Loop M X H
Loop M X H
Loop M X H
Loop M X H
Part no 5100026-01A
Data
Operating voltage range 19-30 VDC
Voltage range loop 29-38 VDC
Current consumption
55 mA
Connections
(at 24 V)
Max. output current 500 mA (< 15 minutes)
Continuous output
250 mA
current
Max no. of loop units 254
Cable terminals 2,5 mm2
Operating temperature
-5°C to +55°C
range
Weight (with housing) 140g
Spare part no.
5100025-01B
(without housing)
Settings
The module is identified by a physical address on
the Backbone Bus. The address is set with an 8-pole
DIP switch.
The specifications described herein are subject to change without notice. Data sheet no: 5100026-01A Loop M X H.10 3.I0E
www.cnsystem.se
2(2) DATA SHEET
Indicators Indicator
Indicator
Status
Loop M X indicators display output and alarm Colour
status. One or more
Red, steady
alarms are present
ALARM Red, flashing Pre-alarm
There are no
None
alarms
One or more faults
Yellow, steady
are present
FAULT
Yellow, flashing Booting
None There are no faults
Green OK
Note! Yellow, steady Power Fault
If all LED's are flashing the DIP switch are set
Yellow, flashing:
to zero. Please set the correct address.
PS 0.5 sec On, Boot loader mode
(Power Supply) 0.5 sec Off.
Yellow, flashing:
1 sec On, Safe State
0.5 sec Off.
Green, steady OK
Green, flashing Unconfigured
COM Faulty
Yellow, steady
(Communication) communication
Yellow, flashing Major fault
None No communication
PS
PS + COM Yellow, flashing Transferring
(both flashing) COM software
Green, flashing
Mounting
Mount the module horizontally on a 35 mm DIN rail.
The specifications described herein are subject to change without notice. Data sheet no: 5100026-01A Loop M X H.10 3.,E
www.cnsystem.se