Tyco T1000
Tyco T1000
Tyco T1000
DATASHEET
T1000
Intelligent Marine Control Panels
Features
Developed for Vessels with less than 300 detectors
Approved by all major Marine Authorities
Customer friendly, miltu language information on LCD
display
Comprehensive fault diagnostics
Executive actions for Fire Doors, Local Extinguishant
Release, Fans/Blowers
Interface to other shipboard Control/Graphic systems
One man installation
8 and 16 Zone panels
Wide range of Minerva Marine approved detectors
4 Monitored sounder outputs up to 4A
4 Monitored relay outputs
3 Programmable auxiliary inputs
3 Levels of alarm discriminations per zone
Programmable cause and effect
The T1000 panels’ default configuration is set for use with the User Interface
companies own highly acclaimed internationally approved Lo-pro The user interface is provided through a combination of LEDs and a
detector range.. 2 x 40 character LCD display. The LEDs provide clear indication that
a fire, fault, isolate or technical alarm condition is present.
The T1000 panel is also fully compatible with the companies unique
MU601 Carbon Monoxide fire detector. The display also shows the first and last zone in Alarm and Fault.
For hazardous applications the panels have been tested with the The user interface provides two rows of user selectable buttons. The
companies intrinsically safe BASEEFA certified System 601 which first row is used to deal with emergency and alarm situations whilst
includes the M300Ex intrinsically safe range of smoke, temperature the second row is used for information enquiries. The first row
and flame detectors (See Note 1). includes the ability to view alarms, silence, accept, reset and
evacuate. The second row provides the ability to view historical
Plant Alarm Monitoring alarms, fault conditions, technical alarms and disable conditions.
Zones on the Panel can also be programmed to monitor Machinery
Spaces Fans/Blowers, Fire Doors and Engine Room Fire Dampers. The LCD display provides a full customer definable text display of the
alarm or fault condition whilst also displaying zones in alarm, fault or
Auxiliary Inputs isolate status. The display also indicates the outputs that have been
Three additional programmable inputs on the panel can be used for activated.
Muster signals, initiation of sounder circuits for indicating class
change in educational establishments and providing Remote Reset
or Remote Accept signals.
PSF096TFIS:Layout 1 07/01/2011 09:53 Page 3
Optional Printer
An optional printer can be fitted within the NT1000 panel to provide
an on-line printout of events as they occur. Alternatively the printer
can be commanded to print out a selected list from the alarm and
T1000 FIRE PANEL event history.
PSF096TFIS:Layout 1 07/01/2011 09:53 Page 4
SPECIFICATIONS
Inputs
Detector Circuit:
2.2mA max with resistor 6k8 EoL (50R max line resistance)
Alarm Level 1 (e.g. Alarm) - 550 to 1kOhms
Alarm Level 2 (e.g. evacuate) - 85 to 270 Ohms (Max. 32 x M300
or M600 detectors per zone or 24 with detector monitoring enabled
Note 1)
Aux Inputs: 24V dc line voltage
Note 1 - Refer to document number 26A for design details on sys-
tem 601 BASEEFA certified Intrinsically Safe applications.
Mounting Arrangement
For further information on how we can help you, please visit our website at www.tycofis.com or e-mail us on [email protected].
The right is reserved to modify or withdraw any product or service without notice. PSF096TFIS Issue 2 November 2006 © 2006