Enclosure Heat Load PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 55

HOW TO CALCULATE ENCLOSURE HEAT LOAD AND WHY

YOU NEED TO COOL ELECTRONICS.


HARMFUL
HEAT
Like people, industrial electronics can over-heat,
causing malfunction and even complete failure.
The good news is that electronic components
HOFFMAN®  MCLEAN®  SCHROFF®
can be kept cool to extend their life and prevent
HOFFMAN®  MCLEAN®  SCHROFF®

expensive operations downtime.

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 2


LEARNING OBJECTIVES

• Understanding why temperature variation can be a problem


• Understand the consequences of over-heated electronics
• Learn the benefits of cooling industrial electronics
• Identify the sources of damaging heat
• Learn how to size a cooling unit for your cabinet

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 3


HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 4


WHY CAN TEMPERATURE VARIATION BE A PROBLEM?
Typical devices housed in an enclosure in an
Automation Control System
▶ VARIABLE FREQUENCY DRIVE (VFD)
▶ SERVO DRIVE
▶ PROGRAMMABLE LOGIC CONTROLLER (PLC)
▶ STARTER KIT
▶ POWER SUPPLY
▶ INVERTER
▶ RELAYS
▶ TERMINAL BLOCKS
▶ INDICATOR LIGHTS
▶ TRANSFORMER*
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

* Typically outside the control panel, but can sometimes be Electrical Enclosure
included inside the enclosure
VFD

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


WHY CAN TEMPERATURE VARIATION BE A PROBLEM?

TEMPERATURE EXTREMES WILL CAUSE


PROBLEMS
AT HIGH TEMPERATURES:
Drive performance is de-rated
I/C- based devices behave strangely-
funky output- voltage migration
(Properties of silicone materials
change with temp extremes)

AT LOW TEMPERATURES
Cooling below the dew point leads to
condensation - promotes corrosion
Batteries
HOFFMAN® 
die
MCLEAN SCHROFF
® ®

I/C
HOFFMAN® 
-based devices behave strangely
MCLEAN SCHROFF
® ®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 6


WHY CAN TEMPERATURE VARIATION BE A PROBLEM?
All Metal-Oxide-Semiconductor electronic components are sensitive to
temperature changes: Metal Oxide field effect transistors (MOSFET) are no
different
• Electrical characteristics
• Threshold voltage = Applied voltage to the gate
• The higher the temperature , the higher the threshold voltage
trigger point requirements
• May cause the transistor to drift out of design requirements
• The higher the temperature, the longer it takes for the gate to open
• The higher the temperature the greater the internal resistance – the
gate may not open at all
• Result: the gate does not open when it is designed to, which
HOFFMAN MCLEAN SCHROFF
® ®

HOFFMAN MCLEAN SCHROFF


® ®
®

adversely affects other components on the circuit


• Life Expectancy
• Properties of silicon oxide used in the components changes with
temperature fluxuations

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 7


WHY CAN TEMPERATURE VARIATION BE A PROBLEM?
Mechanical properties of materials change with increasing temperatures

In Wiring Insulation
• Elasticity and
strength are
reduced
• Ductility increases
temporarily
• Atomic Mobility
increases
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 8


TREND TOWARD MORE HEAT
As information processing becomes more powerful,
the heat generated from electronics continues to increase.

“Semiconductor transistor density and


performance double every 18-24 months.”
Moore’s Law
Named for Intel founder,
Dr Gordon Moore

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

The need for more electronics cooling continues to grow


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


WHY CAN TEMPERATURE VARIATION BE A PROBLEM?
Every 10 C / 18 F over room temperature cuts electronics life in half.

52 C / 126 F 12.5%

42 C / 108 F 25%

32 C / 90 F 50%

22 C / 72 F 100%
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

0 10 20 30 40 50 60 70 80 90 100
Percent of Electronics Life Expectancy
Source: DEC Study

Using cooling can avoid early automation drive replacement


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
RUNNING HOT
COMPONENTS
IS A GAMBLE
Depending on the equipment, allowing
electronic components to run hot can be a
costly gamble.
Early replacement of industrial drives,
hours of automation system downtime,
and out-of-warranty conditions all become
HOFFMAN MCLEAN SCHROFF
® ®

HOFFMAN MCLEAN SCHROFF


® ®
®

risks when cooling is not used.

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 12


CONSEQUENCES OF HOT ELECTRONICS
One hour of industrial operation downtime can cost big money

UP TO $500,000 PER HOUR!

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

Lost production+ direct repair cost + lost opportunity cost= Cost of downtime

A little investment in cooling can save huge costs later


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
CONSEQUENCES OF HOT ELECTRONICS
Operating electronics over its specified temperature
could void the manufacturer’s warranty.

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

Using cooling can prevent unpleasant and expensive surprises


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 15


SOURCES OF DAMAGING HEAT
Typical efficiency of devices housed in an enclosure
in an Automation Control System
▶ VARIABLE FREQUENCY DRIVE (VFD)
▶ APPROX. 95 TO 98% EFFICIENT

▶ SERVO DRIVE
▶ >85% EFFICIENT

▶ POWER SUPPLY
▶ APPROX. 60 TO 83% EFFICIENT

▶ TRANSFORMER*
▶ APPROX. 95-99% EFFICIENT

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

* Typically outside the control panel, but can sometimes be


included inside the enclosure

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


SOURCES OF DAMAGING HEAT
Heat can also come from outside the electrical enclosure and
radiate inside, further adding to the heat stress of the component.

IRON FOUNDRY WELDING PROCESS SOLAR HEAT GAIN DRYING OVEN


MINING INTENSE LIGHTING HOT WEATHER BLAST FURNACE
Heat radiates
HOFFMAN® intoSCHROFF
MCLEAN ® the ® Applies extra heat load Dark-painted enclosures Many factories around
control
HOFFMANcabinet
®
MCLEAN from
®
SCHROFF ®
to the automation collect more heat than the world are hot
outside electronics inside light-colored cabinets environments and use
automation equipment

Most of these conditions require industrial control cooling


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 17
TERMS AND ABBREVIATIONS

Heat Load
The heat generated by the equipment or
system and is usually given in Watts
Max System Temperature TMAX
The maximum internal system
equipment temp allowable. TMAX
Ambient Temperature TA
The Outside or Inlet Temperature to the Heat
equipment or system.
Load
Temperature Rise or T
The difference between the Maximum
HOFFMAN®  MCLEAN®  SCHROFF®
TA
HOFFMAN®  MCLEAN®  SCHROFF®
Internal System Temp. and the Ambient
Temperature.
T = TMAX - TA AMBIENT

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


TERMS AND ABBREVIATIONS

Solar load
This is the contribution to the heat load of the
Sun on outdoor systems
Noise
Quoted in dB(A)
The higher the number the louder the fan.
Volumetric Flow Rate
Air flow performance of the fan in free air
(i.e. fan blows in free space without static
pressure) measured in CFM or m3/hr
Static Pressure
HOFFMANThis
®
is the
MCLEAN®
amount of ambient air pressure.
SCHROFF ®

HOFFMAN MCLEAN SCHROFF


® ® ®

As air pressure increases fan performance


declines.
In general, high static pressure in in an
application is caused by air flow
obstructions and/or inadequate venting

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


TERMS AND ABBREVIATIONS
Fan Curve System Flow Resistance
This is the key performance This curve represents the system or
characteristic for Fan Performance
a particular fan vs System
requirements resistance to the flow of air
Characteristic
itself.
Static Pressure (Inches H2O)

1.2

1
Static
0.8
PressureInc
hes (H2O) 0.6

0.4

0.2

HOFFMAN®  MCLEAN®  SCHROFF®


0
HOFFMAN®  MCLEAN®  SCHROFF® 0 200 400 600 800
Air Air
FlowFlow - CFM
(SCFM)

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


CONVERSIONS/ASSUMPTIONS

1 Watt = 3.413 BTU/HR


1 HP = 746 Watts
1 HP = 2546 BTU/HR

If the efficiency of the drive is known, Watts lost to heat can be estimated if
it is not supplied by the manufacturer.

50 HP drive = 37,300 Watts potential power consumption.


If 93% efficient, and operating at full capacity,
HOFFMAN®  MCLEAN 2,611
®
SCHROFF Watts lost to heat = 8,911BTU/HR cooling required.
®

HOFFMAN®  MCLEAN SCHROFF


® ®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


HEAT TRANSFER BASICS

• Thermal energy moves from high to low. (second law of Thermodynamics)

• A/C’s and HX’s create air movement over a cool surface which “pulls” heat
out of the enclosure.

• A/C’s cooling source is refrigeration system therefore, capable of temp’s


below ambient.

• Heat exchanger cooling source is ambient air therefore, can never create
HOFFMAN MCLEAN SCHROFF
® ® ®
temp’s below ambient.
HOFFMAN MCLEAN SCHROFF
® ® ®

• Forced Convection (open loop)cooling source is ambient air therefore, can


never create temp’s below ambient.

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


WAYS TO COOL INDUSTRIAL ENCLOSURES
There are 3 basic ways to cool industrial enclosures.

SEALED ENCLOSURE FRESH AIR CONDUCTIVE


COOLING COOLING COOLING
1 2 3

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®
Cooling that maintains the Cooling that circulates fresh Cooling that allows the heat
protective seal of the cabinet, air through the cabinet to to simply radiate through
typically with an air conditioner take damaging heat away the cabinet
or heat exchanger

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 23


HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 24


CUSTOMER NEEDS ANALYSIS
Determine ambient and electronics temperatures

A A AMBIENT TEMPERATURE
The maximum temperature outside the enclosure.

B B ELECTRONICS TEMPERATURE
The rated or desired temperature for the electronics
inside the enclosure.

Electrical Enclosure

HOFFMAN
<
B ®  MCLEAN IF ELECTRONICS TEMPERATURE MUST BE LOWER THAN AMBIENT TEMPERATURE
A ®  SCHROFF®
HOFFMAN MCLEAN®  SCHROFF®
®

Then air conditioners, air-to-water heat exchangers, thermoelectric coolers or


vortex coolers are selected.
B > A IF ELECTRONICS TEMPERATURE CAN BE HIGHER THAN AMBIENT TEMPERATURE
Then filter fans, axial fans, fan trays or air-to-air heat exchangers are chosen.

Temperature differences dictate the type of cooling


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 25
WHERE ARE YOU GOING TO DEPLOY YOUR CABINET?

-48/118 -50/105
-70/117 -48/105
-47/106
-54/119 -60/121
-60/118
-60/114 -55/114
-58/120 -52/108 -35/107
-66/115 -51/112
-25/104
-50/125 -47/118 -42/111
-32/106
-47/118 -39/113
-47/118 -34/110
-36/116
-17/110
-69/117 -40/118 -30/110
-61/114
-45/134 -37/114 -37/112 -40/109
-40/121
-40/128
-50/122 -27/120 -34/110
-29/120 -22/113
HOFFMAN MCLEAN SCHROFF
® ® ®

HOFFMAN®  MCLEAN®  SCHROFF®


-19/115 -10/111
-27/112 -17/112
-23/120 -16/114

-80/100
-2/109
12/100

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


AIR CONDITIONER COOLING CAPACITY
Capacity needs to match or exceed amount of total heat load
generated by the electronic system

Total heat load comes from 2 sources:


Internal Heat Load Heat Transfer Load
Electronics in enclosure Ambient heat outside enclosure

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®
+

VFD

TOTAL HEAT LOAD = INTERNAL HEAT LOAD + HEAT TRANSFER LOAD


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 27
STEP 1: DETERMINE INTERNAL HEAT LOAD

Internal heat load =


waste heat generated inside enclosure expressed in Watts (W)

METHODS TO DETERMINE INTERNAL HEAT LOAD


1. Data from Each Electronics Component

2. Component Power – Component Efficiency

3. Incoming – Outgoing Power

4. Automated Equipment Horsepower


HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

VFD

4 methods for determining internal heat load


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 28
STEP 1: DETERMINE INTERNAL HEAT LOAD
METHOD 1:
DATA FROM COMPONENTS

Customer may know amount of heat their equipment is generating

GATHER HEAT LOAD DATA OF EACH ELECTRONIC COMPONENT


Ask your customer . . .
“How much heat is being generated from each electronic
component in your enclosure?”

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

“SUPER COOL SALESMAN”

Gather heat load data for each electronic component


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 29
STEP 1: DETERMINE INTERNAL HEAT LOAD
METHOD 2: INTERNAL HEAT LOAD =
COMPONENT POWER – COMPONENT EFFICIENCY COMPONENT POWER (W) - COMPONENT EFFICIENCY

System uses two components that draw 115 VAC at 15 amps. Each has
a rated efficiency of 90% (10% of each device becomes heat).

Estimated internal heat load is:


Device Power = 115 x 15 = 1725 W
Total Power = 2 x 1725 = 3450
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF® Less Efficiency = 3450 x (1 - .90)
Total Heat Load = 345 W

Utilize component efficiency to estimate heat load


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 30
STEP 1: DETERMINE INTERNAL HEAT LOAD
METHOD 3: INTERNAL HEAT LOAD =
INCOMING – OUTGOING POWER INCOMING POWER (W) – OUTGOING POWER (W)

An enclosure has three input lines of 230 VAC at 11, 6 and 4 A.


It has one output control line of 115 VAC at 9 A.

Estimated internal heat load is:


Incoming Power = (230 x 11) + (230 x 6) + (230 x 4) = 4830 W
Outgoing Power = 115 x 9 = 1035 W
Total Heat Load = 4830 – 1035 = 3795 W
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

Utilize power input and output to estimate heat load


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 31
STEP 1: DETERMINE INTERNAL HEAT LOAD
METHOD 4: 1 hp = 745.6 W
AUTOMATED EQUIPMENT HORSEPOWER

A cabinet has three 5-hp VFDs with 95% efficiency

Estimated internal heat load is:


VFD Watts = 5 hp x 745.6 x 3 = 11184
Adjusted Watts = 11184 x (1 - .95) = 559
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®Total Heat Load = 559 x 1.25 = 699 W
1.25 is an assumed “safety” margin for other minor heat producing components.

Utilize horsepower (hp) to estimate heat load


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 32
FINDING THE EFFICIENCY OF COMPONENTS

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 33


FINDING THE EFFICIENCY OF COMPONENTS

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 34


FINDING THE EFFICIENCY OF COMPONENTS

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 35


STEP 2: DETERMINE HEAT TRANSFER LOAD

Heat transfer load = ambient heat outside enclosure


conducting itself through enclosure walls

METHODS TO DETERMINE HEAT TRANSFER LOAD


1. Simple Chart Method

2. Equation Method

HOFFMAN®  MCLEAN®  SCHROFF®


REMEMBER
HOFFMAN®  MCLEAN®  SCHROFF®
▶ The higher the ambient temperature and/or
the presence of solar heat gain on the
enclosure, the more cooling capacity is
required.

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 36


STEP 2: DETERMINE HEAT TRANSFER LOAD
METHOD 1:
SIMPLE CHART METHOD

Reasonably accurate for most indoor industrial systems

Step A. Determine ΔT in °F or °C

Step B. Find the heat transfer per ft.2 or m2


on the chart, using ΔT and the proper
enclosure material curve.

Step C. Multiply the heat transfer per ft.2 or


m2 by the total surface area of the enclosure
that will conduct heat. (Remember to
HOFFMAN MCLEAN SCHROFF
® ® ®
exclude®
surfaces such as a side mounted to a
HOFFMAN MCLEAN SCHROFF
® ®

wall.)

SURFACE AREA (ft.2) = [2AB (in.) + 2BC (in.) + 2AC (in.)] ÷ 144
SURFACE AREA (m2) = [2AB (mm) + 2BC (mm) + 2AC (mm)] ÷ 1000000
Total Heat Transfer Load = Heat Transfer per ft.2 or m2 x Cabinet Surface Area

Use ΔT and enclosure surface area to estimate heat transfer


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 37
STEP 2: DETERMINE HEAT TRANSFER LOAD
METHOD 1:
SIMPLE CHART METHOD

A painted steel enclosure has 80 ft.2 of surface area and will be


located in a maximum ambient temperature of 95 degrees F. The
rated temperature of the electronics is 75 degrees F.
Estimated internal heat transfer load is:
ΔT = 95 – 75 = 20 F
Heat Transfer = 4 W/ft.2 (from chart)
Total Heat Transfer Load = 80 x 4 = 320 W
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

If system will be deployed outdoors, solar heat gain will need to be added. We recommend
utilizing the online Product Selection Tool in these instances.

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 38


STEP 2: DETERMINE HEAT TRANSFER LOAD
METHOD 2:
EQUATION METHOD
The governing equations for heat transfer load are: Definition of Variables—
English System (°F, inches and feet): q = Heat transfer load per unit of surface area
To = Maximum ambient temperature outside
q = (To - Ti) ÷ [(1/ho) + (1/hi) + R]
the enclosure
Metric System (°C, millimeters and meters): Ti = Maximum rated temperature of the
q = (To - Ti) ÷ [(1/ho) + (1/hi) + R] x 5.67 electronics components
ho = Convective heat transfer coefficient
q = (125 - 75) ÷ [(1/6) + (1/2) + 4] outside the cabinet
q = (50) ÷ (.16 + .5 + 4) Still air: h = 1.6
q = 50 ÷ 4.66 Relatively calm day: h = 2.5
Windy day (approx. 15 mph): h = 6.0
q = 10.7 BTU/hr./ft.2
hi = Convective heat transfer coefficient inside
Total Heat Transfer Load the cabinet
10.7 x 72 = 770 BTU/hr. or 770 ÷ 3.413 = 226 W Still air: h = 1.6
Since the cabinet is outdoors, and assuming it is painted Moderate air movement: h = 2.0
HOFFMAN MCLEAN SCHROFF
® ® ®

ANSI 61 gray
HOFFMAN®
MCLEAN SCHROFF
® ® Blower (approx. 8 ft.3/sec.): h = 3.0
and located in the sun, extra solar load needs to be added R = Value of insulation lining the interior of
to the the enclosure walls
No insulation: R = 0.0
outcome above which is 504 Watts (7 W per ft.2 x 72
1/2 in. or 12 mm: R = 2.0
ft.2). 1 in. or 25 mm: R = 4.0
Total Heat Transfer Load with Extra from Solar Heat Gain 1-1/2 in. or 38 mm: R = 6.0
226 + 504 = 730 WA 2 in. or 51 mm: R = 8.0

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 39


STEP 3: DETERMINE TOTAL HEAT LOAD
The internal heat load from one of the earlier examples was 3795
Watts. If the heat transfer load is 730 W.

Total Heat Load =


3795 + 730 = 4525 W

To convert Watts into BTU/hr. multiply by 3.413

4525 W = 15444 BTU/hr.


HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

Total Heat Load = INTERNAL HEAT LOAD + HEAT TRANSFER LOAD


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 40
AIR CONDITIONER SPEC EXAMPLE
Estimated internal heat load:
Device Power = 115V x 17Amp = 1955 W
Total Power = 6 x 1955W = 11730W
Less Efficiency = 11730W x (1 - .90)
Total Heat Load = 1173 W

Online Product Selection Tool:


Total heat load = 1733 W
BTU/Hr. = 1733 x 3.413 = 5914

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


CUSTOMER NEEDS ANALYSIS
Identify the customer’s remaining requirements

UTILITIES AT THE INSTALLATION ENCLOSURE COOLING LOCATION


 Electricity only  Side of the enclosure
 Chilled circulated water  Top of the enclosure
 Compressed air  19” data rack
 Back panel / inside the enclosure

POWER INPUT
 115 VAC 50/60 Hz AGENCY CERTIFICATION
 230 VAC 50/60 Hz  UL / cUL
 230 VAC 50 Hz  UR
HOFFMAN®   460SCHROFF
MCLEAN
®
VAC 50/60 Hz single-phase
®  CSA
HOFFMAN®  MCLEAN SCHROFF
® ®

 460 VAC 50/60 Hz three-phase  CE


 24 VDC  GOST
 48 VDC  Telcordia GR-487 capable

Leads you to the final cooling product and options


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 42
SPECIFYING FRESH AIR COOLING PRODUCTS
What is air flow?
• Air flow is the volume of air moved by a Fresh Air Cooling product such as a filter fan,
impeller, 19” fan tray or blower
• It’s like gallons or liters per minute of water
• The more that an electronics system puts out heat, the more air flow is needed to cool it
• Air flow is measured in terms of:
 CFM (English system)
 M3/Hr (Metric system)

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

Low Air Flow High Air Flow


19” Blower 19” Blower

As you select a Fresh Air Cooling product, you will use Air Flow
PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 43
SPECIFYING FRESH AIR COOLING PRODUCTS
What is static pressure?
• Static Pressure is the air flow restriction caused by electronic components.
• Here are three examples:

HOFFMAN®  MCLEAN®  SCHROFF®


(187 Pascal) (187 - 436 Pascal) (436 Pascal)
HOFFMAN®  MCLEAN®  SCHROFF®

• Static pressure is measured in terms of:


 Inches of H2O (English system)
 Pascal (Metric system)

You will also use Static Pressure to choose Fresh Air Cooling
PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 44
SPECIFYING FRESH AIR COOLING PRODUCTS
Use these 5 simple steps to specify an Open Loop Product.
1 Determine Delta-T — The difference in maximum desired temperature for the electronics and
maximum temperature outside the enclosure

Electronics vs. Ambient Temperature Difference (ΔT)

Delta-T = Maximum Temperature Maximum Expected


Maximum -
Ambient Desired for the Electronics Ambient Temperature
Maximum Temperature Example—
Electronics
Temperature Delta-T = 35°C (95°F) Maximum - 25°C (77°F) Maximum
Electronics Temperature Ambient Temperature
Delta-T = 10°C (18°F)

2 Determine Heat Load — The amount of heat to be removed from the enclosure

HOFFMAN®  MCLEAN®  SCHROFF® Electronics Heat Load


HOFFMAN®  MCLEAN®  SCHROFF®
Heat Load Definition Example—
10000 Watts Drawn by - 90% System
Heat Load = Total Watts Drawn by - System Heat Load =
the Electronics System Efficiency
the Electronics System Efficiency
Heat Load = 1000 Watts

1000 Watts of heat at a ΔT of 10°C need to be removed


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
SPECIFYING FRESH AIR COOLING PRODUCTS
3 Determine Free Air Flow — Using Delta-T (Step 1) and Heat Load (Step 2)

1
Free Air Flow Requirement

2000

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

180
306

Consult the manufacturers catalog for performance curves


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
SPECIFYING FRESH AIR COOLING PRODUCTS
Estimate Air Flow Restriction — Determine approximate system impedance based on the amount
4 of electronics in the cabinet using your judgment

Levels of Air Flow Restriction


(Need to confirm with actual prototype testing)

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

(187 Pascal) (187 - 436 Pascal) (436 Pascal)

Many Industrial cabinets are lightly packed with electronics


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
SPECIFYING FRESH AIR COOLING PRODUCTS
Select Your Open Loop solution– Pick the Power Input and Protection Level. Then overlay a judgmental
5 airflow restriction curve on the performance curves of your fan options, picking the one with the closest
air flow
ST13 303 CFM (515 M3/Hr) Filter Fan

Under-Sized
Below 180 CFM (306 M3/Hr) target
Light Airflow
Restriction
SF13 376 CFM (638 M3/Hr) Filter Fan

Light Airflow
Restriction

SF13 473 CFM (803 M3/Hr) Filter Fan

Light Airflow Right-Sized


HOFFMAN MCLEAN SCHROFF
® ® ® Restriction
At the 180 CFM (306 M3/Hr) target
HOFFMAN®  MCLEAN®  SCHROFF®

Over-Sized
Above 180 CFM (306 M3/Hr) target

Designers should confirm the filter fan model with a system test
PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
SPECIFYING FRESH AIR COOLING PRODUCTS
Air mover cooling is based on air flow and static pressure.

6
• Fans - High Volume Low
5

Static Pressure (in wg)


680
Pressure 498 MI
• MI’s - High Volume Radial
4
Fan Tray
Medium Pressure 374
Centrifugal
• Centrifugal Blower - High 3

Static Pressure
Static Pressure

Volume High Pressure 2


249

• Radial Blower - Low


(in. of H20)

Volume High Pressure 1 125

(Pa)
HOFFMAN MCLEAN SCHROFF
® ® ®

HOFFMAN®  MCLEAN®  SCHROFF®

0
0
0 200 400 600400 800 1000 1200 1400
Air Flow (CFM) Air Flow (CFM)

Impellers overcome more air restriction than filter fans


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®
SPECIFYING FRESH AIR COOLING PRODUCTS

The capability of each Fresh Air Cooling option varies considerably.

• General vs. concentrated air flow


• Amount of air volume
• Ability to overcome air flow restrictions caused by electronic
components
• Component price
• Power input (AC or DC volt)
• Ability to protect the electronics from dust and water
HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

You will need to carefully consider your Fresh Air Cooling options
PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 50
SPECIFYING FRESH AIR COOLING PRODUCTS
Filter fans often cool Industrial enclosures because the electronics
are “lightly packed”, and the factory is climate controlled.
Industrial Filter Fan Design Options

Push Design
Push Design with Dual Exhaust Pull Design Push / Pull Design Roof Mount Design

A typical application. An extra exhaust grille Pull design is less Push / pull is used Roof mount filter
Pressurizes
HOFFMAN cabinet
MCLEAN to
®
SCHROFF is added to improve
® ® desirable because to increase air flow fans save space
HOFFMAN dust. SCHROFF air flow and cooling.
MCLEAN dust can be sucked through more tightly inside the cabinet.
® ® ®
help keep out
inside the cabinet. packed cabinets.

Filter fans are typically installed using a “Push Design”


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 51
SPECIFYING FRESH
Open Loop AIR Principles
Cooling COOLING PRODUCTS
How to Specify an Open Loop Cooling Solution
 Determining Factors
 Maximum ambient temperature  Negative or positive cabinet
 Maximum enclosure pressure
temperature  Air filtration
 Maximum rise in temperature  Maximum sound levels (dB)
(ΔT)  Power source (AC or DC)
 Heat to be dissipated (heat load)  Voltage range (of power source)
 Hot spots in the cabinet  Optional controls & alarms
 Air mover type (fan tray, blower,
HOFFMAN®  MCLEAN®  SCHROFF®  Power consumption
etc.)
HOFFMAN®  MCLEAN®  SCHROFF®
 Reliability (estimated life)
 Air flow (CFM or M3/HR)
 Budget
 Enclosure system air resistance
 Static pressure (air flow drive)

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®


TYPES OF ENCLOSURE TEMPERATURE REGULATORS
A variety of sealed enclosure and fresh air cooling products exist.
SEALED ENCLOSURE COOLING FRESH AIR COOLING

AIR CONDITIONER AIR-TO-WATER INDUSTRIAL FILTER FAN


Keeps electronics cooler HEAT EXCHANGER
Pushes cool air through the
than temperatures outside Also keeps electronics enclosure to remove heat
the enclosure by using a cooler than temperatures from the electronics
refrigerant system outside the enclosure, but
with chilled water

AIR-TO-AIR COMPACT AXIAL FAN


THERMOELECTRIC COOLER
HEAT EXCHANGER Circulates cool air through
A refrigerant-free form of air or within the electrical
Quickly radiates heat conditioning that relies on enclosure
away from the enclosure
electrified ceramic chips.
by circulating cool air Also known as Peltier cooling
through a metal core
HOFFMAN®  MCLEAN®  SCHROFF® 19” FAN TRAY AND BLOWER
HOFFMAN®  MCLEAN®  SCHROFF® Fits a standard 19” data rack, blowing fresh
VORTEX COOLER ENCLOSURE HEATER cool air through the electronics
Cools electronics lower Used to warm electronics
than temperatures outside rather than cool them. Also
the enclosure using reduces condensation inside
compressed air the electrical enclosure

McLean makes every one of these products available today


PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 53
SUMMARY

• Understanding why temperature variation can be a problem


• Understand the consequences of over-heated electronics
• Learn the benefits of cooling industrial electronics
• Identify the sources of damaging heat
• Learn how to size a cooling unit for your cabinet

HOFFMAN®  MCLEAN®  SCHROFF®


HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF® 54


HOFFMAN®  MCLEAN®  SCHROFF®
HOFFMAN®  MCLEAN®  SCHROFF®

PENTAIR HOFFMAN®  MCLEAN®  SCHROFF®

You might also like