Cummins DQKB DQKC Operators Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56
At a glance
Powered by AI
The manual provides instructions for safely operating and maintaining a PowerCommand Control 3200 Series generator set.

The main sections covered include introduction, specifications, operation, troubleshooting, and maintenance recommendations.

The steps for operating the generator include performing prestart checks, starting the generator from the control panel, running and stopping the generator.

Operator's Manual

PowerCommand Control
3200 Series
Generator Sets

Models
DQKB, DQKC

Printed in U.S.A. 960-0161 9-2001


Table of Contents

SECTION TITLE PAGE


IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
1 INTRODUCTION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How to Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3 OPERATION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Prestart Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Control Panel Power On/Off Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Control Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Running At Idle (Manual) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Menu Display and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Menu Units Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
ENGINE DATA Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
ALTERNATOR DATA Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
CONTROL Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
HISTORY/ABOUT Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
ADJUST Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
BUS DATA Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
PASSWORD Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20

California
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects, and
other reproductive harm.

Redistribution or publication of this document,


by any means, is strictly prohibited.
i
SECTION TITLE PAGE
4 TROUBLESHOOTING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Reading Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Line Circuit Breaker (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Control and Diagnostics VIA Network or PC (Laptop) . . . . . . . . . . . . . . . . . 4-2
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Fault Code Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Troubleshooting Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
5 MAINTENANCE
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Periodic Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Generator Set Maintenance (Battery Disconnected) . . . . . . . . . . . . . . . . . . 5-4
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Heat Exchanger Cooling System (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Fan Bearing Re-lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Fan Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Generator Bearing Re-lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
6 OPERATING RECOMMENDATIONS
No-Load Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Exercise Period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Low Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
High Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1

Redistribution or publication of this document,


by any means, is strictly prohibited.
ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator and batter- • Provide an adequate exhaust system to properly
ies. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
• Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
ator, service personnel, or the equipment.
birth defects, and other reproductive harm.
This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or un- moving parts.
safe practice which can result in severe person-
al injury or death. • Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or un- connect starting batteries, negative (–) cable first.
safe practice which can result in personal injury This will prevent accidental starting.
or product or property damage. • Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result • Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
• DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential • If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
• Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
• Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.

Redistribution or publication of thisLS-14M


document,
by any means, is strictly prohibited.
iii
ELECTRICAL SHOCK CAN CAUSE GENERAL SAFETY PRECAUTIONS
SEVERE PERSONAL INJURY OR DEATH • Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex-
• Remove electric power before removing protective changer pressure cap while the engine is running.
shields or touching electrical equipment. Use rub- Allow the generator set to cool and bleed the system
ber insulative mats placed on dry wood platforms pressure first.
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing • Used engine oils have been identified by some state
(particularly wet shoes) or allow skin surface to be or federal agencies as causing cancer or reproduc-
damp when handling electrical equipment. Do not tive toxicity. When checking or changing engine oil,
wear jewelry. Jewelry can short out electrical con- take care not to ingest, breathe the fumes, or con-
tacts and cause shock or burning. tact used oil.

• Use extreme caution when working on electrical • Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
components. High voltages can cause injury or
such as wood and cloth; Class B fires, combustible
death. DO NOT tamper with interlocks.
and flammable liquid fuels and gaseous fuels; Class
• Follow all applicable state and local electrical C fires, live electrical equipment. (ref. NFPA No. 10).
codes. Have all electrical installations performed by • Make sure that rags are not left on or near the en-
a qualified licensed electrician. Tag and lock open gine.
switches to avoid accidental closure.
• Make sure generator set is mounted in a manner to
• DO NOT CONNECT GENERATOR SET DIRECT- prevent combustible materials from accumulating
LY TO ANY BUILDING ELECTRICAL SYSTEM. under the unit.
Hazardous voltages can flow from the generator set • Remove all unnecessary grease and oil from the
into the utility line. This creates a potential for elec- unit. Accumulated grease and oil can cause over-
trocution or property damage. Connect only heating and engine damage which present a poten-
through an approved isolation switch or an ap- tial fire hazard.
proved paralleling device.
• Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-
MEDIUM VOLTAGE GENERATOR SETS
bris from the set and keep the floor clean and dry.
(601V to 15kV) • Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
• Medium voltage acts differently than low voltage. or drug that makes the operation of equipment un-
Special equipment and training is required to work safe.
on or around medium voltage equipment. Operation • Substances in exhaust gases have been identified
and maintenance must be done only by persons by some state or federal agencies as causing can-
trained and qualified to work on such devices. Im- cer or reproductive toxicity. Take care not to breath
proper use or procedures will result in severe per- or ingest or come into contact with exhaust gases.
sonal injury or death.
• Do not store any flammable liquids, such as fuel,
• Do not work on energized equipment. Unauthorized cleaners, oil, etc., near the generator set. A fire or
personnel must not be permitted near energized explosion could result.
equipment. Due to the nature of medium voltage
electrical equipment, induced voltage remains even
• Wear hearing protection when going near an oper-
after the equipment is disconnected from the power ating generator set.
source. Plan the time for maintenance with autho- • To prevent serious burns, avoid contact with hot
rized personnel so that the equipment can be de-en- metal parts such as radiator, turbo charger and ex-
ergized and safely grounded. haust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

Redistribution or publication of this document,


by any means, is strictly prohibited.
iv
1. Introduction
GENERAL tor. Factory-trained Parts and Service representa-
tives are ready to handle all your service needs.
This manual covers models produced under the
Cummins/Onan and Cummins Power Genera-
tion brand names. To contact your local Cummins Power Generation
distributor in the United States or Canada, call
Each operator should read this manual before oper- 1-800-888-6626 (this automated service utilizes
ating the set for the first time. A generator set (gen- touch-tone phones only). By selecting Option 1
set) must be operated and maintained properly if (press 1), you will be automatically connected to the
you are to expect safe, reliable and quiet operation. distributor nearest you.
The manual includes a troubleshooting guide and a
maintenance schedule. If you are unable to contact a distributor using the
The engine manual is included with the set. Where automated service, consult the Yellow Pages. Typi-
there is conflicting information, this manual takes cally, our distributors are listed under:
precedence over the engine manual.
GENERATORS-ELECTRIC or
WARNING Improper operation and mainte- ELECTRICAL PRODUCTS
nance can lead to severe personal injury or loss
of life and property by fire, electrocution, me- For outside North America, call Cummins Power
chanical breakdown or exhaust gas asphyxi- Generation, 1-763-574-5000, 7:30 AM to 4:00 PM,
ation. Read and follow the safety precautions Central Standard Time, Monday through Friday. Or,
on page iii and carefully observe all instructions send a fax to Cummins Power Generation using the
and precautions in this manual. fax number 1-763-574-8087.
HOW TO OBTAIN SERVICE
When contacting your distributor, always supply the
When the generator set requires servicing, contact complete Model, Specification, and Serial Number
your nearest Cummins Power Generation distribu- as shown on the generator set nameplate.

WARNING

INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL IN-


JURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED
AND EXPERIENCED TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.

Copyright 2001 Cummins Power Generation. All rights reserved.


Cummins, Onan and PowerCommand are registered trademarks of Cummins Inc.
Redistribution or publication of this document,
by any means, is strictly prohibited.
1-1
THIS PAGE LEFT INTENTIONALLY BLANK

Redistribution or publication of this document,


by any means, is strictly prohibited.
1-2
2. Specifications

MODEL DQKB/DQKC
Cummins Diesel Series QSK60 (50/60 Hz)
Generator kW Rating See Genset Nameplate for rating iinformation.
Cooling System Radiator-Cooled Models
40° C
Jacket Water Cooling System
Low-Temp Aftercooling System 82 Gal (310 L)
50° C 42 Gal (159 L)
Jacket Water Cooling System
Low-Temp Aftercooling System 90 Gal (341 L)
40 Gal (152 L)
Oil Capacity, Maximum (see Figure 2-1)
Oil Pan Only
Standard Capacity 69 Gal (261 L)
High Capacity 100 Gal (379 L)
System (w/Std. Filters)
Standard Capacity 74 Gal (280 L)
High Capacity 105 Gal (398 L)
*Oil Type
**Fuel Consumption
Standby/Full Load/60Hz GPH(LHR) 118.9 (450.6) / 136.6 (517.7)
Electrical System
Starting Voltage 24 Volts DC
Battery Four, 12 Volt
Group Number 8D
CCA (minimum)
Cold Soak @ 0° F (-18° C) 1800
* Refer to Cummins QSK45/60 Series Engine Operation and Maintenance Manual for lubricating oil
recommendations/specifications.
** Refer to Data Sheet for other applications.

Redistribution or publication of this document,


by any means, is strictly prohibited.
2-1
STANDARD CAPACITY

HIGH CAPACITY

FIGURE 2-1. OIL PAN TYPES A/B

Redistribution or publication of this document,


by any means, is strictly prohibited.
2-2
3. Operation
GENERAL Lubrication
The following describes the function and operation Check the engine oil level. Keep the oil level near as
of the PowerCommand Control 3200 (PCC). All in- possible to the dipstick high mark without overfilling.
dicators, control switches/buttons and graphical
display are located on the face of the control panel Coolant
as illustrated in Figure 3-1.
Check the engine coolant level. Refer to Section 5.
This section covers prestart checks, starting and
stopping and operating the generator set. Each op- Fuel
erator should read through this entire section before
attempting to start the set. It is essential that the op- Make sure the fuel tanks have sufficient fuel and
erator be completely familiar with the set and the that fuel system is primed. Check to make sure
control panel. Refer to Section 6 for operating rec- there are no leaks and that all fittings are tight.
ommendations.
Exhaust
PRESTART CHECKS
Check to make sure entire exhaust system is tight,
Before starting, be sure the following checks have that no combustible materials are near system, and
been made and the unit is ready for operation. gases are discharged away from building openings.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-1
CONTROL PANEL POWER ON/OFF off. Sleep mode is a feature that is used to reduce
MODES battery power consumption when the control is in
the Auto mode and is not being used.
The power on/off modes of the control panel and op-
erating software are Power On, Screen Saver and When all conditions are met (i.e., no unacknowl-
Sleep/Awake. edged faults, Screen Saver Mode is active, and O/
Manual/Auto switch is in the Auto position) the
Power On Mode: In this mode, power is continu- Sleep mode will be activated.
ously supplied to the control panel. The control’s
operating software and control panel LEDs/graphi- The operating software is initialized and the control
cal display will remain active until the Screen Saver panel LEDs and graphical display is turned on in re-
mode is activated. sponse to one of the following:
Screen Saver Mode: Power to the graphical dis- • moving/pressing any control panel switch/but-
play will be removed after 10 minutes (generator set ton.
not running or running). The 10 minute timer resets • a remote start input signal (generator set in
and begins after each control panel action (any but- Auto mode), or
ton or switch selection) or signal received by the op-
erating software. The bottom LEDs of the Analog
• customer fault 2 or 3 only (shutdown or warning
indicator is on).
AC Metering Panel (bar graphs) may remain on dur-
ing Screen Saver mode, indicating that the operat- To activate the control and view the menu display
ing software is active (Awake mode). without starting the generator set, press any button
on the control panel.
When a “Warning” signal is sensed by the PCC (for
example, low coolant temp), the control will display The InPower service tool is required to enable or
the warning message. The control will remain active disable the Sleep mode. When shipped from the
until the Fault Acknowledge button is pressed to factory, the Sleep mode is disabled. When disabled,
clear the warning message and start the 10 minute the operating software will always remain active
timer. (Awake mode) when the control is in Auto mode.

Sleep/Awake Mode: In the Sleep mode, the con- InPower service tool is required to select desired
trol’s operating software is inactive and the LEDs mode. Contact an authorized service center for as-
and the graphical display on the control panel are all sistance.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-2
OPERATOR PANEL SWITCH PANEL

REMOTE START,
NOT IN AUTO,
SHUTDOWN,
WARNING
STATUS INDICATORS
ANALOG AC PANEL LAMP/ FAULT EMERGENCY
METERING LAMP TEST ACKNOWLEDGE STOP PUSH
PANEL BUTTON BUTTON BUTTON

DISPLAY MENU EXERCISE MANUAL RUN/


SELECTION BUTTONS BUTTON & STOP BUTTON
(1 of 6) INDICATOR & INDICATOR

GRAPHICAL 0/MANUAL/AUTO
DISPLAY SWITCH

FIGURE 3-1. CONTROL PANEL ASSEMBLY (FULL-FEATURED)

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-3
CONTROL PANEL ASSEMBLY Display Menu Selection Buttons: Six momentary
buttons—three on each side of the graphical dis-
The control panel assembly (Figure 3-1) consist of play window—are used to navigate through the sys-
two panels, the Operator Panel and the Switch Pan- tem control menus and to adjust generator set pa-
el. The control panel assembly can be mounted on rameters. The button is active when the message
the genset or in a freestanding cabinet located near adjacent to the button is highlighted (displayed in in-
the genset. In either location, the function of the verse video).
control panel assembly switches and indicators re-
main the same. Switch Panel
Dependent on site requirements, the Operator Pan- The switch panel contains the following compo-
el is either mounted on the control panel assembly nents:
(full-featured) as shown in Figure 3-1 or is con-
tained in a separate enclosure and mounted re- Emergency Stop Button: Push the button in for
motely of the control panel assembly. emergency shutdown of the engine. If the engine is
not running, pushing the button in will prevent the
The function of several buttons on the operator pan- starting of the engine, regardless of the start signal
el will vary dependent on the location of the operator source (local or remote).
panel (remote or local of the control panel assem-
bly). If the function differs, it is noted as either “re- To reset:
mote” or “local operator panel” in the button de- 1. Pull the button out.
scription. 2. Move the 0/Manual/Auto switch to 0.
3. Press the front panel Fault Acknowledge
Operator Panel button.
4. Select Manual or Auto, as required.
The operator panel contains the following compo-
nents: Remote Start Indicator: This green lamp is lit
whenever the control is receiving a remote run sig-
Analog AC Metering Panel: This panel simulta- nal. When flashing, indicates a load demand stop
neously displays 3-phase line to line AC volts and mode.
current, kW, power factor and frequency.
Not in Auto Indicator: This red lamp flashes con-
The meter panel is composed of a series of LEDs, tinuously when the 0/Manual/Auto switch is not in
that are configured in bar graphs for each function. the Auto position. (If in Auto position and lamp is
The LEDs are color coded, with green indicating flashing, service is required.)
normal range values, amber for warning levels and
red for shutdown conditions. Shutdown Status Indicator: This red lamp is lit
whenever the control detects a shutdown condition.
Scales for each function are in % of nominal values. The generator set can not be started when this lamp
Resolution is 1% for values close to nominal, and in- is on. After the condition is corrected, shutdown in-
creases at values further from nominal. dicators can be reset by turning the 0/Manual/Auto
switch to the 0 position, and pressing the Fault Ac-
Graphical Display: The graphical display is capa- knowledge button.
ble of displaying up to 9-lines of data with approxi-
mately 27 characters per line. The display is used to Dependent upon the specific fault that occurs, the
view the menus of the menu-driven operating sys- engine may or may not shut down immediately. A
tem. Refer to the menu trees later in this section. fault that could cause engine damage, causes an
The display is also used to show warning and shut- immediate engine shutdown (bypasses engine
down messages/error codes, modes of operation cool-down sequence). All other faults would allow
(Figure 3-3) and system actions, such as Warning, the engine to run during the cool-down sequence
Derate, Shutdown, etc. before engine shutdown.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-4
Warning Status Indicator: This yellow lamp is lit minate. The illumination will shut off after releasing
whenever the control detects a warning condition. button.
After the condition is corrected, warning indicators
can be reset by pressing the Fault Acknowledge Exercise Button: Press this button to initiate a pre-
button. (It is not necessary to stop the generator set programmed exercise sequence. The 0/Manual/
if the fault becomes inactive during genset opera- Auto switch is used in conjunction with this button to
tion.) enable this function (refer to Exercise Start in this
section).
Fault Acknowledge: Press this button to acknowl-
edge warning and shutdown messages after the Manual Run/Stop Button: This button starts and
fault has been corrected. stops the set locally and will bypass Time Delay to
Start and Stop sequences. The 0/Manual/Auto
To acknowledge a Warning message, the 0/Manu- switch must be in the Manual position to enable this
al/Auto switch can be in any position. (It is not nec- button.
essary to stop the generator set to acknowledge an
inactive Warning condition.) To acknowledge a 0/Manual/Auto Switch: Manual position enables
shutdown message with this button, the 0/Manual/ the use of the switch panel Manual Run/Stop but-
Auto switch must be in the 0 (Off) position. ton.

This button is also used to blink a fault code if the Auto position enables start/stop control of the en-
Shutdown or Warning Status Indicator is lit. (This gine from a remote location. (Disables the use of the
function is used when the control does not contain a switch panel Manual Run/Stop button.)
graphical display.) Refer to Reading Fault Codes in
this section, which describes how to use this button 0 (Off) position prevents the starting of the set (local
for interpreting fault codes. or remote). If moved to 0 during set operation, will
cause an immediate engine shutdown (bypasses
Panel Lamp/Lamp Test Button: Press this button cool-down timers). This hot shutdown should be
to turn on or off the panel lamp. Press and hold avoided, if possible, to help prolong the life of the
down this button for three seconds or more to turn engine. Hot shutdowns are logged by the system
all control panel LEDs on to make sure all lamps illu- software.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-5
STARTING Acknowledge button. Wait two or more minutes for
the starter motor to cool and then repeat the starting
The following headings cover the systems used to procedure. If the engine does not run after a second
start the generator set. Figure 3-2 provides a flow attempt, refer to the Troubleshooting section.
chart for each of the four start/run/stop sequences.
Starting at Remote Operator Panel (Auto
Before starting the generator set, make sure that Mode)
exhaust and fuel fittings are tight and that proper
maintenance has been performed. See Prestart When the operator panel is mounted remotely of the
Checks in this section. control panel assembly, the Start button of the Con-
trol submenu can also be used to start the generator
Starting at Switch Panel (Manual Mode) set. The function of this Start button is identical to
the Starting from Remote Location (non-emergen-
Move the 0/Manual/Auto switch to the Manual posi- cy sequence, Figure 3-2). Refer to Control Subme-
tion and press the Manual Run/Stop button. This nu (page 3-15) for additional information.
will activate the engine control system and the start-
ing system. The starter will begin cranking, and af- The 0/Manual/Auto switch must be in the Auto posi-
ter a few seconds the engine will start and the start- tion to activate the Remote Menu Buttons of the Con-
er will disconnect. trol submenu.

In the Manual position, the control will not complete Starting from Remote Location (Switch or
the time delay to start or time delay to stop (Figure Device) (Auto Mode)
3-2), but will complete the warm-up at idle and cool-
down at rated/idle. Place the 0/Manual/Auto switch in the Auto posi-
tion. This allows the generator set to be started from
When the coolant reaches operating temperature a remote switch or device (e.g., transfer switch).
or the warm-up at idle time delay is reached (0 to
300 seconds), whichever occurs first, the generator There are two start modes that are selectable for
set will ramp to rated speed and voltage. the remote start input, one for non-emergency start
and the other for emergency start. Figure 3-2 illus-
If the engine does not start, the starter will disen- trates how the start/run/stop sequence differs be-
gage after a specified period of time and the control tween the two modes.
will indicate an overcrank shutdown.
In response to the remote run signal, the control
The generator set can be configured for a number of lights the Remote Start indicator and initiates the
starting cycles (1 to 7) and duration of crank and rest starting sequence described in the previous head-
periods. Default setting is for 3 start cycles com- ing (Starting at Switch Panel), except for the follow-
posed of 15 seconds of cranking, and 15 seconds of ing:
rest.
In the Auto position, the control will complete the
The InPower service tool is required to change the Time Delay To Start (0 to 300 seconds) for a non-
number of crank cycles, and the crank and rest emergency start signal and the Time Delay To Stop
times. Contact an authorized service center for as- (0 to 600 seconds) for either a emergency or non-
sistance. emergency start signal (see Figure 3-2).
To clear a Fail To Start shutdown, place the 0/Manu- Refer to Adjust submenu in this section to change
al/Auto switch in the 0 position and press the Fault the time delay settings.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-6
Exercise Start below 70°F (21°C). In applications where the ambi-
ent temperature falls below 40°F (4°C), a cold en-
Press and hold down the Exercise button and move
gine may be indicated even though the coolant
the 0/Manual/Auto switch from Auto to Manual and
heaters are connected and functioning properly.
back to Auto or from Manual to Auto.
Under these conditions, although the generator set
This will activate the engine control system to com- may start, it may not be able to accept load within 10
plete a pre-programmed exercise sequence. The seconds. When this condition occurs, check the
sequence (Figure 3-2) will vary accordingly to the coolant heaters for proper operation. If the coolant
settings/selections of the system control parame- heaters are operating properly, other precautions
ters. may be necessary to warm the engine before apply-
ing a load.
The InPower service tool is required to modify these
parameters. Contact an authorized service center for RUNNING AT IDLE (MANUAL)
assistance.
The Run At Idle mode is selectable only when the op-
The exercise sequence may include running at idle erator panel is mounted on the control panel assem-
speed, ramping to rated speed, running for a prede- bly.
termined period of time and timed shutdown. During
The run mode can be set to Rated or Idle with the set
the exercise operation, the LED lamp adjacent to
running or not running. To manually select the en-
the Exercise button will light. To manually stop the
gine idle function, the 0/Manual/Auto switch must
exercise operation before completion, press the Ex-
be in the Manual position. Once selected and the
ercise button. The set will complete its normal cool-
set is manually started, the control will limit the en-
down sequence. The control will indicate that the
gine idle time to 10 minutes. When the 10 minute
set is in a cool-down mode by flashing the exercise
idle cycle is complete, the genset will ramp to rated
LED.
speed.
All exercise functions are disabled when a remote
CAUTION Do not idle the engine for long peri-
start signal is received by the control.
ods. Idling more than 10 minutes can damage
Cold Starting with Loads an engine. Combustion chamber temperatures
drop so low the fuel will not burn completely,
In accordance with NFPA 110, Cummins Power causing carbon to clog the injector spray holes
Generation recommends installing diesel standby and piston rings, and causing the valves to
generator sets (life safety systems) equipped with stick.
engine jacket water coolant heaters in locations
where the minimum ambient temperature is above CAUTION If the engine coolant temperature
40°F (4°C). NFPA also requires that the engine becomes too low, 140° F (60° C), raw fuel from in-
jacket water coolant be maintained at a minimum of complete combustion will wash the lubricating
90°F (32°C) and for most applications, accept the oil off the cylinder walls and dilute the crank-
emergency load in 10 seconds or less. Although case oil. Therefore, all moving parts of the en-
most generator sets will start in temperatures down gine will not receive the correct amount of lu-
brication.
to –25°F (–32°C) when equipped with engine jacket
water coolant heaters, it might take more than 10 To activate the idle function, refer to page 3-15.
seconds to warm the engine up before a load can be
applied when ambient temperatures are below When the engine idle function is enabled, the con-
40°F (4°C). trol automatically sets lower oil pressure warning
and shutdown trip points to reflect the lower operat-
The Engine Cold (Code 1435) message, in con- ing speed. When the engine idle function is re-
junction with illumination of the Warning LED, is pro- moved and the set reverts to normal operating
vided to meet the requirements of NFPA 110. The speed, the control automatically resets oil pressure
engine cold sensing logic initiates a warning when warning and shutdown trip points to the normal set-
the engine jacket water coolant temperature falls tings.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-7
STOPPING reliability of the engine. Hot shutdowns are logged
in the system software.
Emergency Stop (Code 1434)
Stopping at Remote Operator Panel (Auto
The emergency stop button is located on the upper Mode)
right side of control panel (Figure 3-1). Push the but-
ton in for emergency stop. The red Shutdown status When the operator panel is mounted remotely of the
LED will light, and the graphical display message control panel assembly, the Stop button of the Con-
will be: “EMERGENCY STOP trol submenu can also be used to stop the generator
1434 – SHUTDOWN” set (0/Manual/Auto switch in the Auto position).
To reset: The function of this Stop button is identical to the
1. Pull the button out. Stopping from Remote Location (non-emergency
2. Move the 0/Manual/Auto switch to 0. sequence, Figure 3-2). Refer to Control Submenu
3. Press the front panel Fault Acknowledge (page 3-15) for additional information.
button.
4. Select Manual or Auto, as required. The 0/Manual/Auto switch must be in the Auto posi-
tion to activate the Remote Menu Buttons of the Con-
Emergency Stop shutdown status can be reset only trol submenu.
at the operator control panel.
Stopping from Remote Location (Switch
Stopping at Switch Panel (Manual Mode) or Device) (Auto Mode)
If the set was started at the switch panel (0/Manual/ If the control receives a remote stop signal (0/Manu-
Auto switch in the Manual position), pressing the al/Auto switch in the Auto position), the set will com-
Manual Run/Stop button will cause the set to com- plete its normal shutdown sequence.
plete its normal (Local Start) shutdown sequence
(Figure 3-2). There are two start modes that are selectable for
the remote start input, one for non-emergency start
The preset cool-down time (at rated speed) can and the other for emergency start. Figure 3-2 illus-
vary dependent on the kW output. That is, if prior to trates how the start/run/stop sequence differs be-
shutdown, the kW is 10% or less of rated, the control tween the two modes. Note that the stop sequence
software considers this output as cool-down and is the same for either mode.
will subtract this time from the preset cool-down tim-
er. The set will stop after completing the following cool-
down sequence:
The set will stop after the Cool-down At Idle Timer (0
to 10 minutes) has timed out. (If necessary, the set • Time Delay To Stop (0 to 300 seconds)
will continue to run after time-out until coolant • Cool-down At Idle (0 to 10 minutes) or longer, if
reaches normal operating temperature.) necessary, to obtain normal operating temper-
Moving the 0/Manual/Auto switch to the 0 position ature before shutdown.
will cause an immediate engine shutdown (bypass Refer to Adjust submenu in this section to change
Cool-down At Idle) and display a Cool-down Inter- the Time Delay To Stop setting. The InPower service
rupted Warning message. This hot shutdown tool is required to modify the Cool-down At Idle. Con-
should be avoided, if possible, to help prolong the tact an authorized service center for assistance.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-8
REMOTE START START - REMOTE LOCAL START LOCAL START
CUST. CONNECT OPERATOR PANEL SWITCH PANEL SWITCH PANEL
(Auto Mode) (Auto Mode) (Manual Mode) (Auto Mode)

START GENSET RUN EXERCISE


BUTTON BUTTON BUTTON
OR
EMERGENCY NON-EMERGENCY
REMOTE START REMOTE START

TIME DELAY TO TIME DELAY TO TIME DELAY TO


START START START
1 1 1

WARM-UP WARM-UP WARM-UP


@ @ @
IDLE IDLE IDLE
1 or 2 1 or 2 1 or 2

RATED SPEED RATED SPEED RATED SPEED RATED SPEED


& & & &
VOLTAGE VOLTAGE VOLTAGE VOLTAGE

REMOTE REMOTE CONTROL STOP EXERCISE TIME


STOP STOP BUTTON EXPIRES

TIME DELAY TO TIME DELAY TO TIME DELAY TO


STOP STOP STOP
1 1 1

COOL-DOWN COOL-DOWN COOL-DOWN COOL-DOWN


@ @ @ @
RATED/IDLE3 RATED/IDLE3 RATED/IDLE3 RATED/IDLE3
1 1 1 1

STOP STOP STOP STOP

NOTES:
1. Timer expires.
2. Coolant temperature reaches operating level.
3. Cool-down can be at rated speed and/or idle with
different time-outs for each.

FIGURE 3-2. NORMAL START/RUN/STOP SEQUENCES

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-9
MENU DISPLAY AND SWITCHES • Description Line – Fault code/status mes-
sages.
Figure 3-3 shows the graphical display and the Menu Buttons: Six momentary buttons—three on
menu selection buttons. each side of the graphical display window—are
used to navigate through the system control menus
Graphical Display: The graphical display is capa- and to adjust generator set parameters. The button
ble of displaying up to 9-lines of data with approxi- is active when the message or symbol adjacent to
mately 27 characters per line. The display is used to the switch is highlighted (displayed in inverse vid-
view the menus of the menu-driven operating sys- eo). The displayed message or symbol indicates
tem. Refer to the menu trees later in this section. the function of the button.
The display is also used to show the following sys-
tem information: In the graphical display, the “” symbol indicates
that selecting the adjacent button causes the operat-
• State Line – modes of operation, such as ing program to go to the next menu display—as
shown in the menu diagrams.
Stopped, Time Delay To Start, Warm Up At
Idle, etc. (see Figure 3-2), and paralleling op- In the graphical display, the “” symbol indicates
erations, such as Standby, Dead BUS Close, that selecting the adjacent button causes the operat-
Synchronize, etc. ing program to go back to the previous menu display.

• Action Line – system actions, such as Warning, In the graphical display, the “ ” symbol indicates
Derate, Shutdown Cool-down and Shutdown, that selecting the adjacent button causes the operat-
and fault codes. ing program to go back to Main Menu A (Figure 3-5).

STATE LINE
ACTION LINE
DESCRIPTION LINE

MENU DISPLAY
AREA

GRAPHICAL
DISPLAY

MENU MENU
BUTTONS BUTTONS

FIGURE 3-3. GRAPHICAL DISPLAY AND MENU SELECTION BUTTONS

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-10
MENU UNITS SELECTION
During any control panel operation, you can change
how units are displayed by pressing the two lower
menu buttons (one on each side of display). When LOCATION LOCAL
pressing these two buttons simultaneously, the + TEMP °F
PRESS FLD PSI
units submenus will appear (Figure 3-4). After se- PRESS GAS INHG ENTER
lecting the desired units, press the ENTER button in → FLOW AIR CFM
this submenu to change and save the selections.
Use the + button to select the desired option for each
field. Use the arrow (→) button to move to the next
field. Selected field is highlighted.
FIGURE 3-4. UNITS SUBMENU
Local/Remote Field: This selection must be set to
Local when the graphical display is mounted on the
generator set front control panel or Remote when
mounted remotely of the generator set.
The Local/Remote selection determines which but-
tons in the Control submenu (page 3-15) are active
(displayed).
Temp: Used to select ° F or ° C for temperature
readings.
Pressure Fluid: Used to select PSI, KPA, BAR or
IN for pressure readings.
Pressure Gas: Used to select INHG or MMHG for
pressure readings.
Flow Air: Used to select CFM or CMM for air flow
readings.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-11
MAIN MENU _\_ Button: (Paralleling applications only). Used to
open and close the generator set circuit breaker
Figure 3-5 shows the main menus (Menu A and (CB). The symbol indicates if the CB is opened or
Menu B) of the system control. The two main menus closed. Opened _\_, push to close. Closed _–_,
are used to divide the system submenus into major
push to open.
categories, such as, Engine Data, Alternator Data,
Control, etc.
With the control panel 0/Manual/Auto switch in the
To view system data, simply press the appropriate Auto position, the opening and closing of the CB is
menu button to select the category. After pressing controlled by the control system software. The CB
the desired menu button, refer to the page number symbol will indicate an open or closed CB, but the
shown in Figure 3-5 for detailed information related
button will be inactive when the control is in Auto.
to the selected category.
Adjust Button: The Adjust submenu is intended for In the Manual position, the CB can only be closed
qualified site personnel only. Note that a password by using this button. When manually closed and the
may be assigned to allow only authorized operators CB opens, it must be closed again by using this but-
to modify this data. (Password is not required if not
ton. To close the CB, press and hold the button until
assigned.)
the symbol indicates a closed CB. (CB close will oc-
Setup Button: The Setup submenu is described in cur only when setup conditions allow – dead bus or
the Service manual and is intended for qualified ser- generator synchronized with bus.)
vice personnel only. For this reason, a password
must be entered before this data can be modified.
In the following figures, the boxed/highlighted field
The “Adjust” and “Setup” submenus can be viewed, indicates that the adjacent menu button is active.
but not modified without entering the correct pass- Also, the submenus are shown in the order in which
words. they are displayed when scrolling up  or down .

MENU A
MENU MENU
BUTTONS PAGE MENU BUTTONS
3-13 B

ENGINE MORE>>
PAGE ALTERNATOR _\_ See
3-14 CONTROL HISTORY/ABOUT Above

PAGE PAGE
3-15 3-16

MENU B

PAGE
3-17

ADJUST
BUS DATA PAGE
SETUP BACK<< 3-18

GRAPHICAL
Service DISPLAY MENU
Manual A

FIGURE 3-5. SYSTEM CONTROL MAIN MENUS A AND B


Redistribution or publication of this document,
by any means, is strictly prohibited.
3-12
ENGINE DATA SUBMENUS

If you press the “ENGINE DATA” button in Menu A,


the Engine Data submenus will appear (Figure 3-6). ENGINE DATA
The first submenu displays general information that
applies to all gensets (coolant temp, oil pressure,
etc.) The data in the remaining submenu(s) will vary
according to the type and number of sensors pro- COOLANT TEMP 180 ° F
vided with the engine. OIL PRESSURE 75 PSI 
ENGINE SPEED 1800 RPM
BATTERY 29.1 VDC 

MANF TEMP 75 °F
MANF PRESS ABS 180 INHG 
RAIL PRESS ABS 180 PSI
PUMP PRESS ABS 291 PSI 
FUEL INLET TEMP 172 °F
COOLANT PRESSURE 59 PSI

BLOWBY FLOW 25 CFM


TIMING PRESS 50 PSI 
AFTERCOOLER TEMP 76 °F
AMBIENT PRESS 88 INHG

FIGURE 3-6. ENGINE DATA SUBMENUS

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-13
ALTERNATOR DATA SUBMENUS

If you press the “ALTERNATOR DATA” button in


Menu A, the Alternator Data submenus will appear ALTERNATOR DATA
(Figure 3-7).
Voltage L-L and L-N: Indicates voltage Line-to
Line and Line-to-Neutral. Note that the Line-to-Neu-
tral column will not be displayed for a 3 phase/3 wire V L-L L-N AMPS
system. Accuracy 1%. L1 480 277 1340
L2 480 277 1290
The voltage Line-to-Line (L1, L2 and L3) are mea- L3 480 277 1260 
sured between L1 to L2, L2 to L3 and L3 to L1, re- FREQUENCY 60.0 HZ
spectively. AVR DUTY CYCLE 10.3 %

Amps: All phases. Accuracy 1%.


Frequency: Generator set output frequency.
AVR DUTY CYCLE: Displays voltage regulator kW kVA PF
(drive) level in percentage of maximum. L1 350 500 .80 
L2 350 500 .80
kW, kVA and PF: Displays generator set kW and L3 350 500 .80
kVA output (average and individual phase, and di- TOT 1050 1500 .80
rection of flow) and power factor with leading/lag-
ging indication. Accuracy 5%.
The PF reading will contain an asterisk if the power
factor is leading (for example, *.30). FIGURE 3-7. ALTERNATOR DATA SUBMENUS

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-14
CONTROL SUBMENU

If you press the “CONTROL” button in Menu A, the


Control submenu will appear (Figure 3-8). CONTROL
(Local)
Local CONTROL Submenu Function
When the operator panel is mounted on the control
panel assembly, the Run Mode Idle/Rated button is
active (displayed). Note in Figure 3-8 that this but-
+ RUN MODE IDLE 
ton is not displayed in remote applications.
BARGRAPH TEST
The shaded area in Figure 3-8 displays the se-
lected/active mode of operation, either IDLE or
RATED.

Run Mode Idle/Run At Rated Button: Refer to


Page 3-7 for a complete description of the Run At CONTROL
(Remote)
Idle mode.

Remote CONTROL Submenu Functions


When the operator panel (Figure 3-1) is mounted
remotely of the control panel assembly, the menu START GENSET 
buttons in the Control submenu are used to perform BARGRAPH TEST
the following remote operations. (To activate these FAULT ACKNOWLEDGE
menu buttons for remote/local use, refer to page
3-11.)

The 0/Manual/Auto switch must be in the Auto posi-


tion to activate the Remote Menu Buttons of the Con- FIGURE 3-8. CONTROL SUBMENU
trol submenu.

Remote START or STOP Button: This button is


used to start and stop the generator set when the
operator panel is mounted in a remote location. For
additional information refer to Starting at Remote
Operator Panel (page 3-6) and Stopping at Remote
Operator Panel (page 3-8).

When the generator set is operating, Stop will be


displayed for this button and Start will be displayed
when not operating.

Fault Acknowledge Button: Used to reset inactive


Warning messages, not Shutdown messages.

Local/Remote CONTROL Submenu


Function
Bargraph Test: The function of this button remains
the same and is not dependent on operator panel
location. This button sequentially lights the LEDs to
test the bar graph display.
Redistribution or publication of this document,
by any means, is strictly prohibited.
3-15
HISTORY/ABOUT SUBMENUS

If you press the “HISTORY/ABOUT” button in Menu


A, the History/About submenus will appear (Figure HISTORY/ABOUT
3-9).
HISTORY: The control maintains a data log of the
number of engine starts and number of operating
hours for the engine and control, and the megawatt STARTS 533
and maximum torque hours of the generator set. ENGINE HOURS 1236 
This information is stored in non-volatile memory CONTROL HOURS 7879
KWHRS 890 
and will not be deleted due to loss of battery power.
ABOUT: The About submenus provide the follow-
ing generator set information.
• Genset model and wattage (kW/MW)
• Output voltage and WYE, DELTA or SINGLE
• Frequency 50 or 60 Hz HISTORY-HRS@ %MAX TORQUE
12345@0-9 23455@50-59 
• Rating: Standby, Prime or Base 12345@10-19 12345@60-69

12345@20-29 12345@70-79
• Version level of the controller and panel operat- 12345@30-39 12345@80-89
ing software.

MODEL 1750DQKB 
VOLTAGE 416 WYE
FREQUENCY 60 
RATING STANDBY

CONTROLLER VERSION
RTOP DN30008.DFA 
BATS FEB 15 1999
OP PANEL VERSION 
RTOP 1.08 JUN 4 1999
BATS 1.02 MAY 6 1999

CONTINUED TO NEXT PAGE

FIGURE 3-9. HISTORY/ABOUT SUBMENUS

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-16
HISTORY/ABOUT SUBMENUS (CONT.)

FAULT HISTORY: The control maintains a data log


of all fault conditions as they occur, and time stamps HISTORY/ABOUT (CONT.)
them with the control and engine operating hours.
Up to 32 (unacknowledged) fault codes can be
stored in control panel memory. After the fault is ac-
knowledged and corrected, the recorded fault will
be deleted from the control panel memory, but will FAULT HISTORY: 1 OF 24
+ CNTL HOURS 459 
remain in a data log that maintains a fault code his- OCCURRENCES 5
tory. (The InPower service tool is required to view ENGINE HOURS 334
this data log.) FAULT CODE 1437
(FAULT DESCRIPTION)
The Fault History display line: 1 of 24 indicates that
24 faults are recorded and that the most recent fault
(1) detected by the controller is displayed.
The Occurrences display line: In this example, 5 in- FIGURE 3-9. HISTORY/ABOUT SUBMENUS (CONT.)
dicates that this is the fifth occurrence of this fault.
(The InPower service tool is required to review the
last four faults of this code.)
The Occurrences number is incremented for each
new occurrence of the same fault. The controller
must detect that the original sensed fault is cor-
rected before it will increment the occurrence num-
ber for that fault.
For example, when a Low Oil Pressure fault is de-
tected, the controller will increment the Occurrences
number by 1. This fault will remain active until the
controller detects that the fault is corrected. An ac-
tive fault will prevent the controller from increment-
ing the Occurrences number each time the engine is
started. When the controller detects that the oil pres-
sure is normal the fault will become inactive, allow-
ing the occurrences number to be incremented for
the next detected Low Oil Pressure fault.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-17
ADJUST SUBMENU

If you press the “ADJUST” button in Menu B, the Ad-


just submenu will appear (Figure 3-10).
The Adjust submenu is intended for qualified ser- ADJUST
vice personnel and site personnel only and may re-
quire a USER password. If a password is required,
the USER password menu will appear when you try
to modify the Adjust submenu. (Refer to PASS-
WORD Menu in this section to enter password. ADJUST:
+ VOLTAGE 208 1.2 % 
Changes are automatically saved when you exit FREQ 60.0 HZ -0.0 HZ
– START DELAY 5 SEC
this menu.
→ STOP DELAY 11 SEC
Use the + and – buttons to increase or decrease the
values in the following fields. Use the arrow (→) but-
ton to move the cursor within a field or to the next
field. Selected field is highlighted.
VOLTAGE: Used to adjust the output voltage ±5%. FIGURE 3-10. ADJUST SUBMENU
FREQUENCY: Used to adjust the frequency ±3 Hz.
START DELAY: This delay applies only to remote
starting in the Auto mode. The Start Delay adjust-
ment range is 0 to 300 seconds.
STOP DELAY: This delay applies only to remote
stopping in the Auto mode. The Stop Delay adjust-
ment range is 0 to 600 seconds.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-18
BUS DATA SUBMENU

If you press the “BUS DATA” button in Menu B, the


Bus Data submenu will appear (Figure 3-11). This BUS DATA
menu is displayed in paralleling applications only.
BUS DATA STATUS LINE: The top line of the
graphical display is used to indicate the following LOAD GOVERN
BUS DATA status:
V BUS GEN
– STANDBY L1 480 480 
– DEAD BUS CLOSE: Indicates first genset in L2 480 480
_\_
system to close to bus. L3 480 480
HZ 60.1 60.1
– SYNCHRONIZE: Genset is synchronizing to DEG –122 NOT SYNCHRONIZING
bus.
– LOAD SHARE: Genset has closed to bus and
is sharing load with other gensets in system.
– LOAD GOVERN: Genset closed to bus in par-
allel with utility (mains). FIGURE 3-11. BUS DATA SUBMENU
BUS Voltage L-L: The BUS voltage Line-to-Line
(L1, L2 and L3) are measured between L1 to L2, L2
to L3 and L3 to L1, respectively.
BUS/GEN HZ: BUS/GEN hertz.
BUS/GEN SYNC STATUS: The bottom line of the
graphical display is used to indicate the following
BUS/GEN Sync status:
– NOT SYNCHRONIZING: Genset is in service
mode that does not allow auto sync feature.
– SYNCHRONIZING: Genset is synchronizing to
bus.
– READY TO CLOSE: In manual mode, push cir-
cuit breaker close button to close breaker.
_\_ Button: (Paralleling applications only). Used to
open and close the generator set circuit breaker
(CB). The symbol indicates if the CB is opened or
closed. Opened _\_, push to close. Closed _–_,
push to open.
With the control panel 0/Manual/Auto switch in the
Auto position, the opening and closing of the CB is
controlled by the control system software. The CB
symbol will indicate an open or closed CB, but the
button will be inactive when the control is in Auto.
In the Manual position, the CB must be closed by
this button. When manually closed and the CB
opens, it must be closed again by using this button.
To close the CB, press and hold the button until the
symbol indicates a closed CB. (CB close will occur
only when setup conditions allow – dead bus or
generator synchronized with bus.)

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-19
PASSWORD Menu
When viewing the Adjust submenu, pressing either + OR – BUTTON
the + or – button will display the Password menu
(Figure 3-12) if a User password is assigned to this
field. After entering the correct password, the sys-
ENTER USER PASSWORD
tem will allow you to modify the submenu. To pre- (OR)
vent unauthorized adjustment, the entered pass- ENTER APPLICATION
word is valid for only 10 minutes after the last button + PASSWORD ENTER
is pressed. –
Application Password is intended only for qualified → XXXXXXXX
service personnel to allow adjustment of Setup sub-
menu parameters.
To enter the password:
1. Display Adjust submenu. FIGURE 3-12. PASSWORD MENU
2. Press either the + or – button within the dis-
played submenu. The Password menu ap-
pears. (Adjustment is allowed if Password
menu does not appear.)
3. Press the + and – button to select the first char-
acter of the User password (A–Z or 0–9).
4. Press the → button to select the next character
field. Selected character field is highlighted.
5. Repeat steps 3 and 4 to enter remaining pass-
word characters.
6. Press the Enter button after entering the pass-
word. The Adjust submenu will reappear.
7. Exit Adjust submenu to save changes.

Redistribution or publication of this document,


by any means, is strictly prohibited.
3-20
4. Troubleshooting

GENERAL CAUTION Disconnect battery charger from AC


source before disconnecting battery cables.
The genset control continuously monitors engine Otherwise, disconnecting cables can result in
sensors for abnormal conditions, such as low oil voltage spikes damaging to DC control circuits
pressure and high coolant temperature. If any of of the set.
these conditions occur, the control will light a yellow
Warning lamp or a red Shutdown lamp and display a
WARNING Accidental starting of the generator
message on the graphical display panel.
set can cause severe personal injury or death.
In the event of an engine shutdown fault (red Shut- Prevent accidental starting by disconnecting
down lamp), the control will stop the engine immedi- the negative (–) cable from the battery terminal.
ately; an alternator shutdown fault, the engine will
stop after the cool-down timer has timed out. If the When troubleshooting a set that is shut down, make
generator set is stopped for this reason, the opera- certain the generator set cannot be accidentally re-
tor can restart the set after making adjustments or started as follows:
corrections. This section lists the warning and shut-
down codes/messages (Table 4-1), and suggests 1. Move the O/Manual/Auto switch on the control
troubleshooting procedures (Table 4-2). panel to the O (off) position.
Displayed error codes that are not listed in Table 4-2
will require an authorized service representative to 2. Turn off or remove AC power from the battery
correct the fault. Contact an authorized service cen-
charger.
ter for assistance.

SAFETY CONSIDERATIONS 3. Remove the negative (–) battery cable from the
generator set starting battery.
WARNING Contacting high voltage compo-
nents can cause electrocution, resulting in se-
vere personal injury or death. Keep the output STATUS INDICATORS
box covers in place during troubleshooting.
Not In Auto Indicator: This red lamp flashes con-
High voltages are present when the set is running. tinuously when the O/Manual/Auto switch is not in
Do not open the generator output box while the set the Auto position (Figure 4-1).
is running.

WARNING
Shutdown Status Indicator: This red lamp is lit
Ignition of explosive battery gases
whenever the control detects a shutdown condition.
can cause severe personal injury or death. Arc-
After the condition is corrected, the shutdown indi-
ing at battery terminals, light switch or other
cator can be reset by turning the O/Manual/Auto
equipment, flame, pilot lights and sparks can ig-
switch to the O (off) position, and pressing the Fault
nite battery gas. Do not smoke, or switch
Acknowledge button. The generator set can not be
trouble light ON or OFF near battery. Discharge
started when this lamp is on.
static electricity from body before touching bat-
teries by first touching a grounded metal sur-
face. Warning Status Indicator: This yellow lamp is lit
whenever the control detects a warning condition.
Ventilate battery area before working on or near After the condition is corrected, the warning indica-
battery—Wear goggles—Stop genset and dis- tor can be reset by pressing the Fault Acknowledge
connect charger before disconnecting battery button. (It is not necessary to stop the generator set
cables—Disconnect negative (–) cable first and if the fault becomes inactive during genset opera-
reconnect last. tion.)
Redistribution or publication of this document,
by any means, is strictly prohibited.
4-1
READING FAULT CODES each code. The fourth flash of the Warning lamp in-
dicates the beginning of the second fault code.
If the genset contains the optional graphical display
and a fault occurs, the fault code/message will be There are distinct pauses between repetitions of the
displayed in the display Description Line (Figure code blink transmissions of the Shutdown lamp.
4-1). If the control does not contain the graphical A three digit fault code is indicated by three sets of
display, the fault code is read from the Warning and blinks separated by a two second pause. The first
Shutdown status indicators. set corresponds to the hundreds position, the sec-
After the fault is acknowledged and corrected, the ond to the tens position and the third to the ones dig-
recorded fault will be deleted from the control panel it. Example for Code No. 213:
memory, but will remain in a data log to maintain a Shutdown LED:
fault code history. The InPower service tool is re- blink-blink-pause-blink-pause-blink-blink-blink
quired to view this data log.
Warning LED:
Reading Fault Codes Using Graphical Display blink (2 seconds)
(Optional): The top three lines of the graphical dis-
play contain the following control information in the The light will display the fault codes (active or inac-
order described: tive) in succession, starting with the most recent. Up
to 32 (unacknowledged) fault codes can be stored
• State Line – modes of operation, such as in control panel memory.
Stopped, Time Delay To Start, Warm Up At
Idle, etc. (see Figure 3-2), and paralleling op- To return the control to the most recent fault code,
erations, such as Standby, Dead BUS Close, press and release the Fault Acknowledge button
Synchronize, etc. (less than one second) and repeat procedure.

• Action Line – system actions, such as Warning, When the fault code is acknowledged and the fault
Derate, Shutdown Cool-down and Shutdown, condition is corrected, the fault code will be re-
and fault codes. moved from the LED fault log.

• Description Line – Fault code messages. LINE CIRCUIT BREAKER (OPTIONAL)


Refer to History/About Submenus in Section 3, The optional line circuit breaker mounts on the gen-
which describes how to view fault codes using erator output box. If the load exceeds the generator
graphical display. current rating, the line circuit breaker will open, pre-
venting the generator from being overloaded. If the
Reading Fault Codes Using Warning/Shutdown circuit breaker trips, locate the source of the over-
Indicators: If the Warning or Shutdown status indi- load and correct as necessary. Manually reset the
cator is lit, press and hold the Fault Acknowledge breaker to reconnect the load to the generator.
button and release after one second or more. After
one second, the Shutdown lamp will begin to blink CONTROL AND DIAGNOSTICS VIA
the active fault code(s) as follows. NETWORK OR PC (LAPTOP)
The Warning lamp is used to indicate the start of a See your authorized Cummins Power Generation
new code. The Warning lamp will remain on for 2 dealer regarding software, hardware and network
seconds, followed by the Shutdown lamp blinking requirements for control and diagnostics via net-
the fault code. This sequence occurs three times for work or PC.

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-2
SHUTDOWN,
WARNING
STATUS INDICATORS

FAULT
ACKNOWLEDGE
BUTTON

STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA

OPERATOR SWITCH
GRAPHICAL
PANEL PANEL
DISPLAY

FIGURE 4-1. FRONT CONTROL PANEL (FULL-FEATURED)


Redistribution or publication of this document,
by any means, is strictly prohibited.
4-3
FAULT CODES ate only when generator set is powering critical
loads and cannot be shut down. Requires repair by
The fault codes have been divided into four catego- qualified service personnel.
ries to help you determine what corrective action to
take for safe operation of the generator set. Use Category C Fault Codes: Consist of faults that do
Table 4-1 to find the category (CAT) and fault de- not affect generator set performance but require
scription for all codes. Gaps in the code numbers qualified service personnel to repair. These codes
are for codes that do not apply to this genset. indicate a defective sensor or harness, leaving no
engine protection. (Engine damage can occur with-
Category A Fault Codes: Pertain to engine or al- out detection.) Continued operation may void
ternator shutdown faults that require immediate re- generator set warranty if damage occurs that re-
pair by qualified service personnel (generator set lates to fault condition.
non-operational). Control prevents the generator
set from being restarted. Category D Fault Codes: Consist of faults that are
repairable by site personnel. Service will be re-
Category B Fault Codes: Consist of faults that can quired by qualified service personnel if site person-
affect genset performance or cause engine, alter- nel cannot resolve the problem after taking the cor-
nator, or connected equipment damage. Oper- rective actions suggested in Table 4-2.

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-4
TABLE 4-1. FAULT CODES
CAT CODE LAMP DISPLAYED MESSAGE CAT CODE LAMP DISPLAYED MESSAGE
A 111 Shtdn Internal ECM error A 254 Shtdn Fuel shutoff valve
A 112 Shtdn Actuator not responding C 259 Wrng Fuel shutoff valve
B 113 Wrng Actuator sensor fault C 261 Wrng Fuel temperature sensor
A 115 Shtdn No speed signal C 263 Wrng Fuel temperature sensor
A 116 Shtdn Time press sensor high C 265 Wrng Fuel temperature sensor
A 117 Shtdn Time press sensor low A 266 Shtdn Fuel temperature
B 118 Wrng Pump press sensor high B 316 Wrng Fuel supply pump
B 119 Wrng Pump press sensor low B 318 Wrng Fuel supply pump
C 121 Wrng No engine speed signal D 326 Wrng Oil level warning
B 122 Wrng Manifold air press sensor B 343 Wrng Internal ECM error
B 123 Wrng Manifold air press sensor D 359 Wrng Engine failed to start
C 135 Wrng Oil pressure sensor A 378 Wrng Fueling actuator #1
C 141 Wrng Oil pressure sensor A 379 Wrng Fueling actuator #1
B 143 Wrng Low oil pressure A 394 Wrng Fueling actuator #1
C 144 Wrng Coolant temperature sensor A 395 Wrng Fueling actuator #1
C 145 Wrng Coolant temperature sensor A 396 Wrng Fueling actuator #2
D 146 Wrng High coolant temp warning A 397 Wrng Fueling actuator #2
C 151 Shtdn High coolant temp alarm A 398 Wrng Fueling actuator #2
D 152 Wrng Low coolant temp A 399 Wrng Fueling actuator #2
C 153 Wrng Manifold air temp sensor B 415 Shtdn Low oil pressure alarm
C 154 Wrng Manifold air temp sensor B 421 Wrng High oil temperature
A 155 Shtdn Manifold air temp alarm B 423 Wrng Fuel timing
D 197 Wrng Coolant level warning D 441 Wrng Low battery voltage
C 212 Wrng Oil temperature sensor D 442 Wrng High battery voltage
C 213 Wrng Oil temperature sensor B 449 Wrng High fuel supply pressure
A 214 Shtdn High oil temperature B 451 Wrng Fuel rail pressure sensor
C 221 Wrng Air pressure sensor B 452 Wrng Fuel rail pressure sensor
C 222 Wrng Air pressure sensor A 455 Shtdn Fuel control valve sensor
A 228 Shtdn Low coolant pressure B 467 Wrng Timing rail act sensor
C 231 Wrng Coolant pressure sensor B 468 Wrng Fuel rail actuator sensor
C 232 Wrng Coolant pressure sensor D 471 Wrng Low oil level
A 233 Wrng Coolant pressure warning B 482 Wrng High fuel supply pressure
A 234 Shtdn Overspeed B 488 Wrng High intake manifold temp
D 235 Shtdn Coolant level alarm C 498 Wrng Oil level sensor
A 236 Shtdn Position sensor C 499 Wrng Oil level sensor
D 253 Shtdn Oil level alarm A 514 Shtdn Fuel control valve

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-5
TABLE 4-1. FAULT CODES (CONT)
CAT CODE LAMP DISPLAYED MESSAGE CAT CODE LAMP DISPLAYED MESSAGE
B 546 Wrng Fuel pressure sensor A 1331 Shtdn AVR driver shorted
B 547 Wrng Fuel pressure sensor A 1332 Shtdn Manual switch oor lo
B 554 Wrng Fuel rail pressure sensor A 1333 Shtdn Manual switch oor hi
B 555 Wrng Blowby pressure A 1334 Shtdn Critical scaler oor
A 556 Shtdn Blowby pressure B 1335 Wrng Non critical scaler oor
A 586 Shtdn Run/Stop switch NA 1336 Shtdn Cooldown complete
A 587 Shtdn Run/Stop switch NA 1337 None Network wink
D 611 Wrng Engine hot NA 1341 Shtdn Load demand stop
D 688 Shtdn High oil level alarm A 1342 Shtdn Slot 0 card
B 689 Wrng Crank shaft sensor A 1343 Shtdn Slot 1 card
B 719 Wrng Blowby pressure sensor A 1344 Shtdn Slot 2 card
B 729 Wrng Blowby pressure sensor A 1345 Shtdn Slot 3 card
B 778 Wrng Camshaft sensor A 1346 Shtdn Slot 4 incorrect
NA 1311 Shtdn/ Customer input #1 A 1347 Shtdn Slot 5 card
Wrng
A 1348 Shtdn Slot 6 card
NA 1312 Shtdn/ Customer input #2
Wrng A 1349 Shtdn Slot 7 card

NA 1313 Shtdn/ Network Fault 1 C 1351 Wrng Slot 4 / network enabled


Wrng C 1414 Wrng Run relay contact
NA 1314 Shtdn/ Network Fault 2 C 1415 Wrng Run relay driver
Wrng
D 1416 Wrng Fail to shutdown
NA 1315 Shtdn/ Network Fault 3
Wrng D 1417 Wrng Power down error
NA 1316 Shtdn/ Network Fault 4 B 1419 Wrng Fuel rail driver
Wrng B 1421 Wrng Timing rail driver #1
NA 1317 Shtdn/ Customer input #3 B 1422 Wrng Timing rail driver #2
Wrng
C 1424 Wrng High side driver
NA 1318 Shtdn/ Customer input #4
Wrng C 1427 Wrng Overspeed relay driver
B 1319 Wrng High alternator temp C 1428 Wrng LOP shutdown relay driver
C 1321 Wrng Common warning driver D 1433 Shtdn Emergency stop – local
A 1322 Shtdn Load gov kW setpoint oor hi D 1434 Shtdn Emergency stop – remote
A 1323 Shtdn Load gov kW setpoint oor lo D 1435 Wrng Engine cold
B 1324 Wrng Load gov kVAR oor hi B 1436 Wrng PT fuel system drivers
B 1325 Wrng Load gov kVAR oor lo A 1437 Shtdn E-stop path fuse blown
B 1326 Wrng Backup starter disconnect D 1438 Wrng Fail to crank
A 1327 Shtdn Load gov kW analog oor D 1439 Wrng Fuel level low in day
D 1328 Wrng Genset CB tripped D 1441 Wrng Fuel level low in main
B 1329 Wrng AVR DC power failure D 1442 Wrng Battery is weak

NA– Indicates non-critical operational status of generator set, external faults, or customer fault inputs. May
require repair by qualified service personnel.
Redistribution or publication of this document,
by any means, is strictly prohibited.
4-6
TABLE 4-1. FAULT CODES (CONT)
CAT CODE LAMP DISPLAYED MESSAGE CAT CODE LAMP DISPLAYED MESSAGE
D 1443 Wrng Battery is dead A 1473 Shtdn Watchdog failure
B 1444 Wrng kW overload A 1474 Shtdn Software version mismatch
A 1445 Shtdn Alternator short circuit C 1475 Wrng First start backup
A 1446 Shtdn AC output voltage is high C 1476 Wrng LonWorks card
A 1447 Shtdn AC output voltage is low C 1477 Wrng Crank relay contact
A 1448 Shtdn AC output frequency low C 1478 Wrng Crank relay driver
A 1449 Wrng AC output frequency high A 1481 Shtdn AVR driver open
B 1451 Wrng Gen/Bus voltage differ NA 1483 None Common alarm status
A 1452 Shtdn Gen CB failed to close A 1485 Shtdn EFC driver shorted
A 1453 Shtdn Gen CB failed to open A 1486 Shtdn EFC driver open
C 1454 Wrng Gen CB position contact C 1487 Wrng Auto acknowledge driver
A 1455 Shtdn Util CB contact C 1488 Wrng Warning LED driver
NA 1456 Wrng Bus out of range C 1489 Wrng Shutdown LED driver
NA 1457 Wrng Fail to synchronize C 1491 Wrng Ready to load relay driver
NA 1458 Wrng Phase rotation C 1492 Wrng Load dump relay driver
A 1459 Shtdn Reverse kW C 1493 Wrng Display control driver
A 1461 Shtdn Loss of field C 1494 Wrng Modem power relay driver
B 1462 Wrng High ground current C 1495 Wrng Common shutdown2 driver
NA 1463 None Not in Auto C 1496 Wrng Auto mode relay driver
NA 1464 None Load dump C 1497 Wrng Manual run LED driver
NA 1465 None Ready to load C 1498 Wrng Exercise run LED driver
C 1466 Wrng Modem failure C 1499 Wrng Remote start LED driver
C 1467 Wrng Unable to connect modem C 2111 Wrng Aftercooler temp sensor
C 1468 Wrng Network erorr C 2112 Wrng Aftercooler temp sensor
B 1471 Wrng High current B 2113 Wrng High aftercooler temp
A 1472 Shtdn Overcurrent A 2114 Shtdn High aftercooler temp

NA– Indicates non-critical operational status of generator set, external faults, or customer fault inputs. May
require repair by qualified service personnel.

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-7
TABLE 4-2. WARNING AND SHUTDOWN CODES

WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.

SYMPTOM CORRECTIVE ACTION

CODE: 146 Indicates engine has begun to overheat and jacket water coolant temper-
LAMP: Warning ature has risen to an unacceptable level. If generator is powering non-crit-
MESSAGE: ical and critical loads and cannot be shut down, use the following:
HIGH COOLANT TEMP WARNING a. Reduce load if possible by turning off non-critical loads.
b. Check air inlets and outlets and remove any obstructions to airflow.
If engine can be stopped, follow 151 High Coolant Temp Alarm proce-
dure.

CODE: 151 Indicates engine has overheated (jacket water coolant temperature has
LAMP: Shutdown risen above the shutdown trip point or the coolant level is low. Allow en-
MESSAGE: gine to cool down completely before proceeding with the following checks:
HIGH COOLANT TEMP ALARM a. Check jacket water coolant level and replenish if low. Look for cool-
ant leakage and repair if necessary.
b. Check for obstructions to cooling airflow and correct as necessary.
c. Check fan belt and repair if necessary.
d. Reset control and restart after locating and correcting problem.

CODE: 152 Indicates engine coolant heater is not operating or is not circulating cool-
LAMP: Warning ant. Set is in standby mode but is not operating. Warning occurs when en-
MESSAGE: gine jacket water coolant temperature is 70° F (21° C) or lower.
LOW COOLANT TEMP
NOTE: In applications where the ambient temperature falls below
40° F (4° C), Low Coolant Temp may be indicated even though the
coolant heaters are operating.
Check for the following conditions:
a. Coolant heater not connected to power supply. Check for blown fuse
or disconnected heater cord and correct as required.
b. Check for low jacket water coolant level and replenish if required.
Look for possible coolant leakage points and repair as required.

CODE: 197 Indicates engine jacket water coolant level has fallen to an unacceptable
LAMP: Warning level. If generator is powering critical loads and cannot be shut down, wait
MESSAGE: until next shutdown period, then follow 235 Coolant Level Alarm proce-
COOLANT LEVEL WARNING dure. If engine can be stopped, follow 235 procedure.

CODE: 235 Indicates engine jacket water coolant level has fallen below the alarm trip
LAMP: Shutdown point. Allow engine to cool down completely before proceeding.
MESSAGE: a. Check jacket water coolant level and replenish if low. Look for pos-
COOLANT LEVEL ALARM sible coolant leakage points and repair if necessary.
b. Reset control and restart after locating and correcting problem.

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-8
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)

WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.

SYMPTOM CORRECTIVE ACTION

CODE: 253 Indicates engine oil level has dropped below the shutdown trip point.
LAMP: Shutdown Check oil level, lines and filters. If oil system is OK but oil level is low, re-
MESSAGE: plenish. Reset control and restart.
OIL LEVEL ALARM

CODE: 326 Indicates that the engine oil level has exceeded the warning trip point for
LAMP: Warning high oil level. If generator is powering critical loads and cannot be shut
MESSAGE: down, wait until next shutdown period, then follow 688 High Oil Level
OIL LEVEL WARNING Alarm procedure. If engine can be stopped follow 688 procedure.

CODE: 359 Indicates possible fault with control or starting system. Check for the fol-
LAMP: Warning lowing conditions:
MESSAGE: a. Poor battery cable connections. Clean the battery cable terminals
ENGINE FAILED TO START and tighten all connections.
b. Discharged or defective battery. Recharge or replace the battery.

CODE: 441 Indicates battery voltage is below 24 VDC.


LAMP: Warning a. Discharged or defective battery. Check the battery charger fuse.
MESSAGE: Recharge or replace the battery.
LOW BATTERY VOLTAGE
b. Poor battery cable connections. Clean the battery cable terminals
and tighten all connections.
c. Check engine DC alternator. Replace engine DC alternator if normal
battery charging voltage (24 to 26 VDC) is not obtained.
d. Check float level if applicable (raise float level).

CODE: 442 Indicates battery voltage exceeds 32 VDC.


LAMP: Warning
MESSAGE: Check float level on battery charger if applicable (lower float level).
HIGH BATTERY VOLTAGE Check engine DC alternator. Replace engine DC alternator if normal bat-
tery charging voltage (24 to 26 VDC) is not obtained.

CODE: 471 Indicates engine oil has dropped to an unacceptable level. If generator is
LAMP: Warning powering critical loads and cannot be shut down, wait until next shutdown
MESSAGE: period, then follow 253 Oil Level Alarm procedure. If engine can be
LOW OIL LEVEL stopped follow 253 procedure.

CODE: 611 Indicates that an engine hot shut down has occurred (cool-down timers
LAMP: Warning were bypassed). This condition will occur when the engine coolant tem-
MESSAGE: perature is above the normal operating level and the operator presses the
ENGINE HOT Emergency Switch or moves the 0/Manual/Auto switch to the 0 (Off) posi-
tion. This type of shutdown should be avoided. Can cause possible loss of
performance and engine damage.

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-9
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)

WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.

SYMPTOM CORRECTIVE ACTION

CODE: 688 Indicates that the engine oil level has exceeded the alarm trip point for
LAMP: Shutdown high oil level. Check oil level. Drain oil to operating level.
MESSAGE:
HIGH OIL LEVEL ALARM

CODE: 1311 through 1318 When any one of these customer defined inputs is detected by the control,
LAMP: Shutdown/Warning the corresponding fault message is displayed. The nature of the fault is an
MESSAGE: optional customer selection. These fault functions can be programmed to
Customer Defined Fault initiate a shutdown or warning as indicated by the Warning or Shutdown
lamp.
Note: Customer fault messages are editable. The message displayed for
the code shown (1311 through 1318) is determined by the customer.

CODE: 1416 Status – indicates that the “Fault Bypass” mode is enabled. This mode is
LAMP: Warning primarily used by service personnel for troubleshooting purposes. In this
MESSAGE: mode the generator set ignores the majority of system shutdown faults.
FAIL TO SHUTDOWN

CODE: 1417 Indicates that the control can not power down due to some unknown con-
LAMP: Warning dition. Possible drain on battery. Contact an authorized service center for
MESSAGE: service.
POWER DOWN ERROR

CODE: 1433 / 1434 Indicates local or remote Emergency Stop. Emergency Stop shutdown
LAMP: Shutdown status can be reset only at the local control panel.
MESSAGE: To reset the local/remote Emergency Stop button:
EMERGENCY STOP – LOCAL / Pull the button out.
EMERGENCY STOP – REMOTE Move the O/Manual/Auto switch to O (off).
Press the front panel Fault Acknowledge button.
Select Manual or Auto, as required.

CODE: 1438 Indicates possible fault with control or starting system. Check for the fol-
LAMP: Warning lowing conditions:
MESSAGE: a. Poor battery cable connections. Clean the battery cable terminals
FAIL TO CRANK and tighten all connections.
b. Discharged or defective battery. Recharge or replace the battery.

CODE: 1439 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN DAY

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-10
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)

WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.

SYMPTOM CORRECTIVE ACTION

CODE: 1441 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN MAIN

CODE: 1442 Indicates battery voltage drops below 14.4 volts for two seconds, during
LAMP: Warning starting.
MESSAGE: Discharged or defective battery.
BATTERY IS WEAK See Warning message 441 Low Battery Voltage.

CODE: 1443 Indicates battery has dropped below genset operating range (3.5 volts
LAMP: Warning when cranking) to power the starter and the control circuitry.
MESSAGE: See Warning message 441 Low Battery Voltage.
BATTERY IS DEAD

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-11
THIS PAGE LEFT INTENTIONALLY BLANK

Redistribution or publication of this document,


by any means, is strictly prohibited.
4-12
5. Maintenance
GENERAL • Exposure to salt water

Establish and adhere to a definite schedule for • Exposure to dust, sand or other airborne con-
maintenance and service based on the application taminates
and severity of the environment. Table 5-1 covers Consult with your local Cummins Power Generation
the recommended service intervals for a generator
distributor if the generator set will be subjected to
set on STANDBY service. If the set will be subjected
any extreme operating conditions and determine a
to extreme operating conditions, the service inter-
suitable schedule of maintenance. Use the running
vals should be reduced accordingly. Some of the time meter to keep an accurate log of all service per-
factors that can affect the maintenance schedule formed for warranty support. Perform all service at
are the following: the time period indicated or after the number of op-
• Use for continuous duty (prime power) erating hours indicated, whichever comes first. Use
Table 5-1 to determine the maintenance required
• Extremes in ambient temperature
and then refer to the sections that follow for the cor-
• Exposure to weather rect service procedures.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-1
TABLE 5-1. PERIODIC MAINTENANCE SCHEDULE

SERVICE TIME
Month- 6
Daily Yearly
MAINTENANCE ITEMS See ly Month
or after or after 1000 4000
Engine or after s or af-
8 500 Hours Hours
Schdl. 100 ter 250
Hours Hours
Hours Hours
General set inspection X1 X2
Check engine oil level X
Check coolant level of radiators (Jacket Water
X
& LTA)
Check coolant heater(s) X
Check battery charging system X
Check all hardware (fittings, clamps, fasteners,
X
etc.)
Check drive belts X3
Check battery electrolyte level X
Drain exhaust condensate trap X
Check generator air outlet X
Check radiator hoses for wear and cracks X
Grease fan bearings (two) X
Test generator insulation resistance X4
Grease generator bearing (Frame 7) X5,6
Grease generator bearing (Frame 8) X5, 6
Check air cleaner (replace as necessary) X1
Drain fuel filter(s) X1
Check anti-freeze and DCA concentration X1
Change engine oil and filter X1
Change jacket water coolant filters X1
Clean crankcase breather X1
Change fuel filters X1
Clean Jacket Water & LTA cooling systems X1
X1 - Refer to Cummins QSK45/QSK60 Series Engine Operation and Maintenance Manual for maintenance interval and/or
procedure.
X2 - Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair
any leaks immediately.
X3 - Visually check belts for evidence of wear or slippage. Replace if hard or brittle.
X4 - This procedure should be followed periodically throughout the life of the generator set, or if the generator has set idle for a period
of time with no generator heaters used. Contact your authorized service center.
X5 - Frame 7 outside casing is round, Frame 8 outside casing is octagon-shaped (flat-sided).
X6 - Re-lubrication time periods and amount of grease used may vary in this manual from what is suggested on label located
adjacent to end bearing. Use the information provided in this manual for these values.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-2
GENERAL INSPECTION Frequency: The generator frequency should be
stable and the reading should be the same as the
During operation, be alert for mechanical problems nameplate.
that could create unsafe or hazardous conditions.
The following sections cover several areas that AC Voltage: At no load, the line-to-line voltage(s)
should be frequently inspected for continued safe should be the same as the set nameplate rating.
operation.
AC Ammeter: At no load, the current readings
Exhaust System should be zero. With a load applied, each line cur-
With the generator set operating, inspect the entire rent should be about the same.
exhaust system visually and audibly including the Panel Lamps: Press and hold down the Panel
exhaust manifold, muffler, and exhaust pipe. Check Lamp/Lamp Test button on the control panel. All in-
for leaks at all connections, welds, gaskets, and dicator lamps should light. Verify that all lamps are
joints and also make sure that exhaust pipes are not on and then release the button. Contact an autho-
heating surrounding areas excessively. If any leaks rized service center if any lamps are burned out.
are detected, shut down the generator set and have
leaks corrected immediately. DC Electrical System
WARNING Inhalation of exhaust gases can re-
Check the terminals on the batteries for clean and
sult in severe personal injury or death. Be sure
tight connections. Loose or corroded connections
deadly exhaust gas is piped outside and away
create resistance which can hinder starting. Refer
from any windows, doors, vents or other inlets
to BATTERIES later in this section for cleaning and
to building and not allowed to accumulate in in-
safety precautions.
habitable areas.
Fuel System Engine
With the generator set operating, inspect the fuel Monitor fluid levels and oil pressure and coolant
supply lines, return lines, filters, and fittings for temperatures frequently. Most engine problems
leaks. Check any flexible sections for cuts, cracks give an early warning. Look and listen for changes
and abrasions and make sure they are not rubbing in engine performance, sound, or appearance that
against anything that could cause breakage. If any can indicate service or repair is needed. Some en-
leaks are detected, have them corrected immedi- gine changes to look for are as follows:
ately.
• Misfire
WARNING Ignition of fuel can cause severe • Vibration
personal injury or death by fire or explosion. Do • Unusual noises
not permit any flame, cigarette, arcing switch or • Sudden changes in engine operating tempera-
equipment, pilot light, or other igniter near the tures or pressures
fuel system or in areas sharing ventilation. • Excessive exhaust smoke
• Loss of power
AC Electric System • An increase in oil consumption
Check the following while the generator set is oper- • An increase in fuel consumption
ating. • Fuel, oil, or coolant leaks.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-3
GENERATOR SET MAINTENANCE 6. Remove the negative (–) battery cable from the
(Battery Disconnected) generator set starting battery.

WARNING Ignition of explosive battery gases Mechanical Inspection


can cause severe personal injury or death. Arc- With the generator set stopped, check for loose
ing at battery terminals, light switch or other belts and fittings, leaking gaskets and hoses, or any
equipment, flame, pilot lights and sparks can ig- signs of mechanical damage. If any problems are
nite battery gas. Do not smoke, or switch found, have them corrected immediately.
trouble light ON or OFF near battery. Discharge
static electricity from body before touching bat- FUEL SYSTEM
teries by first touching a grounded metal sur-
face. Refer to the Cummins QSK45 and QSK60 Series
Engines Operation and Maintenance Manual for
Ventilate battery area before working on or near fuel recommendations and fuel system mainte-
battery—Wear goggles—Stop genset and dis- nance, such as, draining of the fuel-water separat-
connect charger before disconnecting battery ors and fuel filter replacement interval and proce-
cables—Disconnect negative (–) cable first and dure.
reconnect last.
Fuel Handling Precautions
CAUTION Disconnect battery charger from AC
WARNING Ignition of fuel can cause serious
source before disconnecting battery cables.
Otherwise, disconnecting cables can result in personal injury or death by fire or explosion. Do
voltage spikes damaging to DC control circuits not permit any flame, cigarette, arc, spark, pilot
of the set. light, or other igniter near the fuel system.
To avoid condensation problems, keep fuel supply
WARNING Accidental starting of the generator tanks as full as possible by filling up each time the
set can cause severe personal injury or death. engine is used. In cold weather, warm fuel returning
Prevent accidental starting by disconnecting from the injectors heats the fuel in the supply tank. If
the negative (–) cable from the battery terminal the fuel level is low, the upper portion of the tank
before beginning maintenance procedures. tends to form condensation. In warm weather, both
the fuel and the tank will be warm during the day-
When performing the following maintenance proce-
time. At night, cool air tends to lower the tempera-
dures, make certain the generator set cannot be ac-
ture of the tank more rapidly than the temperature of
cidentally restarted as follows:
the fuel. If the fuel level is low, the upper portion of
the tank will cool more rapidly and tend to form con-
4. Move the O/Manual/Auto switch on the control
densation.
panel to the O (off) position.
Condensation (water) can cause clogging of fuel fil-
5. Turn off or remove AC power from the battery ters with the sulphur in the fuel forms acid which can
charger. corrode and damage engine parts.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-4
LUBRICATION SYSTEM Keep the oil level as near as possible to the high
mark on the dipstick but never above it. Remove
Gensets are shipped filled with the correct type and the oil fill cap and add oil of the same API viscos-
quantity of oil. Be sure to check oil level before initial ity and brand when necessary. Install the oil fill
start.
cap after adding oil.
Oil API Classification
CAUTION Do not operate the engine with the
Refer to the Cummins QSK45 and QSK60 Series oil level below the low mark or above the high
Engines Operation and Maintenance Manual for lu- mark. Overfilling can cause foaming or aeration
bricating oil classification. of the oil while operation below the low mark
may cause loss of oil pressure.
Oil Viscosity
Refer to the Cummins QSK45 and QSK60 Series Oil and Filter Change
Engines Operation and Maintenance Manual for lu-
bricating oil recommendations/specifications.
Refer to the Cummins QSK45 and QSK60 Series
Engine Oil Level Engines Operation and Maintenance Manual for
maintenance interval and procedure.
Check the engine oil level during engine shutdown
periods at the intervals specified in the Mainte-
WARNING State or federal agencies have de-
nance Table. The dipstick is stamped with high and
termined that contact with used engine oil can
low marks to indicate the level of oil in the crank-
cause cancer or reproductive toxicity. Do not
case. For accurate readings, shut off the engine
contact oil or breath vapors. Use rubber gloves
and wait approximately 15 minutes before checking
and wash exposed skin.
the oil level. This allows oil in the upper portion of the
engine to drain back into the crankcase.
Used oil and filters must be disposed of proper-
WARNING Crankcase pressure can blow out ly to avoid environmental damage and clean-up
hot oil and cause severe burns. Do NOT check liability. Check all federal, state and local regu-
oil while the generator set is operating. lations for disposal requirements.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-5
COOLING SYSTEM Cooling System Maintenance
CAUTION The heater must not be operated Refer to the Cummins QSK45 and QSK60 Series
while the cooling system is empty or when the Engines Operation and Maintenance Manual for all
engine is running or damage to the heater will cooling system maintenance, such as, coolant re-
occur. quirements, filling of the engine jacket water and
CAUTION Remove AC power to the heater be- LTA cooling systems, coolant filter replacement and
fore disconnecting battery cables. Heater will flushing and cleaning.
run continuously without DC power and can
overheat and damage heater. In addition to the cooling system maintenance pro-
cedures in the Engine Operation and Maintenance
CAUTION Do not add cold coolant to a hot en- Manual, also refer to the generator set Installation
gine. Engine castings can be damaged. Allow Manual (Section 9). This manual contains additional
the engine to cool to below 120° F (50° C) before information which must be followed to properly
bleed the air from the cooling system during coolant
adding coolant.
refill.
Coolant Level
If engine coolant heater(s) is installed in the jacket
Check the coolant level during shutdown periods at water cooling system, disconnect heater(s) from
the intervals specified in the Maintenance Table. A power source before performing cooling system
sight glass is provided on both radiators (Figure maintenance.
5-1).
CAUTION The heater element will burn out if
The coolant level should be approximately in the
middle of the sight glass, with the coolant tempera- engine coolant is removed with heater con-
ture at 120° F (50° C) or lower. Refer to the Cum- nected to power source.
mins engine Operation and Maintenance Manual
CAUTION The heater element will burn out if
for coolant recommendations/specifications.
power is connected before it is filled with cool-
WARNING Contact with hot coolant can result ant or if straight antifreeze solution is used for
in serious burns. Allow cooling system to cool coolant. Before connecting power, fill the en-
before releasing pressure and removing jacket gine with coolant and run it for a while to circu-
water radiator cap or LTA expansion tank cap. late coolant through the heater.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-6
COOLANT SIGHT
GLASS
JACKET WATER COOLING
SYSTEM FILL CAP

LTA COOLING
SYSTEM FILL CAP

FIGURE 5-1. COOLING SYSTEM SIGHT GLASSES/FILL LOCATIONS

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-7
Coolant Heater
Check the operation of the coolant heater by verify- OUTLET
ing that hot coolant is being discharged from the
outlet hose. Do not touch outlet hose – if heater is
operational, radiant heat should be felt with hand
held close to outlet hose.
WARNING Contact with cooling system or en-
gine can result in serious burns. Do not touch
cooling system or engine during genset mainte-
nance until they are cool.

HEAT EXCHANGER COOLING SYSTEM


(OPTIONAL)
Heat Exchanger Plugs
Check the zinc plugs in the heat exchanger and re- DRAIN INLET
place if they are eroded to less than half their origi-
nal length. The frequency of replacement is depen-
dent on the chemical reaction that occurs when the
plugs are in contact with the raw water. FIGURE 5-2. COOLANT HEATER

AIR CLEANER
Refer to the Cummins QSK45 and QSK60 Series
Engines Operation and Maintenance Manual for air
cleaner filter element replacement interval and pro-
cedure.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-8
BATTERIES Be sure the vent plugs are tight to prevent cleaning
solution from entering the cells.
WARNING Ignition of explosive battery gases
can cause severe personal injury or death. Arc- After cleaning, flush the outside of the battery and
ing at battery terminals, light switch or other surrounding areas with clean water.
equipment, flame, pilot lights and sparks can ig-
nite battery gas. Do not smoke, or switch Keep the battery terminals clean and tight. After
trouble light ON or OFF near battery. Discharge making connections, coat the terminals with a light
static electricity from body before touching bat- application of petroleum jelly or non-conductive
teries by first touching a grounded metal sur- grease to retard corrosion.
face.
Checking Specific Gravity
Ventilate battery area before working on or near
battery—Wear goggles—Stop genset and dis- Use a battery hydrometer to check the specific
connect charger before disconnecting battery gravity of the electrolyte in each battery cell.
cables—Disconnect negative (–) cable first and Hold the hydrometer vertical and take the reading.
reconnect last. Correct the reading by adding four gravity points
(0.004) for every ten degrees the electrolyte tem-
CAUTION Disconnect battery charger from AC
perature is above 80° F (27° C). A fully charged bat-
source before disconnecting battery cables. tery will have a corrected specific gravity of 1.260.
Otherwise, disconnecting cables can result in Charge the battery if the reading is below 1.215.
voltage spikes damaging to DC control circuits
of the set. Checking Electrolyte Level
Check the condition of the starting batteries at the
CAUTION Do not add water in freezing weather
interval specified in the Maintenance Table. To pre-
unless the engine will run long enough (two to
vent dangerous arcing, always disconnect the neg-
three hours) to assure a thorough mixing of wa-
ative ground cable from the battery before working
ter and electrolyte.
on any part of the electrical system or the engine.
Disregard the sections On Checking Specific Gravi- Check the level of the electrolyte (acid and water
ty and Checking Electrolyte Level if using a “mainte- solution) in the batteries at least every 200 hours of
nance-free” battery. operation.

Cleaning Batteries Fill the battery cells to the bottom of the filler neck. If
cells are low on water, add distilled water and re-
WARNING Electrolyte is a dilute sulfuric acid charge. If one cell is low, check case for leaks. Keep
that is harmful to the skin and eyes. Do not get the battery case clean and dry. An accumulation of
the substance in your eyes or contact with skin. moisture will lead to a more rapid discharge and
Wear goggles and protective, rubber gloves battery failure.
and apron when servicing batteries.
Battery Replacement
In case of contact, immediately wash skin with
soap and water. In case of contact, immediately Always replace the starting battery with the same
flood eyes with large amounts of water for a number and type (vented, lead acid). Properly dis-
minimum of 15 minutes. IMMEDIATELY CALL A pose of battery in accordance with local environ-
PHYSICIAN. mental agency requirements.

Keep the batteries clean by wiping them with a WARNING Electrolyte or explosion of battery
damp cloth whenever dirt appears excessive. can cause severe personal injury or death. Do
not mutilate or burn the battery in a fire for dis-
If corrosion is present around the terminal connec- posal.
tions, remove battery cables and wash the termi-
nals with a solution consisting of 1/4 pound of bak- Damage to case will release electrolyte which is
ing soda added to 1 quart of water. (This solution is harmful to the skin and eyes and is also toxic.
also used for washing down spilled electrolyte.) Burning of battery may cause an explosion.
Redistribution or publication of this document,
by any means, is strictly prohibited.
5-9
FAN BEARING RE-LUBRICATION
BEARINGS
Re-lubricate the fan bearings at the interval speci-
fied in the Maintenance Table. A grease fitting is
provided for each of the two bearings to allow the
use of a grease gun to re-lubricate the bearings.
The grease fittings are located on side of the fan
housing pedestal structure (Figure 5-4).
The recommended lubricant is a lithium based
grease, such as, Mobilux EP 2, Mobilith AW 2, or
Shell Alvania R3.
Note the following quantities when re-lubricating
the bearings.
Fan side bearing – 39 grams
Pulley side bearing – 31 grams

GREASE
FITTINGS

FIGURE 5-4. FAN BEARING GREASE FITTINGS

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-10
FAN BELT REPLACEMENT the spring tension. Slowly turn the wrench until
the spring tension is relieved (Figure 5-5). Re-
WARNING Arcing at battery terminals, arcing move the fan belt.
in light switch or other equipment, flame, pilot
WARNING The fan belt idler is under ten-
lights and sparks can ignite battery gas causing
severe personal injury. sion. Do not allow your hands to get be-
tween the idler and the belt or the fan hub.
Ventilate battery area before working on or near Personal injury will result.
battery—Wear safety glasses—Do not smoke—
Switch trouble light ON or OFF away from bat- Belt Replacement
tery—Stop genset and disconnect charger be- 1. Slip new fan belt onto the crankshaft and fan
fore disconnecting battery cables—Disconnect hub pulley.
negative (–) cable first and reconnect last.
WARNING The fan belt idler is under ten-
CAUTION Disconnect battery charger from AC sion. Do not allow your hands to get be-
source before disconnecting battery cables. tween the idler and the belt or the fan hub.
Otherwise, disconnecting cables can result in Personal injury will result.
voltage spikes damaging to DC control circuits 2. Use an 8-point socket and breaker bar or a
of the set. large wrench to hold the idler in position against
WARNING Accidental starting of the generator
the spring tension. Slowly turn the wrench until
set while working on it can cause severe per- the spring tension is relieved sufficiently to
sonal injury or death. Prevent accidental start- position the belt in front of the idler pulley. Align
ing by disconnecting the negative (–) cable from the grooves of the belt on the ribs of the pulley
the battery terminal. and shaft and then slowly release spring ten-
sion onto belt.
Belt Removal The spring-loaded idler used on this design
maintains the correct belt tension.
1. Disconnect the negative (–) cable from the bat-
tery to prevent accidental starting. 3. Install fan belt guards.
2. Remove fan belt guard (between engine and 4. Reconnect starting batteries (negative cable
radiator) to gain access to fan belt. last).
3. Use an 8-point socket and breaker bar or a 5. Start genset and visually check belt for proper
large wrench to hold the idler in position against alignment with engine running.

TURN WRENCH IN DIRECTION OF ARROW


UNTIL SPRING TENSION IS RELIEVED

FIGURE 5-5. FAN BELT REPLACEMENT


Redistribution or publication of this document,
by any means, is strictly prohibited.
5-11
GENERATOR BEARING RE-LUBRICATION suggested on this label for bearing that is re-lu-
bricated every 4,000 hours.
Re-lubricate the generator bearing at the interval
specified in the Maintenance Table. A grease fitting To determine how much grease is supplied with
is provided to allow the use of a grease gun to re-lu- each pump (stroke) of the device, weigh the quanti-
bricate the bearing. ty required (e.g., 75 grams or 2.7 ounces ÷ 1/4 = 19
grams or 0.68 ounces), against the number of pump
Re-lubrication time periods and amount of grease strokes taken to inject that amount onto a small
used may vary in this manual from what is suggested weighing scale. Also, note in practice:
on label located adjacent to end bearing. Use the in-
formation provided in this manual for these values. • If the pump hits an airlock, (i.e., no pressure
when pumping) these strokes can not be
The bearing must be filled with the same type of counted.
grease used when the generator was manufac-
tured. This grease was chosen to provide the bear- • For greater accuracy, the grease fitting can be
ing with optimum lubricating characteristics, and unscrewed, and a flexible grease-pipe
MUST NOT be mixed with any other type. screwed directly to the fitting adapter. This will
make sure that no grease is expelled outside of
Recommended Lubricant: Use the grease that is the fitting.
recommended on the label adjacent to end bearing • If too much grease is applied, any excess will
– Lithium based Mobilux No. 2 grease or Kluber, be exhausted out of the bearing cartridge via
type ASONIC GHY72. As noted above, do not mix the grease escape. (Any exhausted grease
either of these grease types. should be cleaned out of the PMG cover.
Mobilux No. 2 grease can be found at any Mobil Dis- • Always extend the grease gun pump arm out to
tributor. To locate the nearest Kluber grease distrib- its full extent with each pump, failure to do this
utor, see Kluber Web site at: could mean little or no grease is going into the
bearing.
www.klueber.com
Re-Lubrication Procedure
Lubrication
1. Make sure grease gun nozzle and re-lubricat-
It is important that the correct quantity of grease is ing fitting are free from contaminants or abra-
used for periodic re-lubrication with a grease gun sive material.
during planned maintenance. Refer to label located 2. Apply the specified re-lubrication grease fill
at bearing end of generator which specifies the quantity through the grease fitting.
grease fill quantity. 3. Run the generator for 10 minutes to allow ex-
Use only 1/4 of the amount of grease suggested cess grease to exhaust.
on this label for bearing that is re-lubricated ev- 4. Check inside the PMG cover for expelled
ery 1,000 hours. Use the full amount of grease grease. Clean out as necessary.

Redistribution or publication of this document,


by any means, is strictly prohibited.
5-12
6. Operating Recommendations
NO-LOAD OPERATION LOW OPERATING TEMPERATURE
Periods of no load operation should be held to a Use a coolant heater if a separate source of power
minimum. If it is necessary to keep the engine run- is available. The optional heater available from
ning for long periods of time when no electric output Onan will help provide reliable starting under ad-
is required, best engine performance will be ob- verse weather conditions. Be sure the voltage of the
tained by connecting a load bank of at least 30 per- separate power source is correct for the heater ele-
cent of nameplate MW rating. ment rating.
EXERCISE PERIOD
HIGH OPERATING TEMPERATURE
Generator sets on continuous standby must be able
to go from a cold start to being fully operational in a Refer to the genset nameplate for the maximum
matter of seconds. This can impose a severe bur- ambient operating temperature, if applicable.
den on engine parts.
Regular exercising keeps engine parts lubricated,
prevents oxidation of electrical contacts and in gen-
eral helps provide reliable engine starting.
Exercise the generator set at least once a month for
a minimum of 30 minutes, under not less than 30
percent of the nameplate MW rating.

Redistribution or publication of this document,


by any means, is strictly prohibited.
6-1
THIS PAGE LEFT INTENTIONALLY BLANK

Redistribution or publication of this document,


by any means, is strictly prohibited.
6-2
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
1-800-888-6626
763-574-5000 International Use
Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.

Redistribution or publication of this document,


by any means, is strictly prohibited.

You might also like