Centrifugal, Field-Erected - Tech Guide - Panel
Centrifugal, Field-Erected - Tech Guide - Panel
Centrifugal, Field-Erected - Tech Guide - Panel
JOHNSON CONTROLS
Overview
The standard TITAN chiller control system is based on an Allen-Bradley CompactLogix 1769-L35E programmable logic
controller (PLC), with an Allen-Bradley PanelView Plus 1250 color graphics display and membrane keypad for operator
interface. The control panel and field installed electro-pneumatic devices provide all necessary controls and control logic
to provide manual operation, automatic operation, pneumatic capacity control and safety protection of the chiller unit.
Alarm annunciation is provided by alarm indicators, on the color TFT graphic screens. Also an alarm history screen is
provided which shows the most recent alarms, with the time and date of occurrence. Trip status screens are provided
which show the values of analog inputs at the time of the last five chiller safety shutdowns. The time and date of the
shutdown are also recorded and shown.
Separate Pushbuttons are provided on the face of the control panel for Chiller Start, Stop, Reset and Emergency Stop.
All other functions are software controlled through the Panelview Operator Interface.
JOHNSON CONTROLS
Hardware
All controls are arranged for easy access. Wiring is color coded black (120VAC control circuits), white (neutral), and green
(ground). Wiring enclosed in shielded cables are color coded per the wiring diagram. External (field) wiring connections
are made to clearly marked terminal strips and the Allen-Bradley Flex I/O terminal blocks. Removable plates are provided
on the top and bottom of the enclosure for the field wiring conduit connections. The electrical installation contractor must
determine the locations and size of the conduit connections. Control voltage internal panel wiring is done with MTW
16 AWG wire minimum. The panel will receive a 60 amp 120 volt 60 Hertz power supply from a 5.0 KVA transformer in
the motor control center (MCC) for the oil heaters and controls. The pneumatic controls require 4-6 SCFM of clean dry
filtered instrument air at 80 to 100 psig pressure, taken to a common point at the PRV actuator.
The control panel contains all necessary controls and control logic to provide stand-alone, automatic start-up, fail-safe
fully automatic operation, PID capacity control and safety protection of the compressor, speed increaser, electric motor,
evaporator and condenser. It also provides for automatic pre-lube and post-lube operation of the speed increaser gear
and compressor auxiliary oil pumps (AOP); and operation of the AOPs during any low pressure lube condition. Controls
are also included for automatic control of compressor capacity to limit maximum motor power consumption, manually
adjustable 100 to 40% of chiller capacity.
All chiller operating values contained in the Input/Output list shown later in this section. All temperature and pressure
displays are in English (or metric) units of measure. All points are electronically monitored from locally mounted RTDs
with transmitters and pressure transducers.
The control console is factory (internally) wired in an upright front panel display style, NEMA 12 enclosure. The panel
is fabricated of 10-gauge steel and includes a full height front access door. The panel enclosure is painted ANSI light
gray on the outside, and gloss white on interior surfaces. Included is an Emergency Stop button bypassing all controls.
It mounts on the front of the panel, together with the display. A separate, hardwired condenser refrigerant high-pressure
cutout, remotely mounted at the compressor, is provided in accordance with ANSI/ASHRAE Standard 15 Safety Code
requirements.
JOHNSON CONTROLS
Graphics Interface
The TFT display features graphic animated display of the chiller, chiller subsystems and system parameters, allowing
the presentation of several operating parameters at once.
During startup, operation and shutdown, the system will display vital information available at any time. The locations
of various chiller parameters are clearly marked and instructions for specific operation are provided on many of the
screens.
The main status indicator bar at the top of the screen will display the SYSTEM STATUS with the following messages:
READY TO START
REMOTE START ENABLED
START / PRELUBE = XXX sec
REM START / PRELUBE = XXX sec
SYSTEM RUNNING
SYSTEM COASTDOWN = XXX sec
SYSTEM TRIPPED
ANTI-RECYCLE = XX:XX
Controlled Stop
Remote Lockout
FAULT / ERROR
On (enganged) and Off (disengaged) signals are represented by LED symbols. A red LED symbol is ON
a grey LED symbol is OFF
, and
Running Pumps are shown as RED, and pumps not running are shown as GREEN.
Pre-Trip Alarm (Yellow Blinking _A_) and Trip (Red Blinking _T_) indicators (other than described above) appear
adjacent to the descriptive text of the measurement parameter whenever applicable.
JOHNSON CONTROLS
The measurement parameter text (_PSIG_, _F_ ) changes to YELLOW blinking if the analog input signal goes out
of range and will remain in this state until the RESET pushbutton is pushed after the input signal returns to normal.
The Pre-Trip Alarm indicator will automatically be reset if the abnormal condition progresses to the trip setpoint.
The Trip Alarm indicator will remain in the alarm state until the RESET pushbutton is pressed after the conditions have
returned to normal.
Graphical, animated screens provide a means of data display and service for various system components. Screens
indicate all aspects of operation and sensor data pertaining to the particular component depicted.
At the top of each main screen is displayed the system status, present date and time, local or remote control source
and system access level. Sub-screens may also be available for some system components, providing additional data
access. Screens are selected by selecting the appropriate tabs on the sides of the display. Press the soft button corresponding to a particular screen tab.
JOHNSON CONTROLS
Protocol
Ethernet Indutrial Protocol www.ethernet-ip.org
Allen-Bradley DF1 Full Duplex
Modbus RTU Slave
Any protocol/media requirements not listed here must be called out on the factory order form.
Available protocols will be implemented with a Johnson Controls eLink module* or Prolinx gateway** where applicable:
Modbus RTU over RS-485**
Modbus over TCP/IP**
BACnet MS/TP*
BACnet/IP*
LONworks*
Profibus**
ControlNet
Allen-Bradley DH-485
Check appropriate protocol and include this document attached to the Factory Order Form
All communication interface wiring and hardware, which is required external to the chiller control panel, will be supplied
JOHNSON CONTROLS
JOHNSON CONTROLS
INPUT/OUTPUT LIST
INPUTS
Device
Tag#
Description
FT-100
4-20 mA DC1,6
FT-102
4-20 mA DC1,6
JT-160
4-20 mA DC5
from Starter
LT-114
4-20 mA DC
LT-116
4-20 mA DC
PT-111
4-20 mA DC
PT-113
4-20 mA DC
Signal
Remarks
ANALOG INPUTS:
PT-116
4-20 mA DC
PT-140
4-20 mA DC
PT-143
4-20 mA DC
PT-144
4-20 mA DC
PT-146
4-20 mA DC
PT-150
4-20 mA DC
PT-156
4-20 mA DC
PT-180
4-20 mA DC
TT-100
4-20 mA DC
TT-101
4-20 mA DC
TT-102
4-20 mA DC
TT-103
4-20 mA DC
TT-111
4-20 mA DC
TT-113
4-20 mA DC
TT-114
4-20 mA DC
TT-120
4-20 mA DC
TT-115
4-20 mA DC
TT-142
4-20 mA DC
TT-147
4-20 mA DC
TT-150
4-20 mA DC
TT-151
4-20 mA DC
TT-152
4-20 mA DC
TT-153
4-20 mA DC
TT-154
4-20 mA DC
TT-161
4-20 mA DC
TT-162
4-20 mA DC
JOHNSON CONTROLS
10
Device
Tag#
Description
M1R
120 VAC
from starter
M2
120 VAC
from starter
M3
120 VAC
from starter
MPDA
120 VAC
from starter
LSL-120
120 VAC
LSL-143
120 VAC
PSHH-113A
120 VAC 2
PDSLL-140A
120 VAC 2
PDSLL-101A
120 VAC 2
PDSLL-102A
120 VAC 2
TSHH-147A
120 VAC 2
120 VAC
120 VAC
Reset Push-button
120 VAC
Signal
Remarks
DISCRETE INPUTS:
JOHNSON CONTROLS
OUTPUTS:
ANALOG OUTPUTS:
Device
Tag #
LY-114
Description
Signal
4-20 ma
LY-116
4-20 ma
PDY-116
4-20 ma
TY-100A
4-20 ma
TY-100B
4-20 ma
Remarks
DISCRETE OUTPUTS:
CR
120 VAC
FCV-105
120 VAC
FCV-114
120 VAC
FCV-120
120 VAC
M2
120 VAC
M3
120 VAC
M5
120 VAC
M6
120 VAC
PCV-143B
120 VAC
R1
120 VAC
R2
120 VAC
R3
120 VAC
R4
120 VAC4
Dry contact
Dry contact
FOOT NOTES:
1 Installation methods must comply with industry and manufacturers requirements (particularly straight lengths up and downstream, coordinated
pipe wall thickness).
2 This input will also be hardwired to trip the chiller independent of the Allen-Bradley PLC trip output.
3 An Emergency stop pushbutton is provided on the front of the control panel which when pulled will stop the chiller, even in the event of a failure of
the Allen-Bradley PLC output.
4 This contact output is energized by an evaporator low pressure condition. The customer must establish chilled water flow through the chiller
when this contact is closed to prevent tube freeze-up. It is recommended that this contact be hardwired into the chilled water pump
motor starter control circuit.
5 Isolated Input
6. Optional Input (not necessarily a control or safety point)
JOHNSON CONTROLS
11