Ncma Tek: Fire Resistance Rating of TEK 7-1A Concrete Masonry Assemblies
Ncma Tek: Fire Resistance Rating of TEK 7-1A Concrete Masonry Assemblies
Ncma Tek: Fire Resistance Rating of TEK 7-1A Concrete Masonry Assemblies
Provided by:
Cinder & Concrete Block Corporation
National Concrete Masonry Association
an information series from the national authority on concrete masonry technology
INTRODUCTION
This TEK conforms to the stated parameters of the
Standard Method for Determining Fire Resistance of Concrete and Masonry Construction Assemblies, ACI 216.1-97/
TMS 0216.1-97 (ref. 1hereinafter referred to as the Standard). Concrete masonry is widely specified for fire walls and
fire separation walls because these elements are:
noncombustible,
provide durable fire resistance, and
are economical to construct.
For the most part, the contents of the Standard are not
new, but rather are a compilation and refinement of the many
documents previously published by the various segments of
the masonry and concrete industry. More importantly, the
Standard is a document that has gone through a formal
consensus process and is written in mandatory language, and
therefore is now incorporated by reference into the national
model codes.
Methods of Determining Fire Resistance Ratings
The fire resistance rating period of concrete masonry
elements can be determined by three methods:
calculation,
by testing.
The calculation method is the most practical and most
commonly used method of determining the fire resistance
rating of concrete masonry. It is based on extensive research
which established a relationship between physical properties
of materials and the fire resistance rating. The calculation
method is utilized in the Standard which determines fire
resistance ratings based on the equivalent thickness of concrete masonry units and aggregate types used in their manufacture.
An alternative to the calculation method is provided by
private commercial listing services. The listing service
approach allows the designer to select a fire rated assembly
which has been previously classified and listed in a published
TEK 7-1A
Fire Resistance (2003)
TEK 7-1A 2003 National Concrete Masonry Association (replaces TEK 7-1 and 7-3)
Minimum
4 hours
6.2 (157)
5.9 (150)
5.1 (130)
4.7 (119)
1. Fire resistance rating between the hourly fire resistance rating periods listed may be determined by linear interpolation based on the
equivalent thickness value of the concrete masonry assembly.
2. Minimum required equivalent thickness corresponding to the hourly fire resistance rating for units made with a combination of aggregates
shall be determined by linear interpolation based on the percent by volume of each aggregate used in the manufacture.
and salvageability.
Fire testing of concrete masonry columns evaluates the
ability of the column to carry design loads under standard fire
test conditions. Fire testing of a concrete masonry protected
steel column assembly evaluates the structural integrity of the
steel column under fire test conditions by measuring the
temperature rise of the steel.
Fire testing of concrete masonry beams and lintels evaluates the ability of the member to sustain design loads under
standard fire test conditions. This is accomplished by insuring that the temperature rise of the tensile reinforcing does
not exceed 1100 oF (593 oC) during the rating period.
Equivalent Thickness
Extensive testing has established a relationship between
the fire resistance and the equivalent solid thickness for
concrete masonry walls as shown in Table 1. Equivalent
thickness is essentially the solid thickness that would be
obtained if the same amount of masonry contained in a hollow
unit were recast without core holes. The equivalent thickness
of a hollow unit is equal to the percentage solid times the
actual thickness of the unit. See Figure 1. The percentage
solid is determined in accordance with Standard Methods of
Sampling and Testing Concrete Masonry Units, ASTM C
140 (ref. 2).
The equivalent thickness of a 100% solid unit or a solid
grouted unit is equal to the actual thickness. For partially
grouted walls where the unfilled cells are left empty, the
equivalent thickness for fire resistance rating purposes is
If this hollow
unit is 53% solid,
4.0
n.
4
/8 i )
7 5 mm (103 m in.
4
m)
9
(1
the equivalent
thickness is
4.04 inches
(103 mm)
4
6
8
10
12
(102)
(152)
(203)
(254)
(305)
Based on
typical
hollow units 1
2.7 (69)
3.1 (79)
4.0(102)
5.0(127)
5.7(145)
[73.8]
[55.0]
[53.0]
[51.7]
[48.7]
Based on
percent solid
(75%)
(100%)
2.7 (69)
4.2 (107)
5.7 (145)
7.2 (183)
8.7 (221)
3.6
5.6
7.6
9.6
11.6
(91)
(142)
(193)
(244)
(295)
For multi-wythe walls of clay brick and concrete masonry, use the values of Table 3 for the brick wythe in the
above equation.
Table 3Fire Resistance of Brick or Tile
of Clay or Shale (ref.1)
Material type
3 hours
2 hours
l hour
6.0 (152)
5.0 (127)
6.6 (168)
4.9 (124)
4.3 (109)
5.5 (140)
3.8 (97)
3.4 (86)
4.4 (112)
2.7 (69)
2.3 (58)
3.0 (76)
Where:
R1, R2,...Rn = fire resistance rating of wythe 1, 2,...n,
respectively (hours).
A1, A2,...An = 0.30; factor for each air space, 1, 2,...n,
respectively, having a width of 1/2 to 31/2 in. (13 to 89 mm)
between wythes. Note: It does not matter which side is
exposed to the fire.
Wythe (R 2 )
Wythe (R 2 )
R 1 = Fire resistance rating of wythe 1
R 2 = Fire resistance rating of wythe 2
A 1 = Air space factor = 0.3
Figure 2Fire Resistance of Multi-Wythe
Masonry Wall (ref. 1)
1 hour
2 hours
3 hours
4 hours
8 (203)
10 (254)
12 (305)
14 (356)
Control Joints
Figure 3 shows control joint details in fire rated wall
assemblies in which openings are not permitted or where
openings are required to be protected. Maximum joint width
is in. (13 mm).
Density, D
pcf (kg/m3)
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
(1281)
(1362)
(1442)
(1522)
(1602)
(1682)
(1762)
(1842)
(1922)
(2002)
(2082)
(2162)
(2243)
(2323)
(2403)
Thermal conductivity1, k
Btu/hrftoF (W/mK)
0.207
0.228
0.252
0.278
0.308
0.340
0.376
0.416
0.459
0.508
0.561
0.620
0.685
0.758
0.837
(0.358)
(0.394)
(0.436)
(0.481)
(0.533)
(0.588)
(0.650)
(0.720)
(0.749)
(0.879)
(0.971)
(1.073)
(1.186)
(1.312)
(1.449)
Grout key
tweb
ps = 4d
0.25p
ps = pd
0.25p
Figure 4Details of Concrete Masonry Column
Protection for Commonly Used Shapes (ref. 1)
Siliceous or
carbonate aggregate
concrete masonry
unit
Expanded shale,
expanded clay,
expanded slag, or
pumice less than 20
percent sand
1.00
0.75
Gypsum-sand
plaster
1.25
1.00
Gypsum-vermiculite or perlite
plaster
1.75
1.25
Gypsum wallboard
3.00
2.25
Time, min
Gypsum wallboard
3
10
15
20
25
35
40
25
40
See Note 1
20
25
30
35
40
50
50
60
80
1. For purposes of determining the contribution of portland cementsand plaster to the equivalent thickness of concrete or masonry for
use in Table 1, it shall be permitted to use the actual thickness of
the plaster, or 5 /8 in. (16 mm), whichever is smaller.
Installation of Finishes
Finishes that are assumed to contribute to the total fire
resistance rating of a wall must meet certain minimum installation requirements. Plaster and stucco need only be applied in
accordance with the provisions of the building code. Gypsum
wallboard and gypsum lath may be attached to wood or metal
furring strips spaced a maximum of 24 in. (610 mm) on center or
may be attached directly to the wall with adhesives. Drywall
and furring may be attached in one of two ways:
1). Self-tapping drywall screws spaced a maximum of 12 in.
(305 mm) and penetrating a minimum of 3/8 in. (10 mm) into
resilient steel furring channels running horizontally and
spaced a maximum of 24 in. (610 mm) on center.
2). Lath nails spaced at 12 in. (305 mm) on center maximum, penetrating 3/4 in. (19 mm) into nominal 1 x 2 in.
(25 x 51 mm) wood furring strips which are attached to the
masonry with 2 in. (51 mm) concrete nails spaced a maximum of 16 in. (41 mm) on center.
Gypsum wallboard must be installed with the long dimension parallel to the furring members and all horizontal and vertical
joints must be supported and finished. The only exception is 5/
8 in. (16 mm) Type "X" gypsum wallboard which may be installed
horizontally without being supported at the horizontal joints.
For drywall attached by the adhesive method, a 3/8 in. (10
mm) bead of panel adhesive must be placed around the
perimeter of the wallboard and across the diagonals and then
secured with a masonry nail for each 2 ft 2 (0.19 m2)of panel.
CONCLUSION
The calculated fire resistance procedure is practical, versatile, and economical. It is based on thousands of tests. It is
incorporated by reference into the major model codes of the US
and allows the designer virtually unlimited flexibility to incorporate the excellent fire resistive properties of concrete masonry into the design.
REFERENCES
1.
Standard Method for Determining Fire Resistance of Concrete and Masonry Construction Assemblies, ACI 216.1-97/TMS 0216.1-97.
American Concrete Institute and The Masonry Society, 1997.
2. Standard Methods forSampling and Testing Concrete Masonry Units, ASTM C 140-02a. American Society for Testing and Materials, 2002.
3. Standard Specification for Concrete Aggregates, ASTM C 33-02a. American Society for Testing and Materials, 2002.
4. Standard Specification for Lightweight Aggregates for Concrete Masonry Units, ASTM C 331-02. American Society for Testing and
Materials, 2002.
5. Standard Specification for Lightweight Aggregates for Insulating Concrete, ASTM C 332-99. American Society for Testing and Materials,
1999.
6. Standard Specification for Loadbearing Concrete Masonry Units, ASTM C 90-02. American Society for Testing and Materials, 2002.
7. Standard Test Methods for Fire Tests of Building Construction and Materials, ASTM E 119-00a. American Society for Testing and Materials,
2000.
8. Standard Specification for Vermiculite Loose Fill Thermal Insulation, ASTM C 516-02(1996)e1 . American Society for Testing and Materials,
2002.
9. Standard Specification for Perlite Loose Fill Insulation, ASTM C 549-02. American Society for Testing and Materials, 2002.
10 . Steel Column Fire Protection, TEK 7-6. National Concrete Masonry Association, 2003.
11. 2000 International Building Code, Falls Church, Va. International Code Council, 2000.
Provided by:
Cinder & Concrete Block Corporation
Disclaimer: NCMA and the companies disseminating this technical information disclaim any and all responsibility and
liability for the accuracy and the application of the information contained in this publication.