Cable Selection Guide
Cable Selection Guide
Cable Selection Guide
Par t 2:
C ab le S ele ct io n
Selection of Cable
Why do the Calculation?
When to do the calculation?
General Methodology
Selection of Cables
Page 1
Cable Selection Part 2
Cable Selection Part 2
General Methodology
All cable sizing methods more or less follow the same basic six step process:
1) Gathering data about the cable, its installation conditions, the load that it will carry,
etc
2) Determine the minimum cable size based on continuous current carrying capacity
3) Determine the minimum cable size based on voltage drop considerations
4) Determine the minimum cable size based on short circuit temperature rise
5) Determine the minimum cable size based on earth fault loop impedance
6) Select the cable based on the highest of the sizes calculated in step 2, 3, 4 and 5
Load Details
The characteristics of the load that the cable will supply, which includes:
Page 2
Cable Selection Part 2
Cable Selection Part-2
Cable Construction
The basic characteristics of the cable's physical construction, which includes:
Installation Conditions
How the cable will be installed, which includes:
Page 3
Cable Selection Part 2
Cable Selection Part 2
Cables with larger conductor cross-sectional areas (i.e. more copper or aluminium) have
lower resistive losses and are able to dissipate the heat better than smaller cables.
Therefore a 16 mm2 cable will have a higher current carrying capacity than a 4 mm2 cable.
International standards and manufacturers of cables will quote base current ratings of
different types of cables in tables such as the one shown on the right. Each of these tables
Page 4
Cable Selection Part 2
Cable Selection Part-2
pertain to a specific type of cable construction (e.g. copper conductor, PVC insulated,
0.6/1kV voltage grade, etc) and a base set of installation conditions (e.g. ambient
temperature, installation method, etc). It is important to note that the current ratings are
only valid for the quoted types of cables and base installation conditions.
International standards and cable manufacturers will provide derating factors for a range
of installation conditions, for example ambient / soil temperature, grouping or bunching of
cables, soil thermal resistivity, etc. The installed current rating is calculated by multiplying
the base current rating with each of the derating factors, i.e.
Feeders
When sizing cables for non-motor loads, the upstream protective device (fuse or circuit
breaker) is typically selected to also protect the cable against damage from thermal
overload. The protective device must therefore be selected to exceed the full load current,
but not exceed the cable's installed current rating, i.e. this inequality must be met:
Page 5
Cable Selection Part 2
Cable Selection Part 2
Motors
Motors are normally protected by a separate thermal overload (TOL) relay and therefore
the upstream protective device (e.g. fuse or circuit breaker) is not required to protect the
cable against overloads. As a result, cables need only to be sized to cater for the full load
current of the motor, i.e.
Current flow through the cable – the higher the current flow, the higher the
voltage drop
Impedance of the conductor – the larger the impedance, the higher the voltage
drop
Cable Impedances
The impedance of the cable is a function of the cable size (cross-sectional area) and the
length of the cable. Most cable manufacturers will quote a cable’s resistance and reactance
in Ω/km. The following typical cable impedances for low voltage AC and DC single core and
multicore cables can be used in the absence of any other data.
Page 6
Cable Selection Part 2
Cable Selection Part-2
Page 7
Cable Selection Part 2
Cable Selection Part 2
It is customary for standards (or clients) to specify maximum permissible voltage drops,
which is the highest voltage drop that is allowed across a cable. Should your cable exceed
this voltage drop, then a larger cable size should be selected.
Maximum voltage drops across a cable are specified because load consumers (e.g.
appliances) will have an input voltage tolerance range. This means that if the voltage at
the appliance is lower than its rated minimum voltage, then the appliance may not operate
correctly.
In general, most electrical equipment will operate normally at a voltage as low as 80%
nominal voltage. For example, if the nominal voltage is 230VAC, then most appliances will
run at >184VAC. Cables are typically sized for a more conservative maximum voltage
drop, in the range of 5 – 10% at full load.
Page 8
Cable Selection Part 2
Cable Selection Part-2
Page 9
Cable Selection Part 2
Cable Selection Part 2
As a rough guide, the following temperatures are common for the different insulation
materials:
Page 10
Cable Selection Part 2
Cable Selection Part-2
PVC 75 160
EPR 90 250
XLPE 90 250
Ideally the circuit will have earth fault protection, in which case the protection will be fast
acting and well within the maximum disconnection time. The maximum disconnection time
is chosen so that a dangerous touch voltage does not persist for long enough to cause
injury or death. For most circuits, a maximum disconnection time of 5s is sufficient,
though for portable equipment and socket outlets, a faster disconnection time is desirable
(i.e. <1s and will definitely require earth fault protection).
However for circuits that do not have earth fault protection, the upstream protective
device (i.e. fuse or circuit breaker) must trip within the maximum disconnection time. In
order for the protective device to trip, the fault current due to a bolted short circuit must
exceed the value that will cause the protective device to act within the maximum
disconnection time. For example, suppose a circuit is protected by a fuse and the
maximum disconnection time is 5s, then the fault current must exceed the fuse melting
current at 5s (which can be found by cross-referencing the fuse time-current curves).
Page 11
Cable Selection Part 2
Cable Selection Part 2
Where is the earth fault current required to trip the protective device within the
minimum disconnection time (A)
and are the ac resistances of the active and earth conductors respectively
(Ω/km)
and are the reactances of the active and earth conductors respectively
(Ω/km)
Page 12
Cable Selection Part 2
Cable Selection Part-2
is the earth fault current required to trip the protective device within the
minimum disconnection time (A)
The maximum cable length can therefore be calculated by the following:
is the earth fault current required to trip the protective device within the
minimum disconnection time (A)
and are the ac resistances of the active and earth conductors respectively
(Ω/km)
and are the reactances of the active and earth conductors respectively
(Ω/km)
Note that the voltage V0 at the protective device is not necessarily the nominal phase to
earth voltage, but usually a lower value as it can be downstream of the main busbars. This
voltage is commonly represented by applying some factor to the nominal voltage. A
conservative value of = 0.8 can be used so that:
Worked Example
In this example, we will size a cable for a 415V, 30kW three-phase motor from the MCC to
the field.
Page 13
Cable Selection Part 2
Cable Selection Part 2
The installed current ratings for 25 mm2 and 35 mm2 is 0.7298 78A = 56.92A and
0.7298 96A = 70.06A respectively. Given that the full load current of the motor is
58A, then the installed current rating of the 25 mm2 cable is lower than the full load current
and is not suitable for continuous use with the motor. The 35 mm2 cable on the other hand
has an installed current rating that exceeds the motor full load current, and is therefore
the cable that should be selected.
Page 14
Cable Selection Part 2
Cable Selection Part-2
The cable is operating normally at 75C and has a prospective fault capacity (I2t) of 90 kA2s.
What is the minimum size of the cable based on short circuit temperature rise?
XLPE has a limiting temperature of 160C. Using the IEC formula, the short circuit
temperature rise constant is 111.329. The minimum cable size due to short circuit
temperature rise is therefore:
In this example, we also use the fuse for earth fault protection and it needs to trip within
5s, which is at the upper end of the adiabatic period where the short circuit temperature
rise equation is still valid. Therefore, it's a good idea to also check that the cable can
withstand the short circuit temperature rise for for a 5s fault. The 80A motor fuse has a 5s
melting current of 550A. The short circuit temperature rise is thus:
The cable run is 90m and the maximum length allowed is 117m, therefore our cable is
suitable based on earth fault loop impedance. In fact, our 35 mm2 cable has passed all the
tests and is the size that should be selected.
Page 15
Cable Selection Part 2
Cable Selection Part 2
Waterfall Charts
Sometimes it is convenient to group together similar types of cables (for example, 415V PVC
motor cables installed on cable ladder) so that instead of having to go through the laborious
exercise of sizing each cable separately, one can select a cable from a pre-calculated chart.
These charts are often called "waterfall charts" and typically show a list of load ratings and the
maximum of length of cable permissible for each cable size. Where a particular cable size fails
to meet the requirements for current carrying capacity or short circuit temperature rise, it is
blacked out on the chart (i.e. meaning that you can't choose it).
Preparing a waterfall chart is common practice when having to size many like cables and
substantially cuts down the time required for cable selection.
Page 16
Cable Selection Part 2