Siemens-Sitrans-ProbeLU HartQSG 7ML19985QR81 5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

Quick Start Manual May 2008

sitrans
PROBE LU (HART)
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
• The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments Inc.
• Restrict repair to faulty components only.
• Do not reuse faulty components.

Warning: This product can only function properly and safely if it is correctly transported, stored,
installed, set up, operated, and maintained.

This product is intended for use in industrial areas. Operation of this equipment in a residential area
may cause interference to several frequency based communications.

Note: Always use product in accordance with specifications.

Copyright Siemens Milltronics Process Disclaimer of Liability


Instruments Inc. 2008. All Rights Reserved
This document is available in bound version and in While we have verified the contents of this
electronic version. We encourage users to purchase manual for agreement with the
authorized bound manuals, or to view electronic versions instrumentation described, variations
as designed and authored by Siemens Milltronics Process remain possible. Thus we cannot
Instruments Inc. Siemens Milltronics Process Instruments guarantee full agreement. The contents of
Inc. will not be responsible for the contents of partial or this manual are regularly reviewed and
whole reproductions of either bound or electronic corrections are included in subsequent
versions. editions. We welcome all suggestions for
improvement.

Technical data subject to change.

MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.

Contact SMPI Technical Publications European Authorized Representative


at the following address:
Technical Publications Siemens AG
Siemens Milltronics Process Instruments Inc. Industry Sector
1954 Technology Drive, P.O. Box 4225 76181 Karlsruhe
Peterborough, Ontario, Canada, K9J 7B1 Deutschland
Email: [email protected]

• For a selection of Siemens Milltronics level measurement manuals, go to:


www. siemens.com/processautomation. Under Process Instrumentation, select Level
Measurement and then go to the manual archive listed under the product family.
• For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select Continuous
Weighing Systems and then go to the manual archive listed under the product family.

© Siemens Milltronics Process Instruments Inc. 2008


SITRANS Probe LU Quick Start Manual
This manual outlines the essential features and functions of SITRANS Probe LU. We strongly

English
advise you to acquire the detailed version of the manual so you can use your instrument to its

mmmmm
fullest potential. The complete manual is available on our website at:
https://pia.khe.siemens.com/index.asp?Nr=11157. The printed manual is available from your
local Siemens representative.
Questions about the contents of this manual can be directed to:
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: [email protected]
Copyright Siemens Milltronics
Process Instruments Inc. 2008. Disclaimer of Liability
All Rights Reserved
We encourage users to purchase While we have verified the contents of this manual
authorized bound manuals, or to view for agreement with the instrumentation described,
electronic versions as designed and variations remain possible. Thus we cannot
authored by Siemens Milltronics Process guarantee full agreement. The contents of this
Instruments Inc. Siemens Milltronics manual are regularly reviewed and corrections are
Process Instruments Inc. will not be included in subsequent editions. We welcome all
responsible for the contents of partial or suggestions for improvement.
whole reproductions of either bound or
electronic versions. Technical data subject to change.
MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments Inc.

Safety Guidelines1
Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied by
a clarification of the level of caution to be observed.

WARNING: relates to a caution symbol on the product, and means that failure to
observe the necessary precautions can result in death, serious injury, and/or
considerable material damage.
WARNING1: means that failure to observe the necessary precautions can result
in death, serious injury, and/or considerable material damage.
Note: means important information about the product or that part of the operating manual.

1. This warning symbol is used when there is no corresponding caution symbol on the product.

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-1


SITRANS Probe LU
WARNING: Changes or modifications not expressly approved by Siemens
English
mmmmm

could void the user’s authority to operate the equipment.


Notes:
• SITRANS Probe LU is to be used only in the manner outlined in this manual,
otherwise protection provided by the equipment may be impaired.
• This product is intended for use in industrial areas. Operation of this equipment in a
residential area may cause interference to several frequency based
communications.

SITRANS Probe LU is a loop-powered continuous level monitor, using advanced ultrasonic


techniques. The unit consists of an electronic component coupled to the transducer and
process connection.
The transducer is available in ETFE (ethylene-tetrafluoroethylene) or PVDF (polyvinylidene
fluoride), allowing SITRANS Probe LU to be used in a wide variety of industries and
applications using corrosive chemicals.
The ultrasonic transducer contains a temperature sensing element to compensate for
temperature changes in the application.
Communication is via HART1, and signals are processed using Sonic Intelligence®.

Specifications
For a complete listing, see the SITRANS Probe LU Instruction Manual. For Approvals
information, please refer to the device nameplate.

Ambient/Operating Temperature
Note: Process temperature and pressure capabilities are dependent upon information
on the product nameplate. The reference drawing listed on the nameplate can be
downloaded from the Siemens website. Go to the product page at:
https://pia.khe.siemens.com/index.asp?Nr=11157.

hand programmer
product nameplate
ambient temperature
surrounding enclosure: flange adaptor
–40 to +80 °C (–40 to +176 °F)

customer-
supplied flange

process temperature:
–40 to +85 °C (–40 to +185 °F)

1. HART® is a registered trademark of the HART Communication Foundation.

Page EN-2 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


Power
Nominal 24 V DC at max. 550 Ohm: for other configurations see the full manual.

• Maximum 30 V DC

English
mmmmm
• 4 to 20 mA

Approvals
• General: CSAUS/C, FM, CE
• Hazardous: Intrinsically Safe (Europe) ATEX II 1 G EEx ia IIC T4
(US/Canada) FM/CSA: (barrier required)1
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III T4
(Australia) ANZEx Ex ia IIC T4
(Tamb = –40 to +80 °C) IP67, IP68)
(International) IECEx TSA 04.0020X Ex ia IIC T4
Non-incendive (US) FM: 2
Class I, Div. 2, Groups A, B, C, D T5

• Marine Lloyd’s Register of Shipping


ABS Type Approval

Note: The use of approved watertight conduit hubs/glands is required for Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67, IP68 (outdoor applications).

1.
See FM Intrinsically safe connection drawing on page 1 of Appendix A, for reference drawing
23650516, or CSA Intrinsically Safe connection drawing on page 2 of Appendix A, for reference
drawing 23650517.
2. See FM Class 1, Div. 2 connection drawing on page 3 of Appendix A, for reference drawing 23650583.

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-3


Installation

WARNINGS:
English
mmmmm

• Materials of construction are chosen based on their chemical compatibility (or


inertness) for general purposes. For exposure to specific environments, check with
chemical compatibility charts before installing.
• This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
• The user is responsible for the selection of bolting and gasket materials which will
fall within the limits of the flange and its intended use, and which are suitable for
the service conditions.
Note: Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.

Mounting Location
Recommendations:
• Ambient temperature within –40 to +80 °C (–40 to +176 °F).
• Easy access for viewing the display and programming via the hand programmer.
• An environment suitable to the housing rating and materials of construction.
• Keep the sound path perpendicular to the material surface.
Precautions:
• Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to
variable frequency motor speed controllers.
• Avoid interference to the sound path from obstructions or from the fill path.
Fill

The sound path should be:


pipe
• perpendicular to the
monitored surface
• clear of rough walls, rungs
seams, rungs, or
other obstructions seams
• clear of the fill path
10°

Page EN-4 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


Mounting Instructions
Note: Ideally, mount SITRANS Probe LU so that the face of the transducer is at least
300 mm (1 ft) above the highest anticipated level.

English
mmmmm
SITRANS Probe LU is available in three thread types: 2" NPT, 2" BSP, or PF2/G.
1. Before inserting SITRANS Probe LU into its mounting connection, ensure that the threads
are of the same type to avoid damaging them.
2. Simply screw SITRANS Probe LU into the process connection, and hand tighten.

Wiring
Power1
WARNINGS:
DC terminals shall be supplied from an SELV 1 source in accordance with IEC-
1010-1 Annex H.

All field wiring must have insulation suitable for rated voltages.

Connecting SITRANS Probe LU


Notes: cover screws
• For detailed information on Intrinsically
Safe set-ups, please see the full manual. hinged lid
• Use shielded, twisted pair cable (wire
gauge AWG 22 to AWG 14 /0.34 mm2 to
2.08 mm2).
• Separate cables and conduits may be
required to conform to standard
instrumentation wiring practices, or
electrical codes.
• The non-metallic enclosure does not
provide a continuous ground path threaded water-
connection tight gland
between conduit connections: use
grounding-type bushings and jumpers.

1. Safety Extra Low Voltage

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-5


1. Strip the cable jacket for approximately 70 mm
(2.75") from the end of the cable, and thread the terminals for A
m
loop current
wires through the gland1.
2. Connect the wires to the terminals as shown
English

above: the polarity is identified on the terminal


mmmmm

block.
3. Tighten the gland to form a good seal.
4. Close the cover and tighten screws: please do
cable
not overtighten screws. Recommended torque is
1.1 to 1.7 N-m (10 to 15 in-lb).

RUN Mode and PROGRAM Mode


SITRANS Probe LU has two modes of operation: RUN and PROGRAM.
SITRANS Probe LU automatically starts in RUN mode when power is applied, and detects the
material level. The primary reading displays the material level (in meters) referenced from
Empty (process empty level). This is the default start-up display mode.
System status is displayed on the LCD, or on a remote communications terminal.

RUN Mode Display1


23
Use the hand programmer to control the display.
Normal operation Failsafe operation
2 3 3

1 1
4 4

6 5 5
m 6 m

1 – Primary Reading (displays level, distance, or volume2, in either units or percent).


2 – Secondary Reading (displays Parameter number for Auxiliary Reading3)
3 – Echo status indicator: Reliable Echo or Unreliable Echo
4 – Units or Percent
5 – Active bar graph represents material level
6 – Auxiliary Reading (depending on the parameter selected, it displays milliAmp value,
distance, or echo confidence, with units where applicable.)

1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
2.
For details on displaying flow instead of volume, please see P050 in the full manual.
3.
Press to display the auxiliary reading field when in RUN mode.

Page EN-6 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


If the echo confidence drops below the echo confidence threshold, the failsafe timer starts
running. When the timer expires, the letters LOE (Loss of Echo) alternate with the reading
every two seconds, and the Reliable Echo indicator is replaced by the Unreliable indicator.
When a valid reading is received, the level reading display returns to normal operation.

English
mmmmm
PROGRAM Mode Display
2 3 1– Primary Reading (displays parameter value)
2– Secondary Reading (displays parameter number)
1
3– Programming indicator
4 4– Auxiliary Reading (displays parameter names for P001 to
P010, if a language is selected. It displays the index value
for indexed parameters, such as P054).

Programming
• Set parameters to suit your specific application.
• Activate PROGRAM mode at any time, to change parameter values and set operating
conditions.
• For local programming, use the Siemens hand programmer.
• For programming from a distance, use either a PC running SIMATIC PDM, or a HART
handheld communicator.

Hand programmer
Key Programming Mode
For direct access to SITRANS Probe LU,
point the programmer at the SITRANS Decimal point1
Probe LU display and press the keys.
(For detailed instructions, see the next Negative value
page.)
CLEAR value
hand programmer TOGGLE between Units and % on parameter
value

display End PROGRAM session and enable RUN mode

Update echo quality parameters

max. 600 mm Parameter scroll-up


(2 ft)
Parameter scroll-down

DISPLAY opens parameter fields

ENTER the displayed value

1.
Press plus three-digit parameter number, to set
parameter to show in the auxiliary display.

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-7


Low temperature effects on RUN/PROGRAM modes
If the internal temperature falls to –30 oC (–22 oF) or below, it will affect both RUN and
PROGRAM modes.
English

RUN mode will operate normally, with the following exceptions:


mmmmm

• hand programmer operation is disabled


• the LCD displays only limited information: the bar graph and the reliable/unreliable echo
indicator
PROGRAM mode:
• hand programmer operation is disabled

Security: (P000: Lock)


Value Description
Value stored in P069 * Lock off: programming permitted
other Lock activated: no changes permitted
* Factory setting for P069 is 1954: after a new value is entered and accepted, it becomes the
default setting.

Activating SITRANS Probe LU


Power up the instrument. SITRANS Probe LU starts in RUN mode.

Notes:
• Keep infrared devices such as laptops, cell phones, and PDA’s, away from SITRANS
Probe LU to prevent inadvertent operation.
• The following instructions apply when using the Hand Programmer.
• Do not use the Hand Programmer at the same time as SIMATIC PDM, or erratic operation
may result.
• Press PROGRAM then DISPLAY to access PROGRAM mode, and press
PROGRAM to return to RUN mode.
• You do not need to key in initial zeros when entering a parameter number: for example,
for P005, key in 5.

Page EN-8 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


Accessing a parameter
1. Press PROGRAM then DISPLAY , to activate PROGRAM Icon
PROGRAM mode.

English
mmmmm
Parameter Number
2. Either use the ARROW keys to scroll to a Parameter Value
different parameter, or:
3. Press DISPLAY to open the Parameter Number
field. current value
4. Key in the desired parameter number followed by
ENTER .
5. For example: press then .
6. The LCD displays the new parameter number and
value.

Changing a Parameter Value


Notes:
• Security must be disabled to enable programming: set P000 to the Unlocked Value stored
in P069. (A remote master can still change configuration, if P799 is set to allow this.)
• Invalid entries will be rejected or limited.
• CLEAR can be used to clear the field.
1. Key in the new value.
2. Press ENTER to set the value.
Parameter Reset to Factory Default
1. Scroll to the parameter or enter its address.
2. Press CLEAR then ENTER . The value returns to the default setting.

Master Reset (P999)


Returns all parameters except P000 and P069 to default settings. (The learned TVT curve is not
lost.)
1. Press PROGRAM , then DISPLAY to activate PROGRAM mode.
2. Press DISPLAY to open parameter fields.
3. Key in 999.
4. Press CLEAR then ENTER , to Clear All and initiate
reset. The LCD displays C.ALL.

5. Reset complete. (Reset takes several seconds to complete.)

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-9


Quick Setup: steps 1 to 10
Note: Default values (factory settings) are marked by an asterisk (*) in the tables.
English
mmmmm

1. Select language (P010: Language)


0 * Numeric/None ENGLISH DEUTSCH FRANÇAIS ESPAÑOL
P000 LOCK VERRIEGELG VERROUIL BLOQUEO
1 English
P001 OPERATION BETRIEB FONCTIONMT FUNCIONAM.
Values 2 German P003 MEAS RESP REAKTIONSZ TEMPS REP. TIEMPO R.
3 French P004 ANTENNA ANTENNE ANTENNE ANTENA
P005 UNITS EINHEIT UNITES UNIDADES
4 Spanish
P006 EMPTY MESSBER. VIDE VACIO
P007 SPAN MESSSPANNE PLAGE RANGO
P010 LANGUAGE SPRACHE LANGUE IDIOMA

2. Set P001: Operation (measurement mode)


Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.

Level returns distance to material level referenced from Empty (process empty level). The
1 *
Values reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
2 Space returns distance to material level referenced from Span (process full level).
3 Distance returns distance to material level from reference point (transducer face).

mA Output with Level, Space, and Distance operation


Level Space Distance
(P001 = 1) (P001 = 2) (P001 = 3)
transducer
0%
face (4 mA)
(20 mA) Span (4 mA) Span
Span 100% 0% Distance
Space
P007
P006
Level
Empty Empty
Empty 0% 100% 100%
(4 mA) (20 mA) (20 mA)

Page EN-10 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


3. Set Measurement Response (P003) 4. Select measurement units (P005)
1 * slow 0.1m/minute 1 * meters
Values 2 medium 1m/minute 2 centimeters
3 fast 10m/minute

English
Values 3 millimeters

mmmmm
Set P003 to a measurement response speed 4 feet
just faster than the maximum filling or 5 inches
emptying rate (whichever is greater).

5. Set process empty level (P006: Empty) Level Setup


transducer
Note: face
• P006 and P007 are interlinked: see
notes attached to P007. Span 100%

0.0000 to 6.000 m (20 ft) or


Range P007
Values 0.0000 to 12.000 m (40 ft)
P006
Default Maximum range
Level
Empty can be set to any distance: not necessarily
the bottom of the tank. Empty 0%

6. Set measurement range (P007: Span)1


0.0000 to 6.000 m (20 ft) or
Range Span can be set at any distance above
0.0000 to 12.000 m (40 ft)
Values Empty level
5.725 m (18.78 ft) or
Default
11.725 m (38.47 ft)
.

Notes:
• Setting P006 resets Span, if it has not previously been set to a different value.
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is set to
Empty minus 110% of Blanking distance1, unless Operation is set to distance (P001=3). In
this case, Span is set to Empty distance.
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
transducer face. This provides a 0.05 m (2") safety margin, as 0.25 m (10") is the minimum
distance detectable.

1. Default setting for Blanking is 0.25 m (10").

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-11


7. Minimize false reflections: Set P838 (Auto False Echo Suppression Distance)
Use P838 and P837 Maximum range:
Range
together: follow the 0.000 to 6.000 m (20 ft) or
Value (depends on model)
instructions for P837. 0.000 to 12 m (40 ft)
English
mmmmm

Default 1.000 m (3.28 ft)

8. Enable False Echo Suppression: set P837 (Auto False Echo Suppression)
0 Off
Value 1 * Use "learned" TVT
2 "Learn"

Using P837 and P838 (perform this function at low tank levels)
The TVT (Time Varying Threshold) curve sets a threshold which screens out false echoes1. If
SITRANS Probe LU displays an incorrect full level, or if the reading fluctuates between a false
high level and a correct level, use P838 and P837 together to elevate the TVT (Time Varying
Threshold) in this region and de-sensitize the receiver from any ‘base noise’ caused by internal
transducer reflections, nozzle echoes, or other vessel false echoes2.
. Using P837 and P838 (continued)

Notes:
• Use this function only if there is a minimum distance of 2 meters from SITRANS Probe LU
to the material. This function works best if the vessel is empty or nearly empty.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.

a. Determine the actual distance from the transducer face to the material level.
b. Select P838 and key in [distance to material level – 0.5 m].
c. Select P837, then press 2 (Learn) and ENTER . P837 will automatically revert to 1 (use
Learned TVT) after a few seconds.

9. Return to RUN
Press PROGRAM to return to RUN mode: setup is complete.

1. False echoes can be caused by obstructions in the beam path.


2. For more details on Auto False Echo Suppression, please see the full manual.

Page EN-12 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


SITRANS Probe LU Communications: HART
Note: See mA Output with Level, Space, and Distance operation on page 10 for an
illustration of the mA output with different modes of operation.

English
mmmmm
• You will need the full manual to acquire the list of applicable parameters.
• Please contact your local representative concerning the availability of the HART DD for
SITRANS Probe LU.
• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
instrument.

Maintenance
SITRANS Probe LU requires no maintenance or cleaning.

Unit Repair and Excluded Liability


For detailed information, please see the inside back cover.

Instructions specific to hazardous area installations


(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to the SITRANS Probe LU covered by certificate number SIRA
03ATEX2142X:
1. For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G equipment.
3. The equipment may be used with flammable gases and vapors with apparatus groups IIA,
IIB, and IIC, and temperature classes T1, T2, T3, and T4.
4. The equipment is certified for use in an ambient temperature range of –40 °C to +80 °C.
5. The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6. Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
7. Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
8. Components to be incorporated into or used as replacements in the equipment shall be
fitted by suitably trained personnel in accordance with the manufacturer’s
documentation.
(continued on next page)

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-13


9. It is the responsibility of the user to ensure that manual override is possible in order to
shut down the equipment and protective systems incorporated within automatic
processes which deviate from the intended operating conditions, provided that this does
not compromise safety.
English

10. The ‘X’ suffix to the certificate number relates to the following special conditions for safe
mmmmm

use:
Parts of the enclosure may be non-conducting and may generate an ignition-
capable level of electrostatic charge under certain extreme conditions. The
user should ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high-pressure steam) which
might cause a build-up of electrostatic charge on non-conducting surfaces.
11. If the equipment is likely to come into contact with aggressive substances, then it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
Aggressive substances:e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is
resistant to specific chemicals.
12. Equipment Marking:
The equipment marking contains at least the information on the product nameplate,
shown on the inside front cover of this manual.

Page EN-14 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


HAZARDOUS AREA NON-HAZARDOUS AREA

7ML19985QR81
SAFE AREA APPARATUS
Load
4 – 20 mA

NOTES:
INTRINSICALLY SAFE
1. ANY CSA / FM INTRINSICALLY SAFE BARRIER / POWER SUPPLY, WITH ITS OUTPUT (SEE NOTE 1)
VOLTAGE (Uo) NOT EXCEEDING 30 V AND ITS OUTPUT CURRENT (Io) LIMITED BY
LOAD RESISTANCE (Ro); SUCH THAT Io = Uo / Ro, DOES NOT EXCEED 120 mA

2. APPROVED DUST-TIGHT AND WATER-TIGHT CONDUIT SEALS ARE REQUIRED


FOR CLASS II, DIV.1, Gr. E, F, G AND OUTDOOR NEMA 4X/TYPE 4X LOCATIONS

3. THE MAXIMUM VOLTAGE OF THE NON-INTRINSICALLY SAFE APPARATUS


MUST NOT EXCEED 250 V rms.

4. UNDER THE ENTITY EVALUATION CONCEPT, THE SITRANS Probe LU HAS THE
FOLLOWING:
Ui = 30 VOLTS D.C. Ii = 120 mA Pi = 0.8W
Ci = 3.6 nF Li = 0

5. SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.

6. INSTALL PER NEC / CEC


at: https://pia.khe.siemens.com/index.asp?Nr=11157.

7. USE SUPPLY WIRES RATED FOR 10 ° ABOVE.

8. EXTERNAL BONDING HUBS ARE REQUIRED WHEN BOTH CONDUIT ENTRIES ARE USED.

THE ENTITY EVALUATION CONCEPT IS A METHOD USED TO DETERMINE


ACCEPTABLE COMBINATIONS OF INTRINSICALLY SAFE APPARATUS AND
DEC
CONNECTED ASSOCIATED APPARATUS THAT HAVE NOT BEEN 0 FOR APPROVAL RPC SN 17/03
INVESTIGATED IN SUCH COMBINATION.
Product Group
FM Intrinsically safe connection drawing

SITRANS Probe LU (HART) – QUICK START MANUAL


ULTRASONICS
ENTITY CONCEPT DEFINITION: THE ENTITY CONCEPT ALLOWS THE INTERCONNECTIONS OF INTRINSICALLY NTS B
SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATIONS. 17 / DEC / 03
R. CLYSDALE
Appendix A: Connection Drawings

THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE AND CURRENT WITH INTRINSICALLY SAFE
S. MILLIGAN
SITRANS Probe LU,
APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL OR
GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) LEVELS WHICH CAN BE DELIVERED BY S. NGUYEN
INTRINSICALLY SAFE
THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION, THE MAX. PETERBOROUGH CONNECTION DIAGRAM
FOR INTERNAL
UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF THE INTRINSICALLY SAFE APPARATUS, INCL.
INTERCONNECTING WIRING, MUST BE EQUAL OR LESS THAN THE CAPACITANCE AND INDUCTANCE WHICH
USE ONLY 23650516 0
CAN BE SAFELY CONNECTED TO THE ASSOCIATED APPARATUS.
2365051600 1:1 1 1
Note: Reference drawing 23650516 is available from the product page of our website

Page A-1
A: Connection Drawings
mmmmm
mmmmm

A: Connection Drawings

Page A-2
HAZARDOUS LOCATION NON-HAZARDOUS LOCATION

V OC £ V max
I SC £ I max SAFE AREA
APPARATUS
C a ³ C i + C cable
Load
4-20 mA L a ³ Li + L cable

INTRINSICALLY SAFE BARRIER


(SEE NOTES 1 & 2)
Substitution of components
may impair intrinsic safety.

NOTES:
at: https://pia.khe.siemens.com/index.asp?Nr=11157.

1. ANY CSA CERTIFIED INTRINSICALLY SAFE BARRIER OR ASSOCIATED


APPARATUS WITH A LINEAR OUTPUT.

2. UNDER THE ENTITY EVALUATION CONCEPT, THE SITRANS Probe LU


HAS THE FOLLOWING INPUT PARAMETERS :

Vmax = 30 VOLTS I max = 120 mA Ci = 3.6 nF Li = 0.5 mH

SITRANS Probe LU (HART) – QUICK START MANUAL


FEB
1 CHANGE Li VALUE TO 0.5 mH PER ECN 2004-0046 RPC SN 26/2004
DEC
Pmax = 0.8 W OR (Vmax x I max) / 4 = 0.8 W 0 FOR APPROVAL RPC SN 17/03

3. APPROVED DUST-TIGHT AND WATER-TIGHT CONDUIT SEALS ARE REQUIRED Product Group
ULTRASONICS
FOR CLASS II, DIV.1, GROUP G AND OUTDOOR TYPE 4X LOCATIONS NTS B
17 / DEC / 03
R. CLYSDALE
SITRANS Probe LU,
CSA Intrinsically Safe connection drawing

3. THE MAXIMUM VOLTAGE OF THE SAFE LOCATION APPARATUS S. MILLIGAN


MUST NOT EXCEED 250 V rms. CSA INTRINSICALLY SAFE
S. NGUYEN
PETERBOROUGH CONNECTION DRAWING
FOR INTERNAL
4. INSTALLATION TO BE IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE PART 1.
.
USE ONLY 23650517 1
2365051701 1:1 1 1
Note: Reference drawing 23650517 is available from the product page of our website

7ML19985QR81
FM Class 1, Div. 2 connection drawing

A: Connection Drawings
Note: Reference drawing 23650583 is available from the product page of our website
at: https://pia.khe.siemens.com/index.asp?Nr=11157.

mmmmm
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION
(SAFE) CLASS I, DIV.2, GROUPS A, B, C, D

METAL CONDUIT

1/2 “ NPT

24 V
POWER
SUPPLY
SITRANS Probe LU

NOTES:
1) INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE.

2) USE APPROVED WATER TIGHT CONDUIT FITTINGS FOR OUTDOOR APPLICATIONS.

3) FOR FURTHER INFORMATION REFER TO THE


SITRANS Probe LU INSTRUCTION MANUAL

1
SEPT
0 FOR CONSTRUCTION RPC SN 29/2004

Product Group
ULTRASONICS
29 / SEPT / 2004
NTS A
R. CLYSDALE
S. MILLIGAN
SITRANS Probe LU
CLASS I, Div. 2
S. NGUYEN
CONNECTION DRAWING
PETERBOROUGH
FOR INTERNAL
USE ONLY 23650583 0
2365058300 1:1 1 1

7ML19985QR81 SITRANS Probe LU (HART) – QUICK START MANUAL Page A-3


A: Connection Drawings Loop Voltage versus Loop Resistance

Power Supply Requirements


mmmmm

1000

900 (30.0v,845 ohms)

800
L

RL=44.6*VL - 493.4
Loop Resistance - R

700

600

500

400
(17.8v, 300 ohms)
300
RL=272.7*VL - 4554.1 ALLOWABLE OPERATING
200 AREA
100
(16.7v, 0 ohms)
0
10.00 15.00 20.00 25.00 30.00

Loop Voltage-VL
(Source voltage)

Page A-4 SITRANS Probe LU (HART) – QUICK START MANUAL 7ML19985QR81


www.siemens.com/processautomation

Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. 2008
1954Technology Drive, P.O. Box 4225 Subject to change without prior notice
Peterborough, ON, Canada K9J 7B1
Tel: (705) 745-2431 Fax: (705) 741-0466 Rev. 1.5
Email: [email protected]
*7ML19985QR81*
Printed in Canada