Cummins DQKB DQKC Operators Manual
Cummins DQKB DQKC Operators Manual
Cummins DQKB DQKC Operators Manual
PowerCommand Control
3200 Series
Generator Sets
Models
DQKB, DQKC
California
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects, and
other reproductive harm.
• Use extreme caution when working on electrical • Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
components. High voltages can cause injury or
such as wood and cloth; Class B fires, combustible
death. DO NOT tamper with interlocks.
and flammable liquid fuels and gaseous fuels; Class
• Follow all applicable state and local electrical C fires, live electrical equipment. (ref. NFPA No. 10).
codes. Have all electrical installations performed by • Make sure that rags are not left on or near the en-
a qualified licensed electrician. Tag and lock open gine.
switches to avoid accidental closure.
• Make sure generator set is mounted in a manner to
• DO NOT CONNECT GENERATOR SET DIRECT- prevent combustible materials from accumulating
LY TO ANY BUILDING ELECTRICAL SYSTEM. under the unit.
Hazardous voltages can flow from the generator set • Remove all unnecessary grease and oil from the
into the utility line. This creates a potential for elec- unit. Accumulated grease and oil can cause over-
trocution or property damage. Connect only heating and engine damage which present a poten-
through an approved isolation switch or an ap- tial fire hazard.
proved paralleling device.
• Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-
MEDIUM VOLTAGE GENERATOR SETS
bris from the set and keep the floor clean and dry.
(601V to 15kV) • Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
• Medium voltage acts differently than low voltage. or drug that makes the operation of equipment un-
Special equipment and training is required to work safe.
on or around medium voltage equipment. Operation • Substances in exhaust gases have been identified
and maintenance must be done only by persons by some state or federal agencies as causing can-
trained and qualified to work on such devices. Im- cer or reproductive toxicity. Take care not to breath
proper use or procedures will result in severe per- or ingest or come into contact with exhaust gases.
sonal injury or death.
• Do not store any flammable liquids, such as fuel,
• Do not work on energized equipment. Unauthorized cleaners, oil, etc., near the generator set. A fire or
personnel must not be permitted near energized explosion could result.
equipment. Due to the nature of medium voltage
electrical equipment, induced voltage remains even
• Wear hearing protection when going near an oper-
after the equipment is disconnected from the power ating generator set.
source. Plan the time for maintenance with autho- • To prevent serious burns, avoid contact with hot
rized personnel so that the equipment can be de-en- metal parts such as radiator, turbo charger and ex-
ergized and safely grounded. haust system.
WARNING
MODEL DQKB/DQKC
Cummins Diesel Series QSK60 (50/60 Hz)
Generator kW Rating See Genset Nameplate for rating iinformation.
Cooling System Radiator-Cooled Models
40° C
Jacket Water Cooling System
Low-Temp Aftercooling System 82 Gal (310 L)
50° C 42 Gal (159 L)
Jacket Water Cooling System
Low-Temp Aftercooling System 90 Gal (341 L)
40 Gal (152 L)
Oil Capacity, Maximum (see Figure 2-1)
Oil Pan Only
Standard Capacity 69 Gal (261 L)
High Capacity 100 Gal (379 L)
System (w/Std. Filters)
Standard Capacity 74 Gal (280 L)
High Capacity 105 Gal (398 L)
*Oil Type
**Fuel Consumption
Standby/Full Load/60Hz GPH(LHR) 118.9 (450.6) / 136.6 (517.7)
Electrical System
Starting Voltage 24 Volts DC
Battery Four, 12 Volt
Group Number 8D
CCA (minimum)
Cold Soak @ 0° F (-18° C) 1800
* Refer to Cummins QSK45/60 Series Engine Operation and Maintenance Manual for lubricating oil
recommendations/specifications.
** Refer to Data Sheet for other applications.
HIGH CAPACITY
Sleep/Awake Mode: In the Sleep mode, the con- InPower service tool is required to select desired
trol’s operating software is inactive and the LEDs mode. Contact an authorized service center for as-
and the graphical display on the control panel are all sistance.
REMOTE START,
NOT IN AUTO,
SHUTDOWN,
WARNING
STATUS INDICATORS
ANALOG AC PANEL LAMP/ FAULT EMERGENCY
METERING LAMP TEST ACKNOWLEDGE STOP PUSH
PANEL BUTTON BUTTON BUTTON
GRAPHICAL 0/MANUAL/AUTO
DISPLAY SWITCH
This button is also used to blink a fault code if the Auto position enables start/stop control of the en-
Shutdown or Warning Status Indicator is lit. (This gine from a remote location. (Disables the use of the
function is used when the control does not contain a switch panel Manual Run/Stop button.)
graphical display.) Refer to Reading Fault Codes in
this section, which describes how to use this button 0 (Off) position prevents the starting of the set (local
for interpreting fault codes. or remote). If moved to 0 during set operation, will
cause an immediate engine shutdown (bypasses
Panel Lamp/Lamp Test Button: Press this button cool-down timers). This hot shutdown should be
to turn on or off the panel lamp. Press and hold avoided, if possible, to help prolong the life of the
down this button for three seconds or more to turn engine. Hot shutdowns are logged by the system
all control panel LEDs on to make sure all lamps illu- software.
In the Manual position, the control will not complete Starting from Remote Location (Switch or
the time delay to start or time delay to stop (Figure Device) (Auto Mode)
3-2), but will complete the warm-up at idle and cool-
down at rated/idle. Place the 0/Manual/Auto switch in the Auto posi-
tion. This allows the generator set to be started from
When the coolant reaches operating temperature a remote switch or device (e.g., transfer switch).
or the warm-up at idle time delay is reached (0 to
300 seconds), whichever occurs first, the generator There are two start modes that are selectable for
set will ramp to rated speed and voltage. the remote start input, one for non-emergency start
and the other for emergency start. Figure 3-2 illus-
If the engine does not start, the starter will disen- trates how the start/run/stop sequence differs be-
gage after a specified period of time and the control tween the two modes.
will indicate an overcrank shutdown.
In response to the remote run signal, the control
The generator set can be configured for a number of lights the Remote Start indicator and initiates the
starting cycles (1 to 7) and duration of crank and rest starting sequence described in the previous head-
periods. Default setting is for 3 start cycles com- ing (Starting at Switch Panel), except for the follow-
posed of 15 seconds of cranking, and 15 seconds of ing:
rest.
In the Auto position, the control will complete the
The InPower service tool is required to change the Time Delay To Start (0 to 300 seconds) for a non-
number of crank cycles, and the crank and rest emergency start signal and the Time Delay To Stop
times. Contact an authorized service center for as- (0 to 600 seconds) for either a emergency or non-
sistance. emergency start signal (see Figure 3-2).
To clear a Fail To Start shutdown, place the 0/Manu- Refer to Adjust submenu in this section to change
al/Auto switch in the 0 position and press the Fault the time delay settings.
NOTES:
1. Timer expires.
2. Coolant temperature reaches operating level.
3. Cool-down can be at rated speed and/or idle with
different time-outs for each.
• Action Line – system actions, such as Warning, In the graphical display, the “ ” symbol indicates
Derate, Shutdown Cool-down and Shutdown, that selecting the adjacent button causes the operat-
and fault codes. ing program to go back to Main Menu A (Figure 3-5).
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA
GRAPHICAL
DISPLAY
MENU MENU
BUTTONS BUTTONS
MENU A
MENU MENU
BUTTONS PAGE MENU BUTTONS
3-13 B
ENGINE MORE>>
PAGE ALTERNATOR _\_ See
3-14 CONTROL HISTORY/ABOUT Above
PAGE PAGE
3-15 3-16
MENU B
PAGE
3-17
ADJUST
BUS DATA PAGE
SETUP BACK<< 3-18
GRAPHICAL
Service DISPLAY MENU
Manual A
MANF TEMP 75 °F
MANF PRESS ABS 180 INHG
RAIL PRESS ABS 180 PSI
PUMP PRESS ABS 291 PSI
FUEL INLET TEMP 172 °F
COOLANT PRESSURE 59 PSI
MODEL 1750DQKB
VOLTAGE 416 WYE
FREQUENCY 60
RATING STANDBY
CONTROLLER VERSION
RTOP DN30008.DFA
BATS FEB 15 1999
OP PANEL VERSION
RTOP 1.08 JUN 4 1999
BATS 1.02 MAY 6 1999
SAFETY CONSIDERATIONS 3. Remove the negative (–) battery cable from the
generator set starting battery.
WARNING Contacting high voltage compo-
nents can cause electrocution, resulting in se-
vere personal injury or death. Keep the output STATUS INDICATORS
box covers in place during troubleshooting.
Not In Auto Indicator: This red lamp flashes con-
High voltages are present when the set is running. tinuously when the O/Manual/Auto switch is not in
Do not open the generator output box while the set the Auto position (Figure 4-1).
is running.
WARNING
Shutdown Status Indicator: This red lamp is lit
Ignition of explosive battery gases
whenever the control detects a shutdown condition.
can cause severe personal injury or death. Arc-
After the condition is corrected, the shutdown indi-
ing at battery terminals, light switch or other
cator can be reset by turning the O/Manual/Auto
equipment, flame, pilot lights and sparks can ig-
switch to the O (off) position, and pressing the Fault
nite battery gas. Do not smoke, or switch
Acknowledge button. The generator set can not be
trouble light ON or OFF near battery. Discharge
started when this lamp is on.
static electricity from body before touching bat-
teries by first touching a grounded metal sur-
face. Warning Status Indicator: This yellow lamp is lit
whenever the control detects a warning condition.
Ventilate battery area before working on or near After the condition is corrected, the warning indica-
battery—Wear goggles—Stop genset and dis- tor can be reset by pressing the Fault Acknowledge
connect charger before disconnecting battery button. (It is not necessary to stop the generator set
cables—Disconnect negative (–) cable first and if the fault becomes inactive during genset opera-
reconnect last. tion.)
Redistribution or publication of this document,
by any means, is strictly prohibited.
4-1
READING FAULT CODES each code. The fourth flash of the Warning lamp in-
dicates the beginning of the second fault code.
If the genset contains the optional graphical display
and a fault occurs, the fault code/message will be There are distinct pauses between repetitions of the
displayed in the display Description Line (Figure code blink transmissions of the Shutdown lamp.
4-1). If the control does not contain the graphical A three digit fault code is indicated by three sets of
display, the fault code is read from the Warning and blinks separated by a two second pause. The first
Shutdown status indicators. set corresponds to the hundreds position, the sec-
After the fault is acknowledged and corrected, the ond to the tens position and the third to the ones dig-
recorded fault will be deleted from the control panel it. Example for Code No. 213:
memory, but will remain in a data log to maintain a Shutdown LED:
fault code history. The InPower service tool is re- blink-blink-pause-blink-pause-blink-blink-blink
quired to view this data log.
Warning LED:
Reading Fault Codes Using Graphical Display blink (2 seconds)
(Optional): The top three lines of the graphical dis-
play contain the following control information in the The light will display the fault codes (active or inac-
order described: tive) in succession, starting with the most recent. Up
to 32 (unacknowledged) fault codes can be stored
• State Line – modes of operation, such as in control panel memory.
Stopped, Time Delay To Start, Warm Up At
Idle, etc. (see Figure 3-2), and paralleling op- To return the control to the most recent fault code,
erations, such as Standby, Dead BUS Close, press and release the Fault Acknowledge button
Synchronize, etc. (less than one second) and repeat procedure.
• Action Line – system actions, such as Warning, When the fault code is acknowledged and the fault
Derate, Shutdown Cool-down and Shutdown, condition is corrected, the fault code will be re-
and fault codes. moved from the LED fault log.
FAULT
ACKNOWLEDGE
BUTTON
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA
OPERATOR SWITCH
GRAPHICAL
PANEL PANEL
DISPLAY
NA– Indicates non-critical operational status of generator set, external faults, or customer fault inputs. May
require repair by qualified service personnel.
Redistribution or publication of this document,
by any means, is strictly prohibited.
4-6
TABLE 4-1. FAULT CODES (CONT)
CAT CODE LAMP DISPLAYED MESSAGE CAT CODE LAMP DISPLAYED MESSAGE
D 1443 Wrng Battery is dead A 1473 Shtdn Watchdog failure
B 1444 Wrng kW overload A 1474 Shtdn Software version mismatch
A 1445 Shtdn Alternator short circuit C 1475 Wrng First start backup
A 1446 Shtdn AC output voltage is high C 1476 Wrng LonWorks card
A 1447 Shtdn AC output voltage is low C 1477 Wrng Crank relay contact
A 1448 Shtdn AC output frequency low C 1478 Wrng Crank relay driver
A 1449 Wrng AC output frequency high A 1481 Shtdn AVR driver open
B 1451 Wrng Gen/Bus voltage differ NA 1483 None Common alarm status
A 1452 Shtdn Gen CB failed to close A 1485 Shtdn EFC driver shorted
A 1453 Shtdn Gen CB failed to open A 1486 Shtdn EFC driver open
C 1454 Wrng Gen CB position contact C 1487 Wrng Auto acknowledge driver
A 1455 Shtdn Util CB contact C 1488 Wrng Warning LED driver
NA 1456 Wrng Bus out of range C 1489 Wrng Shutdown LED driver
NA 1457 Wrng Fail to synchronize C 1491 Wrng Ready to load relay driver
NA 1458 Wrng Phase rotation C 1492 Wrng Load dump relay driver
A 1459 Shtdn Reverse kW C 1493 Wrng Display control driver
A 1461 Shtdn Loss of field C 1494 Wrng Modem power relay driver
B 1462 Wrng High ground current C 1495 Wrng Common shutdown2 driver
NA 1463 None Not in Auto C 1496 Wrng Auto mode relay driver
NA 1464 None Load dump C 1497 Wrng Manual run LED driver
NA 1465 None Ready to load C 1498 Wrng Exercise run LED driver
C 1466 Wrng Modem failure C 1499 Wrng Remote start LED driver
C 1467 Wrng Unable to connect modem C 2111 Wrng Aftercooler temp sensor
C 1468 Wrng Network erorr C 2112 Wrng Aftercooler temp sensor
B 1471 Wrng High current B 2113 Wrng High aftercooler temp
A 1472 Shtdn Overcurrent A 2114 Shtdn High aftercooler temp
NA– Indicates non-critical operational status of generator set, external faults, or customer fault inputs. May
require repair by qualified service personnel.
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 146 Indicates engine has begun to overheat and jacket water coolant temper-
LAMP: Warning ature has risen to an unacceptable level. If generator is powering non-crit-
MESSAGE: ical and critical loads and cannot be shut down, use the following:
HIGH COOLANT TEMP WARNING a. Reduce load if possible by turning off non-critical loads.
b. Check air inlets and outlets and remove any obstructions to airflow.
If engine can be stopped, follow 151 High Coolant Temp Alarm proce-
dure.
CODE: 151 Indicates engine has overheated (jacket water coolant temperature has
LAMP: Shutdown risen above the shutdown trip point or the coolant level is low. Allow en-
MESSAGE: gine to cool down completely before proceeding with the following checks:
HIGH COOLANT TEMP ALARM a. Check jacket water coolant level and replenish if low. Look for cool-
ant leakage and repair if necessary.
b. Check for obstructions to cooling airflow and correct as necessary.
c. Check fan belt and repair if necessary.
d. Reset control and restart after locating and correcting problem.
CODE: 152 Indicates engine coolant heater is not operating or is not circulating cool-
LAMP: Warning ant. Set is in standby mode but is not operating. Warning occurs when en-
MESSAGE: gine jacket water coolant temperature is 70° F (21° C) or lower.
LOW COOLANT TEMP
NOTE: In applications where the ambient temperature falls below
40° F (4° C), Low Coolant Temp may be indicated even though the
coolant heaters are operating.
Check for the following conditions:
a. Coolant heater not connected to power supply. Check for blown fuse
or disconnected heater cord and correct as required.
b. Check for low jacket water coolant level and replenish if required.
Look for possible coolant leakage points and repair as required.
CODE: 197 Indicates engine jacket water coolant level has fallen to an unacceptable
LAMP: Warning level. If generator is powering critical loads and cannot be shut down, wait
MESSAGE: until next shutdown period, then follow 235 Coolant Level Alarm proce-
COOLANT LEVEL WARNING dure. If engine can be stopped, follow 235 procedure.
CODE: 235 Indicates engine jacket water coolant level has fallen below the alarm trip
LAMP: Shutdown point. Allow engine to cool down completely before proceeding.
MESSAGE: a. Check jacket water coolant level and replenish if low. Look for pos-
COOLANT LEVEL ALARM sible coolant leakage points and repair if necessary.
b. Reset control and restart after locating and correcting problem.
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 253 Indicates engine oil level has dropped below the shutdown trip point.
LAMP: Shutdown Check oil level, lines and filters. If oil system is OK but oil level is low, re-
MESSAGE: plenish. Reset control and restart.
OIL LEVEL ALARM
CODE: 326 Indicates that the engine oil level has exceeded the warning trip point for
LAMP: Warning high oil level. If generator is powering critical loads and cannot be shut
MESSAGE: down, wait until next shutdown period, then follow 688 High Oil Level
OIL LEVEL WARNING Alarm procedure. If engine can be stopped follow 688 procedure.
CODE: 359 Indicates possible fault with control or starting system. Check for the fol-
LAMP: Warning lowing conditions:
MESSAGE: a. Poor battery cable connections. Clean the battery cable terminals
ENGINE FAILED TO START and tighten all connections.
b. Discharged or defective battery. Recharge or replace the battery.
CODE: 471 Indicates engine oil has dropped to an unacceptable level. If generator is
LAMP: Warning powering critical loads and cannot be shut down, wait until next shutdown
MESSAGE: period, then follow 253 Oil Level Alarm procedure. If engine can be
LOW OIL LEVEL stopped follow 253 procedure.
CODE: 611 Indicates that an engine hot shut down has occurred (cool-down timers
LAMP: Warning were bypassed). This condition will occur when the engine coolant tem-
MESSAGE: perature is above the normal operating level and the operator presses the
ENGINE HOT Emergency Switch or moves the 0/Manual/Auto switch to the 0 (Off) posi-
tion. This type of shutdown should be avoided. Can cause possible loss of
performance and engine damage.
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 688 Indicates that the engine oil level has exceeded the alarm trip point for
LAMP: Shutdown high oil level. Check oil level. Drain oil to operating level.
MESSAGE:
HIGH OIL LEVEL ALARM
CODE: 1311 through 1318 When any one of these customer defined inputs is detected by the control,
LAMP: Shutdown/Warning the corresponding fault message is displayed. The nature of the fault is an
MESSAGE: optional customer selection. These fault functions can be programmed to
Customer Defined Fault initiate a shutdown or warning as indicated by the Warning or Shutdown
lamp.
Note: Customer fault messages are editable. The message displayed for
the code shown (1311 through 1318) is determined by the customer.
CODE: 1416 Status – indicates that the “Fault Bypass” mode is enabled. This mode is
LAMP: Warning primarily used by service personnel for troubleshooting purposes. In this
MESSAGE: mode the generator set ignores the majority of system shutdown faults.
FAIL TO SHUTDOWN
CODE: 1417 Indicates that the control can not power down due to some unknown con-
LAMP: Warning dition. Possible drain on battery. Contact an authorized service center for
MESSAGE: service.
POWER DOWN ERROR
CODE: 1433 / 1434 Indicates local or remote Emergency Stop. Emergency Stop shutdown
LAMP: Shutdown status can be reset only at the local control panel.
MESSAGE: To reset the local/remote Emergency Stop button:
EMERGENCY STOP – LOCAL / Pull the button out.
EMERGENCY STOP – REMOTE Move the O/Manual/Auto switch to O (off).
Press the front panel Fault Acknowledge button.
Select Manual or Auto, as required.
CODE: 1438 Indicates possible fault with control or starting system. Check for the fol-
LAMP: Warning lowing conditions:
MESSAGE: a. Poor battery cable connections. Clean the battery cable terminals
FAIL TO CRANK and tighten all connections.
b. Discharged or defective battery. Recharge or replace the battery.
CODE: 1439 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN DAY
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 1441 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN MAIN
CODE: 1442 Indicates battery voltage drops below 14.4 volts for two seconds, during
LAMP: Warning starting.
MESSAGE: Discharged or defective battery.
BATTERY IS WEAK See Warning message 441 Low Battery Voltage.
CODE: 1443 Indicates battery has dropped below genset operating range (3.5 volts
LAMP: Warning when cranking) to power the starter and the control circuitry.
MESSAGE: See Warning message 441 Low Battery Voltage.
BATTERY IS DEAD
Establish and adhere to a definite schedule for • Exposure to dust, sand or other airborne con-
maintenance and service based on the application taminates
and severity of the environment. Table 5-1 covers Consult with your local Cummins Power Generation
the recommended service intervals for a generator
distributor if the generator set will be subjected to
set on STANDBY service. If the set will be subjected
any extreme operating conditions and determine a
to extreme operating conditions, the service inter-
suitable schedule of maintenance. Use the running
vals should be reduced accordingly. Some of the time meter to keep an accurate log of all service per-
factors that can affect the maintenance schedule formed for warranty support. Perform all service at
are the following: the time period indicated or after the number of op-
• Use for continuous duty (prime power) erating hours indicated, whichever comes first. Use
Table 5-1 to determine the maintenance required
• Extremes in ambient temperature
and then refer to the sections that follow for the cor-
• Exposure to weather rect service procedures.
SERVICE TIME
Month- 6
Daily Yearly
MAINTENANCE ITEMS See ly Month
or after or after 1000 4000
Engine or after s or af-
8 500 Hours Hours
Schdl. 100 ter 250
Hours Hours
Hours Hours
General set inspection X1 X2
Check engine oil level X
Check coolant level of radiators (Jacket Water
X
& LTA)
Check coolant heater(s) X
Check battery charging system X
Check all hardware (fittings, clamps, fasteners,
X
etc.)
Check drive belts X3
Check battery electrolyte level X
Drain exhaust condensate trap X
Check generator air outlet X
Check radiator hoses for wear and cracks X
Grease fan bearings (two) X
Test generator insulation resistance X4
Grease generator bearing (Frame 7) X5,6
Grease generator bearing (Frame 8) X5, 6
Check air cleaner (replace as necessary) X1
Drain fuel filter(s) X1
Check anti-freeze and DCA concentration X1
Change engine oil and filter X1
Change jacket water coolant filters X1
Clean crankcase breather X1
Change fuel filters X1
Clean Jacket Water & LTA cooling systems X1
X1 - Refer to Cummins QSK45/QSK60 Series Engine Operation and Maintenance Manual for maintenance interval and/or
procedure.
X2 - Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair
any leaks immediately.
X3 - Visually check belts for evidence of wear or slippage. Replace if hard or brittle.
X4 - This procedure should be followed periodically throughout the life of the generator set, or if the generator has set idle for a period
of time with no generator heaters used. Contact your authorized service center.
X5 - Frame 7 outside casing is round, Frame 8 outside casing is octagon-shaped (flat-sided).
X6 - Re-lubrication time periods and amount of grease used may vary in this manual from what is suggested on label located
adjacent to end bearing. Use the information provided in this manual for these values.
LTA COOLING
SYSTEM FILL CAP
AIR CLEANER
Refer to the Cummins QSK45 and QSK60 Series
Engines Operation and Maintenance Manual for air
cleaner filter element replacement interval and pro-
cedure.
Cleaning Batteries Fill the battery cells to the bottom of the filler neck. If
cells are low on water, add distilled water and re-
WARNING Electrolyte is a dilute sulfuric acid charge. If one cell is low, check case for leaks. Keep
that is harmful to the skin and eyes. Do not get the battery case clean and dry. An accumulation of
the substance in your eyes or contact with skin. moisture will lead to a more rapid discharge and
Wear goggles and protective, rubber gloves battery failure.
and apron when servicing batteries.
Battery Replacement
In case of contact, immediately wash skin with
soap and water. In case of contact, immediately Always replace the starting battery with the same
flood eyes with large amounts of water for a number and type (vented, lead acid). Properly dis-
minimum of 15 minutes. IMMEDIATELY CALL A pose of battery in accordance with local environ-
PHYSICIAN. mental agency requirements.
Keep the batteries clean by wiping them with a WARNING Electrolyte or explosion of battery
damp cloth whenever dirt appears excessive. can cause severe personal injury or death. Do
not mutilate or burn the battery in a fire for dis-
If corrosion is present around the terminal connec- posal.
tions, remove battery cables and wash the termi-
nals with a solution consisting of 1/4 pound of bak- Damage to case will release electrolyte which is
ing soda added to 1 quart of water. (This solution is harmful to the skin and eyes and is also toxic.
also used for washing down spilled electrolyte.) Burning of battery may cause an explosion.
Redistribution or publication of this document,
by any means, is strictly prohibited.
5-9
FAN BEARING RE-LUBRICATION
BEARINGS
Re-lubricate the fan bearings at the interval speci-
fied in the Maintenance Table. A grease fitting is
provided for each of the two bearings to allow the
use of a grease gun to re-lubricate the bearings.
The grease fittings are located on side of the fan
housing pedestal structure (Figure 5-4).
The recommended lubricant is a lithium based
grease, such as, Mobilux EP 2, Mobilith AW 2, or
Shell Alvania R3.
Note the following quantities when re-lubricating
the bearings.
Fan side bearing – 39 grams
Pulley side bearing – 31 grams
GREASE
FITTINGS