Introduction
ABBs FORMULA molded case circuit breaker line offers simplicity and quality in some of
the smallest dimensions available. The A1 breaker frame size ranges in amperes from 15
through 100 and the A2 breaker frame size ranges from 125 through 250 amperes. All UL
FORMULA circuit breakers offer protection trip units that have fixed thermal and magnetic
threshold values and are standard as a fixed version with front terminals.
Standards
UL 489 & IEC 60947-2
Dimensions (W x D x H):
1 pole: 1.00 x 2.36 x 5.12
2 pole: 2.00 x 2.36 x 5.12
3 pole: 3.00 x 2.36 x 5.12
Weight:
1 pole: 0.54 lbs
2 pole: 1.04 lbs
3 pole: 1.54 lbs 17
Available accessories:
FORMULA
A1 A2
Frame size A 100 250
Rated current, In A 15...100 125...250
Poles [Nr] Nr 1, 2, 3 1, 2, 3
Rated service voltage, Ue (AC) 50-60 Hz V 240 (1p, 2p, 3p) 240 (1p, 2p, 3p)
(DC) V 125 (1p), 250 (2p,3p) 125 (1p), 250 (2p,3p)
Versions Fixed Fixed
Performance Level A N A N
Poles Nr 1 2, 3 1 2, 3 1 2, 3 1 2, 3
Rated ultimate short circuit breaking capacity, Icu
Interrupting rating @ 240 V 50-60 Hz (AC) kA 10 10 18 25 10 10 14 25
Interrupting rating @ 125 V (DC) 1 pole (in 2012) kA 5 - 10 - 5 - 10 -
Interrupting rating @ 250 V (DC) 2 poles in series (2p, 3p) (in 2012) kA - 5 - 10 - 10 - 25
Reference Standard UL 489 UL 489
Isolation behavior Yes Yes
Fixing onto DIN rail DIN EN 50022 DIN EN 50022
Dimensions (Width x Depth x Height)
1 pole in 1.00 x 2.36 x 5.12 1.38 x 2.36 x 5.91
2 poles in 2.00 x 2.36 x 5.12 2.76 x 2.36 x 5.91
3 poles in 3.00 x 2.36 x 5.12 4.13 x 2.36 x 5.91
Weight
1 pole lbs 0.54 0.82
2 poles lbs 1.04 1.61
3 poles lbs 1.54 2.43
Trip Unit - Thermomagnetic TMF Yes Yes
17
A W
Number of Poles
-1= 1 pole (UL&IEC)
-2= 2 pole (UL&IEC)
None= 3 pole (UL&IEC)
-4= 4 pole (IEC)
Type Connectors
W=none
Frame Size:
1=100A, UL; 2=250A, UL
A=125A, IEC; B=250A, IEC; C=400A, IEC; D=630A, IEC
17
A1 - 100A Frame TMF, thermal magnetic fixed - fixed mount (F), front terminals (F)
IC at Rating 1 pole 2 pole 3 pole
Breaker Magnetic trip
240VAC (A) catalog number catalog number catalog number
15 400 A1A015TW-1 A1A015TW-2 A1A015TW
20 400 A1A020TW-1 A1A020TW-2 A1A020TW
25 400 A1A025TW-1 A1A025TW-2 A1A025TW
30 400 A1A030TW-1 A1A030TW-2 A1A030TW
40 400 A1A040TW-1 A1A040TW-2 A1A040TW
A1A 10kA 50 500 A1A050TW-1 A1A050TW-2 A1A050TW
60 600 A1A060TW-1 A1A060TW-2 A1A060TW
70 700 A1A070TW-1 A1A070TW-2 A1A070TW
80 800 A1A080TW-1 A1A080TW-2 A1A080TW
90 900 A1A090TW-1 A1A090TW-2 A1A090TW
100 1000 A1A100TW-1 A1A100TW-2 A1A100TW
15 400 A1N015TW-1 A1N015TW-2 A1A015TW
20 400 A1N020TW-1 A1N020TW-2 A1A020TW
25 400 A1N025TW-1 A1N025TW-2 A1A025TW
30 400 A1N030TW-1 A1N030TW-2 A1A030TW
1 pole 40 400 A1N040TW-1 A1N040TW-2 A1A040TW
18kA
A1N 50 500 A1N050TW-1 A1N050TW-2 A1A050TW
2-3 pole
25kA 60 600 A1N060TW-1 A1N060TW-2 A1A060TW
70 700 A1N070TW-1 A1N070TW-2 A1A070TW
80 800 A1N080TW-1 A1N080TW-2 A1A080TW
90 900 A1N090TW-1 A1N090TW-2 A1A090TW
100 1000 A1N100TW-1 A1N100TW-2 A1A100TW
17
A2 - 250A Frame TMF, thermal magnetic fixed - fixed mount (F), front terminals (F)
IC at Rating 1 pole 2 pole 3 pole
Breaker Magnetic trip
240VAC (A) catalog number catalog number catalog number
125 1250 A2A125TW-1 A2A125TW-2 A2A125TW
150 1500 A2A150TW-1 A2A150TW-2 A2A150TW
175 1750 A2A175TW-1 A2A175TW-2 A2A175TW
A2A 10kA
200 2000 A2A200TW-1 A2A200TW-2 A2A200TW
225 2250 A2A225TW-1 A2A225TW-2 A2A225TW
250 2500 A2A250TW-1 A2A250TW-2 A2A250TW
125 1250 A2N125TW-1 A2N125TW-2 A2N125TW
150 1500 A2N150TW-1 A2N150TW-2 A2N150TW
1 pole
18kA 175 1750 A2N175TW-1 A2N175TW-2 A2N175TW
A1N
2-3 pole 200 2000 A2N200TW-1 A2N200TW-2 A2N200TW
25kA
225 2250 A2N225TW-1 A2N225TW-2 A2N225TW
250 2500 A2N250TW-1 A2N250TW-2 A2N250TW
17
17
17
Catalog
Frame size Description
number
LTC 3p - 2pcs KA1LTC-3
A1
HTC 3p - 2pcs KA1HTC-3
LTC 3p - 2pcs KA2LTC-3
A2
HTC 3p - 2pcs KA2HTC-3
High terminal cover (HTC)
Sealable screws for terminal covers* KA2SSW-T
A1 - A2
Sealable screws for front* KA2SSW-F
* IEC rated only
2-Piece 4-Piece
Frame size Description catalog catalog
17 number number
A1 PB 50mm KA1PBL-2 KA1PBL-3
A2 PB 80mm KA2PBL-2 KA2PBL-3
A1 - A2 PB 100mm KA2PBH-2 KA2PBH-3
Phase barriers
Catalog
Frame size Description
number
RHE KIT A1-A2 STANDARD EXTENDED KA2RHE
RHE KIT A1-A2 EMERGENCY EXTENDED KA2RHEEM
RHE A1-A2 BASE KA2RHE-B
A1 - A2
RHE A1-A2 SHAFT KA2RHE-S
RHE A1-A2 STANDARD HANDLE KA2RHE-H
RHE A1-A2 EMERGENCY HANDLE KA2RHE-HEM
Extended handle (RHE)
Key lock on handle and front lever operating mechanism (RHL) (IEC only)
Catalog
Frame size Description
number
A1 - A2 Bracket for 1p, 2p, 3p KA2DIN
Introduction
ABB is once again demonstrating its The ABB Tmax product line has the performance
commitment to new product development and accessories to satisfy all industry
and its superiority in product technology. requirements in the 600VAC to 600VDC ranges.
Never before has the industry seen such high Frame sizes Nine basic sizes
performance, versatility and standardization in a The ABB Tmax series includes nine basic frame
range of molded case circuit breakers. sizes as well as the T1 single pole with the range
The ABB Tmax line of circuit breakers, with a rated from 15A to 3000A at 480VAC. The various
range up to 3000A, has several key features versions carry the following interrupting capacities:
that go along with its very small size: B Basic breaking capacity
Double insulation this construction N Normal breaking capacity
characteristic allows for the UL Listed field S Standard breaking capacity
installation of internal accessories without H High breaking capacity 17
exposure to energized parts. L Extra high breaking capacity
Complete range of electrical and V Very high breaking capacity
mechanical accessories Derived versions
Positive operation breakers from ABB Thermal magnetic
ensure that the toggle indicates the precise Electronic
position of the moving contacts. This Molded case switches
guarantees safe and reliable signaling by Motor circuit protectors (MCPs)
the device. Direct current (DC) rated
Installation Tmax molded case circuit ABB Tmax versions
breakers can be installed in panels and Fixed: all models
switchboards in either the horizontal Drawout or plug-in: T2, T3, Ts3, T4, T5, T6,
or vertical planes while being fed from T7 & T7M
either end without any derating of their UL File #E93565 (breakers and MCPs)
performance characteristics. #E116596 (Accessories)
Interrupting ratings at 480VAC up to #E116595 (Molded case switches)
150kAIC.
Compact size
Tmax
T1 1P T1 T2 T3 Ts3
T4 T5 T6 T7 T8
T3 S 080 T W - 4 xxx
Number of poles
-1 =1 pole (T1 only)
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Type connectors
W = None
L = Lugs included
Current rating
015 = 15A
17 080 = 80A
100 = 100A
225 = 225A
250 = 250A
400 = 400A
600 = 600A
800 = 800A
1200 = 1200A
Frame size
T1 = 100A
T2 = 100A
T3 = 225A
Ts3 = 225A
T4 = 250A
T5 = 400A, 600A
T6 = 600A, 800A
T7 = 1000A, 1200A (toggle)
T1
Performance levels
The T1 breaker has two performance levels available:
B = Basic single pole IEC 60947-2 Interrupting capacity (kA RMS)
N = Normal three pole Voltage Continuous rating B (1 pole) N
230VAC 15 100A 25 3 50
Number of poles 415VAC 15 100A 36
The T1 molded case circuit breaker is available in single, three and four pole versions.
690VAC 15 100A 6
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB sales
person for details. 500VDC 3 pole series 15 100A 36
17
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous trip
mechanism for self protection.
T2
Trip functions
These tripping functions are available:
L = Long time
S = Short time
I - Instantaneous 17
Performance levels
The T2 breaker has two performance levels available:
S = Standard
H = High - UL Current Limiting
Number of poles
The T2 is available in three and four pole versions. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.
17
T3
Number of poles
The T3 molded case circuit breaker is available in three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB
sales person for details.
17
17
Ts3
General
The Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 trip UL/CSA Interrupting capacity (kA RMS)
mechanisms are non-interchangeable and use sensitive electromagnetic relays for
overcurrent trip protection. Heat sensitive bimetals are used for thermal overcurrent
UL489 / CSA C22.2
protection. Short circuit current protection begins at 10 times the thermal rating of Voltage N H L
the breaker and uses a magnetic coil principle. 150AF, 15A-150A
240 VAC 65 100 150
Standards 480 VAC 25 50 85 1
The UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.
600 VAC 14 14 25
500 VDC 35 50 65
Versions 600 VDC 20 35 50
To meet all application needs, the Ts3 is available in various versions:
T =Thermal-magnetic 225AF, 175A-225A
D = Molded case switch 240 VAC 65 100 150
M = Magnetic only (MCP) 480 VAC 25 50 65
600 VAC
Performance level 500 VDC 20 35 50
Each version is also available in different maximum fault interrupting levels
600 VDC
N = Normal
H = High IEC-60947-2 Interrupting capacity (kA RMS)
L = Extra high 230 VAC 65 100 170
415 VAC 35 65 85
Number of poles 690 VAC 14 18 20
The Ts3 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details. 750 VDC 2 20 35 50
17
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
2 pole,
Magnetic 3 pole, 600VAC/DC
Breaker IC at 480VAC kA Rating 600VAC/500VDC
trip catalog number
catalog number
15A 500A Ts3N015TW-2 Ts3N015TW
20A 500A Ts3N020TW-2 Ts3N020TW
25A 500A Ts3N025TW-2 Ts3N025TW
30A 500A Ts3N030TW-2 Ts3N030TW
35A 500A Ts3N035TW-2 Ts3N035TW
40A 500A Ts3N040TW-2 Ts3N040TW
50A 500A Ts3N050TW-2 Ts3N050TW
Ts3N 25
60A 600A Ts3N060TW-2 Ts3N060TW
70A 700A Ts3N070TW-2 Ts3N070TW
80A 800A Ts3N080TW-2 Ts3N080TW
90A 900A Ts3N090TW-2 Ts3N090TW
100A 1000A Ts3N100TW-2 Ts3N100TW
125A 1250A Ts3N125TW-2 Ts3N125TW
150A 1500A Ts3N150TW-2 Ts3N150TW
2 pole,
Magnetic 600VAC/500VDC 3 pole, 600VAC/DC
Breaker IC at 480VAC kA Rating
trip catalog number catalog number
15A 500A Ts3H015TW-2 Ts3H015TW
20A 500A Ts3H020TW-2 Ts3H020TW
25A 500A Ts3H025TW-2 Ts3H025TW
30A 500A Ts3H030TW-2 Ts3H030TW
35A 500A Ts3H035TW-2 Ts3H035TW
40A 500A Ts3H040TW-2 Ts3H040TW
50A 500A Ts3H050TW-2 Ts3H050TW
Ts3H 50
60A 600A Ts3H060TW-2 Ts3H060TW
17 70A 700A Ts3H070TW-2 Ts3H070TW
80A 800A Ts3H080TW-2 Ts3H080TW
90A 900A Ts3H090TW-2 Ts3H090TW
100A 1000A Ts3H100TW-2 Ts3H100TW
125A 1250A Ts3H125TW-2 Ts3H125TW
150A 1500A Ts3H150TW-2 Ts3H150TW
2 pole,
Magnetic 3 pole, 600VAC/DC
Breaker IC at 480VAC kA Rating 600VAC/500VDC
trip catalog number
catalog number
15A 500A Ts3L015TW-2 Ts3L015TW
20A 500A Ts3L020TW-2 Ts3L020TW
65
25A 500A Ts3L025TW-2 Ts3L025TW
30A 500A Ts3L030TW-2 Ts3L030TW
35A 500A Ts3L035TW-2 Ts3L035TW
40A 500A Ts3L040TW-2 Ts3L040TW
50A 500A Ts3L050TW-2 Ts3L050TW
Ts3L
60A 600A Ts3L060TW-2 Ts3L060TW
70A 700A Ts3L070TW-2 Ts3L070TW
85
80A 800A Ts3L080TW-2 Ts3L080TW
90A 900A Ts3L090TW-2 Ts3L090TW
100A 1000A Ts3L100TW-2 Ts3L100TW
125A 1250A Ts3L125TW-2 Ts3L125TW
150A 1500A Ts3L150TW-2 Ts3L150TW
NOTE: See pages 17.71 - 17.83 for electrical/mechanical accessories.
IC at Magnetic 3 pole
Breaker Rating
480VAC trip catalog number
15A 500A Ts3HQ015TW
20A 500A Ts3HQ020TW
25A 500A Ts3HQ025TW
30A 500A Ts3HQ030TW
35A 500A Ts3HQ035TW
40A 500A Ts3HQ040TW
50A 500A Ts3HQ050TW
Ts3HQ 50kA
60A 600A Ts3HQ060TW
70A 700A Ts3HQ070TW
80A 800A Ts3HQ080TW
90A 900A Ts3HQ090TW
100A 1000A Ts3HQ100TW 17
125A 1250A Ts3HQ125TW
150A 1500A Ts3HQ150TW
17
T4
Performance levels
Each version is also available in different maximum fault interrupting levels: 17
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 3
The T4 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
1 2 poles in series.
2 3 poles in series.
3 2 pole breakers available in N version only. 4 pole breakers available in N and H version only.
17
17
17
T5
Performance levels
Each version is also available in different maximum fault interrupting levels: 17
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 4
The T5 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
1 2 poles in series.
2 3 poles in series.
3 T5 600A not available with thermal magnetic trip unit.
4 2 pole available in N version only. 4 pole available in N and H version only.
17
T6
Versions 600VDC 2 20 20 35 50
To meet all application requirements, the T6 is available in the following versions:
T = Thermal-magnetic, fixed
B = Selectable & adjustable LI or LS
IEC 60947-2 Interrupting capacity (kA RMS)
C = Adjustable LSI Voltage N S H L
E = Adjustable LSIG 230VAC 70 85 100 200
D = Molded Case Switch
415VAC 36 50 70 100
E5 = Electronic instantaneous only (MCP)
690VAC 20 22 25 30
Trip functions 750VDC 2 16 20 36 50
These trip functions are available:
L = Long time
S = Short time
17 I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High
L = Extra high
Number of poles 3
The T6 is available as a three and four pole breaker. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
1 2 poles in series.
2 3 poles in series.
3 4 pole available N and H version only.
T7
Versions
To meet all application requirements, the T7 is available in the following versions:
B = Selectable & adjustable LI or LS Dip switch settings
IEC 60947-2 Interrupting capacity (kA RMS)
C = Adjustable LSI Dip switch settings Voltage S H L
E = Adjustable LSIG Dip switch settings 230VAC 85 100 200
D = Molded Case Switch
415VAC 50 70 120
P = LI LCD display
R = LSI LCD display 690VAC 30 42 50
S = LSIG LCD display
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels 17
Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
L = Extra high
Number of poles 1
The T7 is available as a 3 and 4 pole breaker. Estimate 4 pole pricing by adding 35%
to the 3 pole price and contact your ABB sales person for details.
T7H 65
PR331/P LSIG T7HQ1200EW 17
PR332/P LI T7HQ1200PW
PR332/P LSI T7HQ1200RW
PR332/P LSIG T7HQ1200SW
T7
1000 - 1200A, 600V
Motor circuit protection
Electronic trip, instantaneous only
Breaker IC at 480VAC kA 1 Amp Catalog number
T7S 50 1000 T7S1000E5W
T7H 65 1000 T7H1000E5W
T7L 100 1000 T7L1000E5W
T7S 50 1200 T7S1200E5W
T7H 65 1200 T7H1200E5W
T7L 100 1200 T7L1200E5W
NOTE: See pages 17.71 - 17.83 for electrical/mechanical accessories.
17
T7M
Versions
To meet all application requirements, the T7M is available in the following versions:
B = Selectable & adjustable LI or LS Dip switch setting
C = Adjustable LSI Dip switch setting IEC 60947-2 Interrupting capacity (kA RMS)
E = Adjustable LSIG Dip switch setting
D = Molded Case Switch Voltage S H L
P = LI LCD display 230VAC 85 100 200
R = LSI LCD display 415VAC 50 70 120
S = LSIG LCD display
690VAC 30 42 50
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
17
L = Extra high
Number of poles
The T7M is available as a three and four pole breaker.
Locking provisions:
X = None
A = Keylock; B = Button guard
C = Padlock provision (open)
F = A+B
Accessories:
X = None
A = Mechanical counter
B = Trip signal
C = Trip signal and reset 24-30 VAC/DC
D = Trip signal and reset 110-130 VAC/DC
E = Trip signal and reset 200-240 VAC/DC
F = A+C; G=A+D; H=A+E
Undervoltage:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC;
C = 48 VAC/DC; D = 60 VAC/DC; E = 110...120 VAC/DC
F = 120...127 VAC/DC; G = 220...240 VAC/DC;
H = 240250 VAC/DC; J = 380400 VAC; K = 415440 VAC
Shunt trip:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC;
C = 48 VAC/DC; D = 60 VAC/DC; E = 110120 VAC/DC
F = 120127 VAC/DC; G = 220240 VAC/DC; H = 240250 VAC/DC
J = 380400 VAC; K = 415440 VAC
Trip Unit:
A = PR231/P-I (MCP); B = PR231/P-LS/I; C = PR232/P-LSI; D = Non-Automatic (MCS);
E = PR331/P-LSIG; P = PR332/P-LI; R = PR332/P-LSI; S = PR332P-/LSIG
Rating Plug:
0 = None; Non Automatic (MCS) A = 400A; B = 600/630A; C = 800A; D = 1000A; E = 1200/1250A F = 1600A (IEC only)
Version:
0 = Fixed non-automatic (MCS); B = UL fixed; Q = UL fixed 100% rated; F = IEC fixed
Breaking Capacity:
S, H, L, V = IEC, T7 800, 1000, 1250A only); D = MCS (IEC) Call factory for IEC breaker pricing
17
17
17
17
T7M
1200A, 600V
Molded case switch
IC at Magnetic 3 pole, 600VAC Catalog
Breaker Amp
480VAC kA override number
T7M-H - 1200 20,000 T7MH0B30D000000XX
T7M
1000 - 1200A, 600V
Motor circuit protection
Electronic trip, instantaneous only
Breaker IC at 480VAC kA Amp Catalog number
T7M-S 50 1000 T7MSBP3DA000000XX
T7M-H 65 1000 T7MHBP3DA000000XX
T7M-L 100 1000 T7MLBP3DA000000XX
T7M-S 50 1200 T7MSBB3EA000000XX
T7M-H 65 1200 T7MHBB3EA000000XX
T7M-L 100 1200 T7MLBB3EA000000XX
17
Field installation
Auxiliary contacts Catalog number
2 Form C 400 VAC KT7XAS2
T7/T7M
2 Form C 24 VDC KT7XAS2-AU
Field installation
Ready to close auxiliaries (IEC) Catalog number
24 VDC KT7MX-RTC24V
T7M
250 VAC/DC KT7MX-RTC250V
Signals the circuit breaker is ready to accept a close signal if the following five conditions are met:
Circuit breaker is open Any opening coil de-energized Opening solenoid armed
Closing springs are charged Any undervoltage coil energized
Field/factory
Trip signal installation
Catalog number
T7M Contact for signalling electronic trip unit tripped 1 KT7MTS
Field installation
Spring charging motor 1 Catalog number
380415 VAC KT7MXM2
220250 VAC/DC KT7MXM3
T7M 100130 VAC/DC KT7MXM5
4860 VAC/DC KT7MXM7
2430 VAC/DC KT7MXM9
Field installation
Spring charged contacts (IEC) Catalog number
Contact signalling springs charged 24 VDC KT7MX-SC24V
T7M
Contact signalling springs charged 250 VAC/DC KT7MX-SC250V
Field installation
Shunt trip Catalog number
KT7MXM*
415440 VAC KT7XS1
380400 VAC KT7XS2
240250 VAC/DC KT7XS3
220240 VAC/DC KT7XS4
17 T7/T7M
120127 VAC/DC KT7XS5
110120 VAC/DC KT7XS6
60 VAC/DC KT7XS7
48 VAC/DC KT7XS8
30 VAC/DC KT7XS9
24 VAC/DC KT7XS0
KT7XU*
Field installation
Undervoltage Catalog number
415440 VAC KT7XU1
380400 VAC KT7XU2
240250 VAC/DC KT7XU3
220240 VAC/DC KT7XU4
120127 VAC/DC KT7XU5
T7/T7M
110120 VAC/DC KT7XU6
60 VAC/DC KT7XU7
48 VAC/DC KT7XU8
30 VAC/DC KT7XU9
24 VAC/DC KT7XU0
Field installation
Trip reset (IEC) Catalog number
Trip reset command 24-30 VAC/DC KT7MX-TR9
T7M Trip reset command 110-130 VAC/DC KT7MX-TR5
Trip reset command 200-240 VAC/DC KT7MX-TR4
Allows remote circuit breaker resetting following a trip of the overcurrent release
Padlock provision 3
Field/factory installation
Frame
Catalog number
T7M Padlock-open 3 KT7MXLDO
KT7XPG
Key locks
Frame Sizer
Key lock Field/factory installation 17
open position Catalog number
Key lock on breaker
open position KT7MKL2
key lock # 20005 3
T7M
Key lock on breaker
open position KT7MKL1
different keys 3
Mechanical interlock
Catalog
Frame
part number
Cable T7 KT7XMLC
KT7MKL* T7M/T7M Mechanical interlock plate - drawout KT7XMLPW
Mechanical interlock plate - fixed KT7XMLPF
17
T8
Performance levels
Each version is also available at the following maximum fault interrupting level:
17 V = Very high
Number of poles
The T8 is available in three and four pole versions.
T 8 V
Locking provisions:
X = None; A = Keylock
B = Button guard; C = Padlock provision; D = A+B; E = A+C
T = Heavy duty padlock;
9 = Extra heavy duty padlock
Accessories
X = None; A = Mechanical counter; B = Bell Alarm
C = Bell Alarm w/remote reset, 24..30 VAC/DC
D = Bell Alarm w/remote reset 110..130 VAC/DC
E = Bell Alarm w/remote reset 220..240 VAC/DC
F = A+B; G = A+C; H = A+D; J = A+E
Undervoltage
0 = None
A = 24 VDC; B = 30 VAC/DC
C = 48 VAC/DC; D = 60 VAC/DC
E = 110..120 VAC/DC; F = 125..127 VAC/DC
G = 220..240 VAC/DC; H = 250 VAC/DC
J = 380..400 VAC; K = 440 VAC
Second shunt trip:
L = 24 VDC; M = 30 VAC/DC
N = 48 VAC/DC; P = 60 VAC/DC
Q = 110..120 VAC/DC; R = 125..127 VAC/DC
S = 220..240 VAC/DC; T = 250 VAC/DC
U = 380..400 VAC; V = 440..480 VAC
Shunt trip
0 = None
A = 24 VDC; B = 30 VAC/DC; C = 48 VAC/DC;
D = 60 VAC/DC; E = 110..120 VAC/DC
F = 120..127 VAC/DC; G = 220..240 VAC/DC;
H = 240..250 VAC/DC; J = 380400 VAC;
K = 440 VAC
Contacts:
0 = None
A = 4 aux contacts; (supplied as standard for breakers with PR332 trip units)
B = 4 aux contacts digital (24V)
D = UV energ NO; E = UV energ NC;
F = A+D; G = A+E; H = B+D; J = B+E 17
Closing Coil:
0 = None
A = 24 VDC; B = 30 VAC/DC; C = 48 VAC/DC; D = 60 VAC/DC; E = 110..120 VAC/DC;
F = 120..127 VAC/DC; G = 220..240 AC/DC; H = 240..250 VAC/DC; J = 380..400 VAC; K = 440VAC
Trip Unit:
C = PR331/P-T8-LSI; D = Non-Automatic (MCS); E = PR331/P-LSIG;
P = PR332/P-LI; R = PR332/P-LSI; S = PR332/P-LSIG; H = PR332/P-LSIRc (IEC)
Rating Plug:
D = 1000; E = 1200; F = 1600; G = 2000; H = 2500; J = 3000, 3200; 0 = Non-Automatic (MCS)
Version:
B = UL Fixed; Q = UL Fixed 100% Rated; F = IEC Fixed; 0 = Fixed Non-Automatic (MCS)
Breaking capacity:
V = Very High; L (IEC only. Call factory for IEC breaker pricing.)
2000A Frame, electronic trip unit (AC only) standard 3000A Frame, electronic trip unit (AC only) standard with
horizontal terminals vertical terminals - Required
IC at 3 pole, 600V IC at 480VAC 3 pole, 600V
Breaker Trip Unit Breaker Trip Unit
480VAC kA Catalog number kA Catalog number
PR232 LSI (Dip Switch) T8VBD3GC000000XX PR232 LSI (Dip Switch) T8VBF3JC000000XX
PR331 LSIG (Dip Switch) T8VBD3GE000000XX PR331 LSIG (Dip Switch) T8VBF3JE000000XX
T8V 125 PR332 LI (LCD) T8VBD3GP00A000XX 1 T8V 125 PR332 LI (LCD) T8VBF3JP00A000XX 1
PR332 LSI (LCD) T8VBD3GR00A000XX 1 PR332 LSI (LCD) T8VBF3JR00A000XX 1
PR332 LSIG (LCD) T8VBD3GS00A000XX 1 PR332 LSIG (LCD) T8VBF3JS00A000XX 1
17
2000A Frame, electronic trip unit (AC only) standard 3000A Frame, electronic trip unit (AC only) standard with
horizontal terminals vertical terminals - Required
IC at 3 pole, 600V IC at 3 pole, 600V
Breaker Trip Unit Breaker Trip Unit
480VAC kA Catalog number 480VAC kA Catalog number
PR232 LSI (Dip Switch) T8VQD3GC000000XX PR232 LSI (Dip Switch) T8VQF3JC000000XX
PR331 LSIG (Dip Switch) T8VQD3GE000000XX PR331 LSIG (Dip Switch) T8VQF3JE000000XX
T8V 125 PR332 LI (LCD) T8VQD3GP00A000XX 1 T8V 125 PR332 LI (LCD) T8VQF3JP00A000XX 1
PR332 LSI (LCD) T8VQD3GP00A000XX 1 PR332 LSI (LCD) T8VQF3JR00A000XX 1
PR332 LSIG (LCD) T8VQD3GR00A000XX 1 PR332 LSIG (LCD) T8VQF3JS00A000XX 1
17
2000A Frame, electronic trip unit (AC only) standard 3000A Frame, electronic trip unit (AC only) standard with
horizontal terminals vertical terminals - Required
IC at 4 pole, 600V IC at 4 pole, 600V
Breaker Trip Unit Breaker Trip Unit
480VAC kA Catalog number 480VAC kA Catalog number
PR232 LSI (Dip Switch) T8VBD4GC000000XX PR232 LSI (Dip Switch) T8VBF4JC000000XX
PR331 LSIG (Dip Switch) T8VBD4GE000000XX PR331 LSIG (Dip Switch) T8VBF4JE000000XX
T8V 125 PR332 LI (LCD) T8VBD4GP00A000XX 1 T8V 125 PR332 LI (LCD) T8VBF4JP00A000XX 1
PR332 LSI (LCD) T8VBD4GR00A000XX 1 PR332 LSI (LCD) T8VBF4JR00A000XX 1
PR332 LSIG (LCD) T8VBD4GS00A000XX 1 PR332 LSIG (LCD) T8VBF4JS00A000XX 1
17
2000A Frame, electronic trip unit (AC only) standard 3000A Frame, electronic trip unit (AC only) standard with
horizontal terminals vertical terminals - Required
IC at 4 pole, 600V IC at 4 pole, 600V
Breaker Trip Unit Breaker Trip Unit
480VAC kA Catalog number 480VAC kA Catalog number
PR232 LSI (Dip Switch) T8VQD4GC000000XX PR232 LSI (Dip Switch) T8VQF4JC000000XX
PR331 LSIG (Dip Switch) T8VQD4GE000000XX PR331 LSIG (Dip Switch) T8VQF4JE000000XX
T8V 125 PR332 LI (LCD) T8VQD4GP00A000XX 1 T8V 125 PR332 LI (LCD) T8VQF4JP00A000XX 1
PR332 LSI (LCD) T8VQC4GR00A000XX 1 PR332 LSI (LCD) T8VQF4JR00A000XX 1
PR332 LSIG (LCD) T8VQD4GS00A000XX 1 PR332 LSIG (LCD) T8VQF4JS00A000XX 1
17
Rated Voltage
AC 600VAC
DC
Magnetic Overide 40000
17
Field/factory installation
Accessories for trip units Catalog number
Communication module (Modbus (RTU) PR330/D-M 2
External wireless communication module BT030
T8 Power supply unit PR030/B
Voltage module, 3 pole 3 PR330/V-T83
Voltage module, 4 pole 3 PR330/V-T84
Field installation
Current sensor for external neutral Catalog number
T8 Current sensor for external neutral 1000A-3000A KT8NCT
Field/factory installation
Closing coil Catalog number
440 VAC KE6C1
380400VAC KE6C2
240250 VAC/DC KE6C3
220240 VAC/DC KE6C4
KE6C* 120127 VAC/DC KE6C5
T8
110120 VAC/DC KE6C6
60 VAC/DC KE6C7
48 VAC/DC KE6C8
30 VAC/DC KE6C9
24 VDC KE6C0
Field/factory installation
Auxiliary contacts Catalog number
4 open/closed PR232-T8/PR331 KT8A4
4 open/closed PR332 1 KT8A4-PR332
T8
4 open/closed 24V PR232-T8/PR331 KT8A4D
4 open/closed 24V PR332 KT8A4D-PR332
KT8A4
Field/factory installation
Bell alarm Catalog number
Allows visual signaling (mechanical) and remote signaling (electrical)
T8 of circuit breaker opening by overcurrent release DE6TBA 17
Field/factory installation
Bell alarm with remote reset command Catalog number
Remote setting of circuit breaker after opening by overcurrent release DE6TBAR4
220-240 VAC/DC
Remote setting of circuit breaker after opening by overcurrent release
T8 DE6TBAR5
110-130 VAC/DC
Remote setting of circuit breaker after opening by overcurrent release DE6TBAR9
24-30 VAC/DC
Field/factory installation
Contact signaling undervoltage de-energized Catalog number
NC UV signaling contact KE6UE01
T8
NO UV signaling contact KE6UE10
Field/factory installation
Spring charging motor Catalog number
2430 VAC/DC KE6M9
4860 VAC/DC KE6M7
T8
100130 VAC/DC KE6M5
220250 VAC/DC KE6M3
KE6M*
1 Included as standard on breakers ordered with PR332 trip unit
2 Discount schedule SAT (T0)
3 Factory install only.
Field/factory installation
Shunt trip Catalog number
440 VAC KE6S1
380400 VAC KE6S2
240250 VAC/DC KE6S3
220240 VAC/DC KE6S4
120127 VAC/DC KE6S5
T8
110120 VAC/DC KE6S6
60 VAC/DC KE6S7
48 VAC/DC KE6S8
30 VAC/DC KE6S9
KE6S*
24 VDC KE6S0
Field/factory installation
Second shunt trip 1 Catalog number
440 VAC KE6S1-2
380400 VAC KE6S2-2
240250 VAC/DC KE6S3-2
220240 VAC/DC KE6S4-2
120127 VAC/DC KE6S5-2
T8
110120 VAC/DC KE6S6-2
60 VAC/DC KE6S7-2
48 VAC/DC KE6S8-2
30 VAC/DC KE6S9-2
24 VDC KE6S0-2
Field/factory installation
Undervoltage Catalog number
440 VAC KE6U1
380400 VAC KE6U2
240250 VAC KE6U3
220240 VAC/DC KE6U4
120127 VAC/DC KE6U5
T8
110120 VACV/DC KE6U6
60 VAC/DC KE6U7
KE6U* 48 VAC/DC KE6U8
30 VAC/DC KE6U9
24 VDC KE6U0
17
Field/factory installation
Key lock in open position Catalog number
Key lock n. 20005 1 KT8KL2
Key lock n. 20006 KT8KL3
T8 Key lock n. 20007 KT8KL4
Key lock n. 20008 KT8KL5
Key lock different keys KT8KL1
Field/factory installation
Padlocking button cover Catalog number
3-4mm locks (padlocks not supplied) KE6PD1
T8 HD padlock device KE6PDHD1
Extra HD padlock device KE6PDHD2
Field/factory installation
Button guard Catalog number
Protective cover for opening and
T8 KE6PG
closing pushbuttons
KE6PG
Field/factory installation
Mechanical operation counter Catalog number
T8 Indicates the number of mechanical operations KE6MC
Field installation
Phase barriers-top terminals only Catalog number
Low 100mm 2 pcs (3P) KT8PBL-3
Low 100mm 3 pcs (4P) KT8PBL-4
T8
High 200mm 2 pcs (3P) KT8PBH-3
High 200mm 4 pcs (4P) KT8PBH-4
Field installation
IP54 door protection Catalog number
T8 Protective cover KE6DC
Field installation
Vertical terminals Catalog number
Set of six KT82500VR-6
T8 Rear Vertical Terminals (2)
Set of eight KT82500VR-8
17
Field installation
Cable terminals Wire size
Catalog number
1/0-750 kcmil (4) K8TL
T8 Mechanical Lugs (set of 3)
1/0-750 kcmil (6) K8TM
17
Introduction Weights
Thanks to its experience with Tmax UL, T1 - 3.2 lbs.
ABB is proposing a complete range of T4 - 6.18 lbs.
products in accordance to UL489B, a T5 - 8.55 lbs.
new standard, whose requirements cover T6 - 20.9 lbs.
molded case circuit breakers and molded T7 - 24.25 lbs.
case switches rated up to 1000V DC, in- Accessories
tended for use with photovoltaic systems.
Standard Tmax accessories are able to work
A complete range of MCCB and MCS is
available up to 1000A for use at 1000V
with all UL 489B units. 17
DC, complete with jumpers for connection Jumpers come standard with all breakers in
of poles in series. either all poles in series or 2+1 or 2+2.
17
T4 - 200A Frame TMA, Thermal magnetic adjustable T1-D 100A Molded case switch
Catalog Catalog
IC at 1000VDC Rating Lugs Poles in Series Rating Lugs Poles in Series
number number
2+1 T4PB040TL 2+2 T1PB100DL-4
3kA 40A Yes 100A Yes
3 T4PA040TL 4 T1PA100DL-4
2+1 T4PB050TL
3kA 50A Yes
3 T4PA050TL
2+1 T4PB080TL
3kA 80A Yes T4-D 200A Molded case switch
3 T4PA080TL
Catalog
2+1 T4PB100TL Rating Lugs Poles in Series
number
3kA 100A Yes
3 T4PA100TL 2+1 T4PB200DL
2+1 T4PB125TL 200A Yes
3kA 125A Yes 3 T4PA200DL
3 T4PA125TL
2+1 T4PB150TL
3kA 150A Yes T5-D 400A Molded case switch
3 T4PA150TL
2+1 T4PB200TL Catalog
Rating Lugs Poles in Series
3kA 200A Yes number
3 T4PA200TL
2+1 T5PB400DL
400A Yes
3 T5PA400DL
2+1 T5PB400DW
T5 - 400A Frame TMA, Thermal magnetic adjustable 400A No
3 T5PA400DW
Catalog
IC at 1000VDC Rating Lugs Poles in Series
number
T6-D 800A Frame molded case switch
2+1 T5PB400TL
5kA 400A Yes Rating Lugs Poles in Series
Catalog
3 T5PA400TL number
2+1 T5PB400TW 2+2 T6PB600DL-4
5kA 400A No 600A Yes
3 T5PA400TW 4 T6PA600DL-4
2+2 T6PB800DW-4
800A No
4 T6PA800DW-4
T6 - 800A Frame TMA, Thermal magnetic adjustable
Catalog
IC at 1000VDC Rating Lugs Poles in Series
number
T7-D 1000A Molded case switch
2+2 T6PB600TL-4
10kA 600A Yes Rating Lugs Poles in Series
Catalog
4 T6PA600TL-4 number
2+2 T6PB800TW-4 2+2 T7MPB1000DL-4
10kA 800A No 1000A Yes
4 T6PA800TW-4 4 T7MPA1000DL-4
T1-D
Catalog
Description Rating Poles in Series
number
JUMPER KIT T1PV 100A 4P 2+2PS LUG UL 2+2 KT1PB100-L
100A
JUMPER KIT T1PV 100A 4P 4PS LUG UL 4 KT1PA100-L
T4-D
Catalog
Description Rating Poles in Series
number
JUMPER KIT T4PV 100A 3P 2+1PS LUG UL 2+1 KT4PB100-L
100A
JUMPER KIT T4PV 100A 3P 3PS LUG UL 3 KT4PA100-L
JUMPER KIT T4PV 200A 3P 2+1PS LUG UL 2+1 KT4PB200-L
200A
JUMPER KIT T4PV 200A 3P 3PS LUG UL 3 KT4PA200-L
T5-D
Catalog
Description Rating Poles in Series
number
JUMPER KIT T5PV 400A 3P 2+1PS LUG UL 2+1 KT5PB400-L
JUMPER KIT T5PV 400A 3P 3PS LUG UL 3 KT5PA400-L
400A
JUMPER KIT T5PV 400A 3P 2+1PS BUS UL 2+1 KT5PB400-W
JUMPER KIT T5PV 400A 3P 3PS BUS UL 3 KT5PA400-W
T6-D
Catalog
Description Rating Poles in Series
number
JUMPER KIT T6PV 600A 4P 2+2PS LUG UL 2+2 KT6PB600-L
600A
JUMPER KIT T6PV 600A 4P 4PS LUG UL 4 KT6PA600-L
JUMPER KIT T6PV 800A 4P 2+2PS BUS UL 2+2 KT6PB800-W
800A
JUMPER KIT T6PV 800A 4P 4PS BUS UL 4 KT6PA800-W
T7-D
17 Description Rating Poles in Series
Catalog
number
JUMPER KIT T7PV 1000A 4P 2+2PS LUG UL 2+2 KT7PB1000-L
1000A
JUMPER KIT T7PV 1000A 4P 4PS LUG UL 4 KT7PA1000-L
NOTE: See pages 17.71-17.83 for additional electrical/mechanical accessories
1 For factory installation add suffix given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for field installation.
Included when
Fixed Mount 2 under voltage factory KTS3C-SU
installed
Ts3
Included when under
Plug-In/Draw-out 2 voltage factory KTS3C-SUP
installed
1 For factory installation add suffix given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for field installation.
KTS3AS
17
1 For factory installation add suffix to end of breaker part number per accessory format .
2 Not compatible for T2 with PR221DS trip unit.
3 Must be ordered separately for field installation.
Electrical operators
Allows remote opening and closing of circuit breaker
Catalog
Frame size Voltage
number
Solenoid operator
48 - 60VDC KT3M1
T1-T3
110 - 250VAC/DC KT3M2
KTS3M2
External units
Test and configuration unit 3 PR010/T
Trip coil test-all Tmax electronic trip unit except PR33* K7TUT
External Bluetooth communication module 1 BT030
Includes diagnostic software for Modbus / Bluetooth networks
Battery power supply unit 1 PR030/B
Not suitable for UL applications.
T7 - Allows remote opening when used with PR330/D-M and shunt trip
T7M - Allows remote opening and closing when used with PR330//D-M. shunt trip and closing coil
Undervoltage
Power consumption during permanent operation
Voltage T1,T2,T3 Ts3 T4, T5, T6 T7
AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)
17 24 VAC/DC - - 6 3 - - 3.5 3.5
2430 VAC/DC 1.5 1.5 - - 6 3 - -
30 VAC/DC - - - - - - 3.5 3.5
48 VAC/DC 1 1 6 3 6 3 - -
60 VAV/DC 1 1 - - 6 3 - -
110120 VAC/DC - - 6 - - - 3.5 3.5
120127 VAC/DC - - - - - - 3.5 3.5
110127 VAC 110125 VDC 2 2 - - 6 3 - -
220240 VAC/DC - - - - - - 3.5 3.5
220240 VAC 220250 VDC 2.5 2.5 - 3 6 3 - -
220250 VAC - - 6 - - - - -
240250 VAC/DC - - - - - - 3.5 3.5
380400 VAC - - - - - - 3.5 -
380440 VAC 3 - - - 6 - - -
415 - 440 VAC - - - - - - 3.5 -
480525 VAC 4 - - - 6 - - -
480 VAC - - 6 - - - - -
Opening Time (ms) 15 15 18 18 25 25 25 25
17
Rear terminals 1
Catalog number Catalog number
Frame
(set of 3) (set of 4)
T2 KT2R-3 KT2R-4
T3 KT3R-3 KT3R-4 17
KT2R-3
T4 KT4R-3 KT4R-4
T5 KT5R-3 KT5R-4
T6 KT6R-3 KT6R-4
T7 KT7R-3 KT7R-4
T5, 400A
T5 400A 3 pole with extended front terminal KT5PFEF
T5 400A 3 pole with rear horizontal terminal KT5PMK KT5PFHR
T5 400A 3 pole with rear vertical terminal KT5PFVR
KT4PFVR
Adaptors, T4-T6
Required when adding accessories to plug-in or drawout breakers
Catalog
Adaptors
number
KT4PMK (on back of 1 form C plus 1 BA KT5ADP-6
breaker)
Shunt trip/UVR KT5ADP-5
17
Stored energy operator KT5ADP-10
Stored energy operator plus shunt trip/UVR KT5ADP-10
3 form C plus 1BA KT5ADP-12
Testing extension, T4 - T6
Catalog
Extension
number
5 pin for blank tests w/service release KT5EXT-5
6 pin for blank tests w/aux contacts (1+1)
KE5EXT-6
service and residual current releases
10 pin for blank tests w/motor operator and
KT5EXT-10
early contacts
12 pin for blank tests w/aux contacts (3+1) KT5EXT-12
1 Plug connectors (T2-T3), Adaptors (T4-T5), required when adding accessories to plug-in breakers.
Draw-out kits 1
Catalog number Catalog Number
Item
Adaptor moving part Fixed part
Ts3 3 pole with front terminals KTS3WFF 3
KTS3WMK
Ts3 3 pole with rear terminals KTS3WFR 3
T4 3 pole with extended front terminal KT4WFEF
T4 3 pole with rear horizontal terminals KT4WMK KT4WFHR
T4 3 pole with rear vertical terminals KT4WFVR
T5 3 pole with extended front terminal KT5WFEF
T5 3 pole with rear horizontal terminal KT5WMK KT5WFHR
T5 3 pole with rear vertical terminal KT5WFVR
T5 3 pole with extended front terminal, 600A KT56WFEF
T5 3 pole with rear horizontal terminal, 600A KT56WMK KT56WFHR
KT5WFVR T5 3 pole with rear vertical terminal, 600A KT56WFVR
T6 3 pole with extended front terminal KT6WFEF 3
T6 3 pole with rear horizontal terminal KT6WMK KT6WFHR 3
T6 3 pole with rear vertical terminal KT6WFVR
KT4WMK (on back of T7 3 pole with horizontal/vertical terminals KT7XWMK KT7WFHR 2
breaker)
Adaptors T4-T6
Required when adding accessories to plug-in or drawout breakers
Catalog
Adaptors
number
1 form C plus 1 BA KT5ADP-6
Shunt trip/UVR KT5ADP-5
Stored energy operator KT5ADP-10
Stored energy operator plus shunt trip/UVR KT5ADP-10
3 form C plus 1BA KT5ADP-12
1 Adaptors (T4-T6), Sliding contact blocks (T7) required when adding accessories to draw-out breakers.
2 Comes standard with horizontal terminals field convertible to vertical
3 IEC
Mechanical interlocks
T1-T3 Catalog Number
Sliding bar interlock-front mounted (2 Breakers) KT3MIF2
Sliding bar interlock-front mounted (3 Breakers) KT3MIF3
T3
Rear Interlock-horizontal KT3MI-H
Rear Interlock-vertical KT3MI-V
TS3
Horizontal KTS3MI-H
Vertical KTS3MI-V
KT3MIF2 T4-T5 1
Interlock frame
Mechanical Interlock frame-horizontal KT5MIR-HB
Mechanical Interlock frame-vertical KT5MIR-VB
Plate type
A T4 (F-P-W) T4 (F-P-W) KT5MIR-PA
B T4 (F-P-W) T5 400 (F-P-W) OR T5 600 (F) KT5MIR-PB
C T4 (F-P-W) T5 600 (P-W) KT5MIR-PC
D T5 (F-P-W) T5 400 (F-P-W) OR 630 (F) KT5MIR-PD
E T4 (F-P-W) T5 600 (P-W) KT5MIR-PE
F T4 (F-P-W) T5 600 (P-W) KT5MIR-PF
T6
Horizontal KT6MI-H
Vertical KT6MI-V
T7 2
Cable T7-X1 KT7XMLC
Mech. interlock plate-fixed KT7XMLPF
Mech. interlock plate-draw-out KT7XMLPW
1 T4-T5 Complete assembly consists of one interlock frame and one plate.
2 To interlock two circuit breakers, you have to order a cable kit and two plates.
T1 3 pole
T1 Single pole
17
83
78
T2 2 & 3 pole 90
30 30 70
9.38
Y
76.2
53.25
65
17
X X
181
130
106.5
45
>3 <2
103
T3 2 & 3 pole
17
17
Caption
17
3 POLES 4 POLES
Caption
17
3 POLES 4 POLES
3 POLES 4 POLES
17
17
17
17
17
17
17
17
17
17