TS-63000
Temperature Sensor and Transducers
Product Bulletin
Different length of tubes and wells for duct and immersion applications
Senses the temperature at the desired location
For immersion applications, well can be mounted before duct sensor is mounted
Easy installation and servicing
Application
The TS-6300 are designed for measuring temperature in gaseous media of heating/cooling and air conditioning systems.
In combination with the thermo-well the sensor are suitable for measuring temperature in liquid fluids.
The TS-6300 series of temperature sensors provide, depending on the selected models:
0...10 Vdc voltage output
NTC K2 resistance signal
NTC K10 resistance signal
Pt100 resistance signal (4 wires)
Pt1000 resistance signal
The various TS-6300 output versions can be connected to the following Johnson Controls controllers:
Metasys
System 9100 series
TC-8900 series
TUC03 series
2
PB_TS-63000_12 2013
Ordering Codes
3
PB_TS-63000_12 2013
Accessories
4
PB_TS-63000_12 2013
Mounting
The TS-63000 can be mounted in virtually any position.
For mounting follow the instructions below:
Locate the sensors, where they will be exposed to representative conditions.
Avoid non-representative air draughts, direct sunlight, etc.
For strap-on models use a thermal conductive paste between well or pipe and sensor to improve reaction times.
The sensor should not be exposed to direct radiation (lamps, radiators, etc.) or to the sun, since it would lead to
incorrect measurement.
X
<6D 6D
X
3D
<6D
5
PB_TS-63000_12 2013
Mounting Method
1 2
7 mm
Ceiling Mount Model (TS-63x0C): 3
6
PB_TS-63000_12 2013
Wiring instructions
For wiring follow the instructions below:
All wiring must be in accordance with local regulations and national rules.
Do not attempt field repairs. If the transmitter is not operating properly, even though it is wired correctly, it should be
replaced.
t
4 wires PT100
The 4-wire, 100 ohm, platinum RTD is used where improved measurement accuracy is desired.
The 4-wire design allows for a Kelvin-connection of the sensor to reduce the error caused by lead wire resistance and
contact resistance (see Figure 6). A current source is input to terminals I+ and I-, to provide a known current through
the sensing element. The voltage drop across the sensing element is measured at U+ and U-. The measured voltage
is a function of the sensor resistance so that the measured temperature may be determined. The voltage measurement
circuit should be high impedance to keep the current through U+ and U- to a minimum so that the voltage drop across the
measurement leads is insignificant.
The TS-6350x PT100 4-wire sensor models are not designed for use with Johnson Controls controllers or any specific
third-party controller. Application of these products is at the customers discretion.
Note: The RTD sensor is not polarity sensitive. Terminal block labeling is for customer wiring convenience. Terminal
markings plus (+) and minus (-) identify paired wires and the pairs are interchangeable. Terminals U and I are
equivalent and are interchangeable.
I+ R Lead
U+ R Lead
t
V
U- R Lead
I- R Lead
7
PB_TS-63000_12 2013
Resistance Tables
8
PB_TS-63000_12 2013
9
PB_TS-63000_12 2013
Dimensions (mm)
95 mm 85 mm
79.3 mm 95 mm 85 mm
5 mm 79.3 mm
53.2 mm 5 mm
53.2 mm
20 - 90 mm
95 mm 85 mm
95 mm
79.3 mm
79.3 mm
5 mm 5 mm
53.2 mm
53.2 mm
2m
85 mm
Outdoor Remote
50 mm
6.0 mm
1.5 m
Cable
Cable
10
PB_TS-63000_12 2013
7 7 7 7
R 1/2
32
50
55
40
19
50
8
.5
9 9
11
PB_TS-63000_12 2013
Technical Specifications
K2 NTC K10NTC
0...10Vdc Thermistor Thermistor PT100 RTD PT1000 RTD
Power Supply 15 Vdc 10% --- --- --- ---
24 Vac 20%
24 Vdc 15%
Output Signal 0...10 Vdc 2252 ohm @ 25 C 10 kohm @ 25 C, 100 ohm @ 0 C, 1000 ohm @ 0 C,
Johnson Controls per EN 60751 per EN 60751
Type II
Output Accuracy 1% FS or 0.5 C 0.2 C 0.5 C EN 60751, EN 60751,
( 0.36 F), ( 0.9 F), Class A, Class A,
from 0 to 70 C from 0 to 70 C (0.15 + 0.002 * | T C |) (0.15 + 0.002 * | T C |)
- Measurement Current* 0.1 mA Recommended 0.1 mA Recommended 1 mA Recommended 0.3 mA Recommended
5 mA Maximum 1 mA Maximum 2 mA Maximum 5 mA Maximum 2 mA Maximum
Max Operating Temperature
for Enclosure w/PWA
- Operating Temperature -40 to 70 C (-40 to 158 F)
- Storage Temperature -40 to 70 C (-40 to 158 F)
- Transit Temperature -40 to 70 C (-40 to 158 F)
Humidity
- Operating Humidity 5 % to 95 %RH, non-condensing, 30 C (86 F) Max Dew Point
Storage Conditions
- Storage Humidity 5 % to 95 %RH, non-condensing, 30 C (86 F) Max Dew Point
- Transit 5 % to 95 %RH, non-condensing, 30 C (86 F) Max Dew Point
Protection**
- Protection Class IP54 according to IEC 60529
Exceptions: TS-63x0K Cable or Remote Sensor (without enclosure), probe: IP67
Material
- Housing Polycarbonate, Lexan EXL9330
- Probe Stainless Steel 304
- Cable sensor probe Stainless Steel 304 or 316
Color
- Housing Blue, PMS 300
Terminations
- Terminal Type Screw-clamp type terminal block
- Max Wire Size 1 x 1.5 mm2 (16 AWG)
* Measurement error at Maximum current may excessive from self heating.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Building Efficiency
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners.
Copyright 2013 Johnson Controls, Inc. All rights reserved. Any unauthorized use or copying is strictly prohibited.