Catalogue PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

Smart relays

Zelio Logic
Your advanced solution!

Catalogue
November

03
Contents Zelio Logic smart relays

Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 2 and 3

Zelio Logic smart relays


b Presentation of the smart relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4

b Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5

b Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6

b Presentation of “Zelio Soft” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 7 and 8

b Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 9 to 11

b Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 12 to 13

b References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 14 to 16

b Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17

b Schemes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 18 and 19

Analogue interfaces
b Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 20 and 21

b Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 22 and 23

b References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24

b Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25

Phaseo modular regulated power supplies


b Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26

b Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 27 and 28

b References, dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29

Services
b Schneider Electric worldwide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 30 to 35

1
Selection guide Zelio Logic smart relays 0

Compact and modular smart relays

Smart relay type Compact smart relays

Number of I/O 10 12 20

Number of discrete inputs 6 (0) 8 (4) 12 (2) 12 (6)


(of which analogue inputs)

Number of "relay" or "transistor" outputs 4 4 8

Supply voltage c 24 V, a 100...240 V c 12 V, c 24 V, a 24 V, a 100...240 V

I/O extensions No

Modbus communication module r No

Clock No Yes Depends on model

Display and programming buttons Depends on model

Programming language LADDER / FBD LADDER LADDER / FBD (1) LADDER LADDER / FBD
(1)

References SR2 p101pp SR2 p121pp SR2 B122BD SR2 A201pp SR2 B20ppp
SR2 E201pp

Pages 14102/12 14102/12 14102/12 14102/12 14102/12

(1) FBD: Function Block Diagram


r Available: 1st quarter 2004.

0129Q-EN_Ver1.1.fm/2 Schneider Electric


0

Modular smart relays

10 26

6 (4) 16 (6)

4 10

c 24 V, a 24 V, a 100...240 V

Yes (6, 10 or 14 I/O)

Yes

Yes

Yes

LADDER / FBD (1)

SR3 B10ppp SR3 B26ppp

14102/13 14102/13

(1) FBD: Function Block Diagram

Schneider Electric 0129Q-EN_Ver1.1.fm/3


Presentation Zelio Logic smart relays 0

Compact and modular smart relays

Presentation
Zelio Logic smart relays are designed for use in small automated systems. They are
used in both industrial and commercial applications.
b For industry:
v automation of small finishing, production, assembly or packaging machines.
v decentralised automation of ancillary equipment of large and medium-sized
machines in the textile, plastics and materials processing sectors,
v automated systems for agricultural machinery (irrigation, pumping, greenhouses, ...).
b For the commercial/building sectors:
v automation of barriers, roller shutters, access control,
v automation of lighting installations,
109446

v automation of compressors and air conditioning systems.


Their compact size and ease of setting-up make them a competitive alternative to
solutions based on cabled logic or specific cards.
Simple programming, ensured by the universal nature of LADDER and function block
diagram FBD (1) languages, meets all automation requirements and also the needs
of the electrician.
Compact smart relays are suitable for simple automated systems, up to 20 I/O.
If required, modular smart relays can be fitted with I/O extensions and a module for
communication on the Modbus network, for greater performance and flexibility, from
10 to 40 I/O.
SR2 B121BD
Programming
Programming can be carried out:
b independently, using the buttons on the smart relay (ladder language),
b on a PC, using "Zelio Soft" software.
When using a PC, programming can be carried out either in LADDER language, or
in function block diagram language (FBD).
LCD display backlighting (2)
Backlighting of the display is programmable using “Zelio Soft” software and by direct
action on the smart relay's 6 programming buttons.
Memory
The Zelio Logic smart relay has a backup memory which allows programs to be
copied into another smart relay (examples: for building identical equipment, remote
transmission of updates).
The memory also allows a backup copy of the program to be saved prior to
exchanging the product.
When used with a smart relay without display or buttons, the copy of the program
contained in the cartridge is automatically transferred into the smart relay at power-
up.
Autonomy and backup
Autonomous operating time of the clock, ensured by a lithium battery, is 10 years.
Data backup (preset values and current values) is provided by an EEPROM Flash
memory (10 years).
I/O extensions
Zelio Logic smart relays can, if necessary, take the following I/O extensions:
b 6, 10 or 14 I/O, supplied with c 24 V via the smart relay,
b 6, 10 or 14 I/O, supplied with a 24 V via the smart relay,
b 6, 10 or 14 I/O, supplied with a 100... 240 V via the smart relay.
1 2
Communication module r
109458

A module for communication on the Modbus network will be available for Zelio Logic
modular smart relays. It is supplied with c 24 V via the smart relay.
Communication interface rr
The "communication" products in the Zelio Logic range include:
b a communication interface connected between a smart relay and a modem,
b analogue or GSM modems,
b “Zelio Soft Com” software.
They are designed for monitoring or remote control of machines or installations which
operate without personnel.
1 Modular smart relay The communication interface, supplied with c 12/24 V, allows messages, telephone
(10 or 26 I/O) numbers and call conditions to be stored.
2 I/O extension module
(1) FBD: Functional Block Diagram.
(6,10 or 14 I/O)
(2) LCD: Liquid Crystal Display

r Available 1st quarter 2004.


rr Available 2nd quarter 2004.

14102-EN_Ver2.0.fm/2
Description Zelio Logic smart relays 0

Compact and modular smart relays

Compact smart relays


Without display - 10, 12 and 20 I/O With display - 10, 12 and 20 I/O

1 1 Compact smart relays have


2 2
3 the following on the front
3 panel:
1 Two retractable fixing lugs
2 Two power supply
terminals
3 Terminals for connection of
4 the inputs
5
5 4 Backlit LCD display with 4
lines of 18 characters
5 Slot for a memory cartridge
and connection to a PC
6 6 6 buttons for programming
and parameter entry
1 1 7 Terminals for connection of
7 the outputs
7

Modular smart relays


10 and 26 I/O

1 Modular smart relays have


2 the following on the front
3 panel:
1 Two retractable fixing lugs
2 Two power supply
terminals
4 3 Terminals for connection of
the inputs
5
4 Backlit LCD display with 4
lines of 18 characters
5 Slot for a memory cartridge
and connection to a PC
6
6 6 buttons for programming
and parameter entry
1 7 Terminals for connection of
7 the outputs

I/O extension modules


6 I/O 10 and 14 I/O

1 1 I/O extension modules have


2 2 the following on the front
panel:
4 4 1 Two retractable fixing lugs
2 Terminals for connection of
5 5 the inputs
3 Terminals for connection of
the outputs
4 A connector for connection
to the smart relay
(powered by the smart
5 5 relay)
5 Locating pegs

1 1
3 3

14102-EN_Ver2.0.fm/3
Functions Zelio Logic smart relays 0

Compact and modular smart relays


“Zelio Soft for PC” programming software

“Zelio Soft for PC” (version 2.0)

“Zelio Soft” software allows:


b programming in LADDER language or in function block diagram language (FBD),
b simulation, monitoring and supervision,
b uploading and downloading of programs,
b output of personalised files,
b automatic compiling of programs,
b on-line help.

Coherence test and application languages


Programming in LADDER language “Zelio Soft” software monitors applications by means of its coherence test function.
An indicator turns red at the slightest input error. The problem can be located by
simply clicking the mouse.
"Zelio Soft" software allows switching, at any time, to any of the 6 application
languages (English, French, German, Spanish, Italian, Portuguese), and editing of
the application file in the selected language.

Inputting messages for display on Zelio Logic


"Zelio Soft" software allows Text function blocks to be configured, which can then be
displayed on all smart relays which have a display.

Program testing
Programming in FBD language 2 test modes are provided: simulation and monitoring.

“Zelio Soft” simulation mode allows all the programs to be tested, without the smart
relay, i.e.:
b enable discrete inputs,
b display the status of outputs,
b vary the voltage of the analogue inputs,
b enable the programming buttons,
b simulate the application in real time or in accelerated time,
b dynamically display (in red) the various active elements of the program.

“Zelio Soft” monitoring mode makes it possible to test the program executed by the
smart relay, i.e.:
"Simulation" mode
b display the program "on line",
b force inputs, outputs, control relays and current values of the function blocks,
b adjust the time,
b change from STOP mode to RUN mode and vice versa.

In simulation or monitoring mode, the monitoring window allows the status of the
smart relay I/O to be displayed within your application environment (diagram or
image).

"Monitoring" window

14102-EN_Ver2.0.fm/4
Presentation Zelio Logic smart relays 0

Compact and modular smart relays


“Zelio Soft” programming software

LADDER language
Definition
LADDER language allows a LADDER program to be written with elementary
functions, elementary function blocks and derived function blocks, as well as with
contacts, coils and variables.
Text function block Timer The contacts, coils and variables can be annotated. Text can be placed freely within
the graphic.

b Control scheme input modes


“Zelio input” mode enables users who have directly programmed the Zelio smart
Up/down counter Fast counter relay to find the same user interface, even when using the software for the first time.
“Free input” mode, which is more intuitive, is very user-friendly and incorporates
many additional features.
With LADDER programming language, two alternative types of symbol can be used :
v LADDER symbols,
Analogue comparator Clock v electrical symbols.
"Free input" mode also allows the creation of mnemonics and notes associated with
with each line of the program.
Instant switching from one input mode to the other is possible at any time, by clicking
the mouse.
Control relay Counter comparator Up to 120 control scheme lines can be programmed, with 5 contacts and 1 coil per
program line.

b Functions:
v 16 time delay function blocks; parameters of 11 different types can be set for each
th
LCD backlighting Summer/Winter time switching of these (1/10 second to 9999 hours),
v 16 up/down counter function blocks from 0 to 32767,
v 1 fast counter (1 kHz),
v 16 text function blocks,
v 16 analogue comparator function blocks,
Output coil v 8 clock function blocks, each with 4 channels,
v 28 control relays,
v 8 counter comparators,
v automatic Summer/Winter time switching,
v variety of coil functions, latching (Set/Reset), impulse relay, contactor
v LCD screen with programmable backlighting.

Functions
Function Electrical scheme LADDER language Notes
Contact I corresponds to the real state of the contact connected to the
input of the smart relay.
13

21

I
i corresponds to the inverse state of the contact connected to the
or or input of the smart relay.
14

22

Standard coil The coil is energised when the contacts to which it is connected
are closed.
A1
A2

Latch coil (Set) The coil is energised when the contacts to which it is connected
are closed. It remains tripped when the contacts re-open.
A1

S
A2

Unlatch coil The coil is de-energised when the contacts to which it is


(Reset) connected are closed.
A1

R
It remains inactive when the contacts re-open.
A2

14102-EN_Ver2.0.fm/5
Presentation (continued) Zelio Logic smart relays 0

Compact and modular smart relays


“Zelio Soft” programming software

Function block diagram language (FBD) (1)


Definition
FBD language allows graphical programming based on the use of predefined
function blocks.
This language provides the use of 23 pre-programmed functions for counting, time
delay, timing, definition of switching threshold (temperature regulation for example),
generation of impulses, time programming, multiplexing, display, etc.
Pre-programmed functions
Zelio Logic smart relays provide a high processing capacity, up to 200 function blocks, including 23 pre-programmed functions:

TIMER AC TIMER BH TIMER BW

Timer. Function A/C Timer. Function BH. Timer - Function BW


ON-delay and OFF delay (Adjustable pulsed signal) (pulse on rising/falling edge)
TIMER Li BISTABLE SET- RESET

Pulse generator Impulse relay function Bistable latching - Priority assigned either to
ON-delay, OFF delay SET or RESET function
BOOLEAN CAM PRESET COUNT

Allows logic equations to be created between connected inputs Cam programmer Up/down counter
UP DOWN COUNT PRESET H-METER TIME PROG

Up/down counter with external preset Hour counter Time programmer,


(hour, minute preset) weekly and annual
GAIN TRIGGER MUX

Allows conversion of an analogue value by change of scale and Defines an activation zone with hysteresis. Multiplexing functions on 2 analogue values
offset.
COMP IN ZONE ADD/SUB MUL/DIV

Zone comparison Add and/or subtract function Multiply and/or divide function
(Min. y Value y Max.)
DISPLAY COMPARE STATUS

Display of digital and analogue data, date, time, messages for Comparison of 2 analogue values using the Access to smart relay status
Human-Machine interface. operands =, >, <, y, u.
ARCHIVE SPEED COUNT

Storage of 2 values simultaneously Fast counting up to 1 kHz


SFC functions (2) (GRAFCET)
RESET-INIT INIT STEP STEP

Reinitialisable step Initial step SFC step


DIV-OR 2 CONV-OR 2 DIV-AND 2

Divergence to OR Convergence to OR Divergence to AND


CONV-AND 2

Convergence to AND
Logic functions
AND OR NAND

AND function OR function NOT AND function


NOR XOR NOT

NOT OR function Exclusive OR function NOT function


(1) Functional Block Diagram.
(2) Sequential Function Chart.

14102-EN_Ver2.0.fm/6
Characteristics Zelio Logic smart relays 0

Compact and modular smart relays

Environment characteristics
Product certifications UL, CSA, GL, C-TICK
Conformity with Conforming to 73/23/EEC EN 61131-2 (open equipment)
the low voltage directive
Conformity with Conforming to 89/336/EEC EN 61131-2 (Zone B)
the EMC directive EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4
Degree of protection Conforming to IEC 60529 IP 20
Overvoltage category Conforming to IEC 60664-1 3
Degree of pollution Conforming to IEC/EN 61131-2 2
Ambient air temperature Operation °C -20... +55 (+40 in enclosure), conforming to IEC 60068-2-1 and IEC 60068-2-2
around the device Storage °C -40... +70
Maximum relative humidity 95 % without condensation or dripping water
Maximum operating altitude Operation m 2000
Transport m 3048
Mechanical resistance Immunity to vibrations IEC 60068-2-6, test Fc
Immunity to mechanical shock IEC 60068-2-27, test Ea
Resistance to Immunity to IEC 61000-4-2, level 3
electrostatic discharge electrostatic discharge
Resistance to HF interference Immunity to IEC 61000-4-3, level 3
(Immunity) electromagnetic radiated fields
Immunity to IEC 61000-4-4, level 3
fast transients in bursts
Immunity to shock waves IEC 61000-4-5
Radio frequency IEC 61000-4-6, level 3
in common mode
Voltage dips and breaks (a) IEC 61000-4-11
Immunity to IEC 61000-4-12
damped oscillation wave
Conducted and Conforming to EN 55022/11 Class B
radiated emissions (Group 1)
Connection to screw terminals Flexible cable with cable end mm 2 1 conductor: 0.25...2.5, cable: AWG 24... AWG14
(Tightened using 2 conductors: 0.25...0.75, cable: AWG 24... AWG18
Ø 3.5 screwdriver) Semi-solid cable mm 2 1 conductor: 0.2...2.5, cable: AWG 25... AWG14
Solid cable mm 2 1 conductor: 0.2...2.5, cable: AWG 25... AWG14
2 conductors: 0.2...1.5, cable: AWG 24... AWG16
Tightening torque N.m 0.5

c 12 V supply characteristics
Smart relay type SR2 B121JD SR2 B201JD
Primary Nominal voltage V 12 12
Voltage limits Including ripple V 10.4…14.4 10.4…14.4
Nominal input current mA 120 200
Nominal input current with extensions mA 144 250
Power dissipated W 1.5 2.5
Micro-breaks Permissible duration ms y 1 (repeated 20 times)
Protection Against polarity inversion

c 24 V supply characteristics
Smart relay type SR2 SR2 SR2 SR2 SR3 SR3 SR3 SR3
p1p1BD p1p2BD p2p1BD p2p2BD B101BD B102BD B261BD B262BD
Primary Nominal voltage V 24 24 24 24 24 24 24 24
Voltage limits Including ripple V 19.2…30 19.2…30 19.2…30 19.2…30 19.2…30 19.2…30 19.2…30 19.2…30
Nominal input current mA 100 100 100 100 100 50 190 70
Nominal input current with extensions mA – – – – 100 160 300 180
Power dissipated W 3 3 6 3 3 4 6 5
Power dissipated with extensions W – – – – 8 8 10 10
Micro-breaks Permissible duration ms y 1 (repeated 20 times)
Protection Against polarity inversion

a 24 V supply characteristics
Smart relay type SR2p1p1B SR2p2p1B SR3 B101B SR3 B261B
Primary Nominal voltage V 24 24 24 24
Voltage limits V 20.4…28.8 20.4…28.8 20.4…28.8 20.4…28.8
Nominal frequency Hz 50-60 50-60 50-60 50-60
Nominal input current mA 145 233 160 280
Nominal input current with extensions mA – – 280 415
Power dissipated VA 4 6 4 7.5
Power dissipated with extensions VA – – 7,5 10
Micro-breaks Permissible duration ms y 10 (repeated 20 times)
rms insulation voltage V 1780 (50-60 Hz)

14102-EN_Ver2.0.fm/7
Characteristics (continued) Zelio Logic smart relays 0

Compact and modular smart relays

a 100...240 V supply characteristics


Smart relay type SR2 p101FU SR2 p121FU SR2 p201FU SR3 B101FU SR3 B261FU
Primary Nominal voltage V 100…240 100…240 100…240 100…240 100…240
Voltage limits V 85…264 85…264 85…264 85…264 85…264
Nominal input current mA 80/30 80/30 100/50 80/30 100/50
Nominal input current with extensions mA – – – 80/40 80/60
Power dissipated VA 7 7 11 7 12
Power dissipated with extensions VA – – – 12 17
Micro-breaks Permissible duration ms 10 10 10 10 10
rms insulation voltage V 1780 1780 1780 1780 1780

Processing characteristics
Smart relay type SR2/SR3
Number of With LADDER programming 120
control scheme lines
Number of function blocks With FBD programming Up to 200
Cycle time ms 10...50
Response time ms 20
Back-up time Day/time 10 years (lithium battery) at 25 °C
(in the event of power failure) Program and settings 10 years (EEPROM memory)
Program memory checking At each power-up
Clock drift 12 min/year (0 to 55 °C)
6 sec/month (at 25 °C and calibration)
Timer block accuracy 1 % ± 2 of the cycle time

Discrete c 24 V input characteristics


Smart relay type SR2/SR3
Connection Screw terminal block
Nominal value of inputs Voltage V 24
Current mA 4
Input switching limit values At state 1 Voltage V u 15
Current mA u 2.20
At state 0 Voltage V y5
Current mA < 0.75
Input impedance at state 1 KΩ 7.4
Configurable response time State 0 to 1 ms 0.2
State 1 to 0 ms 0.3
Conformity to IEC 61131-2 Type 1
Sensor compatibility 3-wire Yes PNP
2-wire No
Input type Resistive
Isolation Between supply and inputs None
Between inputs None
Maximum counting frequency kHz 1
Protection Against inversion of terminals Control instructions not executed

Discrete a 100...240 V input characteristics


Smart relay type SR2/SR3
Connection Screw terminal block
Nominal value of inputs Voltage V 100... 240
Current mA 0.6
Frequency Hz 47... 63
Input switching limit values At state 1 Voltage V u 79
Current mA > 0.1750
At state 0 Voltage V y 40
Current mA < 0.05
Input impedance at state 1 KΩ 350
Configurable response time State 0 to 1 (50/60 Hz) ms 50
State 1 to 0 (50/60 Hz) ms 50
Isolation Between supply and inputs None
Between inputs None
Protection Against inversion of terminals Control instructions not executed

14102-EN_Ver2.0.fm/8
Characteristics (continued) Zelio Logic smart relays 0

Compact and modular smart relays

Integral analogue input characteristics


Smart relay type SR2/SR3
Analogue inputs Input range V 0...10 or 0...24
Input impedance KΩ 12
Maximum non destructive voltage V 30
Value of LSB 39 mV, 4 mA
Input type Common mode
Conversion Resolution 8 bit
Conversion time Smart relay cycle time
Precision at 25 °C ±5%
at 55 °C ± 6.2 %
Repeat at 55 °C ±2%
accuracy
Isolation Between analogue None
channel and supply
Cabling distance m 10 maximum, with screened cable (sensor not isolated)
Protection Against inversion of terminals Control instructions not executed

Relay output characteristics


Smart relay type SR2ppp/ SR3 B101pp SR3 B261pp, SR3 XT141pp
Operating limit values V c 5...150. c 5...150.
a 24...250 a 24...250
Contact type N/O N/O
Thermal current A 8 8 outputs: 8 A
2 outputs: 5 A
Electrical durability for Utilisation DC-12 V 24 24
500 000 operating cycles category A 1.5 1.5
DC-13 V 24 (L/R = 10 ms) 24 (L/R = 10 ms)
A 0.6 0.6
AC-12 V 230 230
A 1.5 1.5
AC-15 V 230 230
A 0.9 0.9
Minimum switching capacity At minimum voltage of 12 V mA 10 10
Low power switching 12 V - 10 mA 12 V - 10 mA
reliability of contact
Maximum operating rate No-load Hz 10 10
At Ie (operational current) Hz 0.1 0.1
Mechanical life In millions of operating cycles 10 10
Rated impulse Conforming to IEC 60947-1 kV 4 4
withstand voltage and 60664-1
Response time Trip ms 10 10
Reset ms 5 5
Built-in protection Short-circuit None
Against overvoltage and overload None
Transistor output characteristics
Smart relay type SR2/SR3
Operating limit values V 19.2...30
Load Nominal voltage V c 24
Nominal current A 0.5
Maximum current A 0.625 at 30 V
Drop out voltage At state 1 V y 2 for I=0.5 A
Response time Trip ms y1
Reset ms y1
Built-in protection Against overload Yes
and short-circuits
Against overvoltage (1) Yes
Against inversions Yes
of power supply
(1) If there is no volt-free contact between the relay output and the load.

14102-EN_Ver2.0.fm/9
Curves Zelio Logic smart relays 0

Compact and modular smart relays

Electrical durability of relay outputs


(in millions of operating cycles, conforming to IEC 60947-5-1)
d.c. loads
DC-12 (1)

Millions of operating cycles


3,0

2,5
48 V
2,0
24 V
1,5

1,0

0,5

0,0
0 0,5 1 1,5 2 Current (A)

DC-13 (2)
Millions of operating cycles

1,4 L/R = 10 ms 48 V
1,2 L/R = 10 ms 24 V
1,0
L/R = 60 ms 48 V
0,8
L/R = 60 ms 24 V
0,6

0,4

0,2

0,0
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 Current (A)

(1) DC-12: switching resistive loads and photo-coupler isolated solid state loads, L/R ≤ 1ms.
(2) DC-13: switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: Rated operational voltage, Ie:
rated operational current (with protection diode on load, use the DC-12 curves and apply a
coefficient of 0.9 to the millions of operating cycles value).

14102-EN_Ver2.0.fm/10
Curves (continued) Zelio Logic smart relays 0

Compact and modular smart relays

Electrical durability of relay outputs (continued)


(in millions of operating cycles, conforming to IEC 60947-5-1)
a.c. loads
AC-12 (1)

3,0

Millions of operating cycles


2,5
24 V
2,0
48 V
1,5
110 V
1,0 230 V

0,5

0,0
0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5 Current (A)

AC-14 (2)

2,5
Millions of operating cycles

2,0
110 V

1,5
230 V

1,0 48 V
24 V

0,5

0,0
0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2 Current (A)

AC-15 (3)

1,0
Millions of operating cycles

0,9
0,8
110 V
0,7
0,6 230 V 48 V
0,5
0,4
0,3
0,2
0,1
0,0
0,5 0,7 0,9 1,1 1,3 1,5 1,7 1,9 Current (A)

(1) AC-12: switching resistive loads and photo-coupler isolated solid state loads, cos ≥ 0.9.
(2) AC-14: switching small electromagnetic loads whose power drawn with the electromagnet
closed is ≤ 72 VA, making: cos = 0.3, breaking: cos = 0.3.
(3) AC-15: switching electromagnetic loads whose power drawn with the electromagnet closed is
> 72 VA, making: cos = 0.7, breaking: cos = 0.4.

14102-EN_Ver2.0.fm/11
References Zelio Logic smart relays 0

Compact smart relays

Compact smart relays with display


Number Discrete Of which Relay Transistor Clock Reference Weight
of I/O inputs 0-10 V outputs outputs
analogue
inputs kg
Supply c 12 V
12 8 4 4 0 Yes SR2 B121JD 0.250
20 12 6 8 0 Yes SR2 B201JD 0.250

Supply c 24 V
109440

10 6 0 4 0 No SR2 A101BD (1) 0.250


12 8 4 4 0 Yes SR2 B121BD 0.250
8 4 0 4 Yes SR2 B122BD 0.220
20 12 2 8 0 No SR2 A201BD (1) 0.380
12 6 8 0 Yes SR2 B201BD 0.380
12 6 0 8 Yes SR2 B202BD 0.280

Supply a 24 V
12 8 0 4 0 Yes SR2 B121B 0.250
20 12 0 8 0 Yes SR2 B201B 0.380

Supply a 100...240 V
SR2 A201BD
10 6 0 4 0 No SR2 A101FU (1) 0.250
12 8 0 4 0 Yes SR2 B121FU 0.250
20 12 0 8 0 No SR2 A201FU (1) 0.380
12 0 8 0 Yes SR2 B201FU 0.380

Compact smart relays without display


Number Discrete Of which Relay Transistor Clock Reference Weight
of I/O inputs 0-10 V outputs outputs
analogue
inputs kg
Supply c 24 V
109442

10 6 0 4 0 No SR2 D101BD (1) 0.220


12 8 4 4 0 Yes SR2 E121BD 0.220
20 12 2 8 0 No SR2 D201BD (1) 0.350
12 6 8 0 Yes SR2 E201BD 0.350

Supply a 24 V
12 8 0 4 0 Yes SR2 E121B 0.220
20 12 0 8 0 Yes SR2 E201B 0.350

Supply a 100...240 V
10 6 0 4 0 No SR2 D101FU (1) 0.220
12 8 0 4 0 Yes SR2 E121FU 0.220
SR2 E121BD 20 12 0 8 0 No SR2 D201FU (1) 0.350
12 0 8 0 Yes SR2 E201FU 0.350

Compact "discovery" packs


Number Pack contents Reference Weight
of I/O kg
Supply c 24 V
510345

12 An SR2 B121BD compact smart relay with display, SR2 PACKBD 0.700
a connecting cable and “Zelio Soft” programming
software supplied on CD-Rom.
20 An SR2 B201BD, compact smart relay with display, SR2 PACK2BD 0.850
a connecting cable and “Zelio Soft” programming
software supplied on CD-Rom.
Supply a 100...240 V
12 An SR2 B121FU, compact smart relay with display, SR2 PACKFU 0.700
a connecting cable and “Zelio Soft” programming
software supplied on CD-Rom.
20 An SR2 B201FU, compact smart relay with display, SR2 PACK2FU 0.850
a connecting cable and “Zelio Soft” programming
SR2 PACKppp software supplied on CD-Rom.
(1) Programming on smart relay in LADDER language only.

14102-EN_Ver2.0.fm/12
References Zelio Logic smart relays 0

Modular smart relays

Modular smart relays with display


Number Discrete Of which Relay Transistor Clock Reference Weight
of I/O inputs 0-10 V outputs outputs
analogue
inputs kg
Supply c 24 V
109442

10 6 4 4 0 Yes SR3 B101BD 0.250


6 4 0 4 Yes SR3 B102BD 0.220

26 16 6 10 (1) 0 Yes SR3 B261BD 0.400


16 6 0 10 Yes SR3 B262BD 0.300

Supply a 24 V
10 6 0 4 0 Yes SR3 B101B 0.250

26 16 0 10 (1) 0 Yes SR3 B261B 0.400

Supply a 100-240 V
SR3 B101BD 10 6 0 4 0 Yes SR3 B101FU 0.250

26 16 0 10 (1) 0 Yes SR3 B261FU 0.400


109363

I/O extension modules (2)


Number Discrete Relay Reference Weight
of I/O inputs outputs kg
Supply c 24 V (for smart relays SR3 BpppBD)
6 4 2 SR3 XT61BD 0.125

10 6 4 SR3 XT101BD 0.200

14 8 6 SR3 XT141BD 0.220

Supply a 24 V (for smart relays SR3 BpppB)


6 4 2 SR3 XT61B 0.125
SR3 XT61BD
10 6 4 SR3 XT101B 0.200

14 8 6 SR3 XT141B 0.220

Supply a 100-240 V (for smart relays SR3 BpppFU)


109369

6 4 2 SR3 XT61FU 0.125

10 6 4 SR3 XT101FU 0.200

14 8 6 SR3 XT141FU 0.220

Communication module (2)


For use on Supply voltage Reference Weight
kg
Modbus network c 24 V SR3 MBU01BD r 0.300

Modular "discovery" packs


SR3 XT141BD Number Pack contents Reference Weight
of I/O kg
Supply c 24 V
10 An SR3 B101BD, modular smart relay, a connecting SR3 PACKBD 0.700
cable and “Zelio Soft” programming software
supplied on CD-Rom.
26 An SR3 B261BD modular smart relay, a connecting SR3 PACK2BD 0.850
cable and “Zelio Soft” programming software
supplied on CD-Rom.
Supply a 100...240 V
10 An SR3 B101FU modular smart relay, a connecting SR3 PACKFU 0.700
cable and “Zelio Soft” programming software
supplied on CD-Rom.
26 An SR3 B261FU modular smart relay with display, SR3 PACK2FU 0.850
a connecting cable and “Zelio Soft” programming
software supplied on CD-Rom.
(1) Including 8 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A.
(2) Power supply to the I/O extension and communication modules is via the modular smart
relays
r Available: 1 st quarter of 2004.
Note: The smart relay and its associated extensions must have an identical voltage.

14102-EN_Ver2.0.fm/13
References Zelio Logic smart relays 0

Compact and modular smart relays


Separate components
510352

“Zelio Soft” software for PC


Description Reference Weight
kg
“Zelio Soft” for PC multi-language programming software SR2 SFT01 0.200
supplied on CD-Rom (1), compatible with Windows 95, 98, NT,
2000, XP and ME.
Connecting cable between the PC (SUB-D, 9-way connector) SR2 CBL01 0.150
and the smart relay, length: 3 m
Interface for USB port (for use with cable SR2 CBL01), SR2 CBL06 0.350
length: 1.8 m
Back-up memory
Description Reference Weight
SR2 SFT01
kg
EEPROM back-up memory SR2 MEM01 0.010

Communication interface (2)


510353

Description Supply Reference Weight


kg
Communication interface c 12/24 V SR2 COM01 r 0.140

Converters for Optimum Pt100 probes (3)


109369

Supply voltage c 24 V (20 %, not isolated)


Type Temperature range Output signal Reference Weight
°C °F kg
Pt100 - 40...40 - 40...104 0...10 V or 4...20 mA RMP T13BD 0.116
2-wire, 3-wire - 100...100 - 148...212 0...10 V or 4...20 mA RMP T23BD 0.116
and 4-wire
0... 100 32... 212 0...10 V or 4...20 mA RMP T33BD 0.116
0... 250 32... 482 0...10 V or 4...20 mA RMP T53BD 0.116
SR2 MEM01 SR2 COM01
0... 500 32...932 0...10 V or 4...20 mA RMP T73BD 0.116

Power supplies (3)


Input Nominal Nominal Reference Weight
voltage output voltage output current kg
510354

a 100...240 V c 12 V 1.9 A ABL 7RM1202 0.180


(47...63 Hz) c 24 V 1.4 A ABL 7RM2401 0.182

Mounting accessories (4)


Description Reference Weight
kg
Dust and damp-proof enclosure for mounting through a door 14210 0.350
with split blanking cover arrangement, fitted with an IP 55
dust and damp-proof window with hinged flap.
Mounting capacity:
- 1 or 2 SR2 modules with 10 or 12 I/O,
or
- 1 SR2 module with 20 I/O,
ABL 7RM1202 or
- 1 SR3 module with 10 I/O + 1 I/O extension module (6 or 10 or
14 I/O,
or
- 1 SR3 module with 26 I/O + 1 I/O extension module 6 I/O.
Fixing bracket and symmetrical mounting rail 14211 0.210
14211
DF563990

for mounting enclosure 14210 through a door panel.


Documentation
Description Language Reference Weight
kg
User's manual English SR2 MAN01EN 0.100
for direct programming French SR2 MAN01FR 0.100
on the smart relay
German SR2 MAN01DE 0.100
Spanish SR2 MAN01ES 0.100
Italian SR2 MAN01IT 0.100
Portuguese SR2 MAN01P0 0.100

(1) CD-Rom containing "Zelio Soft" software, an application library, a self-training manual,
installation instructions and a user's manual.
14210 (2) See pages 14011/2 to 14011/7
(3) See pages 14060/2 to 14060/5
(4) Products marketed under the Merlin Gerin brand.

r Available: 2nd quarter of 2004.

14102-EN_Ver2.0.fm/14
Dimensions, Zelio Logic smart relays 0

mounting Compact and modular smart relays

Compact and modular smart relays


SR2 A101BD, SR2 D101FU, SR3 B101BD and SR3 B101FU (10 I/O)
SR2 B121JD, SR2 B12pBD, SR2 B121B, SR2 A101FU, SR2 B121FU, SR2 D101BD, SR2 E121BD, SR2 E121B, SR2 E121FU
(12 I/O)
Mounting on 35 mm 5 rail Screw fixing (retractable lugs)
=

107,6
100
90
=

59,5 71,2
59,9 2xØ4

SR2 B201JD, SR2 A201BD, SR2 B20pBD, SR2 B201B, SR2 A201FU, SR2 B201FU, SR2 D201BD, SR2 E201BD, SR2 E201B,
SR2 D201FU and SR2 E201FU (20 I/O)
SR3 B26pBD and SR3 B261FU (26 I/O)
Mounting on 35 mm 5 rail Screw fixing (retractable lugs)
=

107,6
100
90
=

59,5 124,6
113,3 2xØ4

I/O extension modules


SR3 XT61pp (6 I/O), SR3 XT101pp and SR3 XT141pp (10 and 14 I/O)
Mounting on 35 mm 5 rail Screw fixing (retractable lugs)
=

110
100
90

SR3 a G
=

XT61pp 35,5 25
XT101pp 72 60
59,5 a
G 2xØ4 XT141pp 72 60

Enclosure + fixing bracket


14210 and 14211
Cut-out

104,5 104,5
101,5 101,5
105 234 55 55

r=2
57
=

40,5
32
126

96

40,5
32
=

57

12xØ5

186

14102-EN_Ver2.0.fm/15
Schemes Zelio Logic smart relays 0

Compact and modular smart relays

Input connections
3-wire sensors
SR2 ppppBD, SR2 B121JD and SR3 ppppBD

+ (1)
SR2 ppppBD
c 24 V
SR2 B121JD
c 12 V
SR3 ppppBD
c 24 V

BL BN BL BN

BK BK
+– I1 I2 I3 I4 IB IC ID IE

Q1 Q2 Q3 Q4

(1) 1 A quick-blow fuse or circuit-breaker.


Analogue inputs
SR2 B12pBD, SR2 B121JD and SR3 B10pBD SR2 B201BD, SR3 B26pBD and SR2 B201JD

c 0-10 V ANALOG. c 0-10 V ANALOG.

Ca / Ta Ca / Ta Ca / Ta Ca / Ta
1 2 1 2
+ (1) + (1)

SR2 ppppBD SR2 B201BD


10 m maximum

10 m maximum

c 24 V SR3 B26pBD
c 24 V
SR2 B121JD SR2 B201JD
c 12 V c 12 V
– –

+– I1 I2 I3 I4 IB IC ID IE +– I1 I2 I3 I4 I5 I6 IB IC ID IE IF IG ––

Q1 Q2 Q3 Q4

(1) 1 A quick-blow fuse or circuit-breaker. (1) 1 A quick-blow fuse or circuit-breaker.

14102-EN_Ver2.0.fm/16
Schemes (continued) Zelio Logic smart relays 0

Compact and modular smart relays

Connection of smart relays on c supply


SR2 ppppBD, SR2 B121JD, SR2 p201BD and SR3 B10ppp SR2 B122BD and SR2 B202BD, SR3 B102BD and SR3 B262BD

+ (1) + (1)
SR2 ppppBD
c 24 V c 24 V
SR2 B121JD
c 12 V
– –
+– I1 I2 I3 I4 IB IC ID IE +– I1 I2 I3 I4 IB IC ID IE

Q1 Q2 Q3 Q4 + Q1 Q2 Q3 Q4

(2) (3)
L/+ +
z 12…240 V
50/60 Hz U c 24 V
c 12…24 V
N/– z 12…240 V –
50/60 Hz
or
(3)

c 12…24 V

(1) 1 A quick-blow fuse or circuit-breaker. (1) 1 A quick-blow fuse or circuit-breaker.


(2) Fuse or circuit-breaker.
(3) Inductive load.
Connection of smart relays on a supply
SR2 BpppB, SR2 A1p1FU, SR2 p201FU, SR3 BppB and SR3 BpppFU

L (1)
SR2 B121B
a 24 V
SR2 p101FU
c 100…240 V
50/60 Hz
N
L N I1 I2 I3 I4 I5 I6

Q1 Q2 Q3 Q4

(3) (3)
L/+
(2)

z 12…240 V
50/60 Hz U U
c 12…24 V
N/– z 12…240 V c 12…24 V
50/60 Hz or

(1) 1 A quick-blow fuse or circuit-breaker.


(2) Fuse or circuit-breaker.
(3) Inductive load.

14102-EN_Ver2.0.fm/17
Presentation 0
Analogue interfaces 0

Zelio Analog
Converters for thermocouples and Pt100 probes
Voltage/current converters

The Zelio Analog range of converters is designed to convert signals emitted by


sensors or electrical measurements into standard electrical signals which are
compatible with automation platforms, controllers (thermal processes, speed, …).
They also allow the connection distance between a sensor and the measurement
acquisition device to be increased: for example between a thermocouple and a
programmable controller.
Conforming to IEC standards, UL and CSA certified, these converters are suitable
for universal use.

Measurement signals for thermocouples and Pt100 probes


The voltages induced by thermocouples vary between 10 and 80 µV/°C, Pt100
probes (100 ohms at 0°C) produce about 0.5 mV/°C, with measurement currents of
1 mA. Depending on the sensor, the signal to be measured ranges from a few µV
(thermocouple) to 250 and 700 mV for a Pt100 probe.
It is therefore difficult to transmit these low level signals over long electric lines
without encountering problems of interference, signal reduction or errors.
Connecting Zelio Analog converters close to the sensors resolves these problems :
- 4-20 mA current loops transmitted over a long distance are less sensitive to
interference than low level voltage signals from sensors,
- signal reductions during transmission (resistance) of voltages do not occur,
- the cables used to connect the converters to process equipment (programmable
controllers) are standard cables, which are more cost effective than extension cables
or compensation cables suitable for low level signals for Pt100 probes or
thermocouples.

Presentation
The Zelio Analog range
The Zelio Analog range has been developed both to take account of the most
common applications and to ensure great simplicity of installation:
b pre-set input and output scales, requiring no adjustment
b outputs protected against reverse polarity, overvoltage and short-circuits
b c 24 V power supply
b sealable protective cover
b rail mounting and screw fixing onto mounting plate
b LED indicator on the front panel
b input and output selector switches on the front panel
b output with fallback value if no input signal is present (due to failure of a sensor,
for example).

The Zelio Analog converter range is divided into four families:


b Converters for J and K type thermocouples: RMT J/K
b Converters for Universal Pt100 probes: RMP Tp0
b Converters for Optimum Pt100 probes: RMP Tp3
b Universal voltage/current converters: RMC.

Converters for J and K type thermocouples


108999

108997

Thermocouples, which consist of two metals with different thermo-electric


characteristics, produce a voltage that varies according to temperature. This voltage
is transmitted to the Zelio Analog converter which converts it to a standard signal.
Converters for thermocouples have cold junction compensation to allow detection of
measurement errors induced by the connection to the device itself.

Converters for J and K type thermocouples have :


b for inputs, a pre-set temperature range, depending on the model:
v Type J: 0...150 °C, 0...300 °C, 0...600 °C
RMT J40BD RMT K90BD v Type K: 0...600 °C, 0...1200 °C.
b for outputs, a switchable signal:
v 0...10 V, 0... 20 mA, 4... 20 mA.

Characteristics : References : Dimensions : Schemes :


pages 22 and 23 page 24 page 25 page 25

20
Presentation (continued) 0
Analogue interfaces 0

Zelio Analog
Converters for thermocouples and Pt100 probes
Voltage/current converters
109000

Converters for Universal Pt100 probes


Pt100 probes with platinum resistor are electrical conductors whose resistance
varies according to the temperature.
This ohmic resistance is transmitted to the Zelio Analog converter which converts it
to a standard signal.
Converters for Universal Pt100 probes have :
b for inputs, a pre-set temperature range, depending on the model:
v - 100...100 °C,
v - 40...40 °C,
v 0...100 °C,
RMP T70BD
v 0...250 °C,
v 0...500 °C.
b for outputs, a switchable signal:
v 0... 10 V, 0... 20 mA, 4... 20 mA.
The products in the Universal Pt100 family allow wiring of Pt100 probes in 2, 3 and
4-wire mode.

Converters for Optimum Pt100 probes


Derived from the above family, these converters have:
b for inputs, a pre-set temperature range identical to that of converters for Universal
Pt100 probes.
b for outputs:
v a 0... 10V signal dedicated to Zelio Logic analogue inputs.
They allow allow Pt100 probes to be wired in 2, 3 and 4-wire mode.
109002

Universal voltage/current converters


This family of converters allows the adaptation of electrical values (voltage/current).
Four products are available:
b a cost effective converter which will convert a 0...10 V signal to a 4...20mA signal
or vice versa.
b a Universal voltage/current converter allowing the most common signals. They
have:
v for inputs, a voltage/current range:
- 0...10 V, ± 10 V, 0...20 mA, 4...20 mA.
v for outputs, a switchable voltage/current range:
RMC A61BD
- 0...10 V, ± 10 V, 0...20 mA, 4...20 mA.
b two Universal voltage/current converters which allow conversion of electrical
power signals, both a.c. and d.c.
They have the following, depending on the model:
v for voltage inputs, a range of 0 to 500 V (a or c)
v for outputs, a switchable voltage/current range:
- 0...10 V, 0...20 mA, 4...20 mA.
v for current inputs, a range of 0 to 15 A (a or c)
v for outputs, a voltage/current range:
- 0...10 V, 0...20 mA, 4...20 mA.

Description
108998

Zelio Analog converters have the following on their front panel, depending on the
model:
1 1 Two terminals for c 24 V supply connection
2 A 'Power ON' LED
3 Three input selector switches (depending on model)
4 An output selector switch (depending on model)
2
5 A sealable protective cover
6 A screw terminal block for inputs
3 7 A screw terminal block for outputs.

4
5

7
RMC L55BD

Characteristics : References : Dimensions : Schemes :


pages 22 and 23 page 24 page 25 page 25

21
Characteristics 0
Analogue interfaces 0

Zelio Analog
Converters for thermocouples and Pt100 probes
Voltage/current converters

Environment characteristics
Converter types RMT J/Kppppp, RMP ppppp, RMCppppp
Conforming to standards IEC 947-1, IEC 584-1 (IEC 751, DIN 43760 for RMPpppp)
Approvals UL, CSA, GL, e
Degree of protection
Housing IP 50
Terminal block IP 20
Flame resistance °C 850 conforming to UL, IEC 695-2-1
Shock resistance 50 gn/11ms conforming to IEC 68-2-27
Vibration resistance 5 gn (10...100 Hz) conforming to IEC 68-2-6
Immunity to EMC
Resistance to electrostatic discharge kV Level 3: 8 (air), 6 (contact) conforming to IEC 1000-4-2
Immunity to fast transient currents kV On the power supply: 2; on the input-output: 1 conforming to IEC 1004-4
Surge withstand kV 0.5 - waves 1.2/50µs; 0.5 J conforming to IEC 1000-4-5
Disturbance
Radiated/conducted CISPR11 and CISPR22 Group1- Class B
Insulation voltage kV 2
Ambient air temperature around the device
Storage °C - 40...85 (- 40...185 °F)
Operation °C Mounted side-by-side: 0...50 (32...122 °F); 2 cm spacing: 0...60 (32...140 °F)
Degree of pollution 2 conforming to IEC 60 664-1
Mounting 35 mm DIN rail, clip-on or fixed on mounting plate
Connection mm2 2 x1.5 or 1 x 2.5 cable
Tightening torque Nm 0.6...1.1

Specific characteristics
Types of converter for thermocouples RMT J40BD RMT J60BD RMT J80BD RMT K80BD RMT K90BD
Input types Thermocouple type, to IEC 584 J (Fe-CuNi) K (Ni-CrNi)
Temperature range °C 0...150 0...300 0...600 0...600 0...1200
°F 32...302 32...572 32...1112 12...1112 32...2192
Analogue output switchable to voltage or current
Voltage Range V 0...10
Minimum impedance of load kΩ 100
Current Range mA 0...20; 4...20
Maximum impedance of load Ω 500
Built-in protection Reverse polarity, overvoltage (± 30 V) and short-circuit
Safety feature Output state when no inputs are wired Output predetermined according to type of output selected:
or when input wire broken voltage = - 13 V
current = 0 mA
Supply
Voltage Rated cV 24 ± 20 %, non isolated
Maximum current For voltage output mA 40
consumption For current output mA 60
Built-in protection Reverse polarity
Signalling Green LED (power on)
Measurements
Accuracy At 20°C % ± 1 of the full scale value
Repeatibility error At 20°C % ± 0.25 of the full scale value
At 60°C % ± 0.8 of the full scale value
Temperature coefficient ppm/°C 200 (0.02 %)
Cold junction compensation Built-in, cold junction measurement: 0 to 60 °C (0...140 °F)

Presentation : References : Dimensions : Schemes :


pages 20 and 21 page 24 page 25 page 25

22
Characteristics (continued) 0
Analogue interfaces 0

Zelio Analog
Converters for thermocouples and Pt100 probes
Voltage/current converters

Specific characteristics
Types of converter for Pt100 probes RMP T10/13BD RMP T20/23BD RMP T30/33BD RMP T50/53BD RMP T70/73BD
Input types Probe type Pt100 - IEC 751; DIN 43760 (2, 3, 4-wire)
Temperature range °C - 40...40 - 100...100 0...100 0...250 0...500
°F - 40...104 - 148...212 32...212 32...482 32...932
Analogue output
Output selection 0...10 V/0...20 mA, 4...20 mA switchable for RMP Tp0BD
0...10 V or 4...20 mA for RMP Tp3BD
Voltage Minimum impedance of load kΩ 100
Current Maximum impedance of load Ω 500
Built-in protection Reverse polarity, overvoltage (± 30 V) and short-circuit
Safety feature Output state when no inputs are Output predetermined according to type of output selected:
wired or when input wire broken voltage = - 13 V
current = 0 mA
Supply
Voltage Rated cV 24 ± 20 %, non isolated
Maximum current For voltage output mA 40
consumption For current output mA 60
Built-in protection Reverse polarity
Signalling Green LED (power on)
Measurements
Accuracy At 20°C % ± 0.5 of the full scale value (3, 4-wire connection)
± 1 of the full scale value (2-wire connection)
Repeatibility error At 20°C % ± 0.2 of the full scale value
At 60°C % ± 0.6 of the full scale value
Temperature coefficient ppm/°C 150 (0.015 %)
Connection in 2-wire mode
Maximum resistance of cable mΩ 200

Specific characteristics
Types of voltage/current converters RMC N22BD RMC L55BD RMC V60BD RMC A61BD
Input types Voltage V c 0...10 c 0...10, ±10 0...50; 0...300; –
0...500
c or a 50/60 Hz
Current mA 4...20 0...20; 4...20 – –
A – – – 0...1.5; 0...5; 0...15
c or a 50/60 Hz
Analogue output
Output selection By cabling Switchable Switchable By cabling
Voltage Range V 0...10 0...10; ± 10 0...10 0...10
Minimum impedance of load kΩ 100
Current Range mA 4...20 0...20; 4...20 0...20; 4...20 0...20; 4...20
Maximum impedance of load Ω 500
Built-in protection Reverse polarity, overvoltage (± 30 V) and short-circuit
Safety Output state when no inputs are Output predetermined according to type of output selected:
wired or when input wire broken voltage: voltage: voltage: 0 V
- 2.5 V - 10…+ 10 V = -10 V current:
current: 0…+ 10 V = 0 V 0…20 mA = 0 mA
6 mA current: 4…20 mA = 4 mA
0…20 mA = 0 mA
4…20 mA = 4 mA
Supply
Voltage Rated V c 24 ± 20 % c 24 ± 20 % isolated (1.5 kV)
non isolated
Maximum current For voltage output mA 40 70
consumption For current output mA 60 90
Built-in protection Reverse polarity
Signalling Green LED (power on)
Measurements
Accuracy At 20°C % ± 1 of the full scale value ± 5 of the full scale value
Repeatibility error At 20°C % ± 0.2 of the full scale value
At 60°C % ± 0.6 of the full scale value
Temperature coefficient ppm/°C 200 (0.02 %) 0...1.5 A: 500 (0.05 %)
0...5 A: 1000 (0.1 %)
0..0.15 A: 2000 (0.2 %)

Presentation : References : Dimensions : Schemes :


pages 20 and 21 page 24 page 25 page 25

23
References 0
Analogue interfaces 0

Zelio Analog
Converters for thermocouples and Pt100 probes
Voltage/current converters
108999

108997
Converters for J and K type thermocouples
Supply voltage c 24 V ± 20 %, non isolated
Type Temperature range Switchable Reference Weight
°C °F output signal kg
Type J 0…150 32…302 0…10 V, 0…20 mA, RMT J40BD 0.120
4…20 mA
0…300 32…572 0…10 V, 0…20 mA, RMT J60BD 0.120
4…20 mA
0…600 32…1112 0…10 V, 0…20 mA, RMT J80BD 0.120
4…20 mA
RMT J40BD RMT K90BD
Type K 0…600 32…1112 0…10 V, 0…20 mA, RMT K80BD 0.120
4…20 mA
0…1200 32…2192 0…10 V, 0…20 mA, RMT K90BD 0.120
4…20 mA
109000

Converters for Universal Pt100 probes


Supply voltage c 24 V ± 20 %, non isolated
Type Temperature range Switchable Reference Weight
°C °F output signal kg
Pt100 - 40…40 - 40…104 0…10 V, 0…20 mA, RMP T10BD 0.120
2-wire, 3-wire 4…20 mA
and 4-wire - 100…100 - 148…212 0…10 V, 0…20 mA, RMP T20BD 0.120
4…20 mA
0…100 32…212 0…10 V, 0…20 mA, RMP T30BD 0.120
4…20 mA
RMP T70BD
0…250 32…482 0…10 V, 0…20 mA, RMP T50BD 0.120
4…20 mA
0…500 32…932 0…10 V, 0…20 mA, RMP T70BD 0.120
4…20 mA

Converters for Optimum Pt100 probes (1)


109001

Supply voltage c 24 V ± 20 %, non isolated


Type Temperature range Output signal Reference Weight
°C °F kg
Pt100 - 40…40 - 40…104 0…10 V or 4…20 mA RMP T13BD 0.120
2-wire, 3-wire
and 4-wire - 100…100 - 148…212 0…10 V or 4…20 mA RMP T23BD 0.120

0…100 32…212 0…10 V or 4…20 mA RMP T33BD 0.120


RMP T13BD
0…250 32…482 0…10 V or 4…20 mA RMP T53BD 0.120

0…500 32…932 0…10 V or 4…20 mA RMP T73BD 0.120

Universal voltage/current converters


108996

Supply voltage c 24 V ± 20 %, non isolated


Input signal Output signal Reference Weight
kg
0…10 V or 4…20 mA 0…10 V or 4…20 mA RMC N22BD 0.120

Supply voltage c 24 V ± 20 %, isolated


Input signal Output signal Reference Weight
kg
0…10 V, ± 10 V, Switchable: RMC L55BD 0.120
0…20 mA, 4…20 mA 0…10 V, ± 10 V,
RMC N22BD 0…20 mA, 4…20 mA
0…50 V, 0…300 V, 0…500 V Switchable: RMC V60BD 0.150
108998

109002

c or a 50/60 Hz 0…10 V, 0...20 mA,


4…20 mA
0…1.5 A, 0…5 A, 0…15 A 0…10 V or 0...20 mA RMC A61BD 0.150
c or a 50/60 Hz or 4…20 mA

Connection accessories
Description Type Sold in lots of Unit referenceWeight
kg
Terminal blocks for Screw 100 AB1 RRTP435U 0.025
connection of protective Spring 100 AB1 RRTP435U2 0.015
RMC L55BD RMC A61BD earth conductor
(1) Converters dedicated to Zelio Logic smart relays.

Presentation : Characteristics : Dimensions : Schemes :


pages 20 and 21 pages 22 and 23 page 25 page 25

24
Dimensions, Analogue interfaces 0

mounting, Zelio Analog


Converters for thermocouples and Pt100 probes
schemes 0

Voltage/current converters

Dimensions, mounting
RMT ppppp/RMP ppppp/RMC ppppp
Mounting on rails AM1 ppppp Panel mounting
RMT pppppp RMC A61BD
RMP pppppp 2xØ4
RMC pppppp

(1) (1)

90
78

78

90,5 90,5 83
80 25 45
31 51

(1) Terminal block AB1 RRTP435U or AB1 RRTP435U2.


Schemes
RMT Jpppp, RMT Kpppp RMP Tp0BD RMP Tp3BD

2 mA 2 mA

IP1 c 19…30 V IP1 19…30 V


19…30 V
A1

A1
Type A1 Vo IP2 Vo IP2 Vo (1)
J or K (+) IP2 IP3 IP3 (1)
(–) IP1 Io
IP4 IP4
A2 OPG A2 OPG A2 OPG

0V c0V 0V
(1) Use one output only.
Input connections on RMP Tppppp
2-wire type 3-wire type 4-wire type
RL1 + RL2 ≤ 200 mΩ RL1 = RL2 = RL3 RL1 + RL2 ≤ 200 Ω
RL1 + RL2 ≤ 200 Ω
RL1 IP1 IP2
RL1 IP1
IP2 IP3
IP2
IP3 RL2 IP4 RL2 IP4
RL2 IP4 RL3 IP3 RL1 IP1

RMC ppppp
RMC N22BD RMC L55BD RMC V60BD
19…30 V A1 A2 A1 A2

4…20 mA A1 Vo 19…30 V 19…30 V


Ii 0V 0V
IPG
OPG (1) Vi
(1) V1
A2 I Vo (1) V2 Vo
Ii
V OPG (1) V3 OPG
(1) IPG
0V IPG

19…30 V

0…10 V A1 Io
Vi
IPG
OPG
A2

0V (1) Use one input only. (1) Use one input only.
RMC A61BD
A1 A2

19…30 V 0V

(1) I1
Vo (2)
(1) I2 Io1 (2)
(1) I3 Io2 (2)
Icom OPG (1) Use one input only.
(2) Use one output only.

Presentation : Characteristics : References :


pages 20 and 21 pages 22 and 23 page 24

25
Presentation 0
Power supplies and transformers 0

Phaseo modular regulated power supplies

ABL 7RM modular switch mode power supplies


The ABL 7RM range of power supplies is designed to provide the d.c. voltage
necessary for the control circuits of control system equipment. Comprising 2
products, this range meets the needs encountered in industrial, commercial and
residential applications. These single-phase, modular, electronic switch mode power
supplies provide a quality of output current which is suitable for the loads supplied
and compatible with the Zelio logic range, making them ideal partners. Clear
guidelines are given on selecting the upstream protection devices which are often
used with them, and thus a comprehensive solution is provided which can be used
in total safety.

These switch mode power supplies are totally electronic and regulated. The use of
electronics makes it possible to significantly improve the performance of these power
supplies, which offer:
- very compact size,
- integrated overload, short-circuit, overvoltage and undervoltage protection,
- a very wide range of permissible input voltages, without any adjustment,
- a high degree of output voltage stability,
- good performance,
- considerably reduced weight,
- a modular format allowing integration into panels.
Phaseo power supplies are single-phase. They deliver a voltage which is precise to
3 %, whatever the load and whatever the type of mains supply, within a range of 85 to
264 V for single-phase. Conforming to IEC standards and UL and CSA certified, they
are suitable for universal use. The inclusion of overload and short-circuit protection
makes downstream protection unnecessary if discrimination is not required.
All the products are fitted with an output voltage adjustment potentiometer in order to
be able to compensate for any line voltage drops in installations with long cable runs.
These power supplies are designed for direct mounting on 35 and 75 mm 7 rails, or
on a mounting plate by means of retractable fixing lugs.

These power supplies are single-phase and two references are available :

b ABL 7RM2401 (24 Vc/1.3 A).


b ABL 7RM1202 (12 Vc/1.9 A).
Description
1 2 3 1 2.5 mm2 screw terminal for connection
of the incoming a.c. supply voltage.
2 Output voltage adjustment
potentiometer.
3 2.5 mm2 screw terminal for connection
of the output voltage.
4 4 LED indicating presence of the d.c.
output voltage.
5 Retractable fixing lugs.

Characteristics : References : Dimensions :


page 27 page 29 page 29

26
Characteristics 0
Power supplies and transformers 0

Phaseo modular regulated power supplies

Technical characteristics
Type of power supply ABL 7RM1202 ABL 7RM2401
Approvals UL - CSA - TÜV
Conforming to standards Safety IEC/EN 60950 - IEC/EN 61131-2/A11
EMC EN 50081-1, IEC 61000-6-2 (EN 50082-2)
Input circuit
LED indication no no
Input voltage Rated values V a 100…240 a 100…240
Permissible values V a 85…264 a 85…264
Permissible frequencies Hz 47…63 47…63
Efficiency at nominal load > 80% > 80%
Current consumption A 0.5 (100 V)/0.3 (240 V) 0.6 (100 V)/0.4 (240 V)
Current at switch-on A < 20 < 20
Power factor 0.6 0.6
Output circuit
LED indication Green LED Green LED
Nominal output voltage V c 12 c 24
Nominal output current A 1.9 1.3
Precision Output voltage Adjustable 100 to 120 %
Line and load regulation ±4% ±3%
Residual ripple - interference mV 200 250
Micro-breaks Holding time for I max ms > 10 > 10
and Ve min
Protection Short-circuit Permanent/Thermal protection
Overcurrent, cold state < 1.7 In < 1.6 In
Undervoltage V < 10.5 < 19
Operating characteristics
Connections Input mm2 1 x 2.5 or 2 x 1.5 screw terminals
Output mm2 1 x 2.5 or 2 x 1.5 screw terminals
Environment Storage temperature °C -25 to +70
Operating temperature °C -25 to +55
Maximum relative humidity 95 %
Degree of protection IP2x
Vibrations EN 61131-2, IEC 68-2-6 test Fc
Operating position Vertical
MTBF Not available
Connections Series No No
Parallel Yes (same references) Yes (same references)
Dielectric strength Input/output 3000 VAC/50 Hz/1 min
Protection class conforming to VDE 0106 1 Class II without PE
Input fuse incorporated Yes (not interchangeable)
Emissions Conducted/radiated EN 50081-1 (generic standard), EN 55011, EN 55022 CI:B
Immunity Electrostatic discharge EN 61000-6-2 (generic standard), EN 61000-4-2 (4 kV contact/8 kV air)
Electromagnetic EN 61000-4-3 level 3 (10 V/m)
Conducted interference EN 61000-4-4 level 3 (2 kV), EN 61000-4-6 (10 V)
Mains interference EN 61000-4-11

Presentation : References : Dimensions :


page 26 page 29 page 29

27
Characteristics, Power supplies and transformers 0

selection 0
Phaseo modular regulated power supplies

Output characteristics
Derating
The ambient temperature is a determining factor which limits the power that an
electronic power supply can deliver continuously. If the temperature around the
electronic components is too high, their life will be significantly reduced. Conversely,
a power supply can deliver more than its rated power if the ambient temperature
remains well below the nominal operating temperature.

The maximum ambient temperature for Phaseo power supplies is 55°C. Below this
temperature, uprating is possible up to 110% of the nominal power.
The graph below shows the power (in relation to the nominal power) which the power
supply can deliver continuously, according to the ambient temperature.

P/Pn (%) 120

110

100

90

80

70

60

50
0 10 20 30 40 50 55 60 70
Maximum operating temperature (°C)

Selection
Upstream protection of power supplies
Mains supply a 115 V single-phase a 230 V single-phase
Type of Thermal-magnetic Gg Thermal-magnetic Gg
protection circuit-breaker fuse circuit-breaker fuse
Single-pole GB2 CBpp - - - - -
2-pole GB2 DBpp C60N - GB2 DBpp C60N -
ABL 7RM2401 GB2 CB/DB06 MG24516 (1) 1A GB2 CB/DB07 MG24517 (1) 1A
24184 24185
ABL 7RM1202 GB2 CB/DB06 MG24516 (1) 1A GB2 CB/DB07 MG17453 (1) 1A
24184 24185

(1) UL certified circuit-breaker

Presentation : References : Dimensions :


page 26 page 29 page 29

28
References, Power supplies and transformers 0

dimensions, Phaseo modular regulated power supplies


scheme 0

ABL 7RM modular regulated switch mode power supplies


Mains input voltage Output Nominal Nominal Auto-protect Reference Weight
47…63 Hz voltage power current reset
V cV W A kg

100…240 12 22 1.9 auto ABL 7RM1202 0.180


single-phase
wide range

24 30 1.3 auto ABL 7RM2401 0.182

Dimensions
ABL 7RMpppp power supply
110

100
90

90

44 4 60
59 72
70

Scheme
ABL 7RMpppp
+
+


L

Presentation : Characteristics :
page 26 page 27

29
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Afghanistan Contacts are assured by Schneider Electric India

Albania Contacts are assured by Schneider Electric Austria

Algeria b Schneider Electric voie A Lot C22 Tel. : +213 21 92 97 02 à 09


Zone industrielle Rouiba - Alger Fax : +213 21 92 97 00 à 01

Andorra Contacts are assured by Schneider Electric France

Angola Contacts are assured by Schneider Electric South Africa

Anguilla Contacts are assured by Schneider Electric Dominican Rep.

Antartica Contacts are assured by Schneider Electric Brazil

Antigua & Barbuda Contacts are assured by Schneider Electric Dominican Rep.

Argentina b Schneider Argentina Viamonte 2850 - 1678 Caseros Tel.: +54 1 716 88 88 www.schneider-electric.com.ar
(provincia Buenos Aires) Fax: +54 1 716 88 33

Armenia Contacts are assured by Schneider Electric Russian Fed.

Aruba Contacts are assured by Schneider Electric Dominican Rep.

Australia b Schneider Electric (Australia) Pty. 2 Solent Circuit Tel.: +61 298 51 28 00 www.schneider.com.au
Limited Norwest Business Park Fax: +61 296 29 83 40
Baulkham Hill _ NSW 2153

Austria b Schneider Austria Ges.m.b.H. Birostrasse 11 Tel.: +431 610 540 www.schneider-electric.at
1239 Wien Fax: +431 610 54 54

Azerbaijan Contacts are assured by Schneider Electric Russian Fed.

Bahamas b Schneider Electric Union Village Tel. : +1 242 327 42 91 www.squared.com


PO Box 3901 - Nassau Fax : +1 242 327 42 91

Bahrain b Schneider Electric Floor 1 - Juma Building Tel.: +97 322 7897
Abu Horaira Avenue Fax: +97 321 8313
PO Box 355 - 304 Manama

Bangladesh Contacts are assured by Schneider Electric India

Barbados Contacts are assured by Schneider Electric Dominican Rep.

Belarus b Schneider Electric Industries SA Prospect Macherova 5, of. 202 Tel. : +375 172 23 75 50
220004 Minsk Fax : +375 172 23 97 61

Belgium b Schneider Electric nv/sa Dieweg 3 Tel.: +3223737711 www.schneider-electric.be


B - 1180 Brussels Fax: +3223753858

Belize Contacts are assured by Schneider Electric USA

Benin Contacts are assured by Schneider Electric Ivory Coast

Bermuda Contacts are assured by Schneider Electric Dominican Rep.

Bhutan Contacts are assured by Schneider Electric India

Bolivia Contacts are assured by Schneider Electric Chile

Bosnia and Herzegovina Contacts are assured by Schneider Electric Croatia

Botswana Contacts are assured by Schneider Electric South Africa

Bouvet island Contacts are assured by Schneider Electric Dominican Rep.

Brazil b Schneider Electric Brazil Ltda. Avenida Das Nações Unidas 23223 Tel.: +55 55 24 52 33 www.schneider-electric.com.br
Jurubatuba - CEP 04795-907 Fax: +55 55 22 51 34
São Paulo-SP

Brunei (Darussalam) Contacts are assured by Schneider Electric Singapore

Bulgaria b Schneider Electric Expo 2000, Boulevard Vaptzarov Tel.: +3592 919 42 www.schneiderelectric.bg
1407 Sofiav Fax: +3592 962 44 39

Burkina Faso Contacts are assured by Schneider Electric Ivory Coast

Burundi Contacts are assured by Schneider Electric Kenya

Cambodia Contacts are assured by Schneider Electric Viet Nam

Cameroon b Schneider Electric Cameroon 166, rue de l'Hôtel de Ville Tel.: +237 343 38 84
BP12087 - Douala Fax: +237 343 11 94

Canada b Schneider Canada 19, Waterman Avenue Tel.: +1 416 752 8020 www.schneider-electric.ca
M4 B1Y2 Toronto - Ontario Fax: +1 416 752 4203

Cape Verde Contacts are assured by Schneider Electric Senegal

Caribee Contacts are assured by Schneider Electric Dominican Rep.

Cayman islands Contacts are assured by Schneider Electric Dominican Rep.

Central African Republic Contacts are assured by Schneider Electric Cameroon

Chad Contacts are assured by Schneider Electric Cameroon

Chile b Schneider Electric Chile S.A. Avda. Pdte Ed. Frei Montalva, 6001-31 Tel.: +56 2 444 3000 www.schneider-electric.co.cl
Conchali - Santiago Fax: +56 2 423 9335

China b Schneider Beijing Landmark bldg-Room 1801 Tel.: +86 10 65 90 69 07 www.schneider-electric.com.cn


8 North Dong Sanhuan Rd Fax: +86 10 65 90 00 13
Chaoyang District
100004 Beijing

30
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Christmas island Contacts are assured by Schneider Electric Australia

Cocos (Keeling) islands Contacts are assured by Schneider Electric Australia

Colombia b Schneider Electric de Colombia Calle 45A #102-48 Tel.: +57 1 426 97 00
S.A. Bogota DC Fax: +57 1 426 97 40

Comoros Contacts are assured by Schneider Electric la Reunion

Congo Contacts are assured by Schneider Electric Cameroon

Cook islands Contacts are assured by Schneider Electric Australia

Costa Rica b Schneider Centroamérica Ltda. 1.5 kmts oeste de la Embajada Tel.: +506 232-60-55 www.schneider-ca.com
Americana, Fax: +506 232-04-26
Pavas, San José, Costa Rica C.A.
Apartado: 4123-1000 San Jose

Croatia b Schneider Electric SA Fallerovo Setaliste 22 Tel.: +385 1 367 100


HR - 10000 Zagreb Fax: +385 1 367 111

Cuba b Schneider Electric Bureau de Liaison de La Havane Tel.: +53 724 15 59


Calle 36- N°306-Apto1 Fax: +53 724 12 17
Entre 3ra y 5ta Avenida Miramar
Playa Habana

Cyprus b Schneider Electric Cyprus 28 General Timayia Avenue Tel.: +00357 248 12646
Kyriakos Building, Block #A301 Fax: +00357 246 37382
Larnaca 6046

Czech Republic b Schneider Electric CZ, s.r.o. Thámova 13 Tel.: +420 2 810 88 111 www.schneider-electric.cz
Praha 8 - 186 00 Fax: +420 2 24 81 08 49

Democratic Rep. of Congo Contacts are assured by Schneider Electric Cameroon

Denmark b Schneider Electric A/S Baltorpbakken 14 Tel.: +45 44 73 78 88 www.schneider-electric.dk


DK-2750 Ballerup Fax: +45 44 68 5255

Djibouti Contacts are assured by Schneider Electric Egypt

Dominican Republic b Schneider Electric Calle Jacinto Manon Tel.: +1 809 334 66 63
Esq. Federico Geraldino Fax: +1 809 334 66 68
Edificio D' Roca Plaza Suite 402,
Ens. Paraiso - Santo Domingo

Ecuador b Schneider Electric Ecuador SA Av.Republica del Salvador 1082 y Nac Tel. : +593 2 224 42 42
Edificio Mansion Blanca-Quito Fax : +593 2 224 42 94

Egypt b Schneider Electric Egypt sae 68, El Tayaran Street Tel.: +20 24 01 01 19 www.schneider.com.eg
Nasr City, 11371 - Cairo Fax: +20 24 01 66 87

El Salvador Contacts are assured by Schneider Electric USA

Equatorial Guinea Contacts are assured by Schneider Electric Cameroon

Eritrea Contacts are assured by Schneider Electric Egypt

Estonia b Lexel Electric Ehitajate tee 110 Tel. : +372 650 97 00


EE 12618 Talinn Fax : +372 650 97 22

Ethiopia Contacts are assured by Schneider Electric Egypt

Falkland islands Contacts are assured by Schneider Electric Brazil

Faroe islands Contacts are assured by Schneider Electric Australia

Fiji Contacts are assured by Schneider Electric Australia

Finland b Schneider Electric Oy Sinimäentie 14 Tel. : +358 9 527 000 www.schneider-electric.fi


02630 Espoo Fax : +358 9 5270 0376

France b Schneider Electric SA 5, rue Nadar Tel.: +33 (0)1 41 29 82 00 www.schneider-electric.fr


92500 Rueil Malmaison Fax: +33 (0)1 47 51 80 20

French Polynesia Contacts are assured by Schneider Electric Australia

French West Indies Contacts are assured by Schneider Electric Dominican Rep.

Gabon Contacts are assured by Schneider Electric Cameroon

Gambia Contacts are assured by Schneider Electric Senegal

Georgia Contacts are assured by Schneider Electric Russian Fed.

Germany b Schneider Electric GmbH Gothaer Straße 29 Tel.: +49210 240 40 www.schneiderelectric.de
D-40880 Ratingen Fax: +492 10 240 49 256

Ghana b Schneider Electric Ghana PMB Kia Tel. : +233 21 70 11 687


3rd Floor Opeibea House Fax : +233 21 77 96 22
Airport Commercial Center
Liberation road - Accra

Gilbraltar Contacts are assured by Schneider Electric Spain

Greece b Schneider Electric AE 14th km - RN Athens-Lamia Tel.: +302 106 29 52 00 www.schneider-electric.com.gr


GR - 14564 Kifissia Fax: +302 106 29 52 10

Greenland Contacts are assured by Schneider Electric United States

Grenada Contacts are assured by Schneider Electric Dominican Rep.

Guadeloupe Contacts are assured by Schneider Electric Martinique

Guam Contacts are assured by Schneider Electric Australia

31
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Guatemala Contacts are assured by Schneider Electric United States

Guinea-Bissau Contacts are assured by Schneider Electric Sénégal

Guinea Contacts are assured by Schneider Electric Ivory Coast

Guyana Contacts are assured by Schneider Electric United States

Haiti Contacts are assured by Schneider Electric Dominican Rep.

Heard & Mac Donald isl. Contacts are assured by Schneider Electric Australia

Honduras Contacts are assured by Schneider Electric United States

Hong Kong b Schneider Electric (Hong Kong) Room 3108-28, 31th Floor, Tel.: +852 25 65 06 21
Ltd Sun Hung Kai Centre, Fax: +852 28 11 10 29
30 Harbour Road, Wanchai

Hungary b Schneider Electric Hungária Fehérvári út 108 – 112 Tel.: +36 1 382 26-06 www.schneider-electric.hu
Villamossági Rt. H-1116 Budapest Fax: +36 1 206 1429

Iceland Contacts are assured by Schneider Electric Denmark

India b Schneider Electric India Max House, 1 Dr Jha Marg, Okhla Tel. : +91 11 631 85 84 www.schneiderelectric-in.com
110 020 New Dehli Tel. : +91 11 631 71 61

Indonesia b P.T. Schneider Indonesia Ventura Building 7th Floor Tel.: +62 +21 750 44 06 www.schneider-electric.co.id
Jalan R.A. Kartini Kav.26 Fax: +62 +21 750 44 15/ 16
Cilandak - 12430 Jakarta

Iran (Islamic Republic of) b Telemecanique Iran 1047 Avenue VALI ASSR Tel.: +98 218 71 01 42
P.O. Box 15875-3547 Fax: +98 218 71 81 87
15116 Teheran

Irak b Schneider Electric Industries SA 38050 Grenoble Cedex 9 Tel.: +33 04 76 60 54 27


Fax: +33 04 76 60 56 60

Ireland b Schneider Electric Ireland Maynooth Road Tel.: +353+0 1 6012200 www.schneiderelectric.ie
Cellbridge - Co. Kildare Fax: +353+0 1 6012201

Italy b Schneider Electric S.p.A. Centro Direzionale Colleoni Tel.: +39 39 655 8111 www.schneiderelectric.it
Palazzo Sirio - Viale Colleoni, 7 Fax: +39 39 605 6237
20041 Agrate Brianza (Mi)

Ivory Coast b Schneider Electric Afrique de Rue Pierre et Marie Curie Tel.: +225 21 75 00 10
l'Ouest 18 BP 2027 Abidjan 18 Fax: +225 21 75 00 30

Jamaica b Schneider Electric Shop#5, Plaza Dunrobin Tel. : +1876 755 41 27


30 Dunrobin Avenue - Kingstown Tel. : +931 87 74

Japan b Schneider Electric Japan Ltd Torigoe F. Bldg Tel.: +81 358 35 35 81 www.schneider-electric.co.jp
1-8-2, Torigoe Fax: +81 358 35 35 85
Taito-Ku - 111-0054 Tokyo

Jordan b Schneider Electric Industr. Jordan Jordan University Street Tel.: 962 65 16 78 87
Abu Al Haj Commercial Complex Fax: 962 65 16 79 1
2nd Floor - Office # 202 - Amman

Kazakstan b Schneider Electric Kazakhstan Prospekt Abaia 157 off 9 Tel. : +7 327 250 93 88
Liaison Office 480009 Almaty Tel. : +7 327 250 63 70

Kenya b Schneider East Africa Power Technics Complex Tel. : +254 2.824.156
Monbasa Road - PO Box 46345 Fax : +254 2.824.157
Nairobi

Kiribati Contacts are assured by Schneider Electric Australia

Korea b Schneider Electric Korea Ltd 3Floor, Cheil Bldg., 94-46, 7-Ka Tel. : +82 2 2630 9700 www.csinfo.co.kr/schneider/
Youngdeungpodong, Fax : +82 2 2630 9800
Youngdeungpo-ku
150-037 Seoul

Kurdistan Contacts are assured by Schneider Electric Russian Fed.

Kuwait b Schneider Electric Kuwait Al Gaas Tower - Sharq 2nd Floor Tel.: +965 240 75 46
PO Box 20092 - 13 061 Safat Fax: +965 240 75 06

Kyrgyz Republic Contacts are assured by Schneider Electric Russian Fed.

Laos Contacts are assured by Schneider Electric Thailand

Latvia b Lexel Electric 60A A.Deglava str. Tel. : +371 780 23 74/75
LV1035 Riga Fax : +371 754 62 80

Lebanon b Schneider Electric Liban Tabaris, Avenue Charles Malek Tel. : +961 1 20 46 20
Immeuble Ashada, 8 Tel. : +961 1 20 31 19
P.O. Box 166223 - Beyrouth

Lesotho Contacts are assured by Schneider Electric South Africa

Liberia Contacts are assured by Schneider Electric Ghana

Libya Contacts are assured by Schneider Electric Tunisia

Liechtenstein Contacts are assured by Schneider Electric Switzerland

Lithuania b Lexel Electric 44, Verkiu str. Tel. : +370 278 59 59/61
LT-2012 Vilnius Fax : +370 278 59 60

Loro Sae Contacts are assured by Schneider Electric Australia

Luxembourg b Schneider Electric Industrie SAS Agence de Metz Tel.: 33 03 87 39 06 03 www.schneider-electric.fr


1, Rue Graham Bell - BP n° 35190 Fax: 33 03 87 74 25 96
57075 Metz cedex 3 - France

32
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Macau Contacts are assured by Schneider Electric China

Macedonia Contacts are assured by Schneider Electric Bulgaria

Madagascar Contacts are assured by Schneider Electric la Reunion

Malawi Contacts are assured by Schneider Electric South Africa

Malaysia b Schneider Electric (Malaysia) Sdn No.11 Jalan U1/19, Seksyen U1 Tel. : (603) 7883 6333 www.schneider-
Bhd Hicom-Glenmarie Industrial Park Fax : (603) 7883 6188 electric.com.my
40150 Shah Alam
Selangor Darul Ehsan

Maldives Contacts are assured by Schneider Electric Reunion

Mali Contacts are assured by Schneider Electric Senegal

Malta Contacts are assured by Schneider Electric Tunisia

Marshall islands Contacts are assured by Schneider Electric Australia

Martinique b Schneider Electric Schneider Electric Tel.: +05 96 51 06 00


Immeuble Cottrell - ZI de la Lézarde Fax: +05 96 51 11 26
97232 Le Lamentin

Mauritania Contacts are assured by Schneider Electric Senegal

Mauritius b Schneider Electric Route côtière Tel.: 230 282 18 83


Calodyne - Mauritius Fax: 230 282 18 84

Mayotte Contacts are assured by Schneider Electric Reunion

Mexico b Groupe Schneider Mexico Calz. Rojo Gomez N° 1121-A Tel.: +525 686 30 00 www.schneider-
Col. Guadalupe del Moral Fax: +525 686 24 09 electric.com.mx
México, D.F. - C.P. 09300

Micronesia Contacts are assured by Schneider Electric Australia

Moldova Contacts are assured by Schneider Electric Romania

Monaco Contacts are assured by Schneider Electric France

Mongolia Contacts are assured by Schneider Electric Russian Fed.

Montserrat Contacts are assured by Schneider Electric Dominican Rep.

Morocco b Schneider Electric Morocco 26, rue Ibnou Khalikane Tel.: +212 299 08 48 to 57 www.schneider.co.ma
Quartier Palmiers Fax: +212 299 08 67 and 69
20100 Casablanca

Mozambique Contacts are assured by Schneider Electric South Africa

Myanmar Contacts are assured by Schneider Electric Singapore

Namibia Contacts are assured by Schneider Electric South Africa

Nauru Contacts are assured by Schneider Electric Australia

Nepal Contacts are assured by Schneider Electric India

Netherlands b Schneider Electric BV Waarderweg 40 - Postbus 836 Tel.: +31 23 512 4124 www.schneider-electric.nl
2003 RV Haarlem Fax: +31 23 512 4100

Netherlands Antilles Contacts are assured by Schneider Electric Dominican Rep.

New Caledonia Contacts are assured by Schneider Electric Australia

New Zealand b Schneider Electric (NZ) Ltd 14 Charann Place Avondale Tel. : +64 9 829 04 90 www.schneider-electric.co.nz
P.O. Box 15355 - New Lynn Fax : +64 9 829 04 91
Auckland

Nicaragua Contacts are assured by Schneider Electric United States

Niger Contacts are assured by Schneider Electric Ivory Coast

Nigeria b Schneider Electric Nigeria Limited Biro plaza - 8th Floor - Plot 634 Tel. : +234 1 2702973
Abeyemo Alakija Street Fax : +234 1 2702976
Victoria Islan - Lagos

Niue Contacts are assured by Schneider Electric Australia

Norfolk island Contacts are assured by Schneider Electric Australia

North Korea Contacts are assured by Schneider Electric China

Northern Mariana islands Contacts are assured by Schneider Electric Australia

Norway b Schneider Electric Norge A/S Solgaard Skog 2 Tel.: +47 6924 9700 www.schneider-electric.no
Postboks 128 - 1501 Moss Fax: +47 6925 7871

Oman b Schneider Electric CA c/o Arab Development Co Tel.: +968 77 163 64


PO Box 439 - 113 Muscat Fax: +968 77 104 49

Pakistan b Schneider Electric Pakistan 43-L, 2nd floor, M.M. Alam Road, Tel.: +92 42 5754471 à 73
Gulberg II - Lahore Fax: +92 42 5754474

Palau Contacts are assured by Schneider Electric Australia

Panama Contacts are assured by Schneider Electric United States

Papua New Guinea Contacts are assured by Schneider Electric Australia

Paraguay Contacts are assured by Schneider Electric Uruguay

33
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Peru b Schneider Electric Peru S.A. Los Telares n°231 Urb. Vulcano, Ate Tel.: +511 348 44 11 www.schneider-electric.com.pe
Lima 03 Fax: +511 348 05 23

Philippines b Schneider Electric Philippines, Inc 5th Floor, ALCO Building Tel. : +632 896 6063
391 Sen, Gil Puyat Avenue Fax : +632 896 7229
Makati 1209

Pitcairn Contacts are assured by Schneider Electric Australia

Poland b Schneider Electric Polska Sp.zo.o. ul. Lubinowa 4a Tel.: +48 22 511 8 200 www.schneider-electric.pl
03-878 - Warszawa Fax: +48 22 511 8 210

Portugal b Schneider Electric Portugal Av.do Forte, 3 Tel.: +351 21 416 5800 www.schneiderelectric.pt
Edificio Suécia II, Piso 3-A Fax: +351 21 416 5857
CP 2028 Carnaxide
2795 Linda-A-Velha

Puerto Rico Contacts are assured by Schneider Electric United States

Qatar b Schneider Electric Qatar Branch c/o Khalifa BinFahred Al Thani Tel.: +97 4424358
Trad.and Co - P.O. Box 4484 Fax: +97 4424358
Doha

Reunion b Schneider Electric Immeuble Futura, Tel.: +262 28 14 28


190, rue des 2 canons Fax: +262 28 39 37
BP 646 - 97497 Sainte Clothilde

Romania b Schneider Electric Bd Ficusului n°42 Tel.: +401 203 06 50 www.schneider-electric.ro


Apimondia, Corp.A, et.1, Sector 1 Fax: +401 232 15 98
Bucuresti

Russian Federation b Schneider Electric ZAO Enisseyskaya 37 Tel.: +7095 797 40 00 www.schneider-electric.ru
129 281 Moscow Fax: +7095 797 40 03

Rwanda Contacts are assured by Schneider Electric Kenya

Samoa Contacts are assured by Schneider Electric Australia

San Marino Contacts are assured by Schneider Electric Italy

Sandwich & Georgia island Contacts are assured by Schneider Electric Australia

Sao Tome & Principe Contacts are assured by Schneider Electric Senegal

Saudi Arabia b Schneider Electric Second Industrial City Tel.: +966 1 265 1515
P.O. Box 89249 - 11682 Riyadh Fax: +966 1 265 1860

Senegal b Schneider Electric Sénégal BP 15952 - Dakar-Fann Tel.: +221 820 68 05


Rond point N'Gor - Dakar Fax: +221 820 58 50

Seychelles Contacts are assured by Schneider Electric Reunion

Sierra Leone Contacts are assured by Schneider Electric Ghana

Singapore b Schneider Electric Singapore Pte 10 Ang Mo Kio Street 65 Tel.: +65 484 78 77 www.schneider-electric.com.sg
Ltd #02-17/20 TechPoint Fax: +65 484 78 00
Singapore 569059

Slovak Republic b Schneider Electric Slovakia spol Borekova 10 Tel. : +02 45 52 40 10 and 40 30 www.schneider-electric.sk
s.r.o. SK-821 06 Bratislava Fax : +02 45 52 40 00

Slovenia b Schneider Electric, d.o.o. Dunasjka 47 Tel. : +386 1 23 63 555 www.schneider-electric.si


1000 Ljubljana Fax : +386 1 23 63 559

Solomon islands Contacts are assured by Schneider Electric Australia

Somalia Contacts are assured by Schneider Electric Egypt

South Africa b Schneider Electric South Africa Private Bag X139 Tel.: +27 11 254 6400 www.schneider-electric.co.za
(PTY) Ltd Halfway House Fax: +27 11 315 8830
1685 - Midrand.

Spain b Schneider Electric España, S.A. Pl. Dr. Letamendi, 5-7 Tel.: +34 93 484 3100 www.schneiderelectric.es
08007 Barcelona Fax: +34 93 484 3308

Sri Lanka b Schneider Electric Industries SA Liaison office SRI Lanka Tel. : +94 77 48 54 89 www.schneiderelectric-in.com
Level 3B Valiant towers
46/7 Nawam Mawatha-Colombo 2

St Helena Contacts are assured by Schneider Electric Italy

St Kitts & Nevis Contacts are assured by Schneider Electric Dominican Rep.

St Lucia Contacts are assured by Schneider Electric Dominican Rep.

St Pierre et Miquelon Contacts are assured by Schneider Electric Dominican Rep.

St Vincent & Grenadines Contacts are assured by Schneider Electric Dominican Rep.

Sudan Contacts are assured by Schneider Electric Egypt

Suriname Contacts are assured by Schneider Electric United States

Svalbard & Jan Mayen isl. Contacts are assured by Schneider Electric Denmark

Swaziland Contacts are assured by Schneider Electric South Africa

Sweden b Schneider Electric AB Djupdalsvägen 17/19 Tel.: +46 8 623 84 00 www.schneider-electric.se


19129 Sollentuna Fax: +46 8 623 84 85

Switzerland b Schneider Electric (Switzerland) Schermenwaldstrasse 11 Tel.: +41 31 917 3333 www.schneider-electric.ch
S.A. CH - 3063 Ittigen Fax: +41 31 917 3355

34
Schneider Electric worldwide 0

Up-dated: 28-07-2003
Syrian Arab Republic b Schneider Electric Syria Elba Street - Malki Tel. : +963 11 37 49 88 00
Gheibeh and Qassas bldg, 1st floor Fax : +963 11 37 17 55 9
PO Box 33876-Damascus

Taiwan, Republic of China b Schneider Electric Taiwan Co Ltd 2FI., N°37, Ji-Hu Road, Nei-Hu Dist., Tel. : +886 2 8751 6388 www.schneider-electric.com.tw
Taipei 114 Fax : +886 2 8751 6389

Tajikistan Contacts are assured by Schneider Electric Russian Fed.

Tanzania, United Rep. of Contacts are assured by Schneider Electric Kenya

Thailand b Schneider (Thailand) Ltd 20th Floor Richmond Building Tel.: +662 204 9888 www.schneider-electric.co.th
75 Sukhumvit 26 Road, Klongtoey Fax: +662 204 9816
Bangkok 10110

Togo Contacts are assured by Schneider Electric Ivory Coast

Tokelau Contacts are assured by Schneider Electric Australia

Tonga Contacts are assured by Schneider Electric Australia

Trinidad & Tobago b Schneider Electric 6, 1st Street West Ext. Tel.: 1868 640 42 04
Beaulieu Avenue Fax: 1868 640 42 04
Trincity Trinidad West Indies

Tunisia b Schneider Electric Tunisia Rue du Lac Oubeira Tel.: +216 71 960 477
1053 Les Berges du Lac - Tunis Fax: +216 71 960 342

Turkey b Schneider Elektrik Sanayi Ve Tütüncü Mehmet Efendi Cad. N°:110 Tel.: +90 21 63 86 95 70 www.schneiderelectric.com.tr
Ticaret A.S. Kat 1-2 - 81080 Göztepe – Istanbul Fax: +90 21 63 86 38 75

Turkmenistan b Schneider Electric Turkmenistan rue Neitralny Turkmenistan 28, Tel. : +993 12 46 29 52
Liaison Office off.326/327 Fax : +993 12 46 29 52
74 000 Achgabad

Turks & Caicos islands Contacts are assured by Schneider Electric Dominican Rep.

Tuvalu Contacts are assured by Schneider Electric Australia

Uganda Contacts are assured by Schneider Electric Kenya

Ukraine b Schneider Electric Rue Krechtchalik 2 Tel.: +380 44 462 04 25 www.schneider-electric.com.ua


252601 Kiev Fax: +380 44 462 04 24

United Arab Emirates b Schneider Electric Abu Dhabi PO Box 29580 Tel.: +9712 6 339444
Office Floor 2/Lulu Street Fax: +9712 6 316606
Al Marina Plaza Tower
Abu Dhabi

United Kingdom b Schneider Electric Ltd Braywick House East Tel.: +44 (0)1 628 508 500 www.schneider.co.uk
Windsor Road - Maidenhead Fax: +44 (0)1 628 508 508
Berkshire SL6 1 DN

United States b Schneider Electric North American Division Tel.: +1 847 397 2600 www.squared.com
1415 Roselle Road Fax: +1 847 925 7500
Palatine - IL 60067

Uruguay b Schneider Electric Uruguay S.A. Ramon Masini 3190 Tel. : +59 82 707 2392
Montevideo Fax : +59 82 707 2184

Uzbekistan Contacts are assured by Schneider Electric Russian Fed.

Vanuatu Contacts are assured by Schneider Electric Australia

Vatican city St./Holy See Contacts are assured by Schneider Electric Italy

Venezuela b Schneider Mg SD TE, S.A Calle 162/ Piso 2 Tel.: +58 2 241 13 44 www.schneider-electric.com.ve
Edificio Centro Cynamid Fax: +58 2 243 60 09
La Urbina, 1070 - 75319 Caracas

Viet Nam b R.R.O. of Schneider Electric Unit 2.9, 2nd Floor, e-Town Building Tel.: +84 8 8103 103
Industries S.A.S. in Viet Nam 364 Cong Hoa Street Fax: +84 8 8120 477
Tan Binh District - Ho Chi Minh City

Virgin islands Contacts are assured by Schneider Electric Dominican Rep.

Wallis & Futuna islands Contacts are assured by Schneider Electric Australia

Western Sahara Contacts are assured by Schneider Electric Morocco

Yemen Contacts are assured by Schneider Electric U.A.E.

Yugoslavia b Schneider Electric Jugoslavija Ratarski put 27d Tel.: +381 11 192 414
d.o.o. 11186 Belgrade Fax: +381 11 107 125

Zambia b Schneider Zambia Zambia Office Tel.: +260 222 22 52


c/o Matipi Craft Center Building Fax: +260 222 83 89
Plot 1036 - Accra Road
PO Box 22792 - Kitwe

Zimbabwe b Schneider Electric Zimbabwe Liaison Office Tel.: +263 4 707 179/180
75A Second Street Fax: +263 4 707 176
(corner Livingstone Avenue)
Harare

35
DIA3ED2031108EN

Schneider Electric Industries SAS

Headquarters
Owing to changes in standards and equipment, the characteristics
89, bd Franklin Roosevelt given in the text and images in this document are not binding until
F - 92506 Rueil Malmaison Cedex they have been confirmed with us.

Production : Schneider Electric Industries


Photos : Schneider Electric Industries
http://www.schneider-electric.com Printed by :

ART. 070261 November 2003

You might also like