Earth Leakage Protection
Earth Leakage Protection
Earth Leakage Protection
Risks
Short-circuits
Overloads
Earth leakage
Causes
phase to earth current flow (Ph/Frame)
Consequences
fire hazards
damage to loads
electrocution
Risk of fire
250 mA is enough to ignite a fire
Damage to loads
Damage caused to an
installation
Insulation
material
Conductive
frame
Cable
The leakage current flows again during the next humidity period . 4
Clamping unit
Conductive frame
Insulation material
Cable
Cable
Conductive frame
Insulation material
Conductive frame
Insulation material
Cable
What is the
solution : to
eliminate any
dangerous
leakage
current ?
Risk of electrocution
Direct contact
IEC standards now recognize
high performance RCDs as
supplementary protection
against direct contact
electrocution, especially in
domestic applications.10 mA,
30 mA, may be used to provide
instant tripping of the faulty
phase conductor.
Risk of electrocution
Indirect contact occurs
when exposed
conductive part
becomes alive due to
insulation fault and are
touched.
Electric shock
-It is caused by the current that flows through the human body.
-The current depends mainly upon the skin contact resistance.
-The contact resistance varies with ( thickness, wetness and resistively of the skin ).
-In general :
Current<5mA is not dangerous .
10mA< current <20mA
The current is dangerous because the victim loses muscular control and so may not be
able to let go .
Current>50mA the consequences can be fatal .
Electric shock
Resistance of human body Rb:
Rb : between two hands or between one hand and a leg ranges
from 500 Ohms to 50 K Ohms
if Rb = 50 K ohms
The momentary contact with 600 V may not be fatal .
I body = 600 V / 50 K Ohms = 12 mA
but if Rb = 500 ohm and voltage is as low as 25V ac
I body = 25 V / 500 Ohms = 50 mA (may be fatal )
the current is particularly dangerous when it flows in the region of the heart .
Electric shock
statistical investigations have shown that a current may cause death if it satisfies the
following equation
Ib = 116/ square root ( t )
where :Ib : current flow through the body in mA
t : time of current flow second
116 : an empirical constant, expressing the probability of a fatal out come .
[ IEEE transactions on industry and general application ]
vol. IGA - 4, No. 5 , pages 467 to 475.
example:
A current of 116 mA for 1 s could be fatal .
Ventricular Fibrillation is considered to be the main cause of Electrocution
Earthing Systems
The selection of RCD is according to [ section 533 NF C15-100 Rules ] and method of
earthing of power supply system.
T : Terre
I : Isolated
N : Neutral
C : Common
S : Separate
First letter
: Earthing of system ( Source )
Second letter : Earthing of metallic or conductive part of installation
Grounding systems
IEC 364
TN system
TNS systems
Grounding systems
IEC 364
TN system
TNC systems
Grounding systems
IEC 364
TN system
TNC-S system
Grounding system
IEC 364
TT system
Grounding system
IEC 364
IT system
LV Grounding systems
LV electrical network may supply several types of applications.
Only one type of Earthing System cannot be suitable for all applications.
It is advisable to mix various Grounding Systems in an electrical
installation.
48
EDC
network
TN-C
Hazards
In residential areas
Hazards
In residential areas
Hazards
In residential areas
Hazards
In residential areas
Further Safety
All conventional grounding methods are
usually adequate (up to 65 % 70 % safe)
safety measures are needed in some cases.
Example 1:
suppose a person sticks his finger into a lamp
socket .
special case where a grounding wire does not
afford protection.
(direct contact with live terminal)
although the metal enclosures is securely
grounded, the person will still receive a painful
shock.
Further Safety
EXAMPLE 2:
Suppose a 220 v electric toaster falls suddenly into a swimming pool. The heating
elements and contacts will produce a hazardous leakage current through out the pool
even if the frame of the toaster is security grounded.
Therefore, devices have been developed that will cut the source of power as soon as
such accidents occur.
These ground faults circuit breakers will typically trip in 25 ms if the leakage current
exceeds 5mA
Hazards
In residential areas
Tripping
Measurement
General Specifications
Number of poles 2 or 4
Rated voltage not exceeding 1000 v.
Rated breaking load current
Rated breakage earth leakage fault current.
Installation of RCD
General Notes
Every installation which includes exposed conductive parts should be protected by one
or more RCD
If an installation is protected by one RCD , This device should be Located at the
starting point of the installation
The exposed conductive parts of the protected appliance should be all connected to
an earth electrode of suitable resistance
Installation of RCD
Depending on the type of the installation and the risks involved , it may be
necessary to provide RCD having different sensitivities in order to protect
different parts of the installation
Measures of Selectivity
No Selectivity or only partial Selectivity
Horizontal Selectivity
Vertical selectivity
Measures of Selectivity
DR
MS
DR
MS
DR
DR
HS
HS
Measures of Selectivity
C. The arrangement shown in the Fig. is
similar to the given in B but HS is replaced by
MS devices but their rated residual current is
less than half of the device on the supply side
eg.
If the normal leakage current of the devices
on the consumer side is 100mA therefore the
normal leakage current of the device on the
supply side is 300 mA
Upstream
Down
stream
MSU release
Protection against accident breaking of neutral
Install
Connect
MSU release
Protection against accident breaking of neutral
Protect
RCCB + MCB
Advantages
2, 4P for single or three phase supply.
Rating from : 16 to 100 A
Auxiliaries MSU (possible addition ) if MSU
In case of failure in neutral connection
Possibility to use 1-P & 3-P MCB K60N
Most economic solution.
Disadvantages
No solid connection between MCB and RCCB.
NO possibility to lock (Secure ) the wiring.
MCB 3-pole
RCCB 4-pole
MCB 1-pole
RCCB 2-pole
MCB 2-pole
Advantages
2,3, 4P for single or three phase supply.
Rating up to 125A
Auxiliaries MSU ( Same as before )
Solid connection between Vigi and
MCB.
possibility to lock the wiring.
MCB 4-pole
Disadvantages
MCB should be 2P or 4P.