AN708 Series Intelligent Temperature Controller/ Adjustor User's Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

AN708 Se ri es Int e l li ge nt Adj ust or

AN708 Series Intelligent Temperature Controller/ Adjustor


Users Manual

Measuring Accuracy:0.3%F.S

KKAN708E01-A/1-1

1.Code Illustration
AN708

Input and communication0:One loop input without communication


8:One loop input with RS485 communication (Please indicate when order)
Alarm3: Two alarm output 2:One alarm output 1:Without alarm output
One more alarm will be added when not using Heating or cooling control
Output functionR:Relay output C:420mA current output Q:Logic output
Dimension (mm)4:48W48H 6:48W96H 7:72W72H 8:96W48H 9:96W96H
16:80W160H 80:160W80H
AN708 Series intelligent temperature controller /adjustor

2.Code Illurstration
AN708-4 series product can be ordered for 4--20mA input

Code
AN708 - 4- R20
AN708- 4- C20

Size 48*48

AN708- 4- Q20
AN708- 4- R18

Other size

OUT 1 or OUT 2

Alarm output

Alarm

RS485

Relay output

without

Relay output

without

SSR output

Relay output

without

Relay output

Relay output

without

RS485

Relay output
4-20mA current output

AN708- 4- C18

4-20mA current output

Relay output

without

RS485

AN708- 4- Q18

SSR output

Relay output

without

RS485

AN708 - - R30

Relay output

Relay output

without

AN708- - C30

4-20mA current output

Relay output

without

AN708- - Q30

SSR output

Relay output

without

AN708- - R38

Relay output

Relay output

RS485

AN708- - C38

4-20mA current output

Relay output

RS485

AN708- - Q38

SSR output

Relay output

RS485

5
Can be worked just under heating-cooling control(OT=3); under other control,
worked as alarm 3 (size:48*48 worked as alarm 2)
5
1
Alarm output: Relay output capacity: 1A/250Vac

3. Main Technical Parameters


3. 1 Whole controller parameters

RTU

KKAN708E01-A/1-2

3.2. Input signal table


Symbol
0

-501300

100K

-501200

100K

-501000

100K

-50400

100K

6001800

100K

-101700

100K

-101600

100K

-501200

100K

-199.9850.0

0.1

0.2mA)

10

-199.9500.0

0.1

0.2mA)

11

-50.0150.0

0.1

0.2mA)

12

-50.0150.0

0.1

0.2mA)

13

050mV

0.01%FS

100K

14

420mA

0.01%FS

15

010V

0.01%FS

100K

16

0400

0.01%FS

0.2mA

110

4. Panel Indication
SET function key
OUT1 Indication Lamp
OUT2 Indication Lamp

OUT1

AL1 Indication Lamp


AL2 Indication Lamp
AL3 Indication Lamp
AT:Auto-tuning Indication Lamp

AL1

SET

Shift function key

OUT2

Increase Key

AL2
AL3

Decrease key

AT

PV Value
SV set value Display measured value or parameter code
Display setted value or parameter code

5.Panel Key Operation

KKAN708E01-A/1-3

Temperature unit switch

OUT1 control cycle: when current output ,the cycle is 0; SSR output,
it is 1; Relay output it is more than 4
(it is more than 4 )

KKAN708E01-A/1-4

-50

60
0: unit of celsius 1unit of fahrenheit

0/1

Formula
0

HY

High limit absolute value alarm

AL
1

Low limit absolute value alarm

Alarm:PV<AL
Cancel:PVAL-HY

HY
AL

Temperature drops down

HY
SV+AL

High limit deviation value alarm

SV
3

Temperature rises

Low limit deviation value alarm

Temperature drops down

Alarm:PV>AL
Cancel:PVAL-HY

Temperature rises

HY
SV-AL

Alarm:PV>AL +SV
Cancel:PVSV+AL-HY
Alarm:PV<SV-AL
Cancel:PVSV-AL+HY

SV

8.
A

G +0.5
-0

C
E

J +0.5
-0
B

Code

H(Minimun)

K(Minimun)

48

101

10

91

45

45.5

25

45.5

25

48

96

100

94

91

45.5

25

91.5

25

72

72

100

10

90

67.5

68

25

68

25
25

4:(48*48)

48

6:(96*48)
7:(72*72)

8:(48*96)

96

48

100

94

45

91.5

25

45.5

9:(96*96)

96

96

101

10

91

90.5

91

25

91

25

10

92

76

154

30

76.5

30

10

92

153.5

76.5

30

154

30

80:(80*160)

160

16:(160*80)

80

Note

80

102

160
102
unit(mm) tolerance+0.5%

9
Series

AN708 series
CodeAN708-7
Accuracy0.3%FS3digits 25
Temperature excursion:0.01%FS/

KKAN708E01-A/1-5

AN708 series temperature controller


CodeAN708-9
Accuracy0.3%FS3digits 25
Temperature excursion:0.01%FS/

AN708 series temperature controller


CodeAN708-16/80
Accuracy0.3%FS3digits 25
series temperature controller:0.01%FS/

AN708 series temperature controller


CodeAN708-6 / AN708-8
Accuracy0.3%FS3digits 25
series temperature controller:0.01%FS/

Note:Please subject to the connecting drawing on the actual product if any changes.

10. Simple Problem Shooting


Dispaly Message

Reasons & Solving Methods

Display HHHH

Input disconnect or over upper limit. Please check input signal, FH value and ambient working temperature.

Display LLLL

Input disconnect or under lower limit. Please check input signal, FH value and ambient working temperature.

11.Communication
AN708 series adjustor follow Modbus RTU communication protocol, and it can run RS485 half-duplex communication.Read
function code is 0x03, write function code is 0x10, 16-bit CRC checking is applied. The meter can not return error message.

Data frame format


Start bit

Data bit

Stop bit

Check bit

None

11.1. Read Multiple Registers


For example: The host computer read the float number AL1 (The value of Alarm 1 is 14.5).The address code of AL1 is 0x0000,
for AL1 is float number (4bits), it will occupy 2 data register. Reference IEEE-574 standard the hexadecimal 16 result of the
decimal float number is 0x41766666.
Request from the master unit (Read Multiple Registers)

Meter address

Function code

High bit of
start address

0x01

0x03

0x00

4
Low bit of
start address

0x02

High bit of
data

Low bit of
data

0x00

0x04

Low bit of CRC code High bit of CRC code

0xE5

0xC9

KKAN708E01-A/1-6

Correct answer from slave unit (Read Multiple Registers)

Meter address

Function code

0x01

0x03

Data byte length

0x04

Data 1
high byte

Data 1
low bit

Data 2
high bit

Data 2
low bit

0x41

0x76

0x66

0x66

9
High bit of
CRC code

Low bit of
CRC code

0xE2

0xF4

11.2. Write Multiple Registers


For example: The host computer read the float number (setting value 600) ,
The address code for SV is 0x0000, for SV is float number (4bits), it will occupy 2 data register. Referring to IEEE-574
standard the hexadecimal 16 result of the decimal float number is 0x44160000.
Request from the master unit (Write Multiple Registers)
2

Function High bit of Low bit of High bit of Low bit of Data
Unit
data
start
data
start
Length
address Code
length
address

0x01

0x00

0x10

address

length

0x00

0x00

0x02

10

11

High bit Low bit High bit Low bit


of data 1 of data 1 of data 2 of data 2

0x04

0x44

0x00

0x16

0x00

12

13

Low bit High bit


of CRC of CRC
0xFD

0xFC

Correct answer from slave unit (Write Multiple Registers)


1

Meter
address

Function
Code

Start address
of high 8 bit

Start address
of low 8 bit

Data length
high bit

0x10

0x00

0x00

0x00

0x01

Data length
low bit

0x02

Low bit
of CRC

High bit
of CRC

0x41

0xC8

AN708 Series table reference address


Code

Reference
address

0x0000

Setting Value SV

R/W

0x0002

Alarm value AL1

R/W

0x0004

Alarm value AL2

R/W

0x0006

Alarm value AL3

R/W

0x0008

Correct value PS

R/W

0x000A

Proportion rate P

R/W

0x000C

Integral time I

R/W

0x000E

Differentia lD

R/W

0x0010

ON/OFF Control Hysteresis HY

R/W

0x0012

Heating & cooling dead district DB

R/W

10

0x0014

Alarm 1 Hysteresis HY1

R/W

11

0x0016

Alarm 2 Hysteresis HY2

R/W

12

0x0018

Alarm 2 Hysteresis HY3

R/W

13

0x001A

Control output Lo OLL

R/W

14

0x001C

Control output Hi OLH

R/W

15

0x001E

Display Low limit FL

R/W

16

0x0020

Display High limit FH

R/W

17

0x0022

Low limit value of analog

R/W

18

0x0024

High limit value of analog

R/W

19

0x0026

Measuring value

Number of Variable

Data
Length

Read & Write


allow

Remark

KKAN708E01-A/1-7

Code

Reference
address

Number of Variable

Data
Length

20

0x0028

Manualswitch MAN

21

0x002A

Lock LCK

22

0x002C

Control output OT

R/W

23

0x002E

Heating control Turn CT

R/W

24

0x0030

Cooling proportion C_P

R/W

25

0x0032

Cooling control Turn C_CT

R/W

26

0x0034

Alarm 1 mode AD1

R/W

Note1

27

0x0036

Alarm 2 mode AD2

R/W

Note1

28

0x0038

Alarm 2 mode AD2

R/W

Note1

29

0x003A

Input signal select INP

R/W

Note2

30

0x003C

Decimal DP

31

0x003E

Filter FT

32

0x0040

Baud rate BAD

33

0x0042

Address ADD

Read & Write


allow

Remark

Note3

RRead only R/WRead/Write


For Parameter Setting Range , please refer to users manual

Note 1Please refer to alarm parameter form


Note 2Please refer to input Parameter form
Note 3Please refer to below table
Baud rate BAD

4.8K

9.6K

Data value

16 digit CRC verify program


unsigned int Get_CRC(uchar *pBuf, uchar num)
{
unsigned i,j;
unsigned int wCrc = 0xFFFF;
for(i=0; i<num; i++)
{
wCrc ^= (unsigned int)(pBuf[i]);
for(j=0; j<8; j++)
{
if(wCrc & 1){wCrc >>= 1; wCrc ^= 0xA001; }
else
wCrc >>= 1;
}
}
return wCrc;
}

KKAN708E01-A/1-8