Sizing Genset Project 1 - MTU 6R0113 DS180 - 431CSL6208 - 50°C (122°F) - 20180328143403

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

28/03/2018

PS SPEC™ Power System Sizing and Specification


Project 1

Model: MTU 6R0113 DS180 Sizing: Recommended

Sizing Prepared By: Customer Contact:


Peru
Project Overview
Voltage 277/480V Fuel Type Diesel
Frequency 60 Hz Rating Type Standby
Phase Three Phase Site Altitude 3000 m (9843 ft)
Product Type Standard Ambient Temperature 35°C (95°F)
Permitted Back Pressure 50 mbar (20.1 in. H₂O)
Load Analysis Summary
Peak kVA 196.4 Running kVA 90.6
Peak kW 80.6 Running kW [6] 80.6
Running PF 0.89
Generator Set Details
Generator Set Model MTU 6R0113 DS180 (Qty 1) Nameplate kW Rating 180
Alternator Model 431CSL6208 w/ PMG Rated P.F. 0.8
Temperature Rise 80°C Site kW Rating [7] 166
Engine Model 6068HFG85 Standby
Block Load Transient Response [3] Alternator Motor Starting [2]
Load Change FDip VDip Recovery Times VDip SkVA
0-25 % 1.5% 3% 1.2s 10% 232
0-50 % 2.7% 7.4% 1.1s 20% 463
0-75 % 3.9% 12.6% 0.7s 30% 695
0-100 % 5.1% 17.9% 1.9s 35% 810
Technical Data at 100% Nameplate Rated Load [1]
Make John Deere Governor Electronic Isochronous (JDEC)
Model MTU 6R0113 DS180 Cooling Pkg Ambient Rating 50°C (122°F)
Aspiration TurboCharged Cooling Pkg Airflow 412 m³/min (14550 ft³/min)
Cylinder Configuration 6-In Line Heat Rejection to Coolant 84 kW (4760 BTU/min)
Displacement 6.8 L (415 in³) Heat Rejection to CAC 40 kW (2275 BTU/min)
Rated RPM 1,800 Heat Rejection to Fuel NA [4]
Fuel Consumption 51.9 L/hr (13.7 gal/hr) Heat Radiated to Ambient 24 kW (1376 BTU/min)
Aspiration Airflow 15 m³/min (519 ft³/min) Exhaust Stack Temperature 528°C (982°F)
Emissions Rating EPA Tier 3 Exhaust Flow Rate 39 m³/min (1370 ft³/min)
1. Based on standard conditions of 77 °F, 1000 ft. altitude, 0.5" H 2 O intake restriction. Exhaust Flow Rate is evaluated using Stack Temperature. 
2. Based on instantaneous voltage dip as defined per NEMA MG-1. 
3. Recovery time is based on steady state recovery of voltage. This information is based on average performance, and should not be considered a guarantee. Results may
vary based on production tolerances and site conditions. Consult MTU OE for further information regarding transients. 
4. NA = Not Applicable  5. CF = Consult Factory  6. The average running load on diesel engines should not be less than 30% of rated power. 
7. Site kW Rating is the maximum sustainable kW at the project site conditions. Note that the Starting kW can be higher. 

Disclaimer/Explanation:All information provided in this program is provided for information purposes only and does not constitute a legal contract between MTU Onsite
Energy and any person(s) or entity unless otherwise specified.

Page 1 Version: 9.0.17.330/20180328


28/03/2018
PS SPEC™ Power System Sizing and Specification
Project 1
Model: MTU 6R0113 DS180 Sizing: Recommended

Project Overview
Voltage 277/480V Fuel Type Diesel
Frequency 60 Hz Rating Type Standby
Phase Three Phase Site Altitude 3000 m (9843 ft)
Temperature Rise 80°C Ambient Temperature 35°C (95°F)
External Static Pressure N/A Permitted Back Pressure 50 mbar (20.1 in. H₂O)
Step Load Description Qty SkW SkVA SPF RkW RkVA RPF VDIP [3] FDIP [3]
1 12.4% 1.9%
Three Phase Fire Pump
Permitted V-Dip: 13%
Nonlinear: No
1 58.91 196.35 0.3 80.6 90.6 0.89
Starting Method: Reactor Resistive Star
Delta 33%
HP: 100

1 Loads Total 58.91 196.35 0.3 80.6 90.6 0.89


Project Total at 1 58.91 196.35 80.6 90.6 0.89
2 - Intermittent 12.4% 1.9%
Step I-Three Phase Fire Pump
Permitted V-Dip: 13% 1 58.91 196.35 0.3 80.6 90.6 0.89
Nonlinear: No

2 - Intermittent Step Loads Total 58.91 196.35 0.3 80.6 90.6 0.89
Project Total at 2 - Intermittent
58.91 196.35 80.6 90.6 0.89
Step

Page 2 Version: 9.0.17.330/20180328