MCBs - Merlin Gerin
MCBs - Merlin Gerin
MCBs - Merlin Gerin
breakers
Product
Section
1
Page
10
11
12
14
15
16
20
DPN/C60/C120 auxiliaries
24
DPN/C60/C120 accessories
29
32
41
NG125 auxiliaries
46
NG125 accessories
50
52
55
56
57
Circuit breaker
Selection guide
Circuit breaker
Selection guide
DPN MCBs/RCBOs
DPN MCBs/RCBOs are available up to 40A, with a single phase
breaking capacity of 6kA. Both phase and neutral conductors are
encapsulated in a compact (18/36mm) unit making it ideal for
special applications where the neutral must be disconnected but
space is a constraint.
C60 MCBs/RCBOs
Forming the core part of the Merlin Gerin MCB offer, C60 MCBs
are available up to 63A, B, C or D curve with a breaking capacity
of 15kA. Accepting cables as large as 35mm2, C60 provides a
single or three phase compact solution for a wide range of
commercial or heavy industrial applications.
They may be connected to Isobar 4 pan assemblies or hard wired.
C120 MCBs/RCBOs
New
NG125 MCBs/RCBOs
The revolutionary new NG125 provides current rating up to 125A,
with breaking capacities of 25, 36 or 50kA, (50kA for motor
applications only). Suitable for use as an outgoer to final circuits
being fed from panel applications.
NG125 includes standard features such as:
Integral padlocking facility
Tripped indication
New
DPN
Miniature circuit breakers
Ratings 4 to 40A, breaking capacity 6kA
Applications
Protection and control of circuits against overloads and short circuits where
switching of the neutral is required.
DPN type B
19271
Rating
(A)
4
6
10
16
20
25
32
40
Part
No.
19249
19250
19252
19254
19255
19256
19257
19258
Width in 18mm
SP ways
1
1
1
1
1
1
1
1
DPN type C
Rating
(A)
1
2
4
6
10
16
20
25
32
40
Part
No.
19260
19261
19263
19264
19266
19268
19269
19270
19271
19272
Width in 18mm
SP ways
1
1
1
1
1
1
1
1
1
1
Installation
Technical data
Accessories:
Earth leakage DPNN:
Technical data:
10
DPN RCBO
Combined MCB/RCD
Application
Protection against the effects of earth leakage, overload and short circuit currents.
Technical data
19668
AC
Class
Type
Width
Sens.
in
(mA)
18mm
SP ways
N + 1P 2
30
N
1P
Rat.
(A)
Part No.
6
10
16
20
25
32
40
19661
19663
19665
19666
19667
19668
19669
Dimensions (mm)
RCBO
N 2
70
5
36
45
81
44
Type
No. of MCBs
Comb busbar
1P+N
13
1P+N
24
(bag of 2)
25mm2 insulated
connector (bag of 4)
Comb busbars
Part no.
14880
14890
14885
432
max.24 MCBs
Characteristics
235
max.13 MCBs
Clip-on markers
27
10
15
11
C60H
Miniature circuit breakers
Ratings 1 to 63A, breaking capacity 15kA
Installation
Technical data
12
C60H
Miniature circuit breakers
Ratings 1 to 63A, breaking capacity 15kA
C60HB type B (3 - 5In)
Applications
Protection and control of circuits against overloads
and short circuits.
In applications with general load characteristics.
Tripping characteristics: BS EN 60898 type B:
magnetic setting between 3 and 5 In.
Cable capacity:
2
1 - 25A = 25mm .
2
32 - 63A = 35mm .
Tightening torque:
25A = 2.5Nm.
32 - 63A = 3.5Nm.
1P
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
2P
101
102
104
106
110
116
120
125
132
140
150
163
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
3P
201
202
204
206
210
216
220
225
232
240
250
263
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
4P
301
302
304
306
310
316
320
325
332
340
350
363
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
C60HB
401
402
404
406
410
416
420
425
432
440
450
463
1P
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
2P
101
102
104
106
110
116
120
125
132
140
150
163
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
3P
201
202
204
206
210
216
220
225
232
240
250
263
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
C60HC
4P
301
302
304
306
310
316
320
325
332
340
350
363
24876
24877
24878
24879
24880
24881
24882
24883
24884
1P
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
2P
101
102
104
106
110
116
120
125
132
140
150
163
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
3P
201
202
204
206
210
216
220
225
232
240
250
263
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
C60HD
301
302
304
306
310
316
320
325
332
340
350
363
13
Vigi C60
Add on residual current device for use with C60 MCBs only
Applications
Clipped onto the side of any C60 MCB, add on Vigis
provide a high level of protection against earth fault in
addition to overload and short circuit protection
provided by the MCB alone.
Vigi
MCB
RCBO
25
63
63
63
010
030
100
300
Ratings
(A)
25
63
63
63
2
2
2
2
Sensitivity
(mA)
10
30
100
300
Ratings
Sensitivity
(A)
(mA)
MGV 63 030 4
63
30
MGV 63 300 4
63
300
Terminal screw shields available for Vigi RCDs.
See C60 accessories on page 29.
Cable capacity:
2 pole = 25mm2,
4 pole = 35mm2.
Note: Must not be used as the sole means of protection against direct contact with
live parts (BS 7671).
Dimensions: see page 155.
14
2 4
7
T
Width in
18mm SP ways
4
4
Specification:
Operating voltage:
Width in
18mm SP ways
2
2
2
2
2 4 68
C60HC32R30
Installation
Part No.
C60HC6R30
Ratings
(A)
6A 30mA
Curve
type
C
Class
AC
C60HC10R30
10A 30mA
AC
C60HC16R30
16A 30mA
AC
C60HC20R30
20A 30mA
AC
C60HC32R30
32A 30mA
AC
C60HC45R30
45A 30mA
AC
C60HC6R100
6A 100mA
AC
C60HC10R100
10A 100mA
AC
C60HC16R100
16A 100mA
AC
C60HC20R100
20A 100mA
AC
C60HC32R100
32A 100mA
AC
C60HC45R100
45A 100mA
AC
C60HC6RA10
6A 10mA
C60HC10RA10
10A 10mA
C60HC16RA10
16A 10mA
C60HC20RA10
20A 10mA
C60HC32RA10
32A 10mA
C60HC45RA10
45A 10mA
C60HC6RA30
6A 30mA
C60HC10RA30
10A 30mA
C60HC16RA30
16A 30mA
C60HC20RA30
20A 30mA
C60HC32RA30
32A 30mA
C60HC45RA30
45A 30mA
15
New
Technical data
16
Connection:
Flexible cables: 1.5 to 35mm2.
Rigid cables: 1 to 50mm2.
Terminals ensure:
Degree of protection IP2X.
Clamping of wide cross section cables.
Automatic guiding of cable into the correct
position.
Markers:
4 marker clips next to the upstream terminal.
Label holder on handle (2, 3 and 4 pole).
Degree of pollution: 3.
Degree of protection:
Open or surface mounted device: IP2X.
In a Pragma or Prisma enclosure: IP4X. (IPXXD).
B curve
C curve
D curve
New
B curve
BS EN60898 - BS EN 60947.2: 15kA
B curve C120H
1P
1
2
18404
2P
1
18415
3P
1
18426
4P
18437
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18394
18395
18396
18397
18398
18399
18400
18401
18402
18403
18404
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18405
18406
18407
18408
18409
18410
18411
18412
18413
18414
18415
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18416
18417
18418
18419
18420
18421
18422
18423
18424
18425
18426
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18427
18428
18429
18430
18431
18432
18433
18434
18435
18436
18437
Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
17
New
C curve
BS EN60898 - BS EN 60947.2: 15kA
C curve C120H
1P
1
2
18448
2P
1
18459
3P
1
18470
4P
18481
18
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18438
18439
18440
18441
18442
18443
18444
18445
18446
18447
18448
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18449
18450
18451
18452
18453
18454
18455
18456
18457
18458
18459
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18460
18461
18462
18463
18464
18465
18466
18467
18468
18469
18470
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18471
18472
18473
18474
18475
18476
18477
18478
18479
18480
18481
Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
New
D curve
BS EN60898 - BS EN 60947.2: 15kA
D curve C120H
1P
1
2
18492
2P
1
18503
3P
1
18514
4P
18525
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18482
18483
18484
18485
18486
18487
18488
18489
18490
18491
18492
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18493
18494
18495
18496
18497
18498
18499
18500
18501
18502
18503
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18504
18505
18506
18507
18508
18509
18510
18511
18512
18513
18514
Rating (A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18515
18516
18517
18518
18519
18520
18521
18522
18523
18524
18525
Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3
3
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
19
New
Trip sensitivity
AC class
Tripped by sinusoidal AC currents whether they
are quickly applied or rise slowly.
A class
A
class: ensures tripping with a DC
component current. Tripped by sinusoidal AC
currents as well as by pulsed DC currents
whether they are quickly applied or rise slowly.
Trip type
Instantaneous
Provides a trip upon reaching threshold (no intentional
time delay).
Selective s
2P
6.5 (3+3.5)
SI
4P
11 (6+5)
3P
500
4P
580
Weight (g):
2P
325
3P
9.5 (4.5+5)
20
New
3
T
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18563
18564
18544
18565
18545
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18566
18567
18546
18568
18547
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18569
18570
18548
18571
18549
Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5
2 4
18563
3P
1
5
T
Width in
18mm SP
ways
5
5
5
5
5
24 6
18546
4P
1
7
T
Width in
18mm SP
ways
5
5
5
5
5
2 4 68
18549
21
New
3
T
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
500 s
1000 s
18572
18573
18581
18574
18582
18583
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
500 s
1000 s
18575
18576
18584
18577
18585
18586
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
500 s
1000 s
18578
18579
18587
18580
18588
18589
2 4
Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5
3.5
18572
3P
1
5
T
2 4 6
Width in
18mm SP
ways
5
5
5
5
5
5
18584
4P
1
7
T
2 4 68
18589
22
Width in
18mm SP
ways
5
5
5
5
5
5
New
Vigi modules
si type, BS EN 61009
Class si C120 Vigi module
2P
1
3
T
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18591
18592
18556
18593
18557
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18594
18595
18558
18596
18559
Voltage
(V)
Sens.
(mA)
Part No.
230415
30
300
300 s
500
1000 s
18597
18598
18560
18599
18561
Width in
18mm SP
ways
3.5
3.5
3.5
3.5
3.5
2 4
18591
3P
1
5
T
Width in
18mm SP
ways
5
5
5
5
5
2 4 6
18558
4P
1
7
T
Width in
18mm SP
ways
5
5
5
5
5
2 4 68
18561
23
Electrical auxiliaries
For DPN, C60 and C120 MCBs
Applications
For the remote control and status indication of DPN, C60 or C120 MCBs.
Auxiliary combination
OF+SD/OF
auxiliary
contact
24
OF
auxiliary
contact
SD
fault indication
switch
Mx + OF, MN, MN s
MNx or MSU
auxiliary
Circuit
breaker
Electrical auxiliaries
For DPN, C60 and C120
MX + OF (shunt release and auxiliary contact)
U>
26946
New
14 12
Control
voltage
(V AC)
220...415
48...130
24
12
Disconnects
Part No.
Width in
18mm SP
(V DC)
ways
110...130 26946
1
48
26947
1
24
26948
1
12
26949
1
the MCB when a voltage is applied.
C2 C1
Control
voltage
(V AC)
220...240
Part No.
26979
Width in
18mm SP
ways
2
380...415
26980
Control
voltage
(V AC)
220...240
48
Part No.
Control
voltage
(V AC)
220...240
Part No.
26969
Width in
18mm SP
ways
2
380...415
26971
N L
26979
3P + N
U>>
N L1
L2 L3
Width in
18mm SP
(V DC)
ways
26960
1
26961
1
48
26962
1
220...240 Delayed s
26963
2
Disconnects the MCB when a voltage is removed.
D1 D2
26963
New
U<
26969
E1 E2
Ph to Ph
U<
E1 E2
L1 L2
25
Electrical auxiliaries
For DPN, C60 and C120
SD fault indicating switch
Part No.
26927
Width in
18mm SP
ways
0.5
Contact rating
94 92
91
26927
(V)
240V ac
415V ac
24V dc
48V dc
125V dc
(A)
6A
3A
6A
2A
1A
(V)
240V ac
415V ac
24V dc
48V dc
125V dc
(A)
6A
3A
6A
2A
1A
OF auxiliary contact
Part No.
26924
Width in
18mm SP
ways
0.5
Contact rating
14 12
11
26924
26929
26
24 22
92 94
21
91
Width in
18mm SP
ways
0.5
TM remote control
New
OF+SD/OF
auxiliary
contact
OF
auxiliary
contact
SD
fault
indication
switch
MN s , MNx or MSU
auxiliary
MX + OF or MN
auxiliary
TM
remote control
Tm modules allow:
Technical data
Circuit
breaker
Connection
Weight
1-2P: 300g.
3-4P: 310g.
27
TM remote controls
New
A1
MX
auto
MN
Possible
Voltage
combinations (V)
Part No.
C60 1-2P
C120 1-2P
18310
18312
230
230
Width in
18mm SP
ways
3.5
3.5
230V ~
SD
OF
A2
18310
A1
MX
auto
MN
230V ~
SD
OF
A2
18311
28
Possible
Voltage
combinations (V)
Part No.
C60 3-4P
C120 3-4P
18311
18313
230
230
Width in
18mm SP
ways
3.5
3.5
Accessories
For C60 and C120
Padlocking facility
Breaker
C60
C120
Quantity
Bag of 5
Bag of 2
Part No.
MGLA
27145
Breaker
C60
Quantity
Sealable bag of 2
Part No.
26981
Breaker
C60 Vigi
Quantity
Sealable bag of 10
Part No.
26982
Breaker
C120
Quantity
Sealable and
dividable bag of 2
Part No.
18527
Breaker
C60
Pole
1
2
3
4
Part No.
26975
26976
26975
26976 + 26978
Breaker
C120
Pole
1
2
3
4
Part No.
18526
2 x 18526
3 x 18526
4 x 18526
Breaker
C60/C120
Quantity
Bag of 4
Part No.
19091
Breaker
C60/C120
Quantity
Bag of 1
Part No.
27060
26970
Screw shield
Screw shield
18527
Screw shield
Terminal shield
Terminal shield
18526
27060
29
Accessories
For C60 and C120
Screw connection
Breaker
C60/C120
Quantity
Bag of 8
Part No.
27053
Breaker
C60/C120
Quantity
Bag of 2
Part No.
18528
Breaker
C60/C120
Quantity
Bag of 10
Part No.
27001
Breaker
C60/C120
Width
9mm
Part No.
27062
18528
Inter-pole barrier
Spacer
27062
Marker strips
Breaker
C60/C120
See page 31
Label holder
Breaker
C120
Quantity
Bag of 10
replacements
Part No.
27150
Pole
2
3
4
Part No.
26483
26484
26485
30
Marking accessories
New
Marking
Packing
Markers
27017
27003
Number
0
1
2
3
4
5
6
7
8
9
Part No.
27017
27029
27030
27031
27032
27033
27034
27035
27036
27037
Letter
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Part No.
27003
27004
27005
27006
27007
27008
27009
27010
27011
27012
27013
27014
27015
27016
27017
27018
27019
27020
27021
27022
27023
27024
27025
27026
27027
27028
Marker
+
Blank
Part No.
27038
27039
27040
Miscellaneous
31
New
Selection
Circuit breakers
Standard
Number
of poles
Rating
(A)
Type
Curves
Magnetic
threshold
In
BS EN 60947-2
1, 2
1080
NG125N
3, 4
10125
NG125N
3, 4
80125
NG125N
3, 4
80125
NG125N
12
1, 2, 3, 4
1080
NG125H
2, 3
1.680
NG125LMA
MA
12
Rating
Type
Number
of poles
3, 4
BS EN 60947-3
Earth leakage modules for trip free circuit breakers and switch disconnectors
Standard
BS EN 60947-2
Number
of poles
2, 3, 4
Rating
In at 400C
(A)
63
Vigi
type
Sensitivity
(mA)
Instantaneous
Vigi NG125 30
300
300
1000
125
Vigi NG125 30
300-500-1000
125
Vigi NG125 30
300
300-500-1000
32
Selective s
Instantaneous
or selective
Instantaneous
or selective s
or delayed 150ms
300-500-1000-3000
with fault threshold
indication (1)
300-500-1000-3000
with fault threshold
indication
300-500-1000-3000
with fault threshold
indication
New
Selection
Choice of circuit-breakers
Type
Impulse voltage Uimp (kV)
Insulation voltage Ui (V)
Maximum voltage rating Ue (V)
Number of poles
Breaking
Icu
AC 110130V
capacity
220240V
(kA)
380415V
IEC 947.2
440V
500V
DC 60V
125V
250V
500V
Ics
AC
DC
Tripping
B curve
40C
curves
C curve
40C
/ratings (A)
D curve
40C
NG125N
8
690
500
1
50
25
6
25
75% Icu
100% Icu
MA curve
Fast closing
Positive break indication
Auxiliaries
Degree of pollution 3
40C
1080
2, 3, 4
50
25
20
10
25 (2P)
25 (4P)
75% Icu
100% Icu
80125
10125
80125
NG125H
8
690
500
1
70
36
9
36
75% Icu
100% Icu
1080
2, 3, 4
70
36
30
12
36 (2P)
36 (4P)
NG125LMA
8
690
500
2, 3
100
50
40
15
1080
1.680
18668
33
New
BS EN 60947-3
Applications
The NG125NA is a trip-free switch-disconnector for on-load opening and closing.
Ratings: 63125A.
maximum voltage rating Ue: 500V AC.
Performance as in BS EN 60947.3.
Short-time withstand current (50 ms) Icw:
1.5 kA.
Maximum making capacity: see co-ordination
tables.
Maximum insulation voltage Ui: 690V.
Impulse voltage Uimp: 8 kV
Electrical durability:
Voltage
Category
63/80A
100/125 A
500V AC
AC22B
1500
1000
440V AC
AC22B
1500
1000
415V AC
AC22A-AC23B 1500
1000
125V DC
DC22A
1500
1000
(2P series)
250V DC
DC22A
1500
1000
(4P series)
Isolation with positive contact indication.
Built-in padlocking facility.
Weight (g):
Type
3P
4P
720
960
3P
1
Maximum
rating
(A)
63
80
100
125
Part No.
Maximum
rating
(A)
63
80
100
125
Part No.
18889
18890
18891
18892
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4P
34
18893
18894
18895
18896
Width in
18mm SP
ways
6
6
6
6
New
B curve
BS EN 60947-2: 25kA
Applications
This circuit-breaker is specially designed for functions requiring a high breaking
capacity (up to 25 kA): modular enclosure incomer, main incomer in sub-distribution
switchboards, outgoer, protection of loads directly supplied by a power switchboard.
B curve NG125N
3P
1
Weight (g):
Type
1P
240
2P
480
3P
720
4P
960
B curve
C curve
D curve
Rating
(A)
Part No.
80
100
125
18663
18664
18665
Rating
(A)
Part No.
80
100
125
18666
18667
18668
Width in
18mm SP
ways
4.5
4.5
4.5
18664
2
4P
7
Width in
18mm SP
ways
6
6
6
18668
2
35
New
C curve
BS EN 60947-2: 25kA
C curve NG125N
1P
1
18610
2
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18610
18611
18612
18613
18614
18615
18616
18617
18618
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18621
18622
18623
18624
18625
18626
18627
18628
18629
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18632
18633
18634
18635
18636
18637
18638
18639
18640
18642
18644
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
100
125
18649
18650
18651
18652
18653
18654
18655
18656
18658
18660
18662
Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2P
1
18621
2
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3P
1
18632
2
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4P
1
18662
2
36
Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
6
6
New
D curve
BS EN 60947-2: 25kA
D curve NG125N
3P
1
Rating
(A)
Part No.
80
100
125
18669
18670
18671
Rating
(A)
Part No.
80
100
125
18672
18673
18674
Width in
18mm SP
ways
4.5
4.5
4.5
18669
2
4P
18674
Width in
18mm SP
ways
6
6
6
37
New
C curves
BS EN 60947-2: 36kA
Applications
This circuit-breaker is specially designed for functions requiring a high breaking
capacity (up to 36 kA): main incomer in sub-distribution switchboards; outgoer,
protection of loads directly supplied by a power switchboard.
C curve
1P
1
18705
2
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18705
18706
18707
18708
18709
18710
18711
18712
18713
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18714
18715
18716
18717
18718
18719
18720
18721
18722
Width in
18mm SP
ways
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2P
1
18714
2
38
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
New
C curve
BS EN 60947-2: 36kA
3P
18723
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18723
18724
18725
18726
18727
18728
18729
18730
18731
Rating
(A)
Part No.
10
16
20
25
32
40
50
63
80
18732
18733
18734
18735
18736
18737
18738
18739
18740
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4P
18732
Width in
18mm SP
ways
6
6
6
6
6
6
6
6
6
39
New
MA curve
2P
1
18868
2
Trip unit
(A)
Magn. I
Part No.
MA4
MA6.3
MA10
MA12.5
MA16
MA25
MA40
MA63
MA80
50
75
120
150
190
300
480
750
960
18868
18869
18870
18871
18872
18873
18874
18875
18876
Trip unit
(A)
Magn. I
Part No.
MA4
MA6.3
MA10
MA12.5
MA16
MA25
MA40
MA63
MA80
50
75
120
150
190
300
480
750
960
18879
18880
18881
18882
18883
18884
18885
18886
18887
Width in
18mm SP
ways
3
3
3
3
3
3
3
3
3
3P
40
Width in
18mm SP
ways
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
NG125 Vigi
New
Selection
18668
19049
Non adjustable
10 - 63A
Page
Pole
3P, 4P
Page
45
3P, 4P
45
3P, 4P
45
43
45
45
45
3P, 4P
4P
2P,
2P,
2P,
2P,
3P,
3P,
3P,
3P,
4P
4P
4P
4P
10 - 63A
Non adjustable
Pole
2P, 3P, 4P
2P, 3P, 4P
30 mA
300 mA
80 - 125A
Pole
43
45
Page
42
44
80 - 125A
Adjustable
Pole
3P, 4P
Page
45
3P, 4P
43
Non adjustable
41
New
Technical data
9 mod.
410
450
11 mod.
750
800
Connection:
63 A ratings: tunnel terminals for 1.5 to 50mm2
copper cables,
80 to 125 A ratings: tunnel terminals for 16 to
70mm2 copper cables,
Aluminium cables, copper cables with lug (see
connection accessories).
Class AC ~
2P
1
Sensitivity
(mA)
I Max.
(A)
Part No.
30
63
19000
Sensitivity
(mA)
I Max.
(A)
Part No.
30
63
19002
Sensitivity
(mA)
I Max.
(A)
Part No.
30
63
19004
Width in
18mm SP
ways
2.5
2 4
3P
1
5
T
Width in
18mm SP
ways
4.5
2 4 6
4P
1
7
T
2 4 68
42
Width in
18mm SP
ways
4.5
New
I Max.
(A)
Sensitivity
(mA)
Part No.
63
125
30
30
19010
19008 (1)
I Max.
(A)
Sensitivity
(mA)
Part No.
63
125
30
30
19013
19039
I Max.
(A)
Sensitivity
(mA)
Part No.
63
125
30
30
19015
19041
I Max.
(A)
Sensitivity
(mA)
Part No.
125
30
19100
I Max.
(A)
Sensitivity
(mA)
Part No.
125
30
19101
Width in
18mm SP
ways
2.5
2.5
2 4
19010
3P
1
5
T
Width in
18mm SP
ways
4.5
5.5
2 4 6
4P
1
7
T
Width in
18mm SP
ways
4.5
5.5
2 4 68
Class A
si type
3P
1
5
T
Width in
18mm SP
ways
5.5
2 46
4P
1
6
T
Width in
18mm SP
ways
5.5
2 4 68
43
New
9 mod.
410
450
11 mod.
750
800
Class AC ~
2P
1
I Max.
(A)
Sensitivity
(mA)
Part No.
63
300
19001
I Max.
(A)
Sensitivity
(mA)
Part No.
63
300
19003
I Max.
(A)
Sensitivity
(mA)
Part No.
63
300
19005
Width in
18mm SP
ways
2.5
2 4
3P
1
5
T
Width in
18mm SP
ways
4.5
2 4 6
4P
1
7
T
2 4 68
44
Width in
18mm SP
ways
4.5
New
I Max.
(A)
Sensitivity
(mA)
Part No.
63
2 4
300
300
300 s
1000 s
(1) Voltage rating: 110...220V AC.
19012
19009 (1)
19030
19031
I Max.
(A)
Sensitivity
(mA)
Part No.
63
300
300 s
1000 s
3003000
3003000
3001000
3003000
3003000
19014
19032
19033
19036
19053 (2)
19044
19047
19055 (2)
Width in
18mm SP
ways
2.5
2.5
2.5
2.5
19049
3P
1
2 4 6
125
I/S/D
I/S/D
I/S
I/S/D
I/S/D
Width in
18mm SP
ways
4.5
4.5
4.5
5.5
5.5
5.5
5.5
5.5
I Max.
(A)
7
T
63
300
300 s
1000 s
3003000 I/S/D
3003000 I/S/D
125
300
3001000 I/S
3003000 I/S/D
3003000 I/S/D
(2) Voltage rating: 440/415V AC,
2 4 68
Class A
3P
Part No.
Width in
18mm SP
ways
19016
4.5
19034
4.5
19035
4.5
19037
5.5
19054 (2)
5.5
19042
5.5
19046
5.5
19049
5.5
19056 (2)
5.5
without early warning function.
si type
Sensitivity
(mA)
I Max.
(A)
Sensitivity
(mA)
Part No.
125
3003000 I/S/R
19106
I Max.
(A)
Sensitivity
(mA)
Part No.
125
3003000 I/S/R
19107
Width in
18mm SP
ways
5.5
2 4 6
4P
1
7
T
Width in
18mm SP
ways
5.5
2 4 68
45
New
Electrical auxiliaries
Applications
MX+OF, MXV shunt trip
Remotely indicates:
The "open" or "closed" position (OF).
a fault on the circuit-breaker (SD) or Vigi module
(SDV).
Early warning
Auxiliary contact.
OF+SD
MX+OF
Shunt releases.
Tripping: on energisation.
Equipped with a contact allowing self breaking.
MN
Undervoltage release.
Tripping and opening of the associated circuit
breaker: if supply voltage drops between 70 and
35%.
Reclosing: forbidden if supply voltage is not
restored (e.g.: emergency breaking by
pushbutton).
MN s
46
MXV
Shunt releases.
Tripping: on energisation
Equipped with a contact allowing self breaking.
Impulse withstand: 6kV
High impedance input: use an ACTp if leakage
current is greater than 1mA.
MNx
New
Electrical auxiliaries
Auxiliaries for circuit breaker
OF + OF
11
12 14
21
Voltage
(V AC)
Part No.
220-240 (6A)
19071
Voltage
(V AC)
Part No.
220-240 (6A)
19072
Voltage
(V AC)
Part No.
240 (6A)
19073
Width in
18mm SP
ways
0.5
22 24
19071
95
Width in
18mm SP
ways
0.5
98 96
19072
OF+OF or OF+SD
11
12 14
Width in
18mm SP
ways
0.5
21 22 24
95 98 96
19073
Shunt trip
MX + OF
Voltage
(V AC)
(V DC)
Part No.
230-415
110-130
19064
Width in
18mm SP
ways
1
48-130
24
48
24
19065
19066
1
1
U>
14 12 C2 C1
19064
47
New
Electrical auxiliaries
Undervoltage release
MN
Voltage
(V AC)
Part No.
(V DC)
U>
220-240
48
48
D1
19067
19069
19070
Width in
18mm SP
ways
1
1
1
D2
19067
Voltage
(V AC)
Part No.
230-240
19068
Voltage
(V AC)
Part No.
19058
19059
Voltage
(V AC)
Part No.
110-240
19060
U>
D1
Width in
18mm SP
ways
2
D2
19068
11
12 13
Width in
18mm SP
ways
-
14
19058
MXV
Width in
18mm SP
ways
-
U>
M1
19060
48
M2
Note: High impedance output (use an ACTP Cat. No. 15919, if the leakage current of the control device is
greater than 1mA).
Distribloc
125A splitters
Applications
Distribloc is a fully insulated four pole modular splitters.
Connection by screw terminals or spring terminals.
Technical data
Connection
Incomer:
Tunnel terminal for 35mm2 flexible or rigid cables,
Optional factory-built link for NG125 (catalogue
number: 07054).
Outgoer in spring terminals:
Minimum cross-section: 1mm2,
Simplifies rebalancing of phases and extensions,
Unaffected by temperature variations,
Spring contact pressure automatically adapted to
conductor cross-section,
A single cable without metal end per spring:
- by flexible cables: 2 x 10mm2 + 3 x 6mm2 +
7 x 4 mm2,
- by rigid cables: 2 x 16mm2 + 3 x 6mm2 +
7 x 4mm2,
Outgoer in screw terminals: 1x16mm2 or 25mm2
flexible or rigid cables.
Distribloc
Type
Part No.
Distribloc 125A
Set of 4 125A
flexible links
07105
Width in
18mm SP
ways
6
07054
Distribloc 125
49
New
Accessories
Applications
The following NG125 accessories can be used to increase flexibility and simplify
installation.
Rotary handle
Screw shield
Cable cross-section:
For 63 A ratings:
- flexible cable: 1 to 35mm2,
- rigid cable: 1.5 to 50mm2.
For 80-100-125 A ratings:
- flexible cable: 10 to 50mm2,
- rigid cable: 16 to 70mm2.
Tightening torque and tool type:
For 63 A ratings: 3.5 Nm with 6.5 mm flat
screwdriver or PZ n 2 (Pozidrive recessed head
screw),
For 80-100-125 A ratings: 6 Nm with 4 mm Allen
wrench (hexagon socket screw).
Degree of protection: IP20B.
Cable lugs
Comb busbar
Installation: front.
Utilisation: circuit breaker control from outside
the enclosure.
Retains isolation/padlocking in the O position (3
padlocks).
IP55.
3 positions.
Door interlocking: opening possible in O position
only direct rotary handle.
Padlocking accessory
50
Terminal shield
New
Accessories
Screw shield for circuit breaker
Bag of 10
19087
Type
1P
2P
3P
4P
Part No.
19084
19085
19086
19087
Type
1P
2P
3P
4P
Part No.
19080
19081
19082
19083
19080
19076
125A
Type
2P
3P
3P adjustable
4P
4P adjustable
3P
4P
Part No.
19074
19075
19077
19076
19078
19077
19078
Type
Standard, black
Red handle
yellow background
Part No.
19088
19089
Type
Bag of 4
Part No.
19090
Type
bag of 4
Part No.
19091
Rotary handle
19088
Padlocking accessory
19090
19091
19093
Cable lugs
Type
4 supplied
Part No.
19094
4 supplied
19095
Type
1P
2P
3P
4P
Tooth-shield end (set of 20)
Part No.
14811
14812
14813
14814
14818
Comb busbar
14813
51
Technical data
Voltage (V)
230,240
400,415
440
500
Icu Ics Icu Ics Icu Ics Icu
in
in
in
in
in
in
in
Rating kA
%
kA
%
kA
%
kA
(A)
0.16
to
self protected
1.6
2.5
4
6.3
50 100 50
10
15 100 10
14
15 50
8
50
6
18
15 50
8
50
6
23
50 100 15 40
6
50
4
25
50 100 15 40
6
50
4
Ics
in
%
690
Icu
in
kA
Ics
in
%
100
100
75
75
75
75
3
3
3
3
3
3
3
3
75
75
75
75
75
75
75
75
Rating
In (A)
0.16
0.25
0.40
0.63
1.0
1.6
2.5
4.0
6.3
10
14
18
23
25
Settings
Part No.
0.1 - 0.16
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.0
1.0 - 1.6
1.6 - 2.5
2.5 - 4.0
4.0 - 6.3
6.0 - 10
9.0 - 14
13 - 18
17 - 23
20 - 25
21100
21101
21102
21103
21104
21105
21106
21107
21108
21109
21110
21111
21112
21113
Limiter block
Increases the breaking capacity to 100kA up to 415V.
Individual mounting (upstream) or on the terminal
block part no. 21144 .
21115
52
P
O+F
MX
2
/
SD
/
5
F+F
MN
M
Remote indication:
Position:
O+F contact indicates ON or OFF position of the
P25M,
F+F contact double contact for ON position.
Position + alarm indicator: with red flag trip
indicator:
F+SD.O - ON position + OFF fault indication,
O+SD.O - OFF position + OFF fault indication,
F+SD.F - ON position + ON fault indication,
O+SD.F - OFF position + ON fault indication.
Width in 18mm
SP ways
0.5
Contact position O+F
0.5
Contact position F+F
43 31
33
44
34
21117
21116
Technical data
Voltage
Ue
Position (OF)
Fault (SD)
V AC
24
48
130
240
415
440
V DC
24
48
60
110
220
(A)
(A)
1.5
1
0.5
0.3
44
21118
6
4.5
3.3
2.2
1.5
DC 13
6
5
3
1.3
0.5
DC 13
1
0.3
0.15
MX
Pick up
14
10
Hold
5
1.6
MN
Hold
3.5
1.1
Connection by terminal clamp
Min.: rigid cables 2 x 1 mm2
Max.: flexible cables up to 2 x 2.5 mm2
Flexible cable with cable end 2 x 1.5 mm2
21116
Width in 18mm
SP ways
0.5
Position+alarm
contact F+SD.F
0.5
Position+alarm
contact O+SD.F
0.5
Position+alarm
contact F+SD.O
0.5
Position+alarm
contact O+SD.O
95 53
95 51
96 54
96 52
Part No.
21118
21119
21120
21121
21121
97 53
97 51
98 54
98 52
21118
Remote tripping
32
21117
21120
21127
43
Part No.
21119
Width
Voltage
18mm
(V)
SP ways
MX shunt trip release
1
220.240
380.415
Width
Voltage
18mm
(V)
SP ways
MN under voltage release
1
220.240
380.415
50
50
21127
21128
50
50
21129
21130
53
Enclosure
Neon indicator light 220.240V
21133
green
red
green
red
21140
21142
21141
21143
21146
Part No.
21145
21146
21145
Terminal block
For supply of busbars with cables up to 25mm2 (can
be installed with limiter block).
End cover (bag of 5 pcs)
Terminal block
Part No.
21148
21144
21144
Insulated connector
To supply comb busbars or P25M directly with cables
up to 25mm2.
Insulated connector
21147
54
Part no.
21147
40
Specifications
63
RCD: BS EN 61008.
Technical data
Electrical data
80
100
80
time delayed
100
time delayed
100
time delayed
Installation
On symmetrical DIN rail.
Panel mounting.
Note: RMG residual current devices must be used with
circuit breakers to provide circuit protection of overload
and short circuit faults.
Dimensions: see page 155.
Part No.
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
RMG
16 010 2
25 010 2
25 030 2
40 030 2
40 300 2
63 030 2
63 100 2
63 300 2
80 030 2
80 100 2
80 300 2
100 030 2
100 100 2
100 300 2
23111 (50-70mS)
300
23116 (50-70mS)
100
RMG 1001002S
63
time delayed
80
100
100
time delayed
Sensitivity
(mA)
10
10
30
30
300
30
100
300
30
100
300
30
100
300
100
Sensitivity
(mA)
30
300
30
300
30
100
300
300
Part No.
RMG
RMG
RMG
RMG
RMG
RMG
RMG
25
25
40
40
63
63
63
030
300
030
300
030
100
300
4
4
4
4
4
4
4
23146 (50-70mS)
16261
23213
30
300
300
23227
Class A RCD
Rating
(A)
25A 30mA
40A 30mA
63A 30mA
No. of
poles
2
2
2
23249
23253
23258
40A 30mA
63A 30mA
4
4
23303
23308
Y B
Part No.
or
FEED
LOAD
LOAD
FEED
Y B
Accessories
Padlocking
Padlock with 2 keys
Spare key for MGPL
20719
MGPL
MGPLSK
55
O
F
O
F
Auxiliary
switch OF
Undervoltage
trip module MN
Shunt trip
module MX
Auxiliary
switch OF.S
RCD
MX
or
MN
MX
or
MN
MX
or
MN
O
F
S
R
M
G
O
F
S
R
M
G
O
F
S
R
M
G
No. of
Coil
Consumption
18mm
volt
pickup W or VA
SP ways
1
130dc
10
1
240ac
50
1
415ac
120
1
48-60dc
22
1
48-130ac
200
1
24ac/dc
120
(Also requires OFS 26923)
Part
No.
No. of
Coil
Consumption
18mm
volt
pickup W or VA
SP ways
1
220/240AC 4.1
1
48AC
4.3
1
48DC
2
(Also requires OFS 26923)
Part
No.
No. of
18mm
SP ways
0.5
0.5
Contact ratings (A):
3A at 415V ac
1A at 125V dc
6A at 24V dc
6A at 240V ac
2A at 48V dc
Part
No.
26946
26946
26946
26947
26947
26948
26946
26960
26961
26962
26960
26923
26924
56
OFS
OF
26923
26924
Metal
All insulated
Description
Two piece unit for use with 2P
RMG RCD's (except 100A unit)
Two piece unit for use with 4P
RMG RCD's
One piece unit for use with 2P
RMG RCD's (IP30 enclosure)
One piece unit for use with 4P
RMG RCD's (IP30 enclosure)
Padlocking attachment
Padlock with 2 keys
Spare key for MGPL
Part No.
26976
26978
13392
13394
20719
MGPL
MGPLSK
26978
Description
For use with 2P and 4P
RMG RCD's (bag of 8 shields)
Part No.
26981
26981
Enclosures
(See page 118 for full range)
G9 enclosure IP30
Capacity in
18mm SP ways
4
5
2*-3
*Blanking plate supplied.
Part No.
14599
14603
99560
14599
Mini opale
Impact resistant, all-insulated enclosure self
extinguishing to 650C.
Degree of protection: IP30.
It consists of:
An insulated back plate with integral DlN-rail.
A cover screwed to the back plate,
Four-hole terminal bar (also available separately (Poles) part No. 14901).
Capacity in
18mm SP ways
2
4
6
8
Part No.
13392
13394
13396
13398
13394
10504
Capacity in
18mm SP ways
1-4
4-8
8-12
Dimensions: see page 163.
Accessories: see page 128.
Part No.
10504
10508
10512
57