Siemens-Sitrans-ProbeLU HartQSG 7ML19985QR81 5
Siemens-Sitrans-ProbeLU HartQSG 7ML19985QR81 5
Siemens-Sitrans-ProbeLU HartQSG 7ML19985QR81 5
sitrans
PROBE LU (HART)
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
• The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments Inc.
• Restrict repair to faulty components only.
• Do not reuse faulty components.
Warning: This product can only function properly and safely if it is correctly transported, stored,
installed, set up, operated, and maintained.
This product is intended for use in industrial areas. Operation of this equipment in a residential area
may cause interference to several frequency based communications.
English
advise you to acquire the detailed version of the manual so you can use your instrument to its
mmmmm
fullest potential. The complete manual is available on our website at:
https://pia.khe.siemens.com/index.asp?Nr=11157. The printed manual is available from your
local Siemens representative.
Questions about the contents of this manual can be directed to:
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: [email protected]
Copyright Siemens Milltronics
Process Instruments Inc. 2008. Disclaimer of Liability
All Rights Reserved
We encourage users to purchase While we have verified the contents of this manual
authorized bound manuals, or to view for agreement with the instrumentation described,
electronic versions as designed and variations remain possible. Thus we cannot
authored by Siemens Milltronics Process guarantee full agreement. The contents of this
Instruments Inc. Siemens Milltronics manual are regularly reviewed and corrections are
Process Instruments Inc. will not be included in subsequent editions. We welcome all
responsible for the contents of partial or suggestions for improvement.
whole reproductions of either bound or
electronic versions. Technical data subject to change.
MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments Inc.
Safety Guidelines1
Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied by
a clarification of the level of caution to be observed.
WARNING: relates to a caution symbol on the product, and means that failure to
observe the necessary precautions can result in death, serious injury, and/or
considerable material damage.
WARNING1: means that failure to observe the necessary precautions can result
in death, serious injury, and/or considerable material damage.
Note: means important information about the product or that part of the operating manual.
1. This warning symbol is used when there is no corresponding caution symbol on the product.
Specifications
For a complete listing, see the SITRANS Probe LU Instruction Manual. For Approvals
information, please refer to the device nameplate.
Ambient/Operating Temperature
Note: Process temperature and pressure capabilities are dependent upon information
on the product nameplate. The reference drawing listed on the nameplate can be
downloaded from the Siemens website. Go to the product page at:
https://pia.khe.siemens.com/index.asp?Nr=11157.
hand programmer
product nameplate
ambient temperature
surrounding enclosure: flange adaptor
–40 to +80 °C (–40 to +176 °F)
customer-
supplied flange
process temperature:
–40 to +85 °C (–40 to +185 °F)
• Maximum 30 V DC
English
mmmmm
• 4 to 20 mA
Approvals
• General: CSAUS/C, FM, CE
• Hazardous: Intrinsically Safe (Europe) ATEX II 1 G EEx ia IIC T4
(US/Canada) FM/CSA: (barrier required)1
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III T4
(Australia) ANZEx Ex ia IIC T4
(Tamb = –40 to +80 °C) IP67, IP68)
(International) IECEx TSA 04.0020X Ex ia IIC T4
Non-incendive (US) FM: 2
Class I, Div. 2, Groups A, B, C, D T5
Note: The use of approved watertight conduit hubs/glands is required for Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67, IP68 (outdoor applications).
1.
See FM Intrinsically safe connection drawing on page 1 of Appendix A, for reference drawing
23650516, or CSA Intrinsically Safe connection drawing on page 2 of Appendix A, for reference
drawing 23650517.
2. See FM Class 1, Div. 2 connection drawing on page 3 of Appendix A, for reference drawing 23650583.
WARNINGS:
English
mmmmm
Mounting Location
Recommendations:
• Ambient temperature within –40 to +80 °C (–40 to +176 °F).
• Easy access for viewing the display and programming via the hand programmer.
• An environment suitable to the housing rating and materials of construction.
• Keep the sound path perpendicular to the material surface.
Precautions:
• Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to
variable frequency motor speed controllers.
• Avoid interference to the sound path from obstructions or from the fill path.
Fill
English
mmmmm
SITRANS Probe LU is available in three thread types: 2" NPT, 2" BSP, or PF2/G.
1. Before inserting SITRANS Probe LU into its mounting connection, ensure that the threads
are of the same type to avoid damaging them.
2. Simply screw SITRANS Probe LU into the process connection, and hand tighten.
Wiring
Power1
WARNINGS:
DC terminals shall be supplied from an SELV 1 source in accordance with IEC-
1010-1 Annex H.
All field wiring must have insulation suitable for rated voltages.
block.
3. Tighten the gland to form a good seal.
4. Close the cover and tighten screws: please do
cable
not overtighten screws. Recommended torque is
1.1 to 1.7 N-m (10 to 15 in-lb).
1 1
4 4
6 5 5
m 6 m
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
2.
For details on displaying flow instead of volume, please see P050 in the full manual.
3.
Press to display the auxiliary reading field when in RUN mode.
English
mmmmm
PROGRAM Mode Display
2 3 1– Primary Reading (displays parameter value)
2– Secondary Reading (displays parameter number)
1
3– Programming indicator
4 4– Auxiliary Reading (displays parameter names for P001 to
P010, if a language is selected. It displays the index value
for indexed parameters, such as P054).
Programming
• Set parameters to suit your specific application.
• Activate PROGRAM mode at any time, to change parameter values and set operating
conditions.
• For local programming, use the Siemens hand programmer.
• For programming from a distance, use either a PC running SIMATIC PDM, or a HART
handheld communicator.
Hand programmer
Key Programming Mode
For direct access to SITRANS Probe LU,
point the programmer at the SITRANS Decimal point1
Probe LU display and press the keys.
(For detailed instructions, see the next Negative value
page.)
CLEAR value
hand programmer TOGGLE between Units and % on parameter
value
1.
Press plus three-digit parameter number, to set
parameter to show in the auxiliary display.
Notes:
• Keep infrared devices such as laptops, cell phones, and PDA’s, away from SITRANS
Probe LU to prevent inadvertent operation.
• The following instructions apply when using the Hand Programmer.
• Do not use the Hand Programmer at the same time as SIMATIC PDM, or erratic operation
may result.
• Press PROGRAM then DISPLAY to access PROGRAM mode, and press
PROGRAM to return to RUN mode.
• You do not need to key in initial zeros when entering a parameter number: for example,
for P005, key in 5.
English
mmmmm
Parameter Number
2. Either use the ARROW keys to scroll to a Parameter Value
different parameter, or:
3. Press DISPLAY to open the Parameter Number
field. current value
4. Key in the desired parameter number followed by
ENTER .
5. For example: press then .
6. The LCD displays the new parameter number and
value.
Level returns distance to material level referenced from Empty (process empty level). The
1 *
Values reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
2 Space returns distance to material level referenced from Span (process full level).
3 Distance returns distance to material level from reference point (transducer face).
English
Values 3 millimeters
mmmmm
Set P003 to a measurement response speed 4 feet
just faster than the maximum filling or 5 inches
emptying rate (whichever is greater).
Notes:
• Setting P006 resets Span, if it has not previously been set to a different value.
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is set to
Empty minus 110% of Blanking distance1, unless Operation is set to distance (P001=3). In
this case, Span is set to Empty distance.
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
transducer face. This provides a 0.05 m (2") safety margin, as 0.25 m (10") is the minimum
distance detectable.
8. Enable False Echo Suppression: set P837 (Auto False Echo Suppression)
0 Off
Value 1 * Use "learned" TVT
2 "Learn"
Using P837 and P838 (perform this function at low tank levels)
The TVT (Time Varying Threshold) curve sets a threshold which screens out false echoes1. If
SITRANS Probe LU displays an incorrect full level, or if the reading fluctuates between a false
high level and a correct level, use P838 and P837 together to elevate the TVT (Time Varying
Threshold) in this region and de-sensitize the receiver from any ‘base noise’ caused by internal
transducer reflections, nozzle echoes, or other vessel false echoes2.
. Using P837 and P838 (continued)
Notes:
• Use this function only if there is a minimum distance of 2 meters from SITRANS Probe LU
to the material. This function works best if the vessel is empty or nearly empty.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.
a. Determine the actual distance from the transducer face to the material level.
b. Select P838 and key in [distance to material level – 0.5 m].
c. Select P837, then press 2 (Learn) and ENTER . P837 will automatically revert to 1 (use
Learned TVT) after a few seconds.
9. Return to RUN
Press PROGRAM to return to RUN mode: setup is complete.
English
mmmmm
• You will need the full manual to acquire the list of applicable parameters.
• Please contact your local representative concerning the availability of the HART DD for
SITRANS Probe LU.
• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
instrument.
Maintenance
SITRANS Probe LU requires no maintenance or cleaning.
10. The ‘X’ suffix to the certificate number relates to the following special conditions for safe
mmmmm
use:
Parts of the enclosure may be non-conducting and may generate an ignition-
capable level of electrostatic charge under certain extreme conditions. The
user should ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high-pressure steam) which
might cause a build-up of electrostatic charge on non-conducting surfaces.
11. If the equipment is likely to come into contact with aggressive substances, then it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
Aggressive substances:e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is
resistant to specific chemicals.
12. Equipment Marking:
The equipment marking contains at least the information on the product nameplate,
shown on the inside front cover of this manual.
7ML19985QR81
SAFE AREA APPARATUS
Load
4 – 20 mA
NOTES:
INTRINSICALLY SAFE
1. ANY CSA / FM INTRINSICALLY SAFE BARRIER / POWER SUPPLY, WITH ITS OUTPUT (SEE NOTE 1)
VOLTAGE (Uo) NOT EXCEEDING 30 V AND ITS OUTPUT CURRENT (Io) LIMITED BY
LOAD RESISTANCE (Ro); SUCH THAT Io = Uo / Ro, DOES NOT EXCEED 120 mA
4. UNDER THE ENTITY EVALUATION CONCEPT, THE SITRANS Probe LU HAS THE
FOLLOWING:
Ui = 30 VOLTS D.C. Ii = 120 mA Pi = 0.8W
Ci = 3.6 nF Li = 0
8. EXTERNAL BONDING HUBS ARE REQUIRED WHEN BOTH CONDUIT ENTRIES ARE USED.
THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE AND CURRENT WITH INTRINSICALLY SAFE
S. MILLIGAN
SITRANS Probe LU,
APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL OR
GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) LEVELS WHICH CAN BE DELIVERED BY S. NGUYEN
INTRINSICALLY SAFE
THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION, THE MAX. PETERBOROUGH CONNECTION DIAGRAM
FOR INTERNAL
UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF THE INTRINSICALLY SAFE APPARATUS, INCL.
INTERCONNECTING WIRING, MUST BE EQUAL OR LESS THAN THE CAPACITANCE AND INDUCTANCE WHICH
USE ONLY 23650516 0
CAN BE SAFELY CONNECTED TO THE ASSOCIATED APPARATUS.
2365051600 1:1 1 1
Note: Reference drawing 23650516 is available from the product page of our website
Page A-1
A: Connection Drawings
mmmmm
mmmmm
A: Connection Drawings
Page A-2
HAZARDOUS LOCATION NON-HAZARDOUS LOCATION
V OC £ V max
I SC £ I max SAFE AREA
APPARATUS
C a ³ C i + C cable
Load
4-20 mA L a ³ Li + L cable
NOTES:
at: https://pia.khe.siemens.com/index.asp?Nr=11157.
3. APPROVED DUST-TIGHT AND WATER-TIGHT CONDUIT SEALS ARE REQUIRED Product Group
ULTRASONICS
FOR CLASS II, DIV.1, GROUP G AND OUTDOOR TYPE 4X LOCATIONS NTS B
17 / DEC / 03
R. CLYSDALE
SITRANS Probe LU,
CSA Intrinsically Safe connection drawing
7ML19985QR81
FM Class 1, Div. 2 connection drawing
A: Connection Drawings
Note: Reference drawing 23650583 is available from the product page of our website
at: https://pia.khe.siemens.com/index.asp?Nr=11157.
mmmmm
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION
(SAFE) CLASS I, DIV.2, GROUPS A, B, C, D
METAL CONDUIT
1/2 “ NPT
24 V
POWER
SUPPLY
SITRANS Probe LU
NOTES:
1) INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE.
1
SEPT
0 FOR CONSTRUCTION RPC SN 29/2004
Product Group
ULTRASONICS
29 / SEPT / 2004
NTS A
R. CLYSDALE
S. MILLIGAN
SITRANS Probe LU
CLASS I, Div. 2
S. NGUYEN
CONNECTION DRAWING
PETERBOROUGH
FOR INTERNAL
USE ONLY 23650583 0
2365058300 1:1 1 1
1000
800
L
RL=44.6*VL - 493.4
Loop Resistance - R
700
600
500
400
(17.8v, 300 ohms)
300
RL=272.7*VL - 4554.1 ALLOWABLE OPERATING
200 AREA
100
(16.7v, 0 ohms)
0
10.00 15.00 20.00 25.00 30.00
Loop Voltage-VL
(Source voltage)
Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. 2008
1954Technology Drive, P.O. Box 4225 Subject to change without prior notice
Peterborough, ON, Canada K9J 7B1
Tel: (705) 745-2431 Fax: (705) 741-0466 Rev. 1.5
Email: [email protected]