Load Break Switch SF 6 Gas

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

ENhanced www.entecene.co.

kr
TEChnology

Pole mount SF6 gas insulated


load break switch
for power distribution system
thru 15kV, 27kV, 38kV

Version 2.0
General features
Pole mounted SF 6 load break switches are Microprocessor based controller
designed to meet growing requirements for Microprocessor based control cubicle for feeder
reliability. automation is designed for outdoor pole
Switches filled with SF6 gas as the insulating mounting on an separate external panel and is
and arc quenching medium with puffing normally mounted low on the pole for ease of
principle in make and break ensure the access.
positive breaking of small inductive, mainly The basic control cubicle is provided with
active load current, cable charging current, detection of phase and earth faults sensing from
magnetizing current etc and manufactured current sensing elements and checks the live
under a quality system conforming to ISO 9001. and dead line status from the voltage sensing
element.
The details of the fault and event log can be
stored and transmitted over the SCADA or
Manual and motor operation remote control through modem.
The basic mechanism is operator independent
quick close and quick open spring toggle
mechanism.
The motor operating mechanism is developed to
meet the feeder automation in addition to the
manual switch. The motor driven shaft is
connected to the manual operating lever
through cam with spool so that the manual
operating handle is free to operate regardless
of the position of the motor driven mechanism.

Stainless steel enclosure and safety devices


The switch enclosure is made of stainless
steel plate(STS304L) and filled with SF6 gas
pressure 2kg/cm2.G for maintenance free. The
low pressure locking device operating at the
level of the pressure 0.3-0.7kg/cm2.G and
pressure relief device operating at the level of
the bursting pressure 4.0-6.0kg/cm2.G are
guaranteed for safety operation.

Porcelain and polymeric bushing.


The porcelain and the polymeric bushing have
long creepage distance.
The high voltage terminal is provided with the
NEMA terminal or the molded cone type lead
which has high dielectric strength even under
heavily polluted conditions.
Construction (Type : ETGA6)

Name plate Handle Locking Device

1464 Attention sticke


Hanger

FREE
LOCK

524
115 204.5
CLOSE OPEN

Handle Leg

Indlcator

Electrical ratings

(Rated maximum) Voltage kV 15 27 38


Rated Load current A 400/630 400/630 400/630
Closed loop breaking current A 400/630 400/630 400/630
Cable charging breaking current A 25 25 20
Rated Load breaking capacity No. 200/400 200/400 200/400
Rated Short time withstand current . 1sec kA rms 12.5/20 12.5/16 12.5/16
Rated Short-circuit making current kA peak 32.5/50 32.5/42 32.5/42
Impulse withstand voltage(1.2 50 )
- To earth and between phases kV 95 125/150 150/170
- Across disconnector kV 110 145/165 165/195
Power frequency withstand voltage, dry
- To earth and between phases kV 38 50 70
- Across disconnector kV 45 60 60
Other ratings is available upon request.
Main products

Solid Insulated type SF6 Gas Insulated Type

Automatic Circuit Recloser


Rated Voltage ( kV) 15 27 38
Rated Current ( A ) 630/800
Rated lightning impulse
withstand voltage ( kV) 110 150 170

Rated Interrupting 12.5/20 12.5/16 12.5/16


Current ( kA )

Pad Mount Switchgear


Rated Voltage ( kV) 15 27
Rated Current ( A ) 400/630
Rated lightning impulse
withstand voltage ( kV) 110 125
Rated Interrupting Current ( kA ) 12.5

Pad Mount Load Break Switch


Rated Voltage ( kV) 15 27
Rated Current ( A ) 400/630
Rated lightning impulse
withstand voltage ( kV) 110 125
Rated making current ( kA ) 32.5

Compact light weigh design Long life Cost effectiveness


High quality & reliability Convenient operation Minimum maintenance

78-2 BUNCHEON-RI BONGDAM-EUP HWASEONG-CITY GYUNGGI-DO KOREA


TEL: +82-31-227-1161 FAX : +82-31-227-1164
http://www.entecene.co.kr E-mail : [email protected]