Cummins Power Generation Standby Gen Install Manual C13N6H-C20N6HC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 118

Installation Manual

Onan Generator Set for Home Standby

C13N6H (Spec A)
C17N6H (Spec A)
C20N6H (Spec A)
C20N6HC (Spec A)

English
Original Instructions 4-2017 A053X172 (Issue 8)
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Save These Instructions ........................................................................................................ 1
1.2 General Information ................................................................................................................ 1
1.3 General Precautions .............................................................................................................. 1
1.4 Generator Set Voltage Is Deadly ........................................................................................... 5
1.5 Engine Exhaust Is Deadly ...................................................................................................... 5
1.6 Fuel and Fumes Are Flammable ............................................................................................ 6
1.7 Batteries Can Explode ............................................................................................................ 6
1.8 Starting Batteries .................................................................................................................... 7
1.9 Moving Parts Can Cause Severe Personal Injury or Death .................................................. 7
1.10 The Hazards of Carbon Monoxide........................................................................................ 8

2. INTRODUCTION............................................................................................................................ 9
2.1 About This Manual.................................................................................................................. 9
2.2 Schedule of Abbreviations ...................................................................................................... 9
2.3 Related Literature ................................................................................................................. 11
2.4 Model Specifications ............................................................................................................. 13
2.5 Before Installation ................................................................................................................. 16

3. PRE-INSTALLATION CONSIDERATIONS.................................................................................. 17
3.1 Pre-Installation Considerations Introduction ......................................................................... 17
3.2 Installation Codes and Standards for Safety ........................................................................ 18
3.3 Required Items for Installation .............................................................................................. 20

4. INSTALLATION............................................................................................................................ 27
4.1 Site Assessment and Preparation ........................................................................................ 27
4.2 Fuel Selection and Fuel System Connection........................................................................ 31
4.3 Engine Exhaust..................................................................................................................... 43
4.4 Electrical Connections .......................................................................................................... 44

5. STARTUP AND CONFIGURATION............................................................................................. 55


5.1 "Establishing Communications" Message ............................................................................ 55
5.2 "Clock Setup" Screen............................................................................................................ 55
5.3 "Exercise" Screen ................................................................................................................ 61
5.4 "Brightness and Contrast" Screen ........................................................................................ 64
5.5 "About" Screen...................................................................................................................... 66
5.6 "Event Log" Screen............................................................................................................... 68
5.7 "Fault Log" Screen ................................................................................................................ 69
5.8 "System Status" Screen........................................................................................................ 70
5.9 "Mode" Screen ...................................................................................................................... 71
5.10 Automatic Load Management ............................................................................................. 74
5.11 Manual Start Sequence (Local) .......................................................................................... 75
5.12 Checklist ............................................................................................................................. 75

A053X172 (Issue 8) i Copyright © 2017 Cummins Inc.


Table of Contents 4-2017

5.13 Startup ............................................................................................................................... 78

6. OPTIONAL REMOTE MONITORING SYSTEM (RMS) DESCRIPTION ..................................... 79


6.1 Introduction .......................................................................................................................... 79
6.2 Optional Remote Monitoring System (RMS) Account Setup and Generator Set Control
Connection ............................................................................................................................ 80

APPENDIX A. FUEL LINE SELECTION........................................................................................... 81


A.0 Fuel System Pipe Sizing Introduction................................................................................... 82
A.1 Gas Pipe Sizing .................................................................................................................... 83

APPENDIX B. OUTLINE AND SYSTEM DRAWINGS...................................................................... 95

APPENDIX C. WIRING DIAGRAMS............................................................................................... 101


C.0 Wiring Diagrams................................................................................................................. 102

Copyright © 2017 Cummins Inc. ii A053X172 (Issue 8)


1 Important Safety Instructions

1.1 Save These Instructions


This manual contains important instructions for the generator set that should be
followed during installation, operation and maintenance of the generator set and
batteries.
Thoroughly read the operator manual before operating the generator set. Safe
operation and top performance can only be obtained when equipment is properly
operated and maintained.
The following symbols in this manual alert you to potential hazards to the operator,
service person and equipment.

DANGER
Alerts you to an immediate hazard that will result in severe personal injury or
death.

WARNING
Alerts you to a hazard or unsafe practice that can result in severe personal
injury or death.

CAUTION
Alerts you to a hazard or unsafe practice that can result in personal injury or
equipment damage.

1.2 General Information


This manual should form part of the documentation package supplied by Cummins
Inc. with specific generator sets. If this manual has been supplied in isolation,
please contact your authorized dealer.

NOTICE
It is in the operator's interest to read and understand all warnings and
cautions contained in the documentation relevant to the generator set
operation and daily maintenance.

1.3 General Precautions


• Keep type ABC fire extinguishers accessible.
• Make sure that all fasteners are secure and torqued properly.

A053X172 (Issue 8) 1 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 4-2017

• Keep the generator set and its compartment clean. Do not store any items in
the generator set compartment.
• Before working on the generator set, make sure the generator set is shut down
and disabled.
1. Press the generator set's "O" (Off) button or the red STOP button on the
local display (whichever is applicable) to stop the generator set. Allow the
generator set to thoroughly cool to the touch.
2. If applicable, turn off and disconnect the battery charger from the AC
source before disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.
• Use caution when making adjustments when the generator set is running, hot,
or when parts are electrically live, as all situations may cause personal injury or
death.
• Used engine oil has been identified by some state and federal agencies as
causing cancer or reproductive toxicity. Do not ingest, inhale, or come into
contact with used oil or its vapors.
• Do not work on the generator set when mentally or physically fatigued or after
consuming alcohol or drugs.

NOTICE
Only trained and authorized personnel shall maintain or service the
generator set.

NOTICE
The installation of the generator set shall provide enough ventilation to
ensure that gases generated by vented batteries during charging, or caused
by equipment malfunction, are removed.

General Safety Precautions


WARNING
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or
death.
Make sure that only a trained and experienced electrician makes generator
set electrical output connections, in accordance with the installation
instructions and all applicable codes.

Copyright © 2017 Cummins Inc. 2 A053X172 (Issue 8)


4-2017 1. Important Safety Instructions

WARNING
Electrical Generating Equipment
Faulty electrical generating equipment can cause severe personal injury or
death.
Generator sets must be installed, certified, and operated by trained and
experienced person in accordance with the installation instructions and all
applicable codes.

WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly
fastened to prevent unintended contact.

WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to
cause cancer or reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or
changing engine oil. Wear protective gloves and face guard.

WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or
death.
Do not operate equipment when fatigued, or after consuming any alcohol or
drug.
Make sure that only suitably trained and experienced service personnel
perform electrical and/or mechanical service.

WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal
agencies to cause cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.

WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.

A053X172 (Issue 8) 3 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 4-2017

WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
Wear appropriate PPE when working on hot equipment and avoid contact
with hot surfaces.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause
severe burns or death.
Do not store fuel, cleaners, oil, etc., near the generator set. Do not use
combustible liquids like ether.

WARNING
Combustible Gases
Generator sets in operation have combustible gases under pressure, which
if ignited can cause eye and ear damage.
• Wear appropriate eye and ear protection at all times.
• Do not operate the generator set with any doors open.

WARNING
Fire Hazard
Materials drawn into the generator set, as well as accumulated grease and
oil, are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from
obstructions. Make sure the generator set is mounted in a manner to prevent
combustible materials from accumulating under the unit.

WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
The generator set must be off and locked out of service whenever the air
inlet, air outlet, or any interior panels are removed.

WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables (negative [–] first).

Copyright © 2017 Cummins Inc. 4 A053X172 (Issue 8)


4-2017 1. Important Safety Instructions

NOTICE
Keep type ABC fire extinguishers close by. Class A fires involve ordinary
combustible materials such as wood and cloth. Class B fires involve
combustible and flammable liquid fuels and gaseous fuels. Class C fires
involve live electrical equipment. (Refer to NFPA No. 10 in the applicable
region.)

NOTICE
Before performing maintenance and service procedures on enclosed
generator sets, make sure the service access doors are secured open.

NOTICE
Stepping on the generator set can cause parts to bend or break, leading to
electrical shorts, or to fuel, coolant, or exhaust leaks. Do not step on the
generator set.

1.4 Generator Set Voltage Is Deadly


• Generator set output connections must be made by a trained and experienced
electrician in accordance with all applicable codes.
• This generator set and the public utility may only be connected to house circuits
by means of the automatic transfer switch.

CAUTION
Improper connections can lead to electrocution of utility workers and
damage to equipment. Make sure that the connections are installed
properly by a trained technician.

• Use caution when working on live electrical equipment. Remove jewelry, and
make sure clothing and shoes are dry. Stand on a dry wooden platform.

1.5 Engine Exhaust Is Deadly


• See The Hazards of Carbon Monoxide to learn the symptoms of Carbon
Monoxide poisoning.
• Locate the generator set away from doors, windows, other openings into the
house, and where exhaust gases will disperse away from the house.

A053X172 (Issue 8) 5 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 4-2017

1.6 Fuel and Fumes Are Flammable


Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or
other ignition source near the generator set or fuel system.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the
engine should be made with an approved flexible line. Do not use copper piping
on flexible lines because copper will become brittle if continuously vibrated or
repeatedly bent.
• Be sure all fuel supplies have a positive shutoff valve.
• Be sure the battery area has been well-ventilated prior to servicing near it.
Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by
arcing, sparking, smoking, etc.

1.7 Batteries Can Explode


Batteries can explode, causing severe skin and eye burns and can release toxic
electrolytes.

WARNING
Combustible Gases
Batteries can explode, causing severe skin and eye burns, and can release
toxic electrolytes.
Do not dispose of the battery in a fire, because it is capable of exploding. Do
not open or mutilate the battery.

WARNING
Electric Shock Hazard
Batteries present the risk of high short circuit current.
Remove watches, rings, or other metal objects. Use tools with insulated
handles.

NOTICE
Servicing of batteries must be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.

• Wear safety glasses.


• Do not smoke.
• Do not charge frozen batteries.
• To prevent arcing when disconnecting the battery:
1. Press the Off switch from the display and then press the E-Stop button.

Copyright © 2017 Cummins Inc. 6 A053X172 (Issue 8)


4-2017 1. Important Safety Instructions

2. Disconnect AC power from any battery chargers.


3. Remove the negative (-) battery cable to prevent starting.
• To prevent arcing when reconnecting the battery:
1. Reconnect the positive (+) cable.
2. Reconnect the negative (-) cable.
3. Reconnect the battery charger to AC power supply.
• When replacing the generator set battery, always replace it with a battery as
specified in this manual.

1.8 Starting Batteries


WARNING
Toxic Hazard
The electrolyte in starting batteries is a dilute sulfuric acid that is harmful to
the skin and eyes. It is also electrically conductive and corrosive.
Always:
1. Wear full eye protection and protective clothing;
2. If the electrolyte contacts the skin, wash it off immediately with water;
3. If the electrolyte contacts the eyes, flush them thoroughly and
immediately with water and seek medical attention; and
4. Wash spilled electrolyte down with an acid neutralizing agent. A
common practice is to use a solution of one pound (500 grams)
bicarbonate of soda (also known as baking soda or sodium bicarbonate)
to one gallon (4 liters) of water.
5. Continue to add the bicarbonate of soda solution until the evidence of
reaction (that is, foaming) has stopped.
6. Flush the resulting liquid with water and dry the area.

1.9 Moving Parts Can Cause Severe Personal


Injury or Death
• Do not wear loose clothing or jewelry near moving parts, such as fans.
• Keep hands away from moving parts.
• Keep guards in place over fans.

A053X172 (Issue 8) 7 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 4-2017

1.10 The Hazards of Carbon Monoxide


Carbon monoxide (CO) is an odorless, colorless, tasteless and non-irritating gas.
You cannot see it or smell it. Red blood cells, however, have a greater affinity for
CO than for oxygen. Therefore, exposure even to low levels of CO for a prolonged
period can lead to asphyxiation (lack of oxygen) resulting in death. Mild effects of
CO poisoning include eye irritation, dizziness, headaches, fatigue and the inability to
think clearly. More extreme symptoms include vomiting, seizures and collapse.
Engine-driven generator sets produce harmful levels of carbon monoxide that can
injure or kill you.

Special Risks of CO near the Home


WARNING
Toxic Gases
Carbon monoxide (CO) gas can cause nausea, fainting, or death. Residents
can be exposed to lethal levels of CO when the generator set is running.
Depending on air temperature and wind, CO can accumulate in or near the
home.
To protect yourself and others from the dangers of CO poisoning, it is
recommended that reliable, approved, and operable CO detector alarms are
installed in proper locations in the home as specified by their manufacturer.

Protecting Yourself from CO Poisoning


• Locate the generator set in an area where there are no windows, doors, or
other access points into the home.
• Make sure all CO detectors are installed and working properly.
• Pay attention for signs of CO poisoning.
• Check the exhaust system for corrosion, obstruction, and leaks every time you
start the generator set and every eight hours when you run it continuously.

Copyright © 2017 Cummins Inc. 8 A053X172 (Issue 8)


2 Introduction

2.1 About This Manual


WARNING
Improper installation can result in severe personal injury, death and damage
to equipment. The installation must comply with all applicable building
codes (including project permits and inspections). The installer should be
properly trained and licensed to perform electrical and mechanical
equipment installations (including gaseous fuel installation).

NOTICE
Manuals are updated from time to time to reflect changes in the equipment
and its specifications. The most up-to-date version of this manual is found
on the QuickServe website
(https://quickserve.cummins.com/info/index.html).

This manual is a guide for the installation of the generator set models listed on the
front cover. Proper installation is essential for top performance, reliable operation,
and safety. Read through this manual before starting the installation. This manual
covers outdoor applications only; for other installations, refer to the T-030: Liquid-
Cooled Generator Set Application manual available from your Cummins distributor.

NOTICE
The installation must comply with all applicable building codes.

See the generator set's specific operator manual for operation and maintenance and
specific service manual for service.
Refer to the Model Specifications section for specific information about the system
and its components.
Refer to the Outline and System Drawings appendix and the Wiring Diagrams
appendix for specific information about installation and wiring connections.

2.2 Schedule of Abbreviations


This list is not exhaustive. For example, it does not identify units of measure or
acronyms that appear only in parameters, event/fault names, or part/accessory
names.

A053X172 (Issue 8) 9 Copyright © 2017 Cummins Inc.


2. Introduction 4-2017

Abbr. Description Abbr. Description


AC Alternating Current LED Light-Emitting Diode
AMP AMP, Inc. (part of Tyco MFM Multifunction Monitor
Electronics)
ANSI American National Mil Std Military Standard
Standards Institute
ASOV Automatic Shut Off Valve MPU Magnetic Pickup
ASTM American Society for NC Normally Closed
Testing and Materials
(ASTM International)
ATS Automatic Transfer NC Not Connected
Switch
AVR Automatic Voltage NFPA National Fire Protection
Regulator Agency
AWG American Wire Gauge NO Normally Open
CAN Controlled Area Network NWF Network Failure
CB Circuit Breaker OEM Original Equipment
Manufacturer
CE Conformité Européenne OOR Out Of Range
CCA Cold Cranking Ampere OORH/ Out Of Range High
ORH
CFM Cubic Feet per Minute OORL/ORL Out Of Range Low
CGT Cummins Generator PB Push Button
Technologies
CMM Cubic Meters per Minute PCC PowerCommand® Control
CT Current Transformer PGI Power Generation
Interface
DC Direct Current PGN Parameter Group
Number
DEF Diesel Exhaust Fluid PI Proportional/Integral
DPF Diesel Particulate Filter PID Proportional/Integral/
Derivative
EBS Excitation Boost System PLC Programmable Logic
Controller
ECM Engine Control Module PMG Permanent Magnet
Generator

Copyright © 2017 Cummins Inc. 10 A053X172 (Issue 8)


4-2017 2. Introduction

Abbr. Description Abbr. Description


ECS Engine Control System PPE Personal Protective
Equipment
EMI Electromagnetic PT Potential Transformer
Interference
EN European Standard PTC Power Transfer Control
EPS Engine Protection PWM Pulse-Width Modulation
System
E-Stop Emergency Stop RFI Radio Frequency
Interference
FAE Full Authority Electronic RH Relative Humidity
FMI Failure Mode Identifier RMS Remote Monitoring
System
FSO Fuel Shutoff RMS Root Mean Square
Genset Generator Set RTU Remote Terminal Unit
GCP Generator Control Panel SAE Society of Automotive
Engineers
GND Ground scfh Standard Cubic Feet of
gas per Hour
HMI Human-Machine SCR Selective Catalytic
Interface Reduction
IC Integrated Circuit SPN Suspect Parameter
Number
ISO International Organization SW_B+ Switched B+
for Standardization
LBNG Lean-Burn Natural Gas UL Underwriters
Laboratories
LCD Liquid Crystal Display UPS Uninterruptible Power
Supply
LCT Low Coolant
Temperature

2.3 Related Literature


Before any attempt is made to operate the generator set, the operator should take
time to read all of the manuals supplied with the generator set and familiarize
themselves with the warnings and operating procedures.

A053X172 (Issue 8) 11 Copyright © 2017 Cummins Inc.


2. Introduction 4-2017

NOTICE
A generator set must be operated and maintained properly if you are to
expect safe and reliable operation. The Operator manual includes a
maintenance schedule and a troubleshooting guide.
The Health and Safety manual must be read in conjunction with this manual
for the safe operation of the generator set, as well as the Warranty
Statements.

The literature provided with the generator set is as follows:


• Installation Manual (A053X172)
• Operator Manual (A053X174)
• Quick Start Installation Guide (A053X181)
• Quick Start Operator Guide (A053X183)
• Health and Safety Manual (0908-0110-00)
• Global Warranty Statement (A056F206)
• Emission Warranty Statement (Federal Emissions EPA Title 40 CFR Part 90
Component Warranty) (A028X278)
The relevant manuals appropriate to your generator set are also available. The
documents below are in English:
• Generator Set Service Manual (A053X177)
• RA Series RA112L1 Automatic Transfer Switch Owner Manual (A052S254) - if
applicable
• RA Series 100A/200A/400A Automatic Transfer Switch Owner Manual
(A046S594) - if applicable
• Parts Manual (A053X179)
• Standard Repair Times - HO Family (A053X186)
• Service Tool Manual (A043D529)
• Warranty Failure Code Manual (F1115C)
• Engineering Application Manual T-030: Liquid Cooled Generator Sets
(A040S369)

Copyright © 2017 Cummins Inc. 12 A053X172 (Issue 8)


4-2017 2. Introduction

2.4 Model Specifications


TABLE 1. MODEL VARIATIONS

Natural Gas or
Model kW Amps Frequency Voltage
Propane Vapor
C13N6H Both 13 54.2
C17N6H Both 17 70.8
120/240 VAC
Natural Gas Only 18 75 60 Hz
C20N6H, Single Phase
C20N6HC Propane Vapor
20 83.3
Only

NOTICE
Maximum load imbalance allowed is 50% of generator set rating.

TABLE 2. COLD WEATHER SPECIFICATIONS (ALL MODELS)

Temperature Description
Above 4 °C (40 °F) No starting aids required
-17 to 4 °C (0 to 40 °F) Alternator and regulator heaters (supplied with the generator set)
• Alternator and regulator heaters
Below -17 °C (0 °F) • 0W30 oil (see the oil recommendation below)
• Extreme cold weather kit (A045B984) (includes battery and
oil heaters)

TABLE 3. FUEL SPECIFICATIONS (AT FULL LOAD) (ALL MODELS)

C13N6H C17N6H C20N6H, C20N6HC


Type
scfh BTU/hr scfh BTU/hr scfh BTU/hr
Natural Gas 253 260,000 289 297,000 300 309,000
Propane 85 212,000 101 252,000 116 290,000
Natural Gas: 3.5 - 12 inch water column (0.9 - 3.0 kPa)
Propane Vapor: 1.5 - 3.0 kPa (6 - 12 inch water column)
Fuel Pressure
Maximum pressure for either fuel under any condition: 3.2 kPa (13
inch water column)

A053X172 (Issue 8) 13 Copyright © 2017 Cummins Inc.


2. Introduction 4-2017

TABLE 4. ENGINE SPECIFICATIONS (ALL MODELS)

Type Value
2 cylinder v-twin, OHV, air-cooled, 4-stroke, spark
Engine
ignited
Displacement 999 cc (60.9 in3)
Spark Plug Gap 0.7 - 0.8 mm (0.027 - 0.031 in)
Spark Plug Torque (Cold Engine) 25 - 30 Nm (18 - 22 ft-lb)
RPM 3600
Lubricating Oil Pressure at Rated
310 kPa (45 psi)
Speed (Minimum)
Full synthetic gasoline engine oil which meets or
exceeds API service SN/SN-RC and ILSAC GF-5:
Oil Recommendation • 5W30: Temperatures above -17 °C (0 °F)
• 0W30: All temperatures, required below -17 °C (0
°F)
Lubricating Oil Capacity:
Lubricating Oil Pressure at Rated
310 kPa (45 psi)
Speed (Minimum)
--Full at High Mark on Dipstick 2.3 L (2.4 qt)
--Low Mark on Dipstick 1.3 L (1.4 qt)

TABLE 5. GENERATOR SET SIZE (ALL MODELS)

Dimension Value
Length 865 mm (34.1 in)
Width 915 mm (36 in)
Height 694 mm (27.3 in)

TABLE 6. GENERATOR SET WET WEIGHT (INCLUDING BATTERY)

Model Value
C13N6H 218 kg (479 lb)
C17N6H, C20N6H, C20N6HC 241 kg (531 lb)

Copyright © 2017 Cummins Inc. 14 A053X172 (Issue 8)


4-2017 2. Introduction

TABLE 7. GENERATOR SET DERATING GUIDELINES

Engine Power Available Up To... Derate At…


Model
Elevation Ambient Temperature Elevation Temperature
C13N6H 2100 m (6900 ft) 25 °C (77 °F)
3.5% per
C17N6H 300 m (1000 ft) 25 °C (77 °F) 1% per
300 m
C20N6H, 5.5 °C (10 °F)
0 m (0 ft) 15 °C (60 °F) (1000 ft)
C20N6HC

NOTICE
Derating guidelines: This product's output power is limited by factors such
as BTU content of fuel, ambient temperature, altitude, humidity, engine
condition, etc. The derating guidelines are based on properly maintained
product, using the appropriate fuel. Derate values are based on expected
engine power changes from elevation and temperatures listed.

TABLE 8. ALTERNATOR SPECIFICATIONS (ALL MODELS)

Type Specification
Design Rotating field
Poles 2
RPM 3600
Voltage 240
Hz 60

TABLE 9. CONTROL SPECIFICATIONS (ALL MODELS)

Control
Integrated Microprocessor-Based Engine, Alternator, Transfer Switch Controller

TABLE 10. DC SYSTEM SPECIFICATIONS (ALL MODELS)

Type Value
Nominal Battery Voltage 12 VDC
Battery Group 51 R
Battery Type Lead Acid
Minimum Cold Crank Amps (CCA) 450

A053X172 (Issue 8) 15 Copyright © 2017 Cummins Inc.


2. Introduction 4-2017

2.5 Before Installation


Before beginning the installation of the generator set, verify that the unit was
correctly selected. Check the following features:
• Model
• Specifications
• Options
• Fuel Supply
◦ The gas supplied to the generator set must be of acceptable quality.
◦ The gas supply must have sufficient pressure. Care must be taken to be
sure that the gas supply at the generator set, not just at the source, is of
proper pressure for operation. The specified pressure must be available
while the generator set is starting and running at full load.
◦ The gas must be supplied to the generator set in sufficient volume to
support operation of the generator set. This is normally a matter of
selecting fuel line size to be large enough to transport the volume of fuel
needed. For liquid propane vapor-withdrawal fuel systems the size and
temperature of the fuel tank also affects this requirement.

Copyright © 2017 Cummins Inc. 16 A053X172 (Issue 8)


3 Pre-Installation Considerations

3.1 Pre-Installation Considerations Introduction


WARNING
The installer is responsible for complying with all applicable installation
codes and safety requirements. See the Installation Codes and Standards for
Safety section of this manual for more information.

The following sections create a step-by-step overview of a typical generator set


installation. Review these sections to become familiar with specific procedures and
important safety before beginning the installation.

NOTICE
For information on tools and materials, see the Required Items for
Installation section. For information on locating the generator set, see the
Installation section. For codes and standards, see the Installation Codes
and Standards for Safety section. For specifications, see the Model
Specification section.

Areas of consideration:
• Location of the generator set: this is one of the first decisions to be made, as it
affects all other aspects of the installation, such as:
◦ Length of electric wiring
◦ Length of gas lines (natural gas or propane - must be inspected by the gas
utility inspectors and building inspectors)
◦ Site preparation:
▪ Access to the site
▪ Trenches
▪ Site preparation materials needed
• Fuel supply pressure
• Automatic transfer switch location and connections
• Tools and materials required
• Minimum distance from the propane tank fill:
◦ Verify the legal minimum distance with local code officials.
◦ Verify the minimum distance from the service pressure regulator to the
generator set.

A053X172 (Issue 8) 17 Copyright © 2017 Cummins Inc.


3. Pre-Installation Considerations 4-2017

◦ Verify any minimum clearance requirements to the generator set that the
gas supplier or equipment supplier may have.
• Accessories required (if any) for the customer's application (utility power is
required at the generator set for the battery charger and may be required for
the heaters; make plans accordingly)

NOTICE
Depending on the locality and use of the generator set, it may be necessary
to obtain an air quality emissions permit before installation begins. Check
with local pollution control or air quality authority to determine permit
requirements.

3.2 Installation Codes and Standards for Safety


NOTICE
The generator set installer bears sole responsibility for following all
applicable local codes and regulations.

The following list of codes and standards may apply to the installation and operation
of the generator set. This list is for reference only and not intended to be inclusive of
all applicable codes and standards. The address of each agency is listed so that
copies of the codes may be obtained for reference. Installation codes and
recommendations are subject to change, and may vary by location or over time.

TABLE 11. INSTALLATION CODES AND STANDARDS FOR SAFETY


RECOMMENDATIONS

Code or Standard Organization


NFPA 37 - Installation and Use of Stationary National Fire Protection Association
Combustion Engines and Gas Turbines 470 Atlantic Avenue
NFPA 54 - National Fuel Gas Code Boston, MA 02210
NFPA 58 - Storage and Handling of Liquefied
Petroleum Gases
NFPA 70 - National Electrical Code
CSA Electrical Bulletin Canadian Standards Association
CSA 22.1 Canadian Electrical Code Housing and Construction Materials
CSA B149 Section
CSA C22.2 No. 100 178 Rexdale Blvd.
CSA C22.2 No. 14 Rexdale, Ontario, Canada M9Q 1R3

Copyright © 2017 Cummins Inc. 18 A053X172 (Issue 8)


4-2017 3. Pre-Installation Considerations

Code or Standard Organization


California Administrative Code - Title 25 Chapter 3 State of California
Documents Section
P.O. Box 1015
North Highlands, CA 95660

Operating the Generator Set Cover Safely


To configure the local display or access the generator set, you will need to lift the
cover (lid). The cover of the generator set is designed to latch securely into the "up"
position to prevent accidental closure.
• To open: Lift the cover until the hinge pin drops into the hinge pin slot. Test
that the cover is secure by gently pressing down on the cover.
• To close: Lift up on the cover while pressing upward on the hinge pin and slide
the pin upwards out of the hinge pin slot. Carefully push the cover downward
and let go of the hinge pin allowing it to ride along the hinge until the cover is
closed.

A053X172 (Issue 8) 19 Copyright © 2017 Cummins Inc.


3. Pre-Installation Considerations 4-2017

FIGURE 1. HINGE LOCATION

3.3 Required Items for Installation


Tools and materials are used for the installation of this generator set. These items
are identified in the following sections. Please refer to local codes and standards,
because they may affect the materials required.

Materials Required
NOTICE
Refer to local codes and standards, which may affect material requirements.

Copyright © 2017 Cummins Inc. 20 A053X172 (Issue 8)


4-2017 3. Pre-Installation Considerations

NOTICE
A UL-listed grounding electrode terminal within its ratings and suitable for
the application must be installed and labeled “Grounding Electrode
Terminal”.

NOTICE
Class 1 wiring methods must be used for connecting the generator set.

TABLE 12. MATERIALS REQUIRED

Requirement Specification
Electrical Materials
Code compliant AC power wires Four (L1, L2, N and Gnd)
For accessories (alternator heater, oil heater, battery heater, Code compliant 20 A, 120
and/or regulator heater) (if equipped) VAC, GFCI protected circuit,
copper wire only
RA switches only: Control wires from the generator set to the Four DC wires
transfer switch
Ethernet cable for Internet installation (as required) Cat 5, Cat 5e or Cat 6
All AC and DC wire and cable ratings Must be 75 °C minimum with
600 V minimum insulation,
stranded copper, rated for wet
locations.1
Wire sizes (for all DC customer connections): Under 1000 ft 18-14 AWG
wire length
Conduit Code compliant for all wires
Mounting Materials
Bolts or anchor assemblies Two base tie-down
Fuel System Materials
Fuel line Flexible
Pipe thread sealant UL listed
Fuel service pressure regulator (as required) --
Manual fuel shut-off at generator set ahead of automatic --
valves on generator set fuel system
Remote Display Materials (if Applicable)
Remote display --

A053X172 (Issue 8) 21 Copyright © 2017 Cummins Inc.


3. Pre-Installation Considerations 4-2017

Requirement Specification
Hardware, Cummins Pigtail harnesses Two (one for local display and
provided: one for remote display); 5-
wire (RS485-A2, RS485-B2,
B+, WAKEUP and B-), 1 ft
long each
Hardware, customer provided: Intermediate wires of required Five wires, 600V insulation1, 2
length to connect to the pigtail
harnesses using splices
provided in the remote display
kit
Wire sizes (RS485-A2, Under 1000 ft wire length 20-14 AWG
RS485-B2, B+, WAKEUP):
Wire sizes (B+ and B-): Under 100 ft wire length 18 AWG
Under 200 ft wire length 16 AWG
Under 300 ft wire length 14 AWG
Hardware, Miscellaneous If wires can be concealed in a 3 wall anchors and screws
wall cavity: (number 6 or number 8)
If wires cannot be concealed 3 wall anchors and screws
in a wall cavity: (number 6 or number 8),
standoffs, and conduit or wire
raceway
1
300V insulation is acceptable for Ethernet and DC cables if routed in a separate conduit
from AC wiring.
2
Use twisted pair wires for RS485-A and RS485-B wires.

Tools Required
Use appropriate lifting techniques to position the generator set in place.

Transfer Switch Requirements


A transfer switch must be a part of every generator set installation. Transfer
switches transfer loads to the generator set during power outages.

NOTICE
Cummins offers a variety of transfer switches, including residential and light
commercial options.

Copyright © 2017 Cummins Inc. 22 A053X172 (Issue 8)


4-2017 3. Pre-Installation Considerations

FIGURE 2. CUMMINS AUTOMATIC TRANSFER SWITCH (ATS)


Before beginning the installation of the transfer switch, verify that the unit was
correctly selected. Check the following features:
• Specifications (voltage, amperage, frequency, poles, and phases)
• Enclosure (indoor vs. outdoor)
• Model
Cummins recommends that any RA series transfer switch be used with these
generator sets. Refer to the appropriate RA series ATS owner manual for more
detailed information.

Choosing a Transfer Switch


This section includes block diagrams showing partial or full load coverage for the
following Cummins UL 1008 listed transfer switches:

TABLE 13. CUMMINS TRANSFER SWITCH MODELS

Model Non-Service Entrance Service Entrance


RA 100A ■ ■
RA 200A ■ ■
RA 400A ■ ■
RA112L1 ■

A053X172 (Issue 8) 23 Copyright © 2017 Cummins Inc.


3. Pre-Installation Considerations 4-2017

NOTICE
These generator sets can be used with either service entrance transfer
switches or non-service entrance transfer switches.

NOTICE
If the load exceeds the generator set rating, it may be necessary to use
Cummins’ load management kit (A051C329).

FIGURE 3. TRANSFER SWITCH CONNECTIONS FOR PARTIAL COVERAGE LOAD

Copyright © 2017 Cummins Inc. 24 A053X172 (Issue 8)


4-2017 3. Pre-Installation Considerations

FIGURE 4. TRANSFER SWITCH CONNECTIONS FOR FULL COVERAGE LOAD

Loose Parts Shipped with the Generator Set


The following loose parts are shipped with the generator set:
• Two enclosure keys
• Generator set mounting spacers
• Circuit breaker cover and screw
• Chassis plugs
• Transfer switch TB4 jumper

NOTICE
This jumper must be installed in the RA series transfer switch according
to the interconnect diagram in the RA series transfer switch owner
manual.

• Literature (Operator Manual, Quick Start Operator Guide, Installation Manual,


Quick Start Installation Guide, Health and Safety Manual, and Warranty
Statements)

A053X172 (Issue 8) 25 Copyright © 2017 Cummins Inc.


3. Pre-Installation Considerations 4-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 26 A053X172 (Issue 8)


4 Installation

4.1 Site Assessment and Preparation


Proper component location and site preparation have a very important impact on
completing a successful installation. The major components and sources of power
needed for installation include the following items:
• Generator set
• Transfer switch
• Electrical utility
• Fuel source
• Accessories (may be required under certain conditions)

Generator Set Installation Suggestions and Guidelines


• Locate the generator set on stable ground, not subject to flooding. Generator
set should not be installed where significant water runoff from a roof or
downspouts is present. Sump pump discharge should be routed away from the
generator set.
• Locate and orient the generator set such that prevailing winds will carry exhaust
gases and fuel leaks away from the house or occupied areas.
• This unit is to be installed so that the risk of contact by people is minimized.

Picking a Location
WARNING
Exhaust gas is deadly. Install the generator set outdoors only. Locate the
generator set away from doors, windows, and other openings to the house
and where exhaust gases will disperse away from the house or occupied
areas.

NOTICE
All parts of the generator set enclosure must be at least 60 inches (1524 mm)
from any openings in walls of structures that may be occupied.

Generator set location is critical for safety and performance. Follow the guidelines
below:
• The installation must comply with all applicable codes and standards (NFPA,
NEC, IBC, etc.).
• This manual only covers outdoor installations with Cummins factory installed
enclosures. This product must never be installed indoors.

A053X172 (Issue 8) 27 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

• Consider access to utilities (electric meters, transfer switch, fuel supply line and
fuel tank, etc.).
• Call the local utilities to mark the locations of buried utility services (gas,
electric, telephone, etc.) before digging.
• Verify the locations of any other buried components (gas, electric telephone,
etc.) with the homeowner before digging.
• Consideration should be given to the location of sprinkler heads for irrigation
systems. The generator set should not be located where it is subjected to
substantial wetting (especially on the inlet air side) when the irrigation system is
in operation.
• Always install this generator set service regulator above the snow line.
Follow the clearance requirements below (refer to the Outline and System Drawings
appendix):
• All parts of the generator set enclosure must be at least 60 inches (1524 mm)
from any openings in walls of structures that may be occupied. Examples of
wall openings include but are not limited to: operable windows, doors, dryer
vents, fresh air intake for heaters, etc.
• The engine side and alternator side of the generator set must be located as
follows:
◦ One side (either engine or alternator) must be located not less than 18
inches (458 mm) from any structures having combustible walls. This space
must be free of any obstructions for service access.
◦ The opposite side must be located not less than 60 inches (1524 mm) from
any structures having combustible walls. A minimum of 18 inches (458
mm) of unobstructed space is required for service access.
• The intake (cooling air inlet) side of the generator set must be located not less
than 30 inches (762 mm) from any structures having combustible walls. This
space must be free of obstructions to air flow and service access.
• The generator set must be located such that exhaust gases are not able to
accumulate in an occupied area. The air discharge side must always be
unobstructed and spaced a minimum of 60 inches (1524 mm) from any
structures having combustible walls. A minimum of 36 inches (915 mm) must
be free of any combustible items, and unobstructed for service access.
• The generator set must have enough room for installation, service, and
maintenance.
• The generator set must be located to ensure ventilation openings are not
blocked.
• Position the generator set so that cooling air is free to enter and leave the area.
• Locate and position the generator set so that prevailing winds carry exhaust
gases and potential fuel leaks away from the house or occupied area.

Copyright © 2017 Cummins Inc. 28 A053X172 (Issue 8)


4-2017 4. Installation

Preparing the Generator Set Mounting Surface


Cummins recommends the generator set be installed on a non-combustible
mounting pad (available as an accessory) or a poured concrete slab. The surface
beneath the mounting surface must be properly prepared to minimize the risk of the
generator set settling and causing undue stress on the fuel system or electrical
connections. The surface preparation is the same when preparing the site for
installing on the accessory mounting pad or poured slab.
Cummins recommends the generator set be installed above grade for easier
maintenance, and lower risk of submersion in water.
1. Clear obstructions and make sure that there is adequate clearance for access
to the site.
2. Ensure that the ground is stable and is not subject to flooding.
3. Level the ground, and make sure that the subgrade is compacted and settled.
Local soil condition may dictate the need for addition of sub-base and base
material layers above the subgrade. Consult with your local building officials for
requirements and recommendations for your area.
4. Either pour a concrete slab or set an accessory mounting pad on the prepared
surface. The poured concrete slab should be:
• Constructed of concrete with a 28-day compressive strength of at least
2500 psi (17,200 kPa); typical bagged concrete mix meets this requirement
• A minimum of 3 inches (76.2 mm) thick
• At least 2 inches (50.8 mm) larger in length and width than the generator
set base
5. Place the generator set on the pad and secure it to the mounting surface using
the mounting spacers (provided) and appropriate fasteners. See the Securing
the Generator Set to the Mounting Pad section for more information.

Lifting and Moving the Generator Set


WARNING
Heavy Load
The generator set is heavy. Handle with care.
Dropping the generator set can cause severe personal injury or death. Use
appropriate lifting techniques to move the generator set. Keep feet and
hands clear when lifting the generator set.

CAUTION
The generator set is shipped with oil in the engine crankcase. Keep the
generator set upright.

A053X172 (Issue 8) 29 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

Securing the Generator Set to the Mounting Pad


The generator set should be securely attached to either a poured concrete slab or
prefabricated mounting pad (accessory pad) made of non-combustible material.

NOTICE
An accessory mounting pad is available that includes ½ -13 UNC x 1.25 inch
mounting holes located in the proper location for these generator sets. Two
hex head cap screws (½-13 x 3 inch long) and flat washers are needed with
this accessory pad.

1. Position the two spacers (which were shipped with the generator set)
appropriately on the generator set base.

No. Description No. Description


1 Spacer Length (2.18 in [55.4 mm]) 2 Spacer Through-Hole Diameter (0.59
in)
FIGURE 5. MOUNTING SPACER
2. Prefabricated pad only: Install the bolts into the prefabricated pad and tighten.
Torque value: 37 ft-lb (50 Nm).
3. Poured slab only:
a. Mark the location for the anchor bolts with the generator set in place.
b. Install the anchor bolts per the manufacturer's recommendation for both
embedment and tightening torque.

Copyright © 2017 Cummins Inc. 30 A053X172 (Issue 8)


4-2017 4. Installation

NOTICE
There are several styles of anchor bolts available. Follow the anchor
bolt manufacturer's requirements for hole size and depth. The length of
the anchor bolt must accommodate:
• The embedment length of the bolt into the pad
• The length of the spacer
• The thickness of the washer and
• The thickness of the nut (if used)

4. Install the chassis plugs in the generator set's lifting holes after the unit is in its
final position.

4.2 Fuel Selection and Fuel System Connection


This generator set has a convertible fuel system. The generator may run on natural
gas or propane, depending on the preferences of the owner. All generator sets
come preconfigured from the factory for natural gas fuel. For more information on
converting the fuel system type, see the Service Manual.

NOTICE
Fuel systems must be installed by qualified service technicians. Improper
installation presents hazards of fire and improper operation, resulting in
severe personal injury or property damage.

NOTICE
In some jurisdictions fuel system installations to the generator set must be
performed by licensed or registered personnel. Check with the authority
having jurisdiction for requirements.

WARNING
Gaseous fuels are flammable, explosive, and can cause severe personal
injury or death. Do not smoke if you smell gas, are near fuel tanks for fuel-
burning equipment, or are in an area sharing ventilation with such
equipment. Keep flames, sparks, pilot lights, electrical arcs, arc-producing
equipment and all other sources of ignition well away. Keep a type ABC fire
extinguisher handy.

In all fuel system installations, cleanliness is extremely important.


• Make every effort to prevent fuel contamination from:
◦ Moisture
◦ Dirt

A053X172 (Issue 8) 31 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

◦ Excess thread sealant


◦ Contaminants of any kind
• Clean all fuel system components before installing.
Gaseous-fuel supply system design, materials, components, fabrication, assembly,
installation, testing, inspection, operation, and maintenance must comply with the
applicable codes. See NFPA Standards No. 37, 54, and 58. If this is a seismic
installation, refer to IBC codes and standards. Where seismic installation is
required, there may be specific anchorage requirements for the generator set and
other installed components.
Most codes require a manual shutoff valve ahead of a flexible fuel hose. The
generator set includes electric (battery-powered) shutoff valves.

NOTICE
It is recommended that a shutoff valve be located near the generator set for
emergency shut off or servicing the generator set. Follow applicable codes.

Until the generator set is connected, cap the fuel line stub-up at the generator set to
prevent dirt from entering and gas from discharging if the gas supply shutoff valve is
opened accidentally.
To determine the required capacity, refer to the Fuel Line Selection section.

Fuel Line Connections


WARNING
Fuel presents the hazard of fire or explosion that can result in severe
personal injury or death. Do not smoke or allow any flame, spark, pilot light
or other ignition sources near fuel or in the installation area. Read the
important safety precautions in this manual.

1. Refer to the Outline and System Drawings appendix for the location of the fuel
supply connection through the side of the generator set.
2. Install a flexible fuel hose, which must be used between the engine's fuel
system and fuel supply line to protect the fuel system from damage caused by
vibration, expansion and contraction. The fuel hose must be installed according
to all applicable codes and standards.

Natural Gas Fuel System


WARNING
Fuel leaks can lead to explosive accumulations of gas. Prevent gas leaks
and the accumulation of gaseous fuel in the event of a leak.

Requirements for a natural gas generator set are as follows:

Copyright © 2017 Cummins Inc. 32 A053X172 (Issue 8)


4-2017 4. Installation

TABLE 14. NATURAL GAS GENERATOR SET REQUIREMENTS

Component Description
Gas Pipeline quality
Fuel Supply Adequate fuel supply to operate correctly and run at full load
Shutoff Valve Manual
Fuel Pipe Size The length of the fuel supply pipe from the gas service entrance to the
generator set must be known to determine the correct fuel pipe size.
Refer to the charts in the Fuel Line Selection appendix.
Iron pipe must be a minimum of schedule 40 subject to the authority
having jurisdiction.
Flexible Fuel Line Protects the fuel system from vibration, expansion, and contraction. Must
meet code requirements for application and be installed per
manufacturer instructions.

A053X172 (Issue 8) 33 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

No. Description No. Description


1 Distance as Required by Code and/or 7 Secondary Service Pressure Regulator
Component Suppliers (If Required)
2 Primary Service Pressure Regulator 8 Flexible Fuel Line
3 Natural Gas Supply 9 Sediment Trap
4 Gas Meter 10 Fuel Line Connection at Generator Set
5 Note: A branch in the fuel line to the 11 Generator Set
generator set may allow selection of a
smaller diameter line size to the
generator set and remainder of gas
appliances.
6 Full Flow Manual Shutoff Valve
FIGURE 6. TYPICAL NATURAL GAS INSTALLATION
Natural Gas Supply Line Size
See the Model Specifications section for fuel specifications (such as BTU/hr).
The natural gas supply meter may need to be exchanged for a higher capacity
meter to supply the additional gas consumed by the generator set.

Copyright © 2017 Cummins Inc. 34 A053X172 (Issue 8)


4-2017 4. Installation

To correctly size the fuel pipe, you must also take other loads operated from
the fuel supply line into consideration, such as space heating and water
heating equipment.
Use the total fuel requirement of the generator set and other connected
appliances to determine the size of the fuel supply pipe. Use the tables and
charts in the Fuel Line Selection appendix to determine the correct pipe size.
The installation site might require upgrading and repair of the gas supply
system. Schedule an upgrade or repair to minimize power and gas supply
interruptions.
Make sure the full load fuel supply pressure at the inlet to the generator set
fuel shutoff valves is set between 3.5 - 12 inch water column (0.9 - 3.0 kPa)
for all operating loads (no load to full load). Refer to the Model Specifications
section.
See the Natural Gas Fuel System section for an example of a typical natural
gas installation.

Propane Fuel System


WARNING
Fuel leaks can lead to explosive accumulations of gas. Propane sinks in air
and can accumulate inside housings, basements, and other below-grade
spaces. Prevent gas leaks and the accumulation of gaseous fuel in the event
of a leak.

NOTICE
NFPA Standard No. 58 requires all persons handling and operating propane
to be trained in proper handling and operating procedures.

TABLE 15. REQUIRED COMPONENTS IN A PROPANE VAPOR FUEL SYSTEM

Component Description
Propane Tank Make sure to identify and use the correct tank size based on fuel flow
requirements and the lowest average temperature for your region. If the
tank is sized incorrectly, the generator set could run out of fuel. Refer to
the Minimum LPG Tank Size figure in the Fuel Line Selection appendix.
Shutoff Valve Useful during installation or in the event of a leak (may be required to
meet local codes).
Primary Pressure Located at the tank outlet, the primary regulator reduces the tank
Regulator pressure to the working pressure in the fuel supply line. Primary and
secondary regulators must be properly matched for a safe and functional
system. Consult with your propane supplier to ensure that the regulators
are properly sized.

A053X172 (Issue 8) 35 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

Component Description
Secondary Located near the generator set, the secondary regulator reduces the
Pressure higher line pressure to a working pressure of 6 - 12 inch water column
Regulator (1.5 - 3.0 kPa). Higher pressure before the secondary regulator is
necessary to ensure that there is enough fuel available at the secondary
regulator for a fully loaded generator set. Always install this generator
set’s service regulator above the expected snow line.
Fuel Line Connects to the fuel supply. It must be sized properly using the propane
fuel line sizing charts (see the Fuel Line Selection appendix).
Installation must comply with all national, state, and local codes.
Flexible Fuel Line Protects the fuel system from vibration, expansion, and contraction. Must
meet code requirements for application and be installed per
manufacturer instructions.

Copyright © 2017 Cummins Inc. 36 A053X172 (Issue 8)


4-2017 4. Installation

No. Description No. Description


1 Distance as Required by Code and/or 6 Full Flow Manual Shutoff Valve
Component Suppliers
2 Secondary Service Pressure Regulator 7 Flexible Fuel Line
3 Primary Service Pressure Regulator 8 Sediment Trap
4 Liquid Propane Fuel Tank 9 Fuel Line Connection at Generator Set
5 Note: A branch in the fuel line to the 10 Generator Set
generator set may allow selection of a
smaller diameter line size to the
generator set and the remainder of gas
appliances.
FIGURE 7. TYPICAL PROPANE INSTALLATION
Propane Fuel Requirements
WARNING
Propane presents the hazard of fire or explosion that can cause severe
personal injury or death. Do not permit any flame, spark, arc-producing
equipment, switch, pilot light, cigarette, or other ignition source near
the fuel system. Keep an ABC type fire extinguisher nearby.

WARNING
Fuel leaks can lead to explosive accumulations of gas. Propane sinks
in air and can accumulate inside housings, basements and other
below-grade spaces. Prevent gas leaks and the accumulation of
gaseous fuel in the event of a leak.

A053X172 (Issue 8) 37 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

Use clean, fresh HD-5 grade propane or equivalent product consisting of at


least 90% propane.

NOTICE
NFPA Standard No. 58 requires all persons handling and operating
propane to be trained in proper handling and operating procedures.

NOTICE
Commercial propane may contain more than 2.5% butane, which can
result in poor fuel vaporization and low tank pressure, resulting in poor
engine starting and operation in below 32 °F (O °C) temperatures.

Propane Tank Size


When propane is used, size the tank correctly to ensure successful generator
set operation.
Considerations when figuring the proper propane tank size:
• Temperature is a critical factor that affects the size of the tank.
◦ Ambient temperatures can affect how quickly liquid is converted to
gas.
◦ Generator set fuel consumption is the same regardless of the
surrounding temperatures.
◦ Colder weather climates require larger fuel tanks. Larger tanks have
greater surface area, allowing more liquid propane to vaporize and
maintain the required fuel rate.
◦ Propane is stored as liquid. Keep the fuel tank at least 50% full to
operate properly. Fuel tanks that are less than 50% full may not have
the capacity to vaporize enough propane to operate the generator set
and other LP appliances.
• Propane tanks are sized by their internal volume in gallons, not the
amount of fuel they can hold (which is less).
• Propane tanks are generally filled to only 80% of their capacity.
Therefore, a 500-gallon (1892 L) tank results in 400-gallon (1514 L) tank
capacity.
• Low ambient temperatures affect the amount of fuel available from the
propane tank.
• Approximately 60% of the fuel (in gallons) filled in the tank can be
effectively used. Therefore, a 500-gallon (1892 L) tank results in 240-
gallon (908 L) usable capacity.

Copyright © 2017 Cummins Inc. 38 A053X172 (Issue 8)


4-2017 4. Installation

To assist in the proper installation of the propane tank, follow the guidelines
below.
• Consult your tank and propane supplier for assistance in all aspects of
determining tank size, selection of components and installation
requirements.
• Fit the propane tanks with a pressure reducing regulator before
connection to the generator set to prevent fuel system damage.
• Locate the propane tanks and all other fuel system components at least
10 feet (3 meters) from any source of combustion (including the generator
set). The fuel supplier or local code may require a larger distance
between the tank and source of combustion.
• Install the propane tanks according to all national and local codes and
standards, and as required by the fuel tank and fuel supplier.
Refer to the Fuel Line Selection appendix for propane figures and tables.
Propane Vapor Fuel Supply Line Size and Pressure
Fuel line size depends on the amount of fuel needed to run the generator set
at full load at the distance the fuel must be moved.
To correctly size the fuel pipe, you must also take other loads operated from
the fuel supply line into consideration, such as space heating and water
heating equipment.
Use the total fuel requirement of the generator set and other connected
appliances to determine the size of the fuel supply pipe. Use the tables and
charts in the Fuel Line Selection appendix to determine the correct pipe size.
See the Model Specifications section for fuel system specifications, including
fuel consumption and required fuel system pressure at the generator set.
See the Propane Fuel System section for a typical propane vapor installation.
See the Fuel Line Selection appendix for fuel capacity at given distances and
pipe size.

NOTICE
Make sure the fuel supply pressure at the inlet of the generator set fuel
regulator (at service port) matches the requirements in the Model
Specifications section.

A053X172 (Issue 8) 39 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

Converting the Fuel System Type


The generator set leaves the factory set up for natural gas. For operation on
liquid propane vapor, the generator set must be converted by configuring the
generator set control for propane and manually changing the fuel valve
position from natural gas to propane.
1. To change the generator set control's fuel type from natural gas to liquid
propane vapor:
a. From the Main screen, select Menu.
b. Press and hold the Next key on the Menu screen for at least 5
seconds to view the Config Menu.
c. Use the arrow keys to highlight "Config" and click the Enter key. The
Generator Config screen appears.
d. Use the Next key to navigate to the Fuel Type field. Use the arrow
keys to select the fuel type: NG (natural gas; default) or LP (liquid
propane).

NOTICE
Do not change the number in the Config field.

NOTICE
The Rating field is not configurable by the user. Instead, it will
be automatically populated based on the Config and Fuel Type
field selections.

e. Keep selecting the Back button to save the settings and return to the
Main screen.

Copyright © 2017 Cummins Inc. 40 A053X172 (Issue 8)


4-2017 4. Installation

FIGURE 8. GENERATOR CONFIG SCREEN


2. Adjust the manual fuel selector to the LP setting:
a. Use a 6 mm external hex wrench to rotate the center section of the
fuel valve.
b. Turn the center section clockwise until the detent is reached.
c. When you reach the detent, the required force to turn the valve will
increase significantly - do not rotate center section of valve beyond
this point.

A053X172 (Issue 8) 41 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

FIGURE 9. LOCATION OF FUEL SELECTOR VALVE

No. Description No. Description


1 Natural Gas Fuel Position 2 Liquid Propane Vapor Fuel Position
FIGURE 10. MANUAL FUEL SELECTOR

Testing the Fuel System for Leaks


After assembly and before initial operation, all of the fuel system components must
be tested and proven free of any leaks.

Copyright © 2017 Cummins Inc. 42 A053X172 (Issue 8)


4-2017 4. Installation

WARNING
Fuel presents the hazard of explosion or fire which can result in severe
personal injury or death. Do not use an open flame to check for leaks. Do not
smoke or allow any flame, spark, pilot light, arc-producing equipment, switch
or other ignition sources around fuel or fuel components. Keep multi-class
ABC fire extinguishers handy.

NOTICE
Follow any local codes and standards, as they may require a different
method or documentation of a leak test.

Perform the following fuel piping system leak check:


1. After assembly and before initial operation of generator set, test all fuel system
components as required per the National Fuel Gas Code (NFPA 54).
2. The National Fuel Gas Code requires that the generator set be isolated from
the piping system by disconnecting it and capping the outlet prior to test. The
test pressure required is the greater of 1.5 times the supply pressure or 3 psi
(20.7 kPa) minimum.
3. After successfully completing the previous step, connect the generator set to
the fuel piping system.
4. To verify that all connections from the fuel piping system to the generator set
are free of leaks, conduct a bubble test using an approved leak detection
solution (or equivalent method) with the system pressure of 0.8 to 1.0 psi (5.5 to
7.0 kPa).
5. Spray the bubble solution on all of the joints.
6. Inspect all of the joints and monitor the line pressure. If bubbles appear, there is
a leak.
7. If any leaks are found, repair the joint or replace components as needed.
8. Verify the leak has been fixed.

NOTICE
The leak detection solution (that is, bubble solution) must be non-corrosive
and be free of ammonia and chlorine.

4.3 Engine Exhaust


The exhaust system for this generator set is complete and was designed specifically
for this generator set. Do not modify or add to the exhaust system of this generator
set.

A053X172 (Issue 8) 43 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

WARNING
Exhaust gas is deadly. Make sure that the exhaust system terminates away
from building vents, windows, doors, and sheltered spaces that may not
have ample fresh air ventilation.

WARNING
Engine discharge air and exhaust carry carbon monoxide gas (odorless and
invisible) which can cause asphyxiation and death. Never use engine
discharge air or exhaust for heating a room or enclosed space.

4.4 Electrical Connections


WARNING
Improper installation can lead to electrocution and damage to property.
Electrical connections must be made by a licensed electrician.

NOTICE
Refer to regional codes and the National Electrical Code (NFPA 70) for all
electrical installation requirements.

NOTICE
Class 1 wiring methods must be used for connecting the generator set.

Electrical Preparations
1. Run all wires through a single conduit (unless prohibited by the authority having
jurisdiction).

NOTICE
Be sure to account for any needed accessories, such as a remote
display, etc.

2. Connect the conduit to the generator set. Refer to the specific outline drawing in
the Outline and System Drawings section for the size and location of the hole
provided for electrical conduit connection. The existing hole may be increased
in size to match conduit used.
3. Route and secure customer wiring along the generator set harness above the
engine intake manifold, using wire ties.

Copyright © 2017 Cummins Inc. 44 A053X172 (Issue 8)


4-2017 4. Installation

AC Connections
WARNING
Automatic startup of the generator set during installation can cause severe
personal injury or death.
Make sure the generator set is shut down and disabled:
1. Press the generator set's red STOP button on the local display to stop
the generator set. Allow the generator set to thoroughly cool to the
touch.
2. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.

For grounding and neutral connections, look for the following symbols on the
generator set. The neutral connection is at the rear of the breaker box; the ground
connection is inside the enclosure on the panel to the left of the breaker box.

Equipment Grounding Conductor Symbol Equipment Neutral Connection Symbol

FIGURE 11. SYMBOLS ON CIRCUIT BREAKER BOX

A053X172 (Issue 8) 45 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

No. Description No. Description


1 L1 2 L2
FIGURE 12. CIRCUIT BREAKER AC LOAD CONNECTIONS LOCATION
Make the AC load connections to the generator set in the circuit breaker box as
follows:
1. Open the circuit breaker box door.
2. Place the circuit breaker handle in the OFF position.
3. Lift the top cover. Undo the two screws on top of the intake panel and remove
the panel.
4. Route the load conductors through the access holes found at the bottom of the
circuit breaker box.
5. Connect the conductors to the circuit breaker load side terminals. Torque the
circuit breaker terminals to 45 in-lb (5 Nm).
6. Unless there is no utility source connected to ATS or house loads, remove the
bonding jumper from the neutral lug on the back of the circuit breaker box to the
equipment grounding lug as shown in Figure 12. Refer to NFPA 70E or CEC.
7. Install the neutral line to the neutral lug found on the back of the circuit breaker
box. Torque the neutral lug to 120 in-lb (13.6 Nm).
8. Install the ground line to the equipment grounding lug. Torque the equipment
grounding lug to 120 in-lb (13.6 Nm).

Copyright © 2017 Cummins Inc. 46 A053X172 (Issue 8)


4-2017 4. Installation

9. Install the circuit breaker cover with the screw provided. Torque the pan-head
screw to 12 in-lb (1.36 Nm).
10. Reinstall the intake panel.
11. Reinstall the two screws. Torque to 44 - 58 in-lb (5 - 6.6 Nm).
12. Close the lid and lock it if the installation is complete.
13. Close the circuit breaker box door.

Automatic Transfer Switch AC Connections


WARNING
Failure to use an approved transfer switch can lead to the electrocution
of personnel working on the utility lines, damage to equipment, fire, or
personal injury. An approved switching device must be used to prevent
interconnection to the public utility.

Install the transfer switch in accordance with the appropriate RA series


transfer switch owner manual.
Customer AC Connections
The customer supplied AC circuit is used to power the following components:
• Alternator heater (if applicable)
• Battery charger (standard)
• Battery heater (if applicable)
• Engine oil heater (if applicable)
The AC circuit must be 120 VAC, 20 Amp protected. The wires from this
customer supplied circuit are terminated within the enclosure at the five place
connectors labeled "Ground", "Line" and "Neutral". Follow regional
regulations and applicable electrical codes for installation.

A053X172 (Issue 8) 47 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

FIGURE 13. CUSTOMER AC CONNECTIONS

DC Connections
NOTICE
See the Wiring Diagrams appendix for DC customer connections.

Automatic Transfer Switch (ATS) DC Connections


WARNING
Failure to use an approved transfer switch can lead to the electrocution
of personnel working on the utility lines, damage to equipment, fire, or
personal injury. An approved switching device must be used to prevent
interconnection to the public utility.

Install the transfer switch in accordance with the appropriate RA Series


Transfer Switch Owner Manual.
The following image shows the location of the connectors in the generator
set where the ATS DC control wires terminate. This is also the location of the
connectors where load management control wires terminate.

Copyright © 2017 Cummins Inc. 48 A053X172 (Issue 8)


4-2017 4. Installation

NOTICE
Class 1 wiring methods should be used for connecting the generator
set and transfer switch signal wiring.

FIGURE 14. LOCATION OF CONNECTION POINTS FOR ATS DC CONTROL WIRES


AND LOAD MANAGEMENT CONTROL WIRES
Refer to the Wiring Diagrams appendix for generator set to RA transfer switch
DC customer connections.

Grounding
Use the Typical System Grounding One-Line Diagrams in this section to be sure
that the generator set, transfer switch, power supply wiring and all connected
electrical equipment are bonded to a common grounding point in accordance with
the applicable codes and standards. Refer to local codes and standards for
grounding procedures.

NOTICE
The generator set grounding terminal must be connected to the grounding
terminal in the transfer switch. Do not provide a separate grounding rod for
the generator set.

A053X172 (Issue 8) 49 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

NOTICE
Generator set neutral is not typically grounded at the generator set, but at
the common system grounding point.

WARNING
Contact with electrical equipment can result in severe personal injury or
death. It is extremely important that bonding and equipment grounding be
properly done. All metallic parts that could become energized under
abnormal conditions must be properly grounded.

No. Description No. Description


1 Service Entrance 4 Loads
2 2-Pole Transfer Switch 5 To Utility Service
3 Generator Set
FIGURE 15. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAM (SEPARATE
SERVICE ENTRANCE AND 2-POLE TRANSFER SWITCH)

Copyright © 2017 Cummins Inc. 50 A053X172 (Issue 8)


4-2017 4. Installation

No. Description No. Description


1 Combined Service Entrance and 2- 3 Loads
Pole Transfer Switch
2 Generator Set 4 To Utility Service
FIGURE 16. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAM (COMBINED
SERVICE ENTRANCE AND 2-POLE TRANSFER SWITCH)

Display Communication Wires


NOTICE
There are two unmarked connectors on the back of the display, either one
may be used for connecting the display to the generator set.

Class 1 wiring methods should be used for the remote display and transfer switch
communication conductors between the generator set and transfer switch.
See the Operator Manual for information regarding using the display to operate and
monitor the generator set.

Load Management Wiring


See the Automatic Transfer Switch (ATS) DC Connections section for the location of
the connectors (TB-1, TB-2, TB-3, and TB-4) in the generator set, which are used
for load management control wire termination. Class 1 wiring methods should be
used for installing load management devices.
Cummins offers a kit for load management wiring (A051C329).

A053X172 (Issue 8) 51 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

Battery
The generator set requires a 12V battery for engine cranking and powering the
electronic control system. When the generator set is running, the battery is charged
from the engine-driven battery charger. When the generator set is not running, an
AC powered battery charger is provided to keep the battery charged.

WARNING
To avoid injury, wear proper safety protection when working around
batteries. Keep open flames and sparks away from the equipment.

WARNING
Automatic startup of the generator set during installation can cause severe
personal injury or death. Make sure the generator set is shut down and
disabled:
1. Press the generator set's red STOP button on the local display to stop
the generator set. Allow the generator set to thoroughly cool to the
touch.
2. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.

To connect the battery:


1. Connect the battery cables to the battery with the positive (+) cable first.
Immediately cover the battery post and terminal with the red terminal cover
provided on the battery cable.
2. Connect the negative (-) cable to the battery's minus terminal.
Refer to the Model Specifications section for battery specifications.
An optional thermostatically controlled battery heater is available for more reliable
starting.

Copyright © 2017 Cummins Inc. 52 A053X172 (Issue 8)


4-2017 4. Installation

FIGURE 17. BATTERY LOCATION

A053X172 (Issue 8) 53 Copyright © 2017 Cummins Inc.


4. Installation 4-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 54 A053X172 (Issue 8)


5 Startup and Configuration

5.1 "Establishing Communications" Message


NOTICE
Once the battery is connected to the generator set and any display button is
pressed, the local display shows an "establishing communications"
message for approximately 5 seconds. (This may take longer if the signal
integrity is poor between the control and display due to a bad wire or
Electro-Magnetic Interference [EMI].) Once communication is established,
the display shows the HOME screen.
The “establishing communications” message will also be displayed
whenever the control is brought out of “sleep” mode by pressing any button
on the display. Sleep mode is entered after 30 minutes without utility or
generator set power to preserve battery energy since the battery charger will
not have AC power. The 30-minute timer is reset with any button press on
the display.

5.2 "Clock Setup" Screen


NOTICE
The Clock needs to be reset whenever the battery power is lost or
disconnected, or the control has entered “sleep” mode. Sleep mode is
entered after 30 minutes without utility or generator set power to preserve
battery energy since the battery charger will not have AC power. The 30-
minute timer is reset with any button press on the display.

NOTICE
The optional Remote Monitoring System (RMS) uses the generator set's
clock. The clock must be set accurately for the RMS to function properly.

To set up the generator set clock for the current date and time:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Clock. Select the Enter key.
3. Use the arrow keys to set the time and date.

A053X172 (Issue 8) 55 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

FIGURE 18. CLOCK SETUP SCREEN


4. Select the Next key to go to the Daylight Savings screen.

Copyright © 2017 Cummins Inc. 56 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

5. Use the arrow keys to enable/disable Daylight Savings. If enabling, select the
Next key to highlight the Offset field.

FIGURE 19. DAYLIGHT SAVINGS TIME (ENABLED)


6. Use the arrow keys and Next key to set the offset value for Daylight Savings
time.

A053X172 (Issue 8) 57 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

FIGURE 20. OFFSET VALUE


7. Select the Next key to go the screen that is used to set up when Daylight
Savings should start. Use the arrow keys and Next key to set Month (1 – 12),
Week (0 – 5), Day (Sun – Sat) and Hour (12AM – 12PM).

Copyright © 2017 Cummins Inc. 58 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 21. DAYLIGHT SAVINGS TIME (START TIME SETUP)


8. Select the Next key to go the screen that is used to set up when Daylight
Savings should end. Use the arrow keys and Next key to set Month (1 – 12),
Week (0 – 5), Day (Sun – Sat) and Hour (12AM – 12PM).

A053X172 (Issue 8) 59 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

FIGURE 22. DAYLIGHT SAVINGS TIME (END TIME SETUP)


9. Keep selecting the Back button to save the settings and return to the main
screen.

Copyright © 2017 Cummins Inc. 60 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

5.3 "Exercise" Screen


When installing an RA series transfer switch, follow these steps to configure the
Exercise mode in the generator set's local display or remote display.

NOTICE
Exercise settings need to be reset whenever battery power is lost or
disconnected, or the control has entered “sleep” mode.

NOTICE
Sleep mode is entered after 30 minutes without utility or generator set power
to preserve battery energy since the battery charger will not have AC power.
The 30-minute timer is reset with any button press on the display.

To set up the exercise function:


1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Exercise. Select the Enter key.

NOTICE
If the time and date have not been set, a pop-up will appear that says,
"Set Valid Date and Time".

3. Use the arrow keys to enable or disable the Crank Exercise feature. Select
the Next key to go to the Exercise Time field. See the Exercise Sequences
section in the operator manual for more information.

NOTICE
When the Crank Exercise feature is enabled, an exercise command will
cause the engine starter to engage and rotate the engine, but will not
allow the engine to start. This feature allows the control system to
monitor critical generator set systems without running the engine. When
Crank Exercise is enabled, the generator set's exercising will alternate
between the Crank Exercise sequence and the normal exercise sequence
(that is, engine running) at scheduled times.

4. Use the arrow keys to set how long the generator set will exercise (from 1 to 20
minutes). Select the Next key to go to the Exercise field. The Exercise Sched
screen appears.
5. Use the arrow keys to set how often the generator set will exercise. The
frequency selections are:
• Weekly
• Bimonthly
• Monthly

A053X172 (Issue 8) 61 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

• Never
Select the Next key to go to the date and time fields.
6. Use the arrow keys to set the day and time the generator set will be exercised.
Select the Next key to highlight the Exercise Now field.
7. Select either arrow key to start the Exercise Now function.

NOTICE
Initiating the Exercise Now function will cause the generator set to start
immediately and run for the amount of time indicated by the Exercise
Time field, or run the Crank Exercise sequence. The ATS does not
transfer to generator power during exercise mode. Normally scheduled
exercise events will occur after the completion of the immediate exercise
event.

8. Keep selecting the Back button to save the settings and return to the Main
screen.

Copyright © 2017 Cummins Inc. 62 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 23. EXERCISE SETUP SCREEN

A053X172 (Issue 8) 63 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

5.4 "Brightness and Contrast" Screen


To adjust the brightness and contrast of the display:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Display Setup. Select the Enter key.
3. Use the arrow keys to set brightness and contrast for the display.
4. Keep selecting the Back button to save the settings and return to the Main
screen.

Copyright © 2017 Cummins Inc. 64 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 24. BRIGHTNESS AND CONTRAST SCREEN

A053X172 (Issue 8) 65 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

5.5 "About" Screen


To retrieve information about the display:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight About. Select the Enter key.

Copyright © 2017 Cummins Inc. 66 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 25. ABOUT SCREEN

A053X172 (Issue 8) 67 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

5.6 "Event Log" Screen


To retrieve information from the Event Log:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Event Log. Select the Enter key.
3. Use the arrow keys to navigate through the Event Log.
4. Keep pressing the Back button to return to the Main screen.

FIGURE 26. EVENT LOG SCREEN

Copyright © 2017 Cummins Inc. 68 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

5.7 "Fault Log" Screen


To retrieve information from the Fault Log:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Fault Log. Select the Enter key.
3. Scroll through the fault log using the up and down double-arrows. Each screen
provides a brief description of the fault, the fault code number, the engine hours
and the time and date of the fault.

NOTICE
If there are no faults recorded, the “No Stored Faults" screen will appear.

4. Keep pressing the Back button to return to the Main screen.

A053X172 (Issue 8) 69 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

FIGURE 27. FAULT LOG SCREEN

5.8 "System Status" Screen


To retrieve system status:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight System Status. Select the Enter key.
3. Keep pressing the Back button to return to the Main screen.

Copyright © 2017 Cummins Inc. 70 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 28. SYSTEM STATUS SCREEN

5.9 "Mode" Screen


WARNING
To prevent unexpected starts from remote devices, disable Remote mode
and disconnect the connector on the back of the local display wired to any
remote mounted displays.

When Remote is set to Enabled via the local display, the “Remote On” LED on the
front of the display will illuminate indicating that the control will accept start
commands from remote displays or remote monitoring systems including a web
page or cell phone app.

A053X172 (Issue 8) 71 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

NOTICE
The Remote function can only be activated (that is, enabled) from the local
display.

When Standby is on or set to Enabled, the “Standby On” LED on the front of the
display will illuminate indicating the control will start the generator set in response to
a utility power outage. Standby can be turned on at the local display. It can also be
enabled with a remote display, web page, or a cell phone app if Remote has already
been enabled at the local display. The Standby function cannot be enabled
remotely unless the Remote function is on. A manual Start or Stop event will disable
the Standby function. (If the manual Stop event is performed at the local display, the
Remote mode will also be disabled.)
1. To enable or disable the Remote and Standby modes on the LOCAL display:
a. From any screen, select the Mode key to get to the Mode screen.
b. Use the arrow keys to enable or disable the Remote mode. Select the Next
key to go to the next screen.
c. Use the arrow keys to enable or disable the Standby mode.

NOTICE
Whenever Standby is enabled, the Remote mode will also
automatically be enabled.

d. Keep pressing the Back button to save the settings and return to the Main
screen.

Copyright © 2017 Cummins Inc. 72 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

FIGURE 29. MODE SETUP SCREEN (LOCAL DISPLAY)


2. To enable or disable the Standby mode on the REMOTE display:

NOTICE
Remote must be enabled before Standby mode can be changed from the
Remote display. If Remote mode is not enabled, Standby will remain
disabled and cannot be changed.

a. From any screen, select the Mode key to get to the Mode screen.
b. Use the arrow keys to enable or disable the Standby mode.
c. Keep pressing the Back button to save the settings and return to the Main
screen.

FIGURE 30. MODE SETUP SCREEN (REMOTE DISPLAY)

A053X172 (Issue 8) 73 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

5.10 Automatic Load Management


NOTICE
The capability to automatically add or remove specific electrical loads from
the generator set requires that load management devices be wired to the
generator set load management outputs.

When the generator set is started automatically in Standby mode due to a loss of
utility or manually by the operator, the control will energize all four load
management outputs, disconnecting the associated loads from AC power. Once
the transfer switch transfers to generator set power, the generator set control will
evaluate the total load on the generator set versus a set point programmed into the
control (80% of rated).
If the generator set’s total load is below the set point, the generator set control will
sequentially add the highest priority managed load every three minutes. Managed
loads will continue to be added as long as the size of the next priority load to be
added won’t increase total generator set load above the set point. The control
measures and stores the size of each managed load in its memory. Load priorities
are in the following order:
• Priority #1: load control 1
• Priority #2: load control 2
• Priority #3: load control 3
• Priority #4: load control 4
If the load on the generator set is reduced at any time to below the set point, the
control will add the next highest priority managed load in three minutes provided it
does not increase the total generator set load above the set point.
If the load on the generator set exceeds 95% of its rating, the generator set control
will begin disconnecting the lowest managed priority loads in sequence every
second until the load on the generator set is below 95% of its rating.
Priority #1 load is always the first added and the last disconnected; therefore, it
should be wired to the managed load deemed most critical to the homeowner.
Priority #2 load cannot be added before priority #1 load, nor can it be disconnected
before priority #3 or #4, etc.

Copyright © 2017 Cummins Inc. 74 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

5.11 Manual Start Sequence (Local)


NOTICE
If the utility power supply to the generator set's utility powered battery
charger is interrupted, the battery can become discharged due to parasitic
loads and the generator set may not start when needed. Whenever utility
power is interrupted and the generator set is not in Standby mode for any
reason (fuel preservation, etc.), start and run the generator set for 2 hours
every 24 hour period when temperatures are above 50 °F (10 °C), or every 9
hour period when temperatures are below 50 °F (10 °C).

The following steps will be executed when Manual Start is used at the local display:
1. If you do not want the ATS to transfer load to the generator set, open the
generator set mounted circuit breaker when doing a manual start.
2. From the Main screen, select the START key.
3. A second screen appears notifying the operator that Standby will be disabled.
Select the START key again to start the generator set.
4. After the generator set reaches rated voltage and frequency, the transfer switch
transfers the building load to the generator set (unless the circuit breaker on the
generator set is "off"). The building's electrical power is now provided by the
generator set.

FIGURE 31. GENSET POWER

5.12 Checklist
Tick Area
General
Generator set output is sufficient to handle maximum anticipated load.

A053X172 (Issue 8) 75 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

Tick Area
Proper clearance is provided around the entire generator set for service and
ventilation:
• All parts of the generator set enclosure must be at least 60 inches (1524 mm)
from any openings in walls of structures that may be occupied. Examples of wall
openings include but are not limited to: operable windows, doors, dryer vents,
fresh air intake for heaters, etc.
• The engine side and alternator side of the generator set must be located as
follows:
◦ One side (either engine or alternator) must be located not less than 18
inches (458 mm) from any structures having combustible walls. This space
must be free of any obstructions for service access.
◦ The opposite side must be located not less than 60 inches (1524 mm) from
any structures having combustible walls. A minimum of 18 inches (458 mm)
of unobstructed space is required for service access.
• The intake (cooling air inlet) side of the generator set must be located not less
than 30 inches (762 mm) from any structures having combustible walls. This
space must be free of obstructions to air flow and service access.
• The generator set must be located such that exhaust gases are not able to
accumulate in an occupied area. The air discharge side must always be
unobstructed and spaced a minimum of 60 inches (1524 mm) from any structures
having combustible walls. A minimum of 36 inches (915 mm) must be free of any
combustible items, and unobstructed for service access.
• The generator set must have enough room for installation, service, and
maintenance.
• The generator set must be located to ensure ventilation openings are not blocked.
• Position the generator set so that cooling air is free to enter and leave the area.
• Locate and position the generator set so that prevailing winds carry exhaust
gases and potential fuel leaks away from the house or occupied area.
The generator set is located in an area not subject to flooding.
The generator set's service regulator is installed above the snow line.
All operating personnel have read and are familiar with the generator set operator
manual, all health and safety procedures, and all other documentation supplied with
the generator set.
All operators have been thoroughly briefed on preventive maintenance procedures.
Proper clearance to openings in nearby structures is provided. Clearance around and
over the generator set is provided for operation, service and maintenance.
Generator Set Mounting Pad
The earth on which the generator set mounting pad rests is strong enough and will not
allow shifting or movement. Observe local codes on soil bearing capacity.

Copyright © 2017 Cummins Inc. 76 A053X172 (Issue 8)


4-2017 5. Startup and Configuration

Tick Area
The generator set is properly supported and attached to an approved base.
The supporting base is of non-combustible material and extends 2 inches (50.8 mm)
all around the generator set.
The generator set is located to comply with applicable codes and standards.
Fuel System
Verify that the generator set is configured to the fuel being used. (See the Fuel
Selection and Fuel System Connection section.)
Verify that the fuel line has proper volume capability.
Verify that fuel pressure is correct:
• Natural gas: 3.5 - 12 inch water column (0.9 - 3.0 kPa)
• Propane: 6 - 12 inch water column (1.5 - 3.0 kPa)
Maximum pressure for either fuel under any condition: 13 inch water column (3.2 kPa)
Verify the fuel pressure at the generator set connection does not drop below the range
listed above during startup and full load operation and does not exceed 13 inch water
column (3.2 kPa).
Verify that all fuel connections are tight.
Verify there are no gas leaks in the fuel system.
All electrical and fuel lines are properly separated.
An approved flexible fuel line is properly installed between the generator set fuel inlet
connection and the fuel supply line.
Exhaust System
All areas around the generator set are well ventilated, with no possibility of exhaust
fumes entering building doors, windows, or intake fans.
AC and DC Wiring
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
All load, line and generator set connections are well made and correct.
Flexible conduit is used between the generator set and the building or surrounding
structure.
A transfer switch has been installed properly to prevent connecting the generator set
to the utility.
Verify that 120 VAC power has been provided to the power battery charger and other
AC accessories on the generator set.
Generator Set Pre-Start
The generator set engine is properly serviced with oil.
All generator set and ATS covers and safety shields are installed correctly.

A053X172 (Issue 8) 77 Copyright © 2017 Cummins Inc.


5. Startup and Configuration 4-2017

Tick Area
All fuel shutoff valves are operational and in the open position.
The installation meets all applicable local, state, and federal codes.
Control
Verify that the clock, exerciser and correct fuel type are set.

5.13 Startup
1. Verify that the installation was completed correctly.
2. Read the operator manual. Perform the pre-start checks as instructed.
3. Connect the battery cables to the battery with the positive (+) cable first.
Immediately cover the battery post and terminal with the red cover provided on
the battery cable.
4. Although the generator set is shipped from the factory with the proper level of
engine oil, check the oil level before it is started.
5. Start and test the system.
6. Operate the generator set following all the instructions and precautions in the
operator manual.

NOTICE
Before leaving the site, if the generator set is ready to be placed in service,
enable the Remote and Standby modes from the local display.

NOTICE
Contact your local Cummins service provider if you encounter a fault code.

Copyright © 2017 Cummins Inc. 78 A053X172 (Issue 8)


6 Optional Remote Monitoring System
(RMS) Description

6.1 Introduction
The Remote Monitoring System (RMS) feature allows for in-home or remote access
to your generator set through a web page or smart phone app. Using the RMS, you
can start or stop the generator set, adjust the exerciser date and time, determine if
utility power is available, and view the last 20 events and/or faults on the generator
set. This feature can also help to reduce troubleshooting time and the number of
service calls if a generator service provider has access to the same information.
The internet/email interface can make the same fault, maintenance, and event
notifications available to you and to your generator set service provider with an
appropriate account setup.
RMS is optional. If you do not wish to use this service or do not have an Ethernet
connection available, you are not required to set up an RMS account.

NOTICE
Technical support for setup and troubleshooting of the RMS is available
through the selling Cummins Inc. dealer/distributor.
However, due to variations in network equipment, network configurations,
and internet and cellular service providers, the owner may be required to
contact their Internet Service Provider, email service provider, or cellular
service provider for technical support regarding internet connectivity, email
notifications, and smart phone applications support.
Cummins does not provide technical support for the setup and
troubleshooting of the owner's network, email, and cellular service.

NOTICE
The following Internet browsers are compatible with this option:
• Microsoft Internet Explorer® (version 9 or greater)
• Apple Safari®
• Google Chrome™
• Mozilla Firefox® (version 3.6 or greater)
• Microsoft® Edge

A053X172 (Issue 8) 79 Copyright © 2017 Cummins Inc.


6. Optional Remote Monitoring System (RMS) Description 4-2017

6.2 Optional Remote Monitoring System (RMS)


Account Setup and Generator Set Control
Connection
1. Prior to setting up the account, ensure that the generator set control is
connected to the Internet via an Ethernet cable between the generator set
control and the home’s router.
2. Access the Cummins ConnectCloud website by navigating to
ConnectCloud.Cummins.com.
3. Click on Register to create your account.
4. Add a generator set to your account, using the Serial Number and Customer
Access Code from your generator set. The Serial Number and Customer
Access Code can be found on the display in the Menu/About section.

NOTICE
Android and iPhone apps for the Cummins ConnectCloud are also
available.

Copyright © 2017 Cummins Inc. 80 A053X172 (Issue 8)


Appendix A. Fuel Line Selection

Table of Contents
Table 17. Required Information for Determining Fuel Line Size ............................................................. 82
Table 19. Equivalent Lengths of Pipe Fittings and Valves in Feet (Meters) ........................................... 83
Table 21. Natural Gas Schedule 40 Metallic Pipe Sizing .......................................................................... 85
Table 23. Natural Gas Semirigid Copper Tubing Sizing ........................................................................... 87
Table 25. Propane Vapor Schedule 40 Metallic Pipe Sizing .................................................................... 89
Table 27. Propane Vapor Semirigid Copper Tubing Sizing ..................................................................... 90
Table 29. Propane Schedule 40 Iron Pipe Sizing, Liquid Withdrawal (Maximum Capacity of Pipe in
Cubic Feet of Gas per Hour)* ...................................................................................................................... 92
Figure 32. Minimum LPG Tank Size (50% Full) Required to Maintain 5 PSIG at Specific Withdrawal
Rate and Minimum Expected Winter Temperature ................................................................................... 94

A053X172 (Issue 8) 81 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

A.0 Fuel System Pipe Sizing Introduction


Incorrect fuel line size may cause the generator set to not run or provide
full power output.
Tables are included in this section to help calculate pipe sizing for natural
gas and propane vapor withdrawal under specified conditions. Consult
NFPA 54 or other applicable codes for other operating conditions or other
fuel system installation requirements.
Refer to the Engineering Application Manual T-030: Liquid Cooled
Generator Sets manual (A040S369) for more information.
To determine the optimal fuel line size, the following information is
needed:

TABLE 17. REQUIRED INFORMATION FOR DETERMINING FUEL


LINE SIZE

Category Description
Fuel Flow Fuel flow requirements have a large impact on fuel
Requirements for line size.
the Generator Set
Fuel Source Fuel sources can affect fuel line size. Natural gas
(Natural Gas or installations generally require a higher fuel flow rate
Propane Vapor) compared to propane vapor installations, since
propane has a higher energy content.
Fuel Line Length As fuel line lengths increase, they may require larger
(Including Fittings) diameter fuel lines. Be sure to consider the
equivalent length of all of the fittings (elbows, tees,
valves) in the installation in addition to the straight
pipe length.
Fuel Line Type Most fuel line types are iron pipe or copper tubing.
(e.g., Copper Be sure to use the sizing chart for the fuel line type
Tubing or Iron when sizing the fuel line.
Pipe)

NOTICE
NFPA 54 has selection tables for other approved fuel lines. Verify
with the authorities having jurisdiction the allowed fuel line type for
the generator set installation.

Copyright © 2017 Cummins Inc. 82 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

A.1 Gas Pipe Sizing


NOTICE
The following tables in this section are reprinted with permission
from NFPA 54-2015, National Fuel Gas Code, Copyright © 2014,
National Fire Protection Association.
• Natural Gas Schedule 40 Metallic Pipe Sizing
• Natural Gas Semirigid Copper Tubing Sizing
• Propane Vapor Schedule 40 Iron Pipe Sizing
• Propane Vapor Semirigid Copper Tubing Sizing
• Propane Schedule 40 Iron Pipe Sizing, Liquid Withdrawal
(Maximum Capacity of Pipe in Cubic Feet of Gas per Hour)
This reprinted material is not the complete and official position of
the NFPA on the referenced subject, which is represented only by
the standard in its entirety.

Sizing of gas piping for proper fuel delivery, both flow and pressure, can
become quite complex. A simplified method is to convert all fittings,
valves, etc. to equivalent lengths of pipe in the diameter(s) being
considered. The total equivalent length can then be related to flow
capacity. Equivalent lengths of pipe fittings and valves can be found in the
table below.

TABLE 19. EQUIVALENT LENGTHS OF PIPE FITTINGS AND VALVES IN FEET


(METERS)

NOMINAL INCH (MILLIMETER) PIPE SIZE


TYPE OF
FITTING 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
(15) (20) (25) (32) (40) (50) (65) (80) (100)
90° Std. Elbow or 1.6 2.0 2.6 3.3 4.0 5.0 6.0 7.5 10.0
Tee Reduced ½. (0.5) (0.6) (0.8) (1.0) (1.2) (1.5) (1.8) (2.3) (3.1)
90° Long Radius 1.0 1.4 1.7 2.3 2.6 3.3 4.1 5.0 6.7
Elbow or Straight (0.3) (0.4) (0.5) (0.7) (0.8) (1.0) (1.3) (1.5) (2.0)
Run Tee
45° Elbow 0.8 0.9 1.3 1.7 2.1 2.6 3.2 4.0 5.2
(0.2) (0.3) (0.4) (0.5) (0.6) (0.8) (1.0) (1.2) (1.6)
180° Std. Bend 2.5 3.2 4.1 5.6 6.3 8.2 10.0 12.0 17.0
(0.8) (1.0) (1.2) (1.7) (1.9) (2.5) (3.1) (3.7) (5.2)
TEE, Side Inlet or 3.0 4.0 5.0 7.0 8.0 10.0 12.0 15.0 21.0
Outlet (0.9) (1.2) (1.5) (2.1) (2.4) (3.0) (3.7) (4.6) (6.4)

A053X172 (Issue 8) 83 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

Foot Valve and 3.7 4.9 7.5 8.9 11.0 15.0 18.0 22.0 29.0
Strainer (1.1) (1.5) (2.3) (2.7) (3.4) (4.6) (5.5) (6.7) (8.8)
Swing Check 6.0 8.0 10.0 14.0 16.0 20.0 25.0 30.0 40.0
Valve, (1.8) (2.4) (3.0) (4.3) (4.9) (6.1) (7.6) (9.1) (12.2)
Fully Open
Globe Valve, 18.0 22.0 29.0 38.0 43.0 55.0 69.0 84.0 120.0
Fully Open (5.5) (6.7) (8.8) (11.6) (13.1) (16.8) (21.0) (25.6) (36.6)
Angle Valve, Fully 7.0 9.0 12.0 15.0 18.0 24.0 29.0 35.0 47.0
Open (2.1) (2.7) (3.7) (4.6) (5.5) (7.3) (8.8) (10.7) (14.3)
Gate Valve, Fully 0.7 0.9 1.0 1.5 1.8 2.3 2.8 3.2 4.5
Open (0.2) (0.3) (0.3) (0.5) (0.5) (0.7) (0.9) (1.0) (1.4)
The remaining tables in this section show maximum gas capacity for
equivalent lengths of various pipe sizes.
Here are some basic but very important steps that all installers must
follow to make sure that fuel lines are sized correctly:
1. Verify adequate fuel flow, quality, and pressure available from the
natural gas utility connection or the propane system.
2. Obtain the maximum fuel consumption requirements at full load for
the specific generator set from the Model Specifications section and
for all gas appliances attached to the pipe system.
3. Make a list of all the fittings and valves in the proposed system used
in this generator set installation.
4. Determine the equivalent length of all fuel line fittings (elbows, tees,
and valves). (See the NFPA Pipe Fittings table in this appendix to
determine the equivalent lengths for all fuel line fittings.)
5. Add the equivalent length of the fuel line fittings to the lengths of
straight pipe to determine the total equivalent length of the system.
6. Choose the applicable table in this appendix based on the fuel type
(natural gas, propane vapor or liquid propane) and fuel line material.
7. Determine the fuel line size at full load:
a. Locate the equivalent length of pipe (or next larger equivalent
length) in the left hand column.
b. Move across the row to where the maximum flow capacity
number is as large or larger than the maximum fuel consumption.
c. Move to the top of that column to where the minimum nominal
pipe size or tubing size required for the system as designed is
shown.

Copyright © 2017 Cummins Inc. 84 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

TABLE 21. NATURAL GAS SCHEDULE 40 METALLIC PIPE SIZING

Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Pipe Size (in.)
Nominal 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 5 6 8 10 12
:

Actual 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938
ID:

Length
Capacity in Cubic Feet of Gas per Hour
(ft)

10 172 360 678 1,39 2,09 4,02 6,40 11,3 23,1 41,8 67,6 139, 252, 399,
0 0 0 0 00 00 00 00 000 000 000
20 118 247 466 957 1,43 2,76 4,40 7,78 15,9 28,7 46,5 95,5 173, 275,
0 0 0 0 00 00 00 00 000 000
30 95 199 374 768 1,15 2,22 3,53 6,25 12,7 23,0 37,3 76,7 139, 220,
0 0 0 0 00 00 00 00 000 000
40 81 170 320 657 985 1,90 3,02 5,35 10,9 19,7 31,9 65,6 119, 189,
0 0 0 00 00 00 00 000 000
50 72 151 284 583 873 1,68 2,68 4,74 9,66 17,5 28,3 58,2 106, 167,
0 0 0 0 00 00 00 000 000
60 65 137 257 528 791 1,52 2,43 4,29 8,76 15,8 25,6 52,7 95,7 152,
0 0 0 0 00 00 00 00 000
70 60 126 237 486 728 1,40 2,23 3,95 8,05 14,6 23,6 48,5 88,1 139,
0 0 0 0 00 00 00 00 000
80 56 117 220 452 677 1,30 2,08 3,67 7,49 13,6 22,0 45,1 81,9 130,
0 0 0 0 00 00 00 00 000
90 52 110 207 424 635 1,22 1,95 3,45 7,03 12,7 20,6 42,3 76,9 122,
0 0 0 0 00 00 00 00 000
100 50 104 195 400 600 1,16 1,84 3,26 6,64 12,0 19,5 40,0 72,6 115,
0 0 0 0 00 00 00 00 000
125 44 92 173 355 532 1,02 1,63 2,89 5,89 10,6 17,2 35,4 64,3 102,
0 0 0 0 00 00 00 00 000
150 40 83 157 322 482 928 1,48 2,61 5,33 9,65 15,6 32,1 58,3 92,3
0 0 0 0 00 00 00 00
175 37 77 144 296 443 854 1,36 2,41 4,91 8,88 14,4 29,5 53,6 84,9
0 0 0 0 00 00 00 00

A053X172 (Issue 8) 85 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

200 34 71 134 275 412 794 1,27 2,24 4,56 8,26 13,4 27,5 49,9 79,0
0 0 0 0 00 00 00 00
250 30 63 119 244 366 704 1,12 1,98 4,05 7,32 11,9 24,3 44,2 70,0
0 0 0 0 00 00 00 00
300 27 57 108 221 331 638 1,02 1,80 3,67 6,63 10,7 22,1 40,1 63,4
0 0 0 0 00 00 00 00
350 25 53 99 203 305 587 935 1,65 3,37 6,10 9,88 20,3 36,9 58,4
0 0 0 0 00 00 00
400 23 49 92 189 283 546 870 1,54 3,14 5,68 9,19 18,9 34,3 54,3
0 0 0 0 00 00 00
450 22 46 86 177 266 512 816 1,44 2,94 5,33 8,62 17,7 32,2 50,9
0 0 0 0 00 00 00
500 21 43 82 168 251 484 771 1,36 2,78 5,03 8,15 16,7 30,4 48,1
0 0 0 0 00 00 00
550 20 41 78 159 239 459 732 1,29 2,64 4,78 7,74 15,9 28,9 45,7
0 0 0 0 00 00 00
600 19 39 74 152 228 438 699 1,24 2,52 4,56 7,38 15,2 27,5 43,6
0 0 0 0 00 00 00
650 18 38 71 145 218 420 669 1,18 2,41 4,36 7,07 14,5 26,4 41,8
0 0 0 0 00 00 00
700 17 36 68 140 209 403 643 1,14 2,32 4,19 6,79 14,0 25,3 40,1
0 0 0 0 00 00 00
750 17 35 66 135 202 389 619 1,09 2,23 4,04 6,54 13,4 24,4 38,6
0 0 0 0 00 00 00
800 16 34 63 130 195 375 598 1,06 2,16 3,90 6,32 13,0 23,6 37,3
0 0 0 0 00 00 00
850 16 33 61 126 189 363 579 1,02 2,09 3,78 6,11 12,6 22,8 36,1
0 0 0 0 00 00 00
900 15 32 59 122 183 352 561 992 2,02 3,66 5,93 12,2 22,1 35,0
0 0 0 00 00 00
950 15 31 58 118 178 342 545 963 1,96 3,55 5,76 11,8 21,5 34,0
0 0 0 00 00 00
1,00 14 30 56 115 173 333 530 937 1,91 3,46 5,60 11,5 20,9 33,1
0 0 0 0 00 00 00
1,10 14 28 53 109 164 316 503 890 1,81 3,28 5,32 10,9 19,8 31,4
0 0 0 0 00 00 00
1,20 13 27 51 104 156 301 480 849 1,73 3,13 5,07 10,4 18,9 30,0
0 0 0 0 00 00 00

Copyright © 2017 Cummins Inc. 86 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

1,30 12 26 49 100 150 289 460 813 1,66 3,00 4,86 9,98 18,1 28,7
0 0 0 0 0 00 00
1,40 12 25 47 96 144 277 442 781 1,59 2,88 4,67 9,59 17,4 27,6
0 0 0 0 0 00 00
1,50 11 24 45 93 139 267 426 752 1,53 2,78 4,50 9,24 16,8 26,6
0 0 0 0 0 00 00
1,60 11 23 44 89 134 258 411 727 1,48 2,68 4,34 8,92 16,2 25,6
0 0 0 0 0 00 00
1,70 11 22 42 86 130 250 398 703 1,43 2,59 4,20 8,63 15,7 24,8
0 0 0 0 0 00 00
1,80 10 22 41 84 126 242 386 682 1,39 2,52 4,07 8,37 15,2 24,1
0 0 0 0 0 00 00
1,90 10 21 40 81 122 235 375 662 1,35 2,44 3,96 8,13 14,8 23,4
0 0 0 0 0 00 00
2,00 NA 20 39 79 119 229 364 644 1,31 2,38 3,85 7,91 14,4 22,7
0 0 0 0 0 00 00
NA: Applies to a flow of less than 10 cfh.
Note: All table entries are rounded to 3 significant digits.

TABLE 23. NATURAL GAS SEMIRIGID COPPER TUBING SIZING

Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Tube Size (in.)
Nominal 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2

K & L:

Nominal 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 — —


ACR:

Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125

Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959

Length Capacity in Cubic Feet of Gas per Hour


(ft.)
10 27 55 111 195 276 590 1,060 1,680 3,490
20 18 38 77 134 190 406 730 1,150 2,400
30 15 30 61 107 152 326 586 925 1,930

A053X172 (Issue 8) 87 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

40 13 26 53 92 131 279 502 791 1,650


50 11 23 47 82 116 247 445 701 1,460
60 10 21 42 74 105 224 403 635 1,320
70 NA 19 39 68 96 206 371 585 1,220
80 NA 18 36 63 90 192 345 544 1,130
90 NA 17 34 59 84 180 324 510 1,060
100 NA 16 32 56 79 170 306 482 1,000
125 NA 14 28 50 70 151 271 427 890
150 NA 13 26 45 64 136 245 387 806
175 NA 12 24 41 59 125 226 356 742
200 NA 11 22 39 55 117 210 331 690
250 NA NA 20 34 48 103 186 294 612
300 NA NA 18 31 44 94 169 266 554
350 NA NA 16 28 40 86 155 245 510
400 NA NA 15 26 38 80 144 228 474
450 NA NA 14 25 35 75 135 214 445
500 NA NA 13 23 33 71 128 202 420
550 NA NA 13 22 32 68 122 192 399
600 NA NA 12 21 30 64 116 183 381
650 NA NA 12 20 29 62 111 175 365
700 NA NA 11 20 28 59 107 168 350
750 NA NA 11 19 27 57 103 162 338
800 NA NA 10 18 26 55 99 156 326
850 NA NA 10 18 25 53 96 151 315
900 NA NA NA 17 24 52 93 147 306
950 NA NA NA 17 24 50 90 143 297
1,000 NA NA NA 16 23 49 88 139 289
1,100 NA NA NA 15 22 46 84 132 274
1,200 NA NA NA 15 21 44 80 126 262
1,300 NA NA NA 14 20 42 76 120 251
1,400 NA NA NA 13 19 41 73 116 241
1,500 NA NA NA 13 18 39 71 111 232

Copyright © 2017 Cummins Inc. 88 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

1,600 NA NA NA 13 18 38 68 108 224


1,700 NA NA NA 12 17 37 66 104 217
1,800 NA NA NA 12 17 36 64 101 210
1,900 NA NA NA 11 16 35 62 98 204
2,000 NA NA NA 11 16 34 60 95 199
NA: A flow of less than 10 cfh.
Note: All table entries are rounded to 3 significant digits.
*Table capacities are based on Type K copper tubing inside diameter (shown), which has the
smallest inside diameter of the copper tubing products.

TABLE 25. PROPANE VAPOR SCHEDULE 40 METALLIC PIPE SIZING

Gas: Undiluted Propane


Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between Single- or Second-Stage (Low-Pressure)
Regulator and Appliance
Pipe Size (in.)
Nominal 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4
Inside:

Actual: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026

Length Capacity in Thousands of BTU per Hour


(ft.)
10 291 608 1,150 2,350 3,520 6,790 10,800 19,100 39,000
20 200 418 787 1,620 2,420 4,660 7,430 13,100 26,800
30 160 336 632 1,300 1,940 3,750 5,970 10,600 21,500
40 137 287 541 1,110 1,660 3,210 5,110 9,030 18,400
50 122 255 480 985 1,480 2,840 4,530 8,000 16,300
60 110 231 434 892 1,340 2,570 4,100 7,250 14,800
80 101 212 400 821 1,230 2,370 3,770 6,670 13,600
100 94 197 372 763 1,140 2,200 3,510 6,210 12,700
125 89 185 349 716 1,070 2,070 3,290 5,820 11,900
150 84 175 330 677 1,010 1,950 3,110 5,500 11,200
175 74 155 292 600 899 1,730 2,760 4,880 9,950

A053X172 (Issue 8) 89 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

200 67 140 265 543 814 1,570 2,500 4,420 9,010


250 62 129 243 500 749 1,440 2,300 4,060 8,290
300 58 120 227 465 697 1,340 2,140 3,780 7,710
350 51 107 201 412 618 1,190 1,900 3,350 6,840
400 46 97 182 373 560 1,080 1,720 3,040 6,190
450 42 89 167 344 515 991 1,580 2,790 5,700
500 40 83 156 320 479 922 1,470 2,600 5,300
550 37 78 146 300 449 865 1,380 2,440 4,970
600 35 73 138 283 424 817 1,300 2,300 4,700
650 33 70 131 269 403 776 1,240 2,190 4,460
700 32 66 125 257 385 741 1,180 2,090 4,260
750 30 64 120 246 368 709 1,130 2,000 4,080
800 29 61 115 236 354 681 1,090 1,920 3,920
850 28 59 111 227 341 656 1,050 1,850 3,770
900 27 57 107 220 329 634 1,010 1,790 3,640
950 26 55 104 213 319 613 978 1,730 3,530
1,000 25 53 100 206 309 595 948 1,680 3,420
1,100 25 52 97 200 300 578 921 1,630 3,320
1,200 24 50 95 195 292 562 895 1,580 3,230
1,300 23 48 90 185 277 534 850 1,500 3,070
1,400 22 46 86 176 264 509 811 1,430 2,930
1,500 21 44 82 169 253 487 777 1,370 2,800
1,600 20 42 79 162 243 468 746 1,320 2,690
1,700 19 40 76 156 234 451 719 1,270 2,590
1,800 19 39 74 151 226 436 694 1,230 2,500
1,900 18 38 71 146 219 422 672 1,190 2,420
2,000 18 37 69 142 212 409 652 1,150 2,350
Note: All table entries are rounded to 3 significant digits.

TABLE 27. PROPANE VAPOR SEMIRIGID COPPER TUBING SIZING

Gas: Undiluted Propane


Inlet Pressure: 11.0 in. w.c.

Copyright © 2017 Cummins Inc. 90 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

Pressure Drop: 0.5 in. w.c.


Specific Gravity: 1.50
INTENDED USE: Tube Sizing Between Single- or Second-Stage (Low-Pressure)
Regulator and Appliance
Tube Size (in.)
Nominal 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2

K & L:

Nominal 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 — —


ACR:

Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125

Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959

Length Capacity in Thousands of BTU per Hour


(ft.)
10 45 93 188 329 467 997 1,800 2,830 5,890
20 31 64 129 226 321 685 1,230 1,950 4,050
30 25 51 104 182 258 550 991 1,560 3,250
40 21 44 89 155 220 471 848 1,340 2,780
50 19 39 79 138 195 417 752 1,180 2,470
60 17 35 71 125 177 378 681 1,070 2,240
70 16 32 66 115 163 348 626 988 2,060
80 15 30 61 107 152 324 583 919 1,910
90 14 28 57 100 142 304 547 862 1,800
100 13 27 54 95 134 287 517 814 1,700
125 11 24 48 84 119 254 458 722 1,500
150 10 21 44 76 108 230 415 654 1,360
175 NA 20 40 70 99 212 382 602 1,250
200 NA 18 37 65 92 197 355 560 1,170
250 NA 16 33 58 82 175 315 496 1,030
300 NA 15 30 52 74 158 285 449 936
350 NA 14 28 48 68 146 262 414 861
400 NA 13 26 45 63 136 244 385 801
450 NA 12 24 42 60 127 229 361 752
500 NA 11 23 40 56 120 216 341 710
550 NA 11 22 38 53 114 205 324 674

A053X172 (Issue 8) 91 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

600 NA 10 21 36 51 109 196 309 643


650 NA NA 20 34 49 104 188 296 616
700 NA NA 19 33 47 100 180 284 592
750 NA NA 18 32 45 96 174 274 570
800 NA NA 18 31 44 93 168 264 551
850 NA NA 17 30 42 90 162 256 533
900 NA NA 17 29 41 87 157 248 517
950 NA NA 16 28 40 85 153 241 502
1,000 NA NA 16 27 39 83 149 234 488
1,100 NA NA 15 26 37 78 141 223 464
1,200 NA NA 14 25 35 75 135 212 442
1,300 NA NA 14 24 34 72 129 203 423
1,400 NA NA 13 23 32 69 124 195 407
1,500 NA NA 13 22 31 66 119 188 392
1,600 NA NA 12 21 30 64 115 182 378
1,700 NA NA 12 20 29 62 112 176 366
1,800 NA NA 11 20 28 60 108 170 355
1,900 NA NA 11 19 27 58 105 166 345
2,000 NA NA 11 19 27 57 102 161 335
NA: A flow of less than 10,000 BTU/hr.
Note: All table entries are rounded to 3 significant digits.
*Table capacities are based on Type K copper tubing inside diameter (shown), which has the
smallest inside diameter of the copper tubing products.

TABLE 29. PROPANE SCHEDULE 40 IRON PIPE SIZING, LIQUID WITHDRAWAL


(MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR)*

Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)


Equivalent
Length 1/2 3/4 1 1 1/4 1 1/2 2 3 3 1/2 4
of Pipe (ft.) (0.622) (0.824 (1.049) (1.38) (1.61) (2.067) (3.068 (3.548) (4.026
) ) )
30 733 1,532 2,885 5,924 8,876 17,094 48,16 70,519 98,23
4 8
40 627 1,311 2,469 5,070 7,597 14,630 41,22 60,355 84,07
2 9

Copyright © 2017 Cummins Inc. 92 A053X172 (Issue 8)


4-2017 Appendix A. Fuel Line Selection

Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)


Equivalent
Length 1/2 3/4 1 1 1/4 1 1/2 2 3 3 1/2 4
of Pipe (ft.) (0.622) (0.824 (1.049) (1.38) (1.61) (2.067) (3.068 (3.548) (4.026
) ) )
50 556 1,162 2,189 4,494 6,733 12,966 36,53 53,492 74,51
4 8
60 504 1,053 1,983 4,072 6,100 11,748 33,10 48,467 67,51
3 9
70 463 969 1,824 3,746 5,612 10,808 30,45 44,589 62,11
4 6
80 431 901 1,697 3,484 5,221 10,055 28,33 41,482 57,78
1 7
90 404 845 1,593 3,269 4,899 9,434 26,58 38,921 54,22
3 0
100 382 798 1,504 3,088 4,627 8,912 25,11 36,764 51,21
0 6
150 307 641 1,208 2,480 3,716 7,156 20,16 29,523 41,12
4 8
200 262 549 1,034 2,122 3,180 6,125 17,25 25,268 35,20
8 0
250 233 486 916 1,881 2,819 5,428 15,29 22,395 31,19
5 8
300 211 441 830 1,705 2,554 4,919 13,85 20,291 28,26
9 7
350 194 405 764 1,568 2,349 4,525 12,75 18,667 26,00
0 6
400 180 377 711 1,459 2,186 4,209 11,86 17,366 24,19
1 3
450 169 354 667 1,369 2,051 3,950 11,12 16,295 22,70
9 0
500 160 334 630 1,293 1,937 3,731 10,51 15,391 21,44
2 2
600 145 303 571 1,172 1,755 3,380 9,525 13,946 19,42
8
700 133 279 525 1,078 1,615 3,110 8,763 12,830 17,87
3
800 124 259 488 1,003 1,502 2,893 8,152 11,936 16,62
8

A053X172 (Issue 8) 93 Copyright © 2017 Cummins Inc.


Appendix A. Fuel Line Selection 4-2017

Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)


Equivalent
Length 1/2 3/4 1 1 1/4 1 1/2 2 3 3 1/2 4
of Pipe (ft.) (0.622) (0.824 (1.049) (1.38) (1.61) (2.067) (3.068 (3.548) (4.026
) ) )
900 116 243 458 941 1,409 2,715 7,649 11,199 15,60
1
1000 110 230 433 889 1,331 2,564 7,225 10,579 14,73
7
1500 88 184 348 713 1,069 2,059 5,802 8,495 11,83
4
2000 76 158 297 611 915 1,762 4,966 7,271 10,12
8
*Pipe size recommendations are based on schedule 40 black iron pipe.

FIGURE 32. MINIMUM LPG TANK SIZE (50% FULL) REQUIRED TO MAINTAIN 5 PSIG
AT SPECIFIC WITHDRAWAL RATE AND MINIMUM EXPECTED WINTER TEMPERATURE

Copyright © 2017 Cummins Inc. 94 A053X172 (Issue 8)


Appendix B. Outline and System Drawings

Table of Contents
Figure 33. Generator Set Outline (Sheet 1 of 4) ........................................................................................ 97
Figure 34. Generator Set Outline (Sheet 2 of 4) ........................................................................................ 98
Figure 35. Generator Set Outline (Sheet 3 of 4) ........................................................................................ 99
Figure 36. Generator Set Outline (Sheet 4 of 4) ...................................................................................... 100

A053X172 (Issue 8) 95 Copyright © 2017 Cummins Inc.


Appendix B. Outline and System Drawings 4-2017

The drawings included in this section are representative. For current


complete information, refer to the drawing package that was shipped with
the unit.

Copyright © 2017 Cummins Inc. 96 A053X172 (Issue 8)


4-2017 Appendix B. Outline and System Drawings

FIGURE 33. GENERATOR SET OUTLINE (SHEET 1 OF 4)

A053X172 (Issue 8) 97 Copyright © 2017 Cummins Inc.


Appendix B. Outline and System Drawings 4-2017

FIGURE 34. GENERATOR SET OUTLINE (SHEET 2 OF 4)

Copyright © 2017 Cummins Inc. 98 A053X172 (Issue 8)


4-2017 Appendix B. Outline and System Drawings

FIGURE 35. GENERATOR SET OUTLINE (SHEET 3 OF 4)

A053X172 (Issue 8) 99 Copyright © 2017 Cummins Inc.


Appendix B. Outline and System Drawings 4-2017

FIGURE 36. GENERATOR SET OUTLINE (SHEET 4 OF 4)

Copyright © 2017 Cummins Inc. 100 A053X172 (Issue 8)


Appendix C. Wiring Diagrams

Table of Contents
Figure 37. Wiring Diagram (Sheet 1 of 6) ................................................................................................. 103
Figure 38. Wiring Diagram (Sheet 2 of 6) ................................................................................................. 104
Figure 39. Wiring Diagram (Sheet 3 of 6) ................................................................................................. 105
Figure 40. Wiring Diagram (Sheet 4 of 6) ................................................................................................. 106
Figure 41. Wiring Diagram (Sheet 5 of 6) ................................................................................................. 107
Figure 42. Wiring Diagram (Sheet 6 of 6) ................................................................................................. 108
Figure 43. Harness, Generator Set Electrical (Sheet 1 of 3) .................................................................. 109
Figure 44. Harness, Generator Set Electrical (Sheet 2 of 3) .................................................................. 110
Figure 45. Harness, Generator Set Electrical (Sheet 3 of 3) .................................................................. 111

A053X172 (Issue 8) 101 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

C.0 Wiring Diagrams


The drawings included in this section are representative. For current
complete information, refer to the drawing package that was shipped with
the unit.

Copyright © 2017 Cummins Inc. 102 A053X172 (Issue 8)


4-2017 Appendix C. Wiring Diagrams

FIGURE 37. WIRING DIAGRAM (SHEET 1 OF 6)

A053X172 (Issue 8) 103 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

FIGURE 38. WIRING DIAGRAM (SHEET 2 OF 6)

Copyright © 2017 Cummins Inc. 104 A053X172 (Issue 8)


4-2017 Appendix C. Wiring Diagrams

FIGURE 39. WIRING DIAGRAM (SHEET 3 OF 6)

A053X172 (Issue 8) 105 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

FIGURE 40. WIRING DIAGRAM (SHEET 4 OF 6)

Copyright © 2017 Cummins Inc. 106 A053X172 (Issue 8)


4-2017 Appendix C. Wiring Diagrams

FIGURE 41. WIRING DIAGRAM (SHEET 5 OF 6)

A053X172 (Issue 8) 107 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

FIGURE 42. WIRING DIAGRAM (SHEET 6 OF 6)

Copyright © 2017 Cummins Inc. 108 A053X172 (Issue 8)


4-2017 Appendix C. Wiring Diagrams

FIGURE 43. HARNESS, GENERATOR SET ELECTRICAL (SHEET 1 OF 3)

A053X172 (Issue 8) 109 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

FIGURE 44. HARNESS, GENERATOR SET ELECTRICAL (SHEET 2 OF 3)

Copyright © 2017 Cummins Inc. 110 A053X172 (Issue 8)


4-2017 Appendix C. Wiring Diagrams

FIGURE 45. HARNESS, GENERATOR SET ELECTRICAL (SHEET 3 OF 3)

A053X172 (Issue 8) 111 Copyright © 2017 Cummins Inc.


Appendix C. Wiring Diagrams 4-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 112 A053X172 (Issue 8)


power.cummins.com
Copyright © 2017 Cummins Inc. All rights reserved.
Cummins, Onan, and the "C" logo are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service
marks of others.
Specifications are subject to change without notice.

You might also like