). Under no load testing, the TEST mode is testing function operated under no
AMF-10 starts the genset, but do not test the load from the genset. When switching AMF-10 into
transfer switch and the generator remains without TEST mode, if the system with load and under
load. If conducting the test with load, the module normal power supply status, the module only start
starts the genset and using the transfer switch puts up the genset to conduct a test with no load and
the generator on load. dismiss the test for the transfer switch changeover.
Volt Batt
Amp
The first thing the screen shows is [Vr1.0] for 2sec,
(this is the software version number) after that it Freq Hour
changes to [Pro.] for Programming, next the display
changes to looks like the frame underneath.
Now you can change the hour-meter by using the
UP/DOWN arrows.
Volt Batt
Amp
Freq Hour
______________________________________________________________________________________
9
AMF-10 Automatic Mains Failure Module
See System entry Setting Reference Table lines When using the AMF-10 for overload
6,7,11,12,23,24 for all AC voltage, current display protection, you need to pay special attention
parameter and settings. not to exceed the CT primary rated current,
otherwise the CT will saturation cause
3.5 Engine Over-Load Protection Setting incorrect readings leading to a failure in
overload protection.
ATTENTION!!
For example:CT ratio equals to 1000A:5A,
AMF-10 provides overload protection from then over current setting value can not
the generator only. There is no overload exceed 1000A.
protection on the normal side.
______________________________________________________________________________________
10
AMF-10 Automatic Mains Failure Module
______________________________________________________________________________________
11
AMF-10 Automatic Mains Failure Module
______________________________________________________________________________________
12
AMF-10 Automatic Mains Failure Module
______________________________________________________________________________________
13
AMF-10 Automatic Mains Failure Module
Emergency
5. SPECIFICATION
Shutdown
Shutdown Activated Entry Specification
High Water DC Supply 9 ~ 36 VDC
Shutdown
Temperature Alternator Input Range 15 ~ 510 VAC (Ph-Ph)
Low Oil Pressure Shutdown Alternator Input
50 ~ 60 Hz
Frequency
Start Signal Output 10 Amp @ 12/24VDC
Over-speed Shutdown
Fuel Solenoid Signal
10 Amp @ 12/24VDC
Shutdown Output
Under-speed
or Warning Preheat Signal Output 10 Amp @ 12/24VDC
Shutdown Accessory “ON”
AC over voltage 10 Amp @ 12/24VDC
or Warning Output
Shutdown Idle Control Conductor
AC under voltage 10 Amp @ 12/24VDC
Capacity
or Warning
Warning Signal Output 10 Amp @ 12/24VDC
Shutdown
Genset Over-load Overload Alarm Output 10 Amp @ 12/24VDC
or Warning
Normal Power Connect
Shutdown 8 Amp @ 250VAC
Low Fuel Level to Load Signal
or Warning
Stand by Power
Low Battery Voltage Connect to Load 8 Amp @ 250VAC
Warning Only
Warning Signal
Service & Power Consumption Under 5VA
Maintenance Warning Only Operating Temperature -20 to 70℃
Warning
Relative Humidity Under 95%
Shutdown
Spare Setting 1 Rated CT Capacity Above 2.5VA
or Warning
Shutdown Secondary Rated
Spare Setting 2 5A
current
or Warning
Weight 0.5KG
Normal Power
available
______________________________________________________________________________________
15
AMF-10 Automatic Mains Failure Module
MC GC
MAIN GENSET
ON Coil ON Coil
J2-1 J2-2 J2-3 J3-1 J3-2 J3-3 J3-4 J4-3 J4-2 J4-1 J3-7 J3-8 J3-9 J3-10
8A 8A
AMF-10 Controller 8A 8A 8A 8A 8A 8A 8A
J3-5 J3-6 J1-11 J1-12 J1-13 J1-14 J1-15 J1-16 J1-17 J1-2 J1-3 J1-10 J1-6 J1-7 J1-9 J1-5 J1-4 J1-8
Temperature SW
Emergency Stop
Oil Pressure SW
Fuel Level SW
Remote Test
Prog.-1
prog.-2
MC ON
GC ON
BZ
Comm. Alarm
Pre-Heat
Start
Over-Load
Stop
IDLE
Accessory
+
Alarm
"ON"
BATTERY
LOAD
MC GC
MAIN GENSET
ON Coil ON Coil
J2-1 J2-2 J2-3 J3-1 J3-2 J3-3 J3-4 J4-3 J4-2 J4-1 J3-7 J3-8 J3-9 J3-10
8A 8A
AMF-10 Controller 8A 8A 8A 8A 8A 8A 8A
J3-5 J3-6 J1-11 J1-12 J1-13 J1-14 J1-15 J1-16 J1-17 J1-2 J1-3 J1-10 J1-6 J1-7 J1-9 J1-5 J1-4 J1-8
Temperature SW
Emergency Stop
Oil Pressure SW
Fuel Level SW
Remote Test
Prog.-1
prog.-2
MC ON
GC ON
BZ
Comm. Alarm
Pre-Heat
Start
Over-Load
Stop
IDLE
Accessory
+
Alarm
"ON"
BATTERY
______________________________________________________________________________________
16
AMF-10 Automatic Mains Failure Module
LOAD
MC GC
MAIN GENSET
ON Coil ON Coil
J2-1 J2-2 J2-3 J3-1 J3-2 J3-3 J3-4 J4-3 J4-2 J4-1 J3-7 J3-8 J3-9 J3-10
8A 8A
AMF-10 Controller 8A 8A 8A 8A 8A 8A 8A
J3-5 J3-6 J1-11 J1-12 J1-13 J1-14 J1-15 J1-16 J1-17 J1-2 J1-3 J1-10 J1-6 J1-7 J1-9 J1-5 J1-4 J1-8
Temperature SW
Emergency Stop
Oil Pressure SW
Fuel Level SW
Remote Test
Prog.-1
prog.-2
MC ON
GC ON
BZ
Comm. Alarm
Pre-Heat
Start
Over-Load
Stop
IDLE
Accessory
+
Alarm
"ON"
BATTERY
LOAD
MC GC
MAIN GENSET
ON Coil ON Coil
J2-1 J2-2 J2-3 J3-1 J3-2 J3-3 J3-4 J4-3 J4-2 J4-1 J3-7 J3-8 J3-9 J3-10
8A 8A
AMF-10 Controller 8A 8A 8A 8A 8A 8A 8A
J3-5 J3-6 J1-11 J1-12 J1-13 J1-14 J1-15 J1-16 J1-17 J1-2 J1-3 J1-10 J1-6 J1-7 J1-9 J1-5 J1-4 J1-8
Temperature SW
Emergency Stop
Oil Pressure SW
Fuel Level SW
Remote Test
Prog.-1
prog.-2
MC ON
GC ON
BZ
Comm. Alarm
Pre-Heat
Start
Over-Load
Stop
IDLE
Accessory
+
Alarm
"ON"
BATTERY
______________________________________________________________________________________
17
AMF-10R
AMF-10R
AMF-10R
AMF-10R