Onan Ek Service 928-0505
Onan Ek Service 928-0505
Onan Ek Service 928-0505
5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings
according to the size of each page you wishRedistribution
to print. or publication of this document
by any means, is strictly prohibited.
EK Begin Spec D, EM Begin Spec W
Printed U.S.A. 9280505 1295
LS-11b
iii Redistribution or publication of this document
by any means, is strictly prohibited.
ELECTRICAL SHOCK CAN CAUSE GENERAL SAFETY PRECAUTIONS
SEVERE PERSONAL INJURY OR DEATH
Coolants under pressure have a higher boiling
Remove electric power before removing pro- point than water. DO NOT open a radiator or
tective shields or touching electrical equip- heat exchanger pressure cap while the engine
ment. Use rubber insulative mats placed on is running. Allow the generator set to cool and
dry wood platforms over floors that are metal or bleed the system pressure first.
concrete when around electrical equipment.
Do not wear damp clothing (particularly wet Benzene and lead, found in some gasoline,
shoes) or allow skin surface to be damp when have been identified by some state and federal
handling electrical equipment. agencies as causing cancer or reproductive
Use extreme caution when working on electri- toxicity. When checking, draining or adding
gasoline, take care not to ingest, breathe the
cal components. High voltages can cause inju-
fumes, or contact gasoline.
ry or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical Used engine oils have been identified by some
codes. Have all electrical installations per- state or federal agencies as causing cancer or
formed by a qualified licensed electrician. Tag reproductive toxicity. When checking or
and lock open switches to avoid accidental clo- changing engine oil, take care not to ingest,
sure. breathe the fumes, or contact used oil.
DO NOT CONNECT GENERATOR SET DI- Provide appropriate fire extinguishers and
RECTLY TO ANY BUILDING ELECTRICAL install them in convenient locations. Consult
SYSTEM. Hazardous voltages can flow from the local fire department for the correct type of
the generator set into the utility line. This extinguisher to use. Do not use foam on electri-
creates a potential for electrocution or property cal fires. Use extinguishers rated ABC by
damage. Connect only through an approved NFPA.
isolation switch or an approved paralleling de-
vice.
Make sure that rags are not left on or near the
engine.
HIGH VOLTAGE GENERATOR SETS
Remove all unnecessary grease and oil from
(1.9kV to 15kV) the unit. Accumulated grease and oil can
High voltage acts differently than low voltage. cause overheating and engine damage which
Special equipment and training is required to present a potential fire hazard.
work on or around high voltage equipment. Op- Keep the generator set and the surrounding
eration and maintenance must be done only by area clean and free from obstructions. Re-
persons trained and qualified to work on such move any debris from the set and keep the floor
devices. Improper use or procedures will result clean and dry.
in severe personal injury or death.
Do not work on this equipment when mentally
Do not work on energized equipment. Unau- or physically fatigued, or after consuming any
thorized personnel must not be permitted near
alcohol or drug that makes the operation of
energized equipment. Due to the nature of high
equipment unsafe.
voltage electrical equipment, induced voltage
remains even after the equipment is discon- Substances in exhaust gases have been iden-
nected from the power source. Plan the time for tified by some state or federal agencies as
maintenance with authorized personnel so that causing cancer or reproductive toxicity. Take
the equipment can be de-energized and safely care not to breath or ingest or come into contact
grounded. with exhaust gases.
ABOUT THIS MANUAL Read Safety Precautions and carefully observe all
instructions and precautions in this manual.
This service manual is for the EK (begin Spec D)
and EM (begin Spec W) series gasoline and gas- TEST EQUIPMENT
eous-fuel generator sets. It includes engine and Most of the tests in this manual can be done with an
generator troubleshooting guides. Engine service AC-DC multimeter, frequency meter, Wheatstone
instructions are in the applicable engine service bridge (0.001 ohm precision is necessary for mea-
manual. Operating and maintenance instructions suring stator winding resistance) and load test pan-
are in the applicable Operators Manual. el.
This manual does not have instructions for servic- HOW TO OBTAIN SERVICE
ing printed circuit board assemblies. Always re-
Always give the complete Model, Specification and
place a faulty printed circuit board assembly. At-
Serial number of the generator set as shown on the
tempts to repair a printed circuit board can lead to
nameplate when seeking additional service infor-
costly damage to the equipment.
mation or replacement parts. The nameplate is lo-
cated on the side of the generator output box.
This manual contains basic (generic) wiring dia-
grams and schematics that are included to help in WARNING Incorrect service or replacement of
troubleshooting. Service personnel must use the parts can result in severe personal injury or
actual wiring diagram and schematic shipped with death, and/or equipment damage. Service per-
each unit. The wiring diagrams and schematics that sonnel must be qualified to perform electrical
are maintained with the unit should be updated and mechanical service. Read and follow Safety
when modifications are made to the unit. Precautions, on pages ii and iii.
OUTPUT SCALE
VOLTAGE INDICATOR
TRIMMER LAMPS
AC
VOLTMETER
FIELD
CIRCUIT
BREAKER
AC
AMMETER
PHASE
SELECTOR
SWITCH
FREQUENCY
METER
POWER
FACTOR
WATTMETER METER
STABILITY
GENSET RANGE
kW
RATING S1-1/4 S1-2/3
S2
S1
R32
R34
THIS JUMPER S3
MUST BE 3 TO 4
MAIN
ROTOR
EXCITER
STATOR
MAIN
STATOR
T10 F1 (+)
T9 F2 ()
T8
T7
T4
OUTPUT
VOLTAGE
SENSING TB21
LEADS
32
31 VRAS-2
(3002880)
VOLTAGE
T10 REGULATOR
26
T9 (VR21)
25
T4
24
T8
23
T7 1 2 3 4 5 6 7 8 9 10
22
21
FIELD
CIRCUIT
BREAKER
CB21
VOLTAGE
TRIMMER
R21
(optional)
SELF-EXCITED GENERATORS
MAIN STATOR
EXCITER ROTATING
ROTOR MECHANICAL
MAIN ROTOR
AND POWER
STATOR INPUT
CONTROL PANEL Reset / Lamp Test / Panel Lamp Switch (S11) The
switch is pushed to the Reset position (momentary
The control box is mounted on top of the generator, contact) to reset the engine control to restore opera-
facing the rear. Figure 3-1 shows the components tion following a fault shutdown. The Run / Stop / Re-
on the engine control panel. mote switch must be in the Stop position for reset to
occur. The Lamp Test position (momentary con-
tact) lights all the fault indicator lamps. Replace
STANDARD CONTROL PANEL lamps that do not light. Also, this switch has a light
COMPONENTS which lights following a fault or emergency shut-
down. The light remains lit until the engine control
Run/Stop/Remote Switch (S12) The switch is has been reset. The Panel Lamp position lights the
pushed to the Run position to start and run the gen- panel illumination lamp.
erator set and to the Stop position to stop the set. Coolant Temperature Gauge (M12) The coolant
The Remote position allows a remote controller to temperature gauge indicates engine coolant tem-
automatically run the set. The switch must be in the perature.
Stop position when the reset switch (described
next) is used to restore generator set operation fol- Oil Pressure Gauge (M11) The oil pressure gauge
lowing a fault shutdown. indicates engine oil pressure.
COOLANT INDICATOR
TEMPERATURE LAMPS
GAUGE
HOUR
METER
DC
VOLTMETER
TIME DELAY
START/STOP
VOLTAGE MODULE A15
REGULATOR
(VRAS-2)
TERMINAL BOARD
TB21 OVERSPEED
MODULE
ES1561s-
1
8 7 6 5 4 3 2 1 6 5 4 3 2 1
FIGURE 3-4. ENGINE CONTROL MONITOR FUSES AND FUNCTION SELECTION JUMPERS
T26 OF ENGINE
HARNESS
LOW OIL PRESSURE
SENSOR (S1)
OIL PRESSURE
SENDER (E1)
RADIATOR
TOP TANK
LOW COOLANT
LEVEL SWITCH
ADJUST
SCREW
GENERATOR
SHAFT AIR GAP (NOT LESS
THAN 0.005 IN. (13 MM)
SWITCH
CONTACTS
END
BELL
K1 K2 K3
300-4111c
3003141
TB1
A11-TB1-2 A11-TB1-6
(PRIMARY START DISCONNECT) (REMOTE START)
A11-TB1-3 A11-TB1-7
(SECONDARY START DISCONNECT) (B+)
REMOTE
CONTROL
A11-TB1-5 A11-TB1-7
(GND) (B+)
ES1855s
2. The starting cycle begins when relay K7 is 11. Relay K3 is de-energized (by latching relay K6)
powered, either manually by pushing the panel causing shutdown to occur during operation
Run switch, or automatically by a remote con- when a low oil pressure, high engine tempera-
troller connected at terminal TB1-6. (The panel ture or engine overspeed condition is sensed
switch must be in the Remote position for re- or the optional emergency stop button is
mote, automatic operation.) pressed. The appropriate fault indicator lamp
3. Relay K7 powers relays K2 and K3. lights and common alarm terminal TB1-4 is
powered. (There is no fault lamp for emergency
4. Relay K2 powers the engine gauges and termi- stop. The switch button will light, however, and
nal TB1-10, to which the fuel solenoid and igni- the light in switch S11.)
tion module are connected.
5. Relay K3 powers terminal TB1-8 to which start- The low oil pressure and high engine tempera-
er relay K4 is connected. Engine cranking be- ture shutdowns have 10 second time delays to
allow oil pressure and engine temperature to
gins.
stabilize during startup.
6. The engine starts and runs up to governed
speed in a matter of seconds. 12. To restore operation after a shutdown fault has
been serviced, reset latching relay K6 by push-
7. The starter is disconnected when engine
ing the panel Stop switch and then the Reset
speed gets to about 500 RPM. This is done by
switch. The set should run or be ready to run
relay K10 or K14, whichever acts first to open
when the panel switch is pushed to Run or to
the circuit powering relay K3.
Remote.
8. Relay K10 is powered by the generator output
voltage (120 VAC) through plug-in connectors If the emergency stop switch has been used, the
P1-1 and P1-2. The remote Run indicator lamp control will have to be reset to restore operation.
should light (connected through terminal First pull the emergency stop switch button and
then push the panel Stop and Reset switches.
TB1-3).
9. Relay K14 is powered by the engine-driven 13. The set is stopped manually by pressing the
battery charging alternator (12 VDC) through panel Stop switch or automatically by a remote
plug-in connector P1-3. The panel Run indica- controller. (The panel switch must be in the Re-
tor lamp should light. Relays K10 and K14 are mote position for remote, automatic opera-
redundant.* tion.)
These troubleshooting charts are designed to help WARNING Hazards present in troubleshooting
you think through generator set problems. To save can cause equipment damage, severe personal
time troubleshooting, read the entire manual ahead injury or death. Troubleshooting must be per-
of time to understand the generator set. Try to think formed by qualified persons who know about
through problems. Go over what was done during fuel, electrical and machinery hazards. Read
the last service call. The problem could be as simple the Safety Precautions page and carefully ob-
as an empty fuel tank, closed fuel shutoff valve, serve all instructions and precautions in this
loose wire, blown fuse or tripped circuit breaker. manual.
Cranking voltage is too low to crank the Clean and tighten or replace the battery cable connec-
engine. tors and cables at the battery and the set.
Fuse F1 on the ECM (A11) board has Replace the fuse with one of the same type and amp
blown. rating.
The wire between ECM terminal TB1-8 Push the Run-Stop-Remote switch to Run and check
and starter solenoid terminal SW is loose, for battery voltage at starter solenoid terminal SW. If
damaged or missing. there is no voltage repair the wiring as necessary.
When the Run-Stop-Remote switch is in the Run position, the control will attempt to crank the engine for approximate-
ly 75 seconds (including two rest periods) and then the red OVERCRANK lamp will light if the engine does not start. If
the OVERCRANK lamp comes on, reset the control by pushing the Run-Stop-Remote switch to Stop and the Reset
switch to Reset. Then push the Run-Stop-Remote switch to Run or Remote.
Fuse F2 on the ECM board (A11) has Replace the fuse with one of the same type and amp
blown. rating.
Low engine temperature is causing too Plug in, repair or install engine coolant and engine oil
low a cranking speed for starting. heaters.
THE ENGINE RUNS UNTIL FAULT SHUTDOWN (RED SHUTDOWN LAMP ON)
If the set still shuts down due to low oil pressure, dis-
connect the wire to fuel solenoid K1 (to keep the en-
gine from starting) and observe oil pressure while
cranking the engine. Service the lubricating oil system
according to the engine service manual if oil pressure
is less than 10 psi. Replace the low oil pressure cutout
switch if oil pressure is greater than 10 psi. See Figure
3-5, Engine Control to locate the switch.
Fuel delivery to the set is inadequate. Check for and replace clogged fuel lines and filters.
Check for air in the fuel lines and repair all air leaks.
The engine air filter element is dirty. Replace the air filter element.
The engine fuel system (lift pump, injec- Service the fuel system according to the engine ser-
tion pump, injectors, timing) is faulty. vice manual.
The LOW ENGINE TEMPERATURE Plug in, repair or install engine coolant and engine oil
lamp comes on while the set is in standby. heaters.
THE GREEN RUN LAMPS STAY OFF BUT THE SET RUNS NORMALLY
The set mounted RUN lamp does not light
Press the panel Lamp Test switch and replace the run
although the starter has disconnected
lamp bulb if it does not light.
normally and the engine is running
Find out why the circuit breaker was turned OFF, make
The line circuit breaker is OFF. sure it is safe to reconnect power, and then throw the
circuit breaker ON.
Shut down the set, make sure the power output lines
from the set have been disconnected from all other
sources of power, attempt to RESET the circuit break-
The line circuit breaker is faulty. er and throw it ON and check for electrical continuity
across each line contact. Replace the circuit breaker if
there is measurable resistance across any contact.
Determine, as follows, whether the fault is in the VOLTAGE REGULATING or GENERATOR circuits:
1. Throw the line circuit breaker OFF and shut down the set.
CAUTION This test involves unregulated excitation of the generator. To prevent damage to the genera-
tor due to overcurrent, make sure that all loads have been disconnected and that all faults have been
cleared from the power output terminals of the generator.
2. Open the control panel and disconnect the F1 (+) and the F2 () leads from the voltage regulator. See Figure 2-2.
HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in
severe personal injury or death. Measurements and adjustments must be done with care to avoid touch-
ing high voltage parts.
For your protection, stand on a dry wooden platform or rubber insulating mat, make sure your clothing
and shoes are dry, remove jewelry from your hands and wear elbow length insulating gloves.
3. Start the set and check for output voltage at the main stator terminals.
a. Is there 520 VAC residual voltage at the output of the main stator windings when the exciter leads are dis-
connected?
YES: The main stator windings are good, continue with step 4.
NO: Use the GENERATOR FAULT chart to troubleshoot generator.
4. If the residual voltage is good, stop the set and reconnect the exciter leads to the exciter stator. Start the set. Has
the output voltage increased?
YES: Adjust the Coarse Voltage Adjust pot on VRAS-2.
NO: Check if CB21 is closed. If CB21 is OK, flash the field using the procedure in Section 5.
5. When field is flashed, does the output voltage from the main stator increase?
YES: The generator assembly is OK.
NO: Use the GENERATOR FAULT chart to troubleshoot generator.
6. If the output voltage increased when the field was flashed, does the output voltage remain after the flash circuit is
removed?
YES: The generator assembly and VRAS-2 are OK.
NO: VRAS-2 is defective. Use the VOLTAGE REGULATING FAULTS chart to troubleshoot VRAS-2.
7. Put a full load on the generator set. Does the generator set output stay up after the generator set has responded to
the load?
YES: The generator assembly and VRAS-2 are OK.
NO: Check each diode according to Section 5, Servicing the Generator.
VRAS-2 FAULTS
GENERATOR FAULTS
Shut down the set and check exciter field winding re-
The exciter field winding is faulty (open or sistance according to Section 5, Servicing the Genera-
shorted). tor. Replace the exciter field assembly if winding re-
sistance does not meet specifications.
Shut down the set and check main rotor winding resist-
The main rotor winding is faulty (open or ance according to Section 5, Servicing the Generator.
shorted). Replace the generator rotor assembly if main rotor
winding resistance does not meet specifications.
The voltage has been adjusted improper- Adjust output voltage according to Section 2, AC Con-
ly. trol.
The voltage has been adjusted improper- Adjust output voltage according to Section 2, AC Con-
ly. trol.
Shut down the set and check exciter field winding re-
sistance according to Section 5, Servicing the Genera-
The exciter field winding is shorted. tor. Replace the exciter field assembly if winding re-
sistance does not meet specifications.
Shut down the set and check main rotor winding resist-
ance according to Section 5, Servicing the Generator.
The main rotor winding is shorted.
Replace the generator rotor assembly if main rotor
winding resistance does not meet specifications.
Improper connections have been made at Shut down the set and reconnect according to the re-
the generator output terminals. connection diagram on page 7-9.
A load has a ground fault or short circuit. Service the faulty equipment as necessary.
MAIN PMG
BLOWER STATOR ASSEMBLY EXCITER
STATOR
ROTATING
RECTIFIER
ASSEMBLY
OVERSPEED
SWITCH
END
BEARING
EXCITER
ROTOR
DRIVE
DISCS
MAIN ROTOR
SCREEN (GENERATOR FIELD)
These tests are used for insulation testing and to DRYING THE WINDINGS
verify that the windings are dry before the generator
set is operated and develop a base line for future If low readings are obtained and moisture is deter-
test comparison. mined to be the problem, the windings should be
dried out and the test repeated. Use the generator
Megger Testing heaters or blow warm air through the generator with
a fan. A more effective way is to use a bolted 2 /
A 500 VDC megger is recommended for insulation 3-phase short across the generator terminals. This
testing. A test consists of applying the voltage be- procedure must be done as described or equipment
tween the winding and ground for one minute. damage can result. To do this:
Resistance value of at least 5 megohms should be 1. Bolt the two or the three phases of the genera-
obtained for a new generator with dry windings. For tor together at the terminals. See the reconnec-
a set that has been in service, the resistance read- tion diagram in Section 7.
ing should not be less than 1 megohm. 2. Disconnect the F1 and F2 leads (Figure 5-2) at
the voltage regulator and connect them to a
PI Testing variable 12 VDC source. Positive lead to F1,
negative lead to F2.
The PI test consists of applying a voltage between
the winding and ground for ten minutes and record- 3. Attach a clamp-on ammeter to the generator
ing resistance values at one minute and at ten min- leads to measure generator current, adjust the
utes. The PI is the ratio of a ten minute reading in 12 VDC source for zero volts, start the set and
megohms divided by a one minute reading in meg- slowly increase the excitation voltage. Obtain
ohms. A ratio of two or greater is considered good the highest current possible without exceeding
for new and in service sets. generator rating.
4. Run the set for approximately one hour and re-
If low readings are obtained, the cause should be in- peat the insulation resistance tests. If further
vestigated and corrected before the generator set is drying time is indicated, continue the drying
returned to service. process.
EXCITER
STATOR
L1
MAIN STATOR
12-AMPERE, L3
300-VOLT DIODE ()
10
AVR REFERENCE
VOLTAGE
9
(+) L0
L2
() (+)
REMOVE DIODE (1 OF
6) FROM HEATSINK AND
MEASURE ELECTRICAL
RESISTANCE BETWEEN
THE PIGTAIL AND THE
METAL PLATE UNDER
THE DIODE
DIODE
HEATSINKS
MEASURE WINDING
INSULATION RESISTANCE
BETWEEN ANY LEAD OR
THE TERMINAL TO WHICH
IT IS CONNECTED AND
THE ROTOR LAMINATIONS
WINDING SCHEMATIC
REMOVE DIODES CR1 THROUGH
CR6 FROM DIODE HEAT SINK
ASSEMBLIES AND MEASURE
T11 T21 ELECTRICAL RESISTANCE
ACROSS EACH PAIR OF
T1 WINDINGS: T1-T2, T2-T3, T3-T1
T2
T23 T3 T12
T13 T22
VOLTAGE CODE Disconnect all stator leads and winding taps from
MODEL their respective terminals and make sure the ends
L, R, 15, & 32 H & 9X E & 6D do not touch the generator frame.
EK 0.116-0.141 0.425-0.520 0.432-0.528 Testing For Grounds: Using a megger (voltage set
EM 0.047-0.058 0.193-0.236 0.202-0.248 at 500 VDC), measure electrical resistance be-
tween any stator lead and the stator laminations.
* These values are approximate, plus or minus
Replace the stator if insulation resistance is less
10 percent at 68 F (20 C).
than 1 megohm.
Alternatively, winding resistance can be measured Testing for Shorts: Using a megger (voltage set at
line-to-line at the generator terminals (L1-L2, 500 VDC) measure electrical resistance between
L2-L3, L3-L1) on star connected generators. On a each winding, for example T1/T4 to T7/T10, T1/T4
600 volt generator, line-to-line resistance should be to T2/T5, etc. Replace the stator if insulation resist-
twice the table value (two winding elements in se- ance is less than 1 megohm.
MEGGER OR WHEATSTONE
INSULATION BRIDGE
RESISTANCE
METER
ADJUST
SCREW
GENERATOR
SHAFT AIR GAP (NOT LESS
THAN 0.005 IN. [13 MM]
SWITCH
CONTACTS
END
BELL
ROTOR
EXCITER
ROTOR
MODIFIED HEX
HEAD BOLT
OVERSPEED
SWITCH
STATOR-TO-FLYWHEEL
HOUSING BOLT SLEEVE
SPACER
BALL
BEARING
EXCITER-TO-END
BELL BOLT
GENERATOR
STATOR
OVERSPEED
CONTACT
GENERATOR
ASSEMBLY
AIR SCREEN
EXCITER
STATOR
O-RING
OIL SEAL
END
BELL STUD
50 Hz ON OFF OFF OFF 6. Shut down and restart the genset to check for
60 Hz ON OFF OFF ON overspeed shutdown on startup.
GAIN 1
GOVERNOR CONTROLLER
CONNECTIONS SEE STABILITY 1
FIGURE 6-3
SPEED TRIM
SW1
SW2
SW3
SW4 ON POSITION
DIP
SWITCHES
BALL JOINT
SCREW
BALL JOINT
SCREW
GASEOUS
CARB
GASOLINE
CARB
THROTTLE
LEVER
TO GOVERNOR
CONTROLLER
MAGNETIC SPEED
PICKUP UNIT
MPU TYPE
GENERATOR
ADAPTER
TO GOVERNOR
CONTROLLER
IGNITION
TYPE
BOWL
DRAIN
PLUG
MAIN
ADJUSTMENT
No. 612-6489 sh 1 of 1
Rev. H Sys: CADAM
Modified 10/3/95
AC WIRING (WITHOUT METERS)
7-3 Redistribution or publication of this document
by any means, is strictly prohibited.
THIS IS A REPRESENTATIVE (GENERIC)
SCHEMATIC/WIRING DIAGRAM. FOR
TROUBLESHOOTING, REFER TO THE
WIRING DIAGRAM PACKAGE THAT WAS
INCLUDED WITH YOUR GENSET.
No. 612-6490 sh 1 of 1
Rev. S Sys: CADAM
Modified 10/3/95
AC WIRING (WITH METERS)
7-4 Redistribution or publication of this document
by any means, is strictly prohibited.
THIS IS A REPRESENTATIVE (GENERIC)
SCHEMATIC/WIRING DIAGRAM. FOR
TROUBLESHOOTING, REFER TO THE
WIRING DIAGRAM PACKAGE THAT WAS
INCLUDED WITH YOUR GENSET.
No. 612-6684 sh 1 of 2
Rev. A Sys: CADAM
Modified 9-26-95
No. 612-6684 sh 2 of 2
Rev. A Sys: CADAM
Modified 9-26-95
No. 612-6685 sh 1 of 2
Rev. A Sys: CADAM
Modified 9-27-95
No. 612-6685 sh 2 of 2
Rev. A Sys: CADAM
Modified 9-27-95
RECONNECTION DIAGRAM
7-9 Redistribution or publication of this document
by any means, is strictly prohibited.
TB1-10 (SWITCHED B+ OUTPUT) OUTPUT TO RELAY K12, FUSED AT 20 AMPS, ENERGIZED WHEN THE
START SIGNAL IS APPLIED AND DE-ENERGIZED AT SHUTDOWN (NORMAL AND FAULT)
+ K12
TB1-9 (B+ INPUT) BATTERY POSITIVE (+) CONNECTION
TB1-6 (REMOTE START) CONNECTED TO TIME DELAY START/STOP MODULE A15. CONNECT REMOTE START
CONTACT OF THE AUTOMATIC TRANSFER SWITCH TO TERMINAL TB1-5 OF MODULE A15.
TB1-5 (GROUND)
LEAD TABULATION
FROM TO
STATION STATION
No. 336-3322 sh 1 of 1
Rev. A Sys: CADAM
Modified 9-26-95
ENGINE HARNESS
7-12 Redistribution or publication of this document
by any means, is strictly prohibited.
THIS IS A REPRESENTATIVE (GENERIC)
SCHEMATIC/WIRING DIAGRAM. FOR
TROUBLESHOOTING, REFER TO THE
WIRING DIAGRAM PACKAGE THAT WAS
INCLUDED WITH YOUR GENSET.
No. 338-3326 sh 1 of 1
Rev. A Sys: CADAM
Modified 9-27-95
DC HARNESS
7-13 Redistribution or publication of this document
by any means, is strictly prohibited.
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
1-800-888-6626
763-574-5000 International Use
Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.