Basler IM For DECS-100 Digital Excitation Control System 9 2
Basler IM For DECS-100 Digital Excitation Control System 9 2
Basler IM For DECS-100 Digital Excitation Control System 9 2
for
DECS-100
Digital Excitation Control System
INTRODUCTION
This instruction manual provides information about the operation and installation of the DECS-100
Digital Excitation Control System. To accomplish this, the following information is provided.
C
C
C
C
C
C
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
Lethal voltage is present at the rear panel when the unit is energized. Rear
panel connections should be made only when the unit is de-energized.
CAUTION
The Manual mode excitation level must be evaluated prior to enabling this
feature. If the level of excitation current is inappropriate for the generator, severe
damage to the generator may occur.
Improper PID numbers will result in poor system performance or system
damage.
When applying operating power to the DECS-100 for programming purposes,
observe the precautions called out in Section 4, Installation, Preliminary Setup.
When programming the DECS-100 without the generator spinning, the
connections to DECS-100 terminals F+ and F should be removed.
Before uploading a settings file, remove operating power from the DECS-100,
disconnect the field wiring from terminals F+ and F, and re-apply operating
power to the DECS-100.
NOTE
Be sure that the DECS-100 is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the unit case.
When the unit is configured in a system with other devices, it is recommended to
use a separate lead to the ground bus from each unit.
DECS-100 Introduction
CONFIDENTIAL INFORMATION
of Basler Electric, Highland, IL. It is loaned for confidential use, subject to return
on request, and with the mutual understanding that it will not be used in any
manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this
manual provide data for every possible contingency regarding installation or operation. The availability
and design of all features and options are subject to modification without notice. Should further
information be required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL, 62249 USA
http://www.basler.com, [email protected]
PHONE 618-654-2341
FAX 618-654-2351
ii
DECS-100 Introduction
Firmware
Version and Date
Change
1.09.XX, 01/01
Initial release
1.11.XX, 07/01
1.12.XX, 03/02
BESTCOMS for
Windows OS
Version and Date
Change
1.02.XX, 02/01
Initial release
1.03.XX, 08/01
1.04.XX, 04/02
BESTCOMS for
Palm OS
Version and Date
Change
1.01.XX, 01/01
Initial release
1.02.XX, 08/01
Added a Check for New Version button to the Contact Basler screen
Added a date/time stamp to the Save to File names
Added version checking
1.03.XX, 04/02
DECS-100 Introduction
iii
Hardware
Version and Date
Change
E, 01/01
Initial release
F, 05/01
G, 10/01
H, 02/02
SIL-PADS were added between some power components and the heat
sinks.
Added manufacturing origin to the rear label.
J, 07/02
Revised EEPROM
K, 02/03
L, 03/03
M, 01/04
Manual
Revision and Date
Change
None, 03/01
Initial release
A, 03/01
B, 08/01
C, 05/02
D, 01/03
E, 03/04
iv
Revised the torque specification for the mounting screws supplied with
the unit.
In Section 5, BESTCOMS Software for the Windows Operating
System and Section 6, BESTCOMS Software for the Palm OS
Platform, text and illustrations were revised to accommodate software
enhancements.
Revised Voltage Matching Time Adjustment Range from 0 to 300
seconds to 1 to 300 seconds through manual.
Corrected figure number references in Sections 5 and 6.
Added Operating Power Considerations During DECS-100
Programming to Section 4, Installation, Preliminary Setup.
Added caution box regarding application of operating power during
DECS-100 programming to Section 5, BESTCOMS for Windows OS
and Section 6, BESTCOMS for Palm OS.
Corrected CT ratio setting range stated in Section 5.
DECS-100 Introduction
CONTENTS
A detailed table of contents is provided at the start of each manual section. The manual sections are
ordered as follows.
Section 1
Section 2
Section 3
Section 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Section 5
Section 6
Section 7
DECS-100 Introduction
1-1
1-1
1-1
1-1
1-1
1-1
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-3
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Figures
Figure 1-1. DECS-100 Style Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Figure 1-2. Typical V/Hz Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
FEATURES
DECS-100 units have the following features and capabilities.
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
Four control modes: automatic voltage regulation (AVR), manual or field current regulation (FCR), power
factor (PF) regulation, and reactive power (var) regulation.
Programmable stability settings.
Soft start and voltage buildup control with an adjustable ramp in AVR control mode.
Overexcitation (OEL) limiting in AVR, var, and PF control modes.
Underfrequency (volts/hertz) regulation.
Three-phase or single-phase generator voltage (rms) sensing/regulation in AVR mode.
Single-phase bus voltage (rms) sensing.
Single-phase generator current sensing for metering and regulation purposes.
Field current and field voltage sensing.
One analog input for proportional remote control of the setpoint.
Five contact sensing inputs for system interface.
One common output relay for alarm indication and trip functions.
Four protection functions (field overvoltage, field overcurrent, generator overvoltage, and loss of sensing).
Generator paralleling with reactive droop compensation and reactive differential compensation.
Rear RS-232 communication port for personal computer communication using BESTCOMS Windows
based software for fast, user-friendly, setup and control.
1-1
SPECIFICATIONS
DECS-100 electrical and physical specifications are listed in the following paragraphs.
Bus Voltage Sensing (Optional)continued
Operating Power
Voltage:
Frequency Range:
Burden:
Terminals:
Voltage Buildup:
1-phase/3-phase, 4 ranges
<1 VA per phase
E1, E2, E3
50 Hertz Sensing
Range 1:
Range 2:
Range 3:
Range 4:
60 Hertz Sensing
Range 1:
Range 2:
Range 3:
Range 4:
1-2
60 Hertz Sensing
Range 1:
Range 2:
Range 3:
Range 4:
Accessory Input
50 Hertz Sensing
Range 1:
Range 2:
Range 3:
Range 4:
1-phase, 4 ranges
<1 VA per phase
B1, B3
Voltage Range:
Setpoint Range:
Burden:
Terminals:
3 Vdc to +3 Vdc
30% to +30% shift
1 kS
A, B
Communication Port
Interface:
Connection:
Baud:
Data Bits:
Parity:
Stop Bit:
Dry Contact
13 Vdc (supplied by DECS-100)
Adjustment Range:
Increment:
Adjustment Range:
Increment:
Type:
Rated Load:
Make:
Break:
Operating Voltage:
Terminals:
Form A
7 Aac/Adc continuous
30 Aac/Adc, carry for 0.2 sec
7 Aac/0.1 Adc
240 Vac/250 Vdc maximum
AL1, AL2
Parallel Compensation
Modes:
Field Output
Field Resistance:
Terminals:
Continuous Rating:
0 to 7 Adc
0.1 A
5 S minimum
F+, F
63 Vdc, 7 Adc
0 to 250 Vdc
10 seconds (fixed)
Temperature Drift:
V/Hz Characteristic:
Response Time:
0 Adc to 15 Adc
0.001 Adc
Time Delay
Range:
Increment:
0 to 10 seconds
1 second
1 to 7,200 seconds
1 second
Voltage Matching
Accuracy:
Time Adjustment
Range:
Increment:
Metering (BESTCOMS)
Generator Voltage
Range:
Accuracy:
Generator Current
Range:
Accuracy:
10 V to 79 kV
0.5% (at 25C)
0.04 to 3,000 A (1 A CTs)
0.2 to 15,000 A (5 A CTs)
0.5% (at 25C)
1-3
Metering (BESTCOMS)continued
UL Recognition
Frequency
Range:
Accuracy:
40 to 65 Hz
0.2 Hz (at 25C)
Field Voltage
Range:
Accuracy:
0 to 200 V
5.0% (at 25C)
Field Current
Range:
Accuracy:
0 to 20 A
0.5% (at 25C)
Bus Voltage
Range:
Accuracy:
10 V to 79 kV
0.5% (at 25C)
Auxiliary DC Input
Range:
Accuracy:
3 V to +3 V
0.5% (at 25C)
CSA Certification
Certified per Standard CAN/CSA-C22.2, Number 1495, CSA File LR23131-139
CE Compliance
Emissions
CISPR11/EN55011, Level A
Electrostatic Discharge (ESD)
IEC 1000-4-2/EN 61000-4-2, Level B
Radiated Susceptibility
IEC 1000-4-3/EN 61000-4-3, Level A
Electrical Fast Transient
IEC 1000-4-4/EN 61000-4-4, Level B
Radio FrequencyConducted
IEC 1000-4-6/EN 61000-4-6, Level A
Power FrequencyMagnetic
IEC 1000-4-8/EN 61000-4-8, Level A
Dielectric
IEC 255
Patent
0 to 360 degrees
2.0 degrees (at 25C)
Environment
Operating Temperature
DECS-100:
40C to 70C
(40F to 158F)
Storage Temperature
DECS-100:
40C to 85C
(40F to 185F)
CD-ROM:
0C to 50C
(32F to 122F)
Type Tests
Shock:
Vibration:
Salt Fog:
20 Gs in 3 perpendicular
planes
1.2 Gs at 5 to 26 Hz
0.914 mm (0.036") double
amplitude at 27 to 52 Hz
5 Gs at 53 to 500 Hz
Tested per MIL-STD-810E
Physical
Weight
Unit:
Shipping:
1-4
2-1
2-1
2-1
2-2
Figures
Figure 2-1. DECS-100 Front Panel Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Figure 2-2. DECS-100 Communication Port Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Tables
Table 2-1. DECS-100 Front Panel Indicator Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Description
Overexcitation Shutdown
Generator Overvoltage
2-1
Indicator
Description
Overexcitation Limiting
This LED lights when the field current exceeds the programmed
overexcitation limit. It stays lit until the overexcitation condition
ceases or the overexcitation time delay expires and the DECS-100
shuts down. The Overexcitation Limiting LED will flash for 5 seconds
when the DECS-100 is powered up following an overexcitation
limiting shutdown.
Underfrequency Active
This LED lights when the generator frequency decreases below the
underfrequency setpoint and the DECS-100 is regulating on the
selected volts per hertz curve.
COMMUNICATION PORT
The communication port is located on the rear panel and
consists of a female RS-232 (DB-9) connector. The
communication port serves as an interface for programming
(setup) of the DECS-100. Figure 2-2 illustrates the location of the
communication port.
Programming requires a standard 9-pin serial communication
cable connected between the DECS-100 and an IBM-compatible
PC or handheld computer operating with BESTCOMS software.
BESTCOMS software is a Microsoft Windows-based communication software package that is supplied with the DECS-100. A
detailed description of BESTCOMS software is provided in
Section 5, BESTCOMS Software for the Windows Operating
System.
WARNING!
Lethal voltage is present at the rear panel when the unit is
energized. Rear panel connections should be made only
when the unit is de-energized.
3-1
3-1
3-1
3-1
3-1
3-2
3-2
3-2
3-2
3-2
3-2
3-2
3-2
3-2
3-3
3-3
3-3
3-3
3-3
3-3
3-3
3-3
3-3
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-5
3-5
3-5
3-5
3-5
3-6
3-6
3-6
Figures
Figure 3-1. Simplified Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3-1
Generator Voltage
Generator voltage is monitored at terminals E1 (A-phase), E2 (B-phase), and E3 (C-phase). Nominal voltages
of up to 600 Vac may be sensed at these terminals. Voltage applied to these inputs is scaled and conditioned
before being applied to the input of the ADC. The voltage signal from phase C and A (VC-A) of the generator
is used by the ADC to calculate the Rms value of generator voltage across phases C and A. Likewise, the
voltage signal from phase C and B (VC-B) of the generator is used by the ADC to calculate the Rms value of
generator voltage across phases C and B. The Rms value of generator phase B to phase A voltage (VB-A) is
calculated by the microprocessor from the phase C to phase A signal (VC-A)and the phase C to phase B (VC-B)
signal.
Additionally, the generator phase C to phase A (VC-A) signal is applied to a filtered zero cross detector circuit.
This signal is applied to the microprocessor and is used to calculate generator frequency.
Phase B Line Current
The phase B line current (IB) signal is developed through a customer supplied current transformer (CT) and
monitored through terminals CT1 and CT2. Depending on the option selected, current up to 1 ampere (style
number xx1) or 5 amperes (style number xx5) rms may be monitored at these terminals. The current
monitored at these terminals is scaled and conditioned by an internal current transformer and active circuitry
for use by the ADC. The signal applied to the ADC is used to calculate the rms value of phase B line current.
Additionally, the phase angle between phase B line current and phase C to phase A generator voltage is
calculated for use during Droop and Var/Power Factor operation.
Accessory Input (Auxiliary Adjust)
This input allows adjustment of the DECS-100 regulation setpoint by the application of a positive or negative
dc voltage across terminals A and B. Positive voltage applied to terminal A with respect to terminal B will
cause the active mode setpoint to increase. Voltage from 3 to +3 Vdc may be applied to this input. The circuit
induces a 1,000-ohm burden on the dc source. The Application of a 3 Vdc signal corresponds to a 30
percent change in setpoint.
Field Voltage
Voltage (VFIELD) across the regulator field output terminals, F+ and F, is monitored, scaled, and
conditioned before being applied to the ADC. This signal is used to calculate the dc value of field voltage
for use in system protection.
Field Current
Current (IFIELD) through the main power output switch is converted to a proportional voltage level. This voltage
signal is scaled and conditioned before being applied to the input of the ADC. The result is used to calculate
the dc value of field current for use in the Manual mode of operation as well as protection of the system.
Contact Input Circuits
Five contact input circuits powered from an internal 13 Vdc power supply provide input control from usersupplied, isolated, dry-type contacts.
Raise
Closing a contact across terminals 6U and 7 causes the active operating setpoint to increase. This function
is active as long as the contact is closed.
Lower
Closing a contact across terminals 6D and 7 causes the active operating setpoint to decrease. This function
is active as long as the contact is closed.
Var/Power Factor Control (52J/K) Option
Closing a contact across terminals 52J and 52K disables var/power factor control. An open contact enables
the DECS-100 to control the generator reactive power in either the var or the power factor mode. The contact
3-2
has no effect when this function is not enabled in the software. For more information, see Parallel Generator
Compensation (52L/M) and Voltage Matching Control Option.
Parallel Generator Compensation (52L/M)
Closing a contact across terminals 52L and 52M disables parallel operation. An open contact enables parallel
operation and the DECS-100 operates in reactive droop compensation mode.
If the Var/Power Factor Control option is present and is enabled in the software, the 52J/K input has priority.
Therefore, if the 52J/K and the 52L/M inputs are both open, the system operates in var/power factor mode.
For more information, see Voltage Matching Control Option.
Voltage Matching Control Option
If the Voltage Matching option is enabled in the software, closing a contact across terminals VM and VMC
causes the DECS-100 to operate in the voltage matching mode. An open contact disables voltage matching.
Voltage matching is also disabled when either the 52J/K or 52L/M inputs are open.
RS-232 Communication Port
The communication port provides the interface for user programming (setup) of the DECS-100. Connection
is made to the female RS-232 (DB-9) connector with a user-supplied, standard 9-pin cable. The
communication port is optically isolated and is powered from a transformer-isolated supply.
Microprocessor
The microprocessor is the heart of the DECS-100 and performs measurement, computation, control, and
communication functions by the use of its embedded programming and the nonvolatile settings stored in its
memory.
Power Input Stage
Input power applied to terminals 3, 4, and 5 is rectified and filtered before being applied to the power amplifier
and the power supply. Input power may be single-phase or three-phase in the range of 88 to 250 Vac at a
frequency of 50 to 400 hertz.
The input power source should be properly fused for the application.
Power Supply
The internal switch-mode power supply receives power from the power input stage and supplies power at the
required dc voltage levels to the internal circuitry of the DECS-100.
Power Amplifier Stage
The power amplifier receives power from the power input stage and supplies a controlled amount of power
to the exciter field via terminals F+ and F. The amount of power supplied to the exciter field is based on
gating pulses received from the microprocessor. The power amplifier uses a solid state power switch to
provide the required power to the exciter field. Power amplifier output to the field is rated up to 63 Vdc at 7 Adc
continuous and 135 Vdc at 15 Adc for 10 seconds.
Front Panel Indicators
Seven front panel LED indicators light to indicate various protective functions and operating modes. Section
2, Human-Machine Interface provides more information about the front panel indicators.
Relay Output
A common alarm output contact is provided through terminals AL1 and AL2. This normally open, form A
contact annunciates alarm or trip conditions. The relay output is non-latching.
3-3
through the Parallel Generator Compensation contact input circuit (terminals 52L and 52M). Droop is also
disabled when operating in var or power factor control modes.
Underfrequency
When generator frequency drops below the selected knee frequency setpoint, the voltage setpoint is
automatically adjusted by the DECS-100 so that generator voltage follows the selected PU (per unit) V/Hz
curve. When operating on the selected PU V/Hz curve, the UNDERFREQUENCY ACTIVE indicator lights on
the front panel and in BESTCOMS. Underfrequency control is disabled below 12 hertz. The knee frequency
is adjustable from 40 to 65 hertz in 0.1 hertz increments and the PU V/Hz curve may be set at a slope of 0
to 3 in 0.01 steps through BESTCOMS software. A slope of 0 effectively disables the underfrequency function.
The DECS-100 has a minimum regulation point of approximately 30 percent of the nominal setpoint.
Protection
The DECS-100 includes four protective functions: overexcitation shutdown, generator overvoltage shutdown,
loss of generator sensing shutdown or transfer, and overexcitation limiting. Each function has a corresponding
front panel indicator that lights when the function is active. An active function is also annunciated through
BESTCOMS software.
Overexcitation Shutdown (Field Voltage)
This function is enabled or disabled through BESTCOMS software. When enabled, if field voltage exceeds
the adjustable field overvoltage setpoint for 10 seconds, the OVEREXCITATION SHUTDOWN indicator on
the front panel and in BESTCOMS lights, the relay output closes, and the DECS-100 shuts down. When the
DECS-100 is powered up following an overexcitation shutdown, the OVEREXCITATION SHUTDOWN
indicator will light for 5 seconds. The Field Overvoltage setpoint is adjustable from zero to 250 Vdc in integer
steps.
Generator Overvoltage Shutdown
The DECS-100 monitors the sensed generator output voltage. If it exceeds the adjustable Generator
Overvoltage setpoint of the nominal setpoint for 0.75 seconds, the GENERATOR OVERVOLTAGE indicator
lights on the front panel HMI and in BESTCOMS, the relay output closes, and the DECS-100 shuts down.
When the DECS-100 is powered up following a generator overvoltage shutdown, the GENERATOR
OVERVOLTAGE indicator will light for 5 seconds. The Generator Overvoltage setpoint is adjustable from 100
to 120 percent in integer steps.
Loss of Generator Sensing Shutdown or Transfer
The DECS-100 monitors the sensed generator output voltage and takes protective action if a loss of sensing
voltage is detected. A loss of sensing voltage is detected during the following conditions.
C
C
C
The sensed voltage is less than 50 percent of the rated voltage (one-phase or three-phase sensing).
A total loss of any phase occurs (three-phase sensing).
The voltage difference between any phase (line-to-line) and the three-phase average exceeds 20 percent
of nominal (three-phase sensing).
A time delay of zero to 25 seconds is adjustable through BESTCOMS software. This delays the protective
action in order to allow field forcing in applications that do not sense B-phase generator current. The default
time delay setting is 10 seconds.
BESTCOMS software allows the selection of one of two protective actions for a loss of sensing. Either a
complete shutdown or a transfer to Manual mode may be selected.
If shutdown is selected and a loss of sensing occurs, the LOSS OF GENERATOR SENSING indicator on the
front panel and in BESTCOMS lights, the relay output closes, and the DECS-100 shuts down after the
adjustable time delay expires. When the DECS-100 is powered up following a loss of generator sensing
shutdown, the LOSS OF GENERATOR SENSING indicator will light for five seconds. However, if the loss of
sensing conditions still exists, the DECS-100 will not shut down due to loss of sensing until the soft-start time
delay and the loss of sensing time delay expires.
If transfer to Manual is selected and a loss of sensing occurs, the relay output closes, and the DECS-100
transfers to the Manual mode of operation after the adjustable time delay expires. The DECS-100 will remain
DECS-100 Functional Description
3-5
in this mode of operation until switched via BESTCOMS. Prior to selecting transfer to Manual on loss of
sensing, it is necessary to determine an appropriate Manual (FCR) mode setpoint level to be transferred to.
An inappropriate excitation level could result in severe damage to equipment.
This function is disabled when the frequency decreases below 12 hertz or when a generator short circuit
condition is detected. A generator short-circuit is determined when the B-phase CT current exceeds three
times the per unit value. Loss of sensing shutdown or transfer is not active during the soft-start time.
Overexcitation Limiting (Field Current)
The DECS-100 field current limit is adjustable from 0 to 15 amperes in 0.1 ampere increments with an
adjustable time delay that has a range of 0 to 10 seconds in 1 second increments. Both settings are made
through BESTCOMS software. When the overexcitation limit is exceeded, the OVEREXCITATION LIMITING
indicator on the front panel and in BESTCOMS lights. When the adjustable time delay expires, the relay output
closes and the DECS-100 shuts down. When the DECS-100 is powered up following overexcitation limiting,
the OVEREXCITATION LIMITING indicator will light for 5 seconds.
Soft Start
The DECS-100 also incorporates an adjustable soft start feature that controls the time for generator voltage
or field current to ramp to the regulation setpoint. The ramp rate is adjustable from 1 to 7,200 seconds in 1
second increments through BESTCOMS. The underfrequency feature is also active during soft start and takes
priority in control of the generator voltage in an effort to minimize voltage overshoot.
Voltage Matching (Optional)
Voltage matching is useful when the PT ratios in an application are not matched exactly. The DECS-100
voltage matching option automatically matches the rms generator output voltage with the rms bus voltage prior
to synchronizing. The DECS-100 compares and matches the generator voltage with the bus voltage by
adjusting the dc excitation current. As long as the values of generator and bus voltage (applies to the DECS100 voltage sensing inputs) are within the same range, voltage matching can be achieved. (Refer to Section
1, General Information, Specifications for the four generator and bus sensing voltage ranges.) for Voltage
matching is automatically disabled if bus voltage is not within 10 percent of the nominal sensing range
selected. The voltage matching option is enabled and disabled through BESTCOMS software. When enabled
in BESTCOMS, voltage matching is enabled or disabled through external contacts connected to the voltage
matching contact input circuit. Using BESTCOMS to enter the generator PT ration and bus PT ratio will
automatically compensate for the offset. The voltage matching speed setting is adjustable from 1 to 300
seconds in 0.01 second increments. This setting changes the rate at which the DECS-100 matches the
generator input level with the bus input level.
3-6
SECTION 4 INSTALLATION
TABLE OF CONTENTS
SECTION 4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
DECS-100 Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Bus Voltage Sensing Inputs (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Generator Voltage Sensing Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Phase B Line Current Sensing Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Accessory Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Raise and Lower Contact Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Var/Power Factor Control Contact Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Parallel Generator Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Parallel Control and Var/PF Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Voltage Matching (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Power Supply Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Chassis Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Power (Field) Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Relay Output (Alarm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
DECS-100 Connections for Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
INSTALLATION FOR CE COMPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
PRELIMINARY SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Operating Power Considerations During DECS-100 Programming . . . . . . . . . . . . . . . . . . . . . 4-13
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Figures
Figure 4-1. DECS-100 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-2. Cutout and Drilling Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Figure 4-3. DECS-100 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Figure 4-4. RS-232 Port Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-5. Personal Computer to DECS-100 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-6. Typical Connections for PMG Application with ABC Rotation and Three-Phase Sensing . . 4-8
Figure 4-7. Typical Connections for PMG Application with ABC Rotation and Single-Phase Sensing . . 4-9
Figure 4-8. Typical Connections for Shunt Application with ABC Rotation and Three-Phase Sensing 4-10
Figure 4-9. Typical Connections for Shunt Application with ABC Rotation and Single-Phase Sensing 4-11
Figure 4-10. Cross-Current (Reactive Differential) Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Figure 4-11. Operating Power Connections for DECS-100 Programming (Input Voltage >120 Vac) . . 4-13
Tables
Table 4-1. Bus Voltage Sensing Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-2. Generator Voltage Sensing Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-3. 52L/M and 52J/K Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-4. Communication Port Pin Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DECS-100 Installation
4-5
4-5
4-6
4-7
SECTION 4 INSTALLATION
GENERAL
DECS-100 Digital Excitation Control Systems are delivered in sturdy cartons to prevent shipping damage.
Upon receipt of a system, check the part number against the requisition and packaging list for agreement.
Inspect for damage, and if there is evidence of such, immediately file a claim with the carrier and notify the
Basler Electric Regional Sales Office, your Sales Representative or a Sales Representative at Basler Electric,
Highland, Illinois.
If the unit is not installed immediately, store it in the original shipping package in a moisture and dust free
environment.
MOUNTING
The DECS-100 is normally located in the generator conduit box. It is designed for behind the panel mounting
and requires a cutout for front panel viewing. Supplied mounting hardware consists of six #12 thread-forming
screws that pass through mounting holes in the conduit box and thread into the plastic shell of the DECS-100.
The recommended torque range for the steel mounting screws is 4.07 to 4.52 newton-meters (36 to 40 inchpounds). The unit must be mounted where the ambient temperature does not exceed the allowable
environmental conditions called out in Section 1, General Information, Specifications. DECS-100 package
dimensions are shown in Figure 4-1. Cutout and drilling dimensions are shown in Figure 4-2. Drawing
dimensions are shown in inches and millimeters (in parenthesis).
DECS-100 Installation
4-1
4-2
DECS-100 Installation
DECS-100 Installation
4-3
CONNECTIONS
DECS-100 connections are dependent on the application and excitation scheme. Incorrect wiring may result
in damage to the unit. Check the part number to ensure that you have the correct unit before connecting and
applying power.
NOTE
Be sure that the DECS-100 is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the unit case.
When the unit is configured in a system with other devices, connect a separate
lead from the ground bus to each DECS-100 unit.
DECS-100 Terminations
DECS-100 units have two types of interface terminals (Figure 4-3). One type is quarter-inch, quick-connect
terminals and the other is a 9-pin DB9 connector. All terminals are located on the rear of the unit. The quarterinch, quick-connect terminal labels are located on the rear of the case. Wires performing common functions,
such as voltage sensing leads, should be grouped together. The 9-pin DB-9 type connector is used for
temporary interface with both IBM compatible PCs and hand-held computers.
Figure 4-3 shows the terminal connections located on the rear panel of the DECS-100. Except as noted
above, connections should be made with minimum wire size of 14 AWG.
DECS-100 Installation
Terminal
B1
B3
3-Phase
Generator
Phase
Terminal
E1
E2
E3
E1
E2, E3
1-Phase
DECS-100 Installation
4-5
52L/M
52J/K
closed
closed
Single unit/stand-alone
open
closed
open
open
4-6
DECS-100 Installation
Communication Port
The RS-232 port on the rear panel uses a DB-9
female connector. Figure 4-4 Illustrates the pin
assignments of the communication port and Table 44 Identifies the RS-232 connector pin functions. A
standard communication cable terminated with a
DB-9 male connector is used for PC interface with
the DECS-100 as shown in Figure 4-4.
Function
Name
Direction
N/C
N/A
Transmit Data
TXD
From DECS-100
Receive Data
RXD
To DECS-100
N/C
Signal Ground
N/A
GND
N/A
N/C
N/A
N/C
N/A
N/C
N/A
N/C
N/A
4-7
Figure 4-6. Typical Connections for PMG Application with ABC Rotation and Three-Phase Sensing
4-8
DECS-100 Installation
D2881-09
05-10-02
FIELD
OUTPUT
FF+
10
GEN
PMG
INPUT
POWER
3
4
5
11
10
CTB
CT1 CT2
CTB
10
10
7
10
GND
GROUND
Generator
Side
SENSING
VOLTAGE
E3 E2
E1
Utility
Side
52
B1
B3
BUS
52b
10
10
AL 2
5
AUX.
ADJUST
A
B
S3
8
9
10
11
10
VOLTAGE
MATCHING
VM VMC
S1
AL 1
ALARM
NOTES:
S2
10
Figure 4-7. Typical Connections for PMG Application with ABC Rotation and Single-Phase Sensing
DECS-100 Installation
4-9
D2881-11
05-10-02
FIELD
OUTPUT
FF+
10
GEN
PMG
INPUT
POWER
3
4
5
10
CTB
CT1 CT2
CTB
10
10
7
10
GND
GROUND
Generator
Side
SENSING
VOLTAGE
E3 E2
E1
Utility
Side
52
B1
B3
BUS
S2
10
10
AL 2
AUX.
ADJUST
A
B
S3
8
9
10
11
10
VM VMC
VOLTAGE
MATCHING
S1
AL 1
ALARM
NOTES:
52b
10
Figure 4-8. Typical Connections for Shunt Application with ABC Rotation and Three-Phase Sensing
4-10
DECS-100 Installation
D2881-10
05-10-02
FIELD
OUTPUT
FF+
11
10
GEN
INPUT
POWER
3
4
5
12
10
CTB
CT1 CT2
CTB
10
10
7
10
GND
GROUND
Generator
Side
SENSING
VOLTAGE
E3 E2
E1
Utility
Side
52
B1
B3
BUS
1
3
10
AL 2
5
AUX.
ADJUST
A
B
S3
10
11
12
3
4
10
VM VMC
VOLTAGE
MATCHING
S1
AL 1
ALARM
10
S2
NOTES:
52b
10
Figure 4-9. Typical Connections for Shunt Application with ABC Rotation and Single-Phase Sensing
DECS-100 Installation
4-11
D2659-18
05-10-02
FIELD
OUTPUT
FF+
11
10
GEN
INPUT
POWER
5
3
4
12
10
CTB
CT1 CT2
CTB
10
10
7
10
GND
GROUND
Generator
Side
SENSING
VOLTAGE
E3 E2
E1
Utility
Side
52
B1
B3
BUS
52b
10
10
AL 2
AUX.
ADJUST
A
B
S3
8
9
10
11
12
10
VM VMC
VOLTAGE
MATCHING
S1
AL 1
ALARM
NOTES:
S2
10
CT
GEN 1
0.1
CTB1
CTB2
DECS-100
DECS-100
LOAD
CCC
ENABLE
CONTACT
0.1
CTB1
CTB2
D2880-16
05-19-00
GEN 2
CT
PRELIMINARY SETUP
WARNING!
Lethal voltage is present at the rear panel when the unit is energized. Rear panel
connections should be made only when the unit is de-energized.
Before starting the generator and DECS-100 for the first time, proceed as follows.
4-12
DECS-100 Installation
1. Tag and disconnect all wiring to the DECS-100. Be sure to insulate the wire terminals to prevent a
short circuit.
2. Start the prime mover and perform all engine governor adjustments.
3. After all initial governor adjustments have been made, shut down the prime mover.
4. Connect only the DECS-100 power input terminals to an auxiliary power source. Before applying
DECS-100 operating power, observe the precautions noted in Operating Power Considerations During
DECS-100 Programming.
5. Perform all initial DECS-100 settings by connecting a PC or handheld operating with BESTCOMS to
the rear communication port of the DECS-100 and save all new settings.
6. Remove power from the DECS-100.
7. Connect the rest of the DECS-100 leads using the tagged identification.
8. Start the prime mover/generator and perform the final adjustments at rated speed and load.
9. After the initial startup, the DECS-100 should not require any further adjustments unless there is a
change in the system.
Operating Power Considerations During DECS-100 Programming
Due to its pulse-width modulated (PWM) power stage, the DECS-100 operating power input has a substantial
amount of capacitance. High inrush current can be experienced upon DECS-100 power-up when a solid
power source is used. When powering the DECS-100 for programming with voltage greater than 120 Vac,
high inrush current may damage the unit. Therefore, during programming, DECS-100 operating power should
be within the range of 30 to 120 Vac (50/60 Hz).
CAUTION
When programming the DECS-100 without the generator spinning, the
connections to DECS-100 terminals F+ and F should be removed.
If it is necessary to perform programming with applied operating power over 120 Vac, a current-limiting resistor
must be connected between the power source and DECS-100 (Figure 4-11). A resistor rated at 20 ohms and
20 watts may be used to limit the inrush current to a safe level. During the duration of the inrush current (about
one cycle), the resistor power rating will be exceeded. Once the inrush has passed, the resistor power
dissipation level will be minimal. If desired, a 10 ohm, 50 watt resistor may be used instead.
These special operating considerations are to be observed only during DECS-100 programming. Applications
where the DECS-100 is powered from the generator output (shunt powered) or a permanent magnet generator
(PMG) are still valid within the constraints given in Section 1, General Information, Specifications.
ADJUSTMENTS
All adjustments are made using external switching, or with BESTCOMS software via the rear panel
communication port. See Sections 5 and 6 for more information regarding setting adjustments with
BESTCOMS software.
DECS-100 Installation
4-13
Figures
Figure 5-1. Basler Electric Folder Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-3. System Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-2. BESTCOMS Title and Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-4. Communication Port Menu Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-5. Password Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-6. Communication Initiation Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-7. Wait Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-8. System Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Figure 5-9. Setting Adjustments Screen, Setpoint Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Figure 5-10. Setting Adjustments Screen, Startup Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Figure 5-11. Control Gain Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Figure 5-12. Analysis Screen, AVR Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Figure 5-13. AVR Setpoint Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Figure 5-14. Analysis Screen, FCR Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Figure 5-15. FCR Setpoint Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Figure 5-16. Analysis Screen, PF Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Figure 5-17. PF Setpoint Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Figure 5-18. Analysis Screen, VAR Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Figure 5-19. Var Setpoint Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Figure 5-20. Protection and Relay Settings Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Figure 5-21. Metering, Operation, and Alarms, Operation Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Figure 5-22. Metering, Operation, and Alarms, Alarm/Status Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Figure 5-23. PID Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
Figure 5-24. User Information Dialog Box for Settings List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
Figure 5-25. Settings Upload Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
Figure 5-26. Password Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
Figure 5-27. DECSLoad Menu Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Figure 5-28. Software Uploading Advisory Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-29. DECS-100 Embedded Program Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-30. Retrieved DECS-100 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-31. Settings File Reminder Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
Figure 5-32. Open Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
Figure 5-33. File Transfer Progress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
Figure 5-34. DECS-100 Information After Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
Tables
Table 5-1. DECS-100 Stability Range Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Table 5-2. Analysis Screen Tab Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
ii
INSTALLATION
BESTCOMS-DECS100 software operates with IBM compatible personal computers (PCs) using Microsoft
Windows 95, Windows 98, or Windows NT operating systems. The minimum recommended operating
requirements are listed below.
C
C
C
IBM compatible PC, 486DX2 or faster (100 MHz or higher microprocessor is recommended)
CD-ROM Drive
One available serial port
Installing BESTCOMS-DECS100
BESTCOMS-DECS100 software contains a setup utility that installs the program on your PC. An uninstall
utility is loaded with the program that can be used to remove BESTCOMS from your PC if desired. Use the
following procedure to install BESTCOMS-DECS100.
1. Insert the CD-ROM into the PC CD-ROM drive.
2. When the DECS-100 Setup and Documentation CD menu appears, click the Install button for the
BESTCOMS PC Program. The setup utility automatically installs BESTCOMS-DECS100 on your PC.
When BESTCOMS is installed, a Basler Electric
folder is added to the Windows program menu.
This folder is accessed by clicking the Start button
and pointing to Programs. As illustrated in Figure
5-1, the Basler Electric folder contains icons for
the BESTCOMS-DECS100 program and a utility
to remove BESTCOMS.
STARTING BESTCOMS
BESTCOMS is started by clicking the Windows
Start button, pointing to Programs, the Basler
Electric folder, and then clicking the BESTCOMSDECS100 icon. At startup, a dialog box with the
program title and version number is displayed briefly
(Figure 5-2). After this dialog box is displayed, the
System Configuration screen is displayed (Figure
5-3).
DECS-100 BESTCOMS for Windows OS
CAUTION
When applying operating power to the DECS-100
for programming purposes, observe the precautions called out in Section 4, Installation, Preliminary Setup.
5-1
Establishing Communication
Communication between BESTCOMS and the
DECS-100 must be established before viewing
metering values or reading or changing settings.
BESTCOMS screen settings are updated only after
communication is opened or the communication
settings have been changed.
Open the DECS-100 communication port by clicking
on Communications on the menu bar, hovering the
mouse pointer over Open Comm Port, and clicking
RS-232 Port. Figure 5-4 illustrates the menu
selections for opening the DECS-100 communication
port.
When RS-232 Port is selected, the Password dialog box of Figure 5-5 appears and prompts you to enter a
password. Each DECS-100 is delivered with decs as the default password. See the Password Protection
sub-section for information about changing the password.
After the correct password is entered, the Communication Initiation screen of Figure 5-6 is displayed. Select
Comm 1, Comm 2, Comm 3, or Comm 4 as the active communication port on your PC and click the Initialize
button. BESTCOMS initializes communication by obtaining the configuration settings from the DECS-100.
NOTE
CHANGING SETTINGS
Settings are arranged into six groups.
C System Configuration
C Setting Adjustments
C Control Gain
C
C
C
Analysis
Protection/Relay
Metering/Operation
Each setting group has a corresponding button (shown in Figure 5-3) that can be selected to access that
group of settings. The six setting groups can also be accessed by clicking Screens on the menu bar and then
selecting the desired setting group from the list. Once a setting group is accessed, the individual settings of
the group can be viewed and changed.
A setting is changed by clicking within the setting field and typing the new setting. The range limits of a setting
can be viewed by double-clicking the setting. Once all desired setting changes have been made on a setting
group screen, the settings must be sent to the DECS-100 before viewing other screens. Otherwise, the
settings changes will be lost. Settings changes can be sent to the DECS-100 by clicking the SendToDECS
button. Settings can also be sent to the DECS-100 by clicking Communications on the menu bar and clicking
Send To DECS.
SETTING DEFINITIONS
Each of the six setting groups has a corresponding BESTCOMS screen. The settings of each screen are
categorized by one or more tabs. In the following paragraphs, settings are arranged and defined according
to the organization of the BESTCOMS screens and tabs.
System Configuration
The System Configuration screen consists of one tab labeled System Settings. Click the Configure button
to access the System Configuration screen or click Screens on the menu bar and click System
Configuration.
DECS-100 BESTCOMS for Windows OS
5-3
System Settings
System settings are shown in Figure 5-8 and are described in the following paragraphs.
5-4
Setting Adjustments
The Setting Adjustments screen consists of two tabs: Setpoint and Startup.
Setpoint Tab
The Setpoint tab settings of the Setting Adjustments screen are shown in Figure 5-9. Each setting of the
Setpoint tab is described in the following paragraphs.
5-5
Generator
Size
Generator (Tdo)
Exciter (Texc)
Stability
Range
SMALL
1.0
0.17
1.5
0.25
2.0
0.33
2.5
0.42
3.0
0.50
3.5
0.58
4.0
0.67
4.5
0.75
5.0
0.83
5.5
0.92
10
6.0
1.00
11
6.5
1.08
12
7.0
1.17
13
7.5
1.25
14
8.0
1.33
15
8.5
1.42
16
9.0
1.50
17
9.5
1.58
18
10.0
1.67
19
10.5
1.75
20
LARGE
5-7
AVR/FCR - Integral Gain KI. This setting selects the integral constant (KI) stability parameter. The DECS-100
supplies a value that is equivalent to KI multiplied by the integral of the error between the voltage setpoint and
the actual generator output voltage. KI values of 0.01 to 1,000 may be entered in increments of 0.01.
Increasing the value of KI decreases the time required to reach steady state.
AVR/FCR - Derivative Gain KD. This setting selects the derivative constant (KD) stability parameter. The
DECS-100 provides an output value that is equivalent to KD multiplied by the derivative of the error between
the voltage setpoint and the actual generator output voltage. KD values of 0 to 1,000 may be entered in
increments of 0.01.
Increasing the value of KD reduces transient response ringing.
AVR/FCR - AVR<=Loop Gain Kg=>FCR. This setting adjusts the loop-gain level of the PID algorithm. Loop
Gain values of 0 to 1,000 may be entered for AVR and FCR operation in increments of 0.01.
VAR/PF - PF Integral Gain KI. This setting adjusts the integral gain and determines the characteristic of the
DECS-100 dynamic response to a changed PF setting. PF KI values of 0 to 1,000 may be entered in
increments of 0.01.
VAR/PF - Var Integral Gain KI. This setting adjusts the integral gain and determines the characteristic of the
DECS-100 dynamic response to a changed var setting. Var KI values of 0 to 1,000 may be entered in
increments of 0.01.
VAR/PF - VAR<=Loop Gain Kg=>PF. This setting adjusts the loop-gain level of the PI algorithm for var or
power factor control. Loop Gain values of 0 to 1,000 may be entered for var and power factor operation in
increments of 0.01.
OEL - Integral Gain KI. This setting controls the rate at which the DECS-100 responds during an
overexcitation event. KI values of 0 to 1,000 may be entered in increments of 0.01.
OEL - Loop Gain Kg. This setting adjusts the coarse loop-gain level of the PID algorithm for the over-excitation
limiting function. Loop Gain values of 0 to 1,000 may be entered in increments of 0.01.
Analysis
Click the Analysis button or click Screens on the Menu bar and click Analysis to view the Analysis screen.
The Analysis screen consists of four tabs: VAR, PF, AVR, and FCR. Each of the tabs displays four metered
sensing values and has five alarm signal indicators. Metered sensing values include Vrms (rms voltage), Ifd
(dc field current), reactive power (vars), and power factor (PF). Alarm signal indicators include Overexcitation
Shutdown, Generator Overvoltage, Loss of Generator Sensing, Overexcitation Limiting, and Underfrequency
Active.
The operating status and control mode of the DECS-100 determine which tabs of the Analysis screen are
enabled and can be accessed by the user. Table 5-2 lists the DECS-100 operating status and control modes
that enable the four tabs of the Analysis screen.
Table 5-2. Analysis Screen Tab Combinations
Control Mode
Operating Status
Tab Enabled
AVR
OFF
AVR
AVR
PF
AVR, PF
AVR
VAR
AVR, VAR
FCR
N/A
FCR
Control mode and operating status selections are made at the Operation tab of the BESTCOMS Metering
screen and are discussed later in this section.
5-8
AVR Tab
Figure 5-12 illustrates the settings, sensing values, and alarm signal indicators of the AVR tab. The settings
of the AVR tab make it possible to increment and decrement the AVR setpoint of the DECS-100.The sensing
values and alarm signal indicators of the AVR tab are also displayed by the other tabs of the Analysis screen.
5-9
FCR Tab
Figure 5-14 illustrates the settings, sensing values, and alarm signal indicators of the FCR tab. The settings
of the FCR tab make it possible to increment and decrement the FCR setpoint of the DECS-100. The sensing
values and alarm signal indicators of the FCR tab are also displayed by the other tabs of the Analysis screen.
5-10
Field Current Step Response - Decrement of FCR Setpoint (A). These two fields indicate the change that will
occur to the FCR setpoint when the corresponding Decrement button is clicked. The "% decrease" field is
used to set and indicate the percentage that the FCR setpoint is decreased when the Decrement button is
clicked. The "FCR Setpoint =" field indicates the value of current that corresponds to the "% decrease" field.
The FCR setpoint changes to this value when the adjacent button is clicked. When clicked, the Decrement
button changes from gray to red to indicate that the FCR setpoint has decreased to the value in the "FCR
Setpoint =" field.
Field Current Step Response - Meter Value. This field and the dial pointer indicate the value of the selected
FCR setpoint. When the AVR setpoint is changed by clicking the increment, decrement, or setpoint button,
the meter value field and dial pointer indicate the new setpoint value. A new FCR setpoint can be typed
directly into the Meter Value field or selected by dragging the dial pointer to the desired value. The new value
is sent to the DECS-100 by clicking the Send button.
Field Current Step Response - Current Setpoint. The
active DECS-100 setpoint (adjusted by using any of the
previously mentioned methods) is displayed in this field.
To return the FCR setpoint to the nominal setting, the
button adjacent to the FCR Setpoint (A) (Nominal) field
should be clicked. If the FCR tab is left to view other
tabs or screens without returning the FCR setpoint to
nominal, the dialog box of Figure 5-15 appears. The
FCR setpoint is returned to nominal by clicking Yes. The
AVR setpoint is maintained at the current value by
clicking No.
PF Tab
Figure 5-16 illustrates the settings, sensing values, and alarm signal indicators of the PF tab. Each setting of
the PF tab is described in the following paragraphs.
5-11
Power Factor Step Response - Increment of PF Setpoint. This field indicates the new PF setpoint that is
established when the corresponding increment button is clicked. Any setpoint value within range or higher
than the existing setpoint value can be typed into the Increase PF Setpoint = field. The PF setpoint changes
to this value when the adjacent button is clicked. When clicked, the Increment button changes from gray to
red to indicate that the PF setpoint has increased to the value in the Increase PF Setpoint = field.
Power Factor Step Response - Decrement of PF Setpoint. This field indicates the new PF setpoint that is
established when the corresponding decrement button is clicked. Any setpoint value within range or lower than
the existing setpoint value can be typed into the Decrease PF Setpoint = field. The PF setpoint changes to
this value when the adjacent button is clicked. When clicked, the Decrement button changes from gray to red
to indicate that the PF setpoint has decreased to the value in the Decrease PF Setpoint = field.
Power Factor Step Response - PF Value. This field and the dial pointer indicate the value of the selected PF
setpoint. When the PF setpoint is changed by clicking the increment, decrement, or setpoint button, the meter
value field and dial pointer indicate the new setpoint value. A new PF setpoint can be typed directly into the
PF Value field or selected by dragging the dial pointer to the desired value. The new value is sent to the
DECS-100 by clicking the Send button.
Power Factor Step Response - Current Setpoint. The
active DECS-100 setpoint (adjusted by using any of the
previously mentioned methods) is displayed in this field.
To return the PF setpoint to the nominal setting, the
button adjacent to the PF Setpoint (Nominal) field
should be clicked. If the PF tab is left to view other tabs
or screens without returning the PF setpoint to nominal,
the dialog box of Figure 5-17 appears. The PF setpoint
is returned to nominal by clicking Yes. The PF setpoint
is maintained at the current value by clicking No.
Figure 5-17. PF Setpoint Dialog Box
VAR Tab
Figure 5-18 illustrates the settings, sensing values, and alarm signal indicators of the VAR tab. Each setting
of the VAR tab is described in the following paragraphs.
Reactive Power Step Response - VAR Setpoint (%) (Nominal). This read-only field indicates the var setpoint.
(The var setpoint is set by using the Setpoint tab of the Setting Adjustments screen.) The value displayed in
the VAR Setpoint field is selected by clicking the adjacent button. Clicking this button sends the var setpoint
value to the DECS-100 and changes the color of the pushbutton from gray to red.
Reactive Power Step Response - Increment of VAR Setpoint (%). This field indicates the increase that occurs
to the FCR setpoint when the corresponding Increment button is clicked. The Increase VAR Setpoint = field
is used to set and indicate the percentage that the var setpoint is increased to when the Increment button is
clicked. Any setpoint value (expressed as a percent of nominal) within range or higher than the existing
setpoint value can be typed into the Increase VAR Setpoint = field. The var setpoint changes to the new
value when the adjacent button is clicked. Clicking this button sends the var setpoint value to the DECS-100
and changes the color of the pushbutton from gray to red.
Reactive Power Step Response - Decrement of VAR Setpoint (%). This field indicates the decrease that
occurs to the FCR setpoint when the corresponding Decrement button is clicked. The Decrease VAR
Setpoint = field is used to set and indicate the percentage that the var setpoint is decreased to when the
Decrement button is clicked. Any setpoint value (expressed as a percent of nominal) within range or lower
than the existing setpoint value can be typed into the Decrease VAR Setpoint = field. The var setpoint
changes to the new value when the adjacent button is clicked. Clicking this button sends the var setpoint value
to the DECS-100 and changes the color of the pushbutton from gray to red.
Reactive Power Step Response - Meter Value. These fields and the dial pointer indicate the value of the
selected var setpoint. When the var setpoint is changed by clicking the increment, decrement, or setpoint
button, the meter value fields and dial pointer indicate the setpoint value. A new var setpoint, expressed as
a kvar value or a percentage of nominal, can be typed directly into either Meter Value field or selected by
dragging the dial pointer to the desired value. The new value is sent to the DECS-100 by clicking the Send
button.
Reactive Power Step Response - Current Setpoint (%).
The active var setpoint (adjusted by using any of the
previously mentioned methods) is displayed in this field.
To return the var setpoint to the nominal setting, the
button adjacent to the VAR Setpoint (%) (Nominal)
field should be clicked. If the VAR tab is left to view
other tabs or screens without returning the VAR setpoint
to nominal, the dialog box of Figure 5-19 appears. The
var setpoint is returned to nominal by clicking Yes. The
var setpoint is maintained at the current value by
clicking No.
Protection Settings
The Protection Settings screen consists of one tab labeled Protection. Click the Protection button to access
the Protection screen or click Screens on the menu bar and click Protection/Relay.
Protection Tab
Protection settings are shown in Figure 5-20 and are described in the following paragraphs.
OEL - Current Level (A). The value of current in this field determines the excitation level that will cause the
DECS-100 to issue an overexcitation limit alarm. A current level of 0 to 15 A may be entered in 0.001
increments. When the level of field current increases above the value of this field, the OVEREXCITATION
SHUTDOWN LED on the front panel lights and the OEL time delay starts timing down.
OEL - Alarm Time Delay (sec). The value of this field determines the time delay between when the DECS-100
recognizes an overexcitation condition and the DECS-100 Alarm output (terminals AL1, AL2) closes. A time
delay of 0 to 10 seconds may be entered in 1 second increments.
5-13
Generator Overvoltage - Hardware Shutdown. Enabling Hardware Shutdown will cause the DECS-100 to
remove field excitation when the generator overvoltage setting is exceeded. Disabling Hardware Shutdown
prevents the DECS-100 from removing excitation during a generator overvoltage condition.
Metering, Operation and Alarms
The Metering, Operation and Alarms screen is viewed by clicking the Metering button or by clicking Screens
on the Menu bar and clicking Metering/Operation. Information displayed on the Metering, Operation and
Alarms screen can be frozen by clicking the Metering button while viewing the screen or by clicking Metering
on the Menu bar and clicking Disable Metering. Metering can be resumed by clicking the Metering button or
by clicking Metering on the Menu bar and clicking Enable Metering. The Metering, Operation and Alarms
screen consists of two tabs: Operation and Alarm/Status.
Operation Tab
Operation tab metering values, setpoint values, and control functions are illustrated in Figure 5-21.
5-15
Bus Voltage (V). This metering value indicates the amount of bus voltage present at the utility side of the tie
circuit breaker. The displayed value is the product of the voltage sensed at terminals B1 and B3 and the bus
PT ratio.
Phase Angle (Degree). This metering value indicates the phase angle difference (in degrees) between the
generator voltage and the generator current.
Aux DC Input (V). This metering value indicates the level of dc control voltage applied from a remote device
to DECS-100 terminals A and B. The displayed value correlates to the generator voltage setpoint.
Apparent Power (VA). This value is the calculated product of the metered generator voltage (VAVG), PT ratio
(entered at the System Configuration screen), metered generator current (Ib), CT ratio (entered at the System
Configuration screen), and the square root of 3. See Equation 5-1.
VA= VAVG IB
Equation 5-1
Real Power (W). This value is the calculated product of the metered generator voltage(VAVG), PT ratio (entered
at the System Configuration screen), metered generator current (Ib) CT ratio (entered at the System
Configuration screen), square root of 3, and the cosine of the metered phase angle. See Equation 5-2.
W = VAVG I B
3 cos
Equation 5-2
Reactive Power (var). This value is the calculated product of the metered generator voltage(VAVG), PT ratio
(entered at the System Configuration screen), metered generator current (Ib) CT ratio (entered at the System
Configuration screen), square root of 3, and the sine of the metered phase angle. See Equation 5-3.
var = VAVG I B
3 sin
Equation 5-3
Power Factor. This value is the calculated result of dividing the Real Power (W) value by the Apparent Power
(VA) value. See Equation 5-4.
PF = W VA
Equation 5-4
Operating Status. The Operating Status controls and indicators include three buttons and three corresponding
indicators. Operating Status buttons are labeled PF, VAR, and OFF. Clicking the PF button changes the color
of the adjacent PF indicator to green and causes the DECS-100 to maintain the desired power factor
regulation point. The power factor regulation point can be set within the range of 0.6 lead to 0.6 lag. Clicking
the VAR button changes the color of the adjacent VAR indicator to green and causes the DECS-100 to
maintain the desired var regulation point. The var regulation point can be set within the range of 100 percent
absorb to 100 percent generate. Clicking the OFF button changes the color of the adjacent OFF indicator to
red and disables power factor and var regulation.
Operation of the Operating Status controls is determined by the status of the contacts connected across the
DECS-100 Var/PF Control terminals (52J, 52K). When these contacts are open, the Operating Status controls
are enabled. Closing the contacts at terminals 52J and 52K disables the Operating Status controls and
interrupts regulation of vars or power factor until the contacts are opened again.
Setpoint - Voltage (V). This setting field can be used to enter the desired generator output terminal voltage.
The voltage setpoint can also be entered at the Setting Adjustments screen, Setpoint tab, Automatic Voltage
Regulator (AVR) - AVR Setpoint (V). The background color of this field is green when operating in AVR mode
and power factor and var regulation is disabled.
Setpoint - Current (A). This setting defines the field current setpoint when operating in FCR mode. The current
setpoint can also be entered at the Setting Adjustments screen, Setpoint tab, Field Current Regulator (FCR)
- FCR Setpoint. Current values from 0 to 7 Adc may be entered in increments of 0.01 Adc. The background
color of this field is green when operating in FCR mode.
Setpoint - Var (% of nom.). This setting determines the level of generator vars maintained by the DECS-100
when operating in var mode. The var setpoint can also be entered at the Setting Adjustments screen, Setpoint
tab, Reactive Power Control (VAR) - VAR Setpoint (% of nom.). The background color of this field is green
when the DECS-100 is operating in AVR mode and is regulating the var setpoint.
5-16
Setpoint - Power Factor. This setting determines the level of power factor regulation maintained by the
DECS-100. The power factor setpoint can also be entered at the Setting Adjustments screen, Setpoint tab,
Power Factor Control (PF) - PF Setpoint. Power Factor setpoint values are adjustable from -0.6 to -1 (1) or
0.6 to +1 in 0.001 increments. The background color of this field is green when the DECS-100 is operating
in AVR mode and is regulating the power factor setpoint.
Voltage Matching. The Voltage Matching controls and indicators consist of two buttons and two adjacent
indicators. Clicking the ON button changes the color of the adjacent ON indicator to green and enables voltage
matching by the DECS-100. When Voltage Matching is enabled, the DECS-100 automatically adjusts the field
current to match the generator output voltage with the bus voltage prior to synchronizing. In order for Voltage
Matching to be enabled, the following conditions must be met.
C
C
C
C
The Parallel Generator Compensation Contacts (terminals 52L and 52M) must be shorted.
The DECS-100 Voltage Matching input must be shorted (terminals VM and VMC).
Var/PF control must be disabled by shorting terminals 52J and 52K (open breaker).
The DECS-100 must be operating in AVR mode.
Clicking the OFF button changes the color of the adjacent OFF indicator to red and disables the voltage
matching function.
Control Mode. Clicking the AVR button changes the color of the adjacent AVR indicator to green and enables
the AVR operating mode. When operating in AVR mode, the DECS-100 regulates the generator output voltage
at the AVR setpoint. Clicking the FCR button changes the color of the adjacent FCR indicator to green and
enables the FCR operating mode. When operating in FCR mode, the DECS-100 maintains the field current
at the FCR setpoint. Enabling the FCR mode turns off Voltage Matching.
Fine Adjustment. Raise and Lower buttons control the fine adjustment of the operating setpoint. These buttons
perform the same function as closing the appropriate set of contacts connected to the External Adjust
terminals (6D and 7 to decrease, 6U and 7 to increase) of the DECS-100. For AVR mode, each click of the
Raise button increases the voltage setpoint 0.01 volts; each click of the Lower button decreases the voltage
setpoint 0.01 volts. The minimum and maximum limits for fine adjustment of the voltage setpoint are controlled
by the Regulator Sensing Voltage setting (System Configuration screen) and the Fine Voltage Adjustment Band setting (Setting Adjustments screen). Fine adjustment of the voltage setpoint can be
increased/decreased no higher/lower than the Regulator Sensing Voltage setting plus/minus the Band setting.
For example, a Regulator Sensing Voltage setting of 100 volts and a Band setting of 10 percent allows the
Fine Adjustment function to increase the voltage setpoint to a maximum of 110 volts and decrease the voltage
setpoint to a minimum of 90 volts. For Var, PF, or FCR modes, the Raise and Lower buttons provide fine
adjustment over the entire adjustment range.
Alarm/Status Tab
The Alarm/Status tab indicators provide the status of DECS-100 protection functions, control modes, and
contact inputs. Alarm/Status tab indicators are illustrated in Figure 5-22 and are described in the following
paragraphs.
Protection Alarms. Five Protection Alarm indicators provide the status of DECS-100 protection functions.
Alarm indicators include Overexcitation Shutdown, Overexcitation Limiting, Underfrequency, Generator
Overvoltage, and Loss of Generator Sensing. When a DECS-100 protection function detects an alarm
condition, the appropriate indicator changes from black to red.
Control Status. Two Control Status indicators indicate when the VAR/PF and Manual modes are active. The
Manual Mode Active indicator changes from black to red when the FCR control mode is active. The VAR/PF
Mode Active indicator changes from black to red when the DECS-100 is operating in AVR mode and
correction of power factor or vars is selected.
Switch Status. Three Switch Status indicators indicate when the DECS-100 control inputs are open or closed.
The 52JK switch open indicator changes from black to red when the user-supplied contacts at terminals 52J
and 52K are closed. When this control input is open, selection of PF or VAR mode can be made on the
Operation tab of the Metering, Operation, and Alarms screen. The 52LM switch closed indicator changes from
black to red when the user-supplied contacts at terminals 52L and 52M are closed. When this control input
is closed, parallel control and droop is inactive. The VM switch closed indicator changes from black to red
DECS-100 BESTCOMS for Windows OS
5-17
when the user-supplied contacts at terminals VM and VMC are closed. When this control input is closed, the
Voltage Matching function is active.
PID DATA
BESTCOMS-DECS100-32 enables generator stability to be set through the automatic calculation of PID
parameters. PID stands for Proportional, Integral, Derivative. The word proportional means that the response
of the DECS-100 output is proportional or relative to the amount of change that is observed. Integral means
that the DECS-100 output is proportional to the amount of time that a change is observed. Integral action
eliminates offset. Derivative means that the DECS-100 output is proportional to the required rate of excitation
change. Derivative action avoids excitation overshoot.
BESTCOMS automatically calculates PID values after the user selects the generator frequency, generator
time constant (T'do), and exciter time constant (Texc). With BESTCOMS, the user may generate new PID
numbers, add to a PID list file, and update the AVR gain settings in the Control Gain or Step Response
screens.
The PID window (Figure 5-23) is accessed by clicking the PID button. The PID button can be clicked only
when the Stability Range setting of the Control Gain screen is set at a value of 21. (A setting of 21 enables
the entry of custom stability settings through the PID window.) Then, when a field of the Control Gain screen
is changed or selected, the PID button changes from gray to yellow and the button can be clicked to view the
PID window. After the PID numbers are modified, calculated, and updated, the PID window is closed by
clicking the Update Setting Screen button. The modified PID values are then shown on the Control Gain
screen.
5-18
5-19
SETTINGS FILES
BESTCOMS software enables you to print a list of DECS-100 settings, save DECS-100 settings to a file, and
open a settings file and upload those settings to a DECS-100. A settings file may also be opened and edited
within any text editing software.
Printing Settings Files
A printout of DECS-100 settings can be useful for record keeping or comparison purposes. DECS-100 settings
are printed by clicking the print icon or clicking File on the Menu bar and then clicking Print. When the print
command is given, a print dialog box prompts you to select a printer. Once the printer is selected, a second
dialog box (Figure 5-24) provides the opportunity to add a title, unit information, and comments to the settings
list. Each entry is limited to a maximum of 54 characters. After this information is entered, OK is clicked and
the report is printed.
Saving Settings Files
Saving DECS-100 settings to a file for uploading to other DECS-100 units saves setup time when configuring
multiple units to the same configuration. A settings file can also be created in BESTCOMS without being
connected to a DECS-100. The settings of the desired screens can be changed and these settings can then
be saved to a file. Once a settings file is created, it can be edited using any text editing software, and then
saved for uploading.
5-20
CAUTION
Before uploading a settings file, remove operating power from the DECS-100,
disconnect the field wiring from terminals F+ and F, and re-apply operating
power to the DECS-100.
The upload process is started by clicking the open icon or clicking File on the menu bar and then clicking
Open. A dialog box is then displayed (Figure 5-25) reminding you that the DECS-100 should be off-line before
uploading settings. Clicking Yes loads the settings into DECS-100 memory.
PASSWORD PROTECTION
Password protection guards against unauthorized changing or viewing of DECS-100 settings. A single
password protects all DECS-100 settings. The DECS-100 is delivered with a default password of decs. Once
the password is changed, it should be stored in a secure location. If the user-defined password is lost or
forgotten, BESTCOMS-DECS100-32 must be reloaded to restore the default password.
Changing the Password
NOTE
A password change can be made only after communication between BESTCOMS
and the DECS-100 is established.
A new password can be programmed by performing the following steps.
1. Click Communications on the menu bar and click
Password Change on the drop-down menu. The Change
Password dialog box of Figure 5-26 appears.
2. Type the current password in the "Enter your access
password" field of the Change Password dialog box and
press the Enter key on your keyboard.
3. Another dialog box will appear with instructions for making
the password change. Click the OK button and type a new
password (8 alphanumeric characters, maximum) in the
"Enter your new password" field.
4. Press the Enter or Tab key on your keyboard to advance
the cursor into the field labeled "Re-enter your new
password". Type the new password again to confirm the
changed password and press the Enter key. When the
Enter key is pressed, the new password is enabled and a
dialog box appears to remind you to keep your password
in a secure location.
5-21
TERMINATING COMMUNICATION
DECS-100 communication is terminated by clicking on Communications on the menu bar, and clicking Close
Comm Port. You are asked if you want to save the settings to EEPROM. This question is asked even if no
changes were made to the DECS-100 settings. When you execute the Close command (with a Yes or No to
save settings to EEPROM), communication with the DECS-100 is terminated. If you choose to exit
BESTCOMS (by clicking File on the menu bar and then Exit) without first closing communication, you are still
given the opportunity to save the settings to EEPROM.
EMBEDDED FIRMWARE
Embedded firmware is the operating program that controls the actions of the DECS-100. The DECS-100
stores firmware in nonvolatile flash memory that can be reprogrammed through the RS-232 communication
port. It is not necessary to replace EPROM chips when replacing the firmware with a newer version.
Updating the Firmware
Future enhancements to DECS-100 functionality may make a firmware update desirable. DECS-100
embedded firmware can be updated by performing the following steps.
CAUTION
If power is lost or communication is interrupted during file transfer, the DECS100 will not recover and will cease to be operational.
NOTE
Communication must be closed prior to uploading embedded firmware to the
DECS-100. Refer to the Terminating Communication subsection for information
about closing DECS-100 communication.
1. Connect a communication cable between the rear RS-232 connector of the DECS-100 and the
appropriate communication port of your PC.
2. Click DECSLoad on the BESTCOMS menu bar and click Uploading Embedded Software (Figure 5-27).
If this menu selection is grayed out, youll need to close DECS-100 communication. Refer to the
Terminating Communication subsection for information about closing DECS-100 communication.
5-22
5-23
5-24
5-25
Tables
Table 6-1. BESTCOMS Settings Group Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
ii
INSTALLATION
BESTCOMS software for the Palm OS platform has the following minimum recommended installation and
operating requirements.
!
!
Installing BESTCOMS
BESTCOMS software for the Palm OS platform is comprised of a series of files that run as a single
application on your handheld. A setup utility on the CD supplied with the DECS-100 automatically loads the
files into the Palm Desktop application Install Tool on your PC. BESTCOMS is then installed on your
handheld when you perform your next HotSync operation.
Use the following procedure to install BESTCOMS on your handheld.
NOTE
The Palm Desktop software supplied with your handheld must be installed on
your PC before the BESTCOMS setup utility is run.
Your handheld must have a unique identification number in order for the
installation of BESTCOMS to be successful. This is accomplished by performing
a HotSync operation before installing BESTCOMS.
Installing this version of BESTCOMS software will overwrite all existing DECS-100
settings files. Make a written record of all desired DECS-100 settings before
installing BESTCOMS.
Some settings in this version of BESTCOMS may not be compatible with DECS100 firmware version 1.09.09. (Information about checking the firmware version
is provided in the BESTCOMS Version Information sub-section.) To obtain the
latest version of DECS-100 firmware, contact Basler Electric. (Information about
viewing contact information for Basler Electric is provided in the Basler Electric
Contact Information sub-section.)
BESTCOMS is compatible only with USA regional numeric settings.
6-1
1.
2.
When the
DECS-100
Setup and
Documentation CD menu appears, click the
Install button for the BESTCOMS Palm OS
Program. The setup utility starts and displays
the Welcome screen of Figure 6-1. Click the
Next> button to view the Select Destination
Directory screen of Figure 6-2.
Figure 6-1. Welcome Screen
3.
Accept the default installation location by clicking Next> or change the location to the desired folder and
click Next>. The Modules Selection screen (Figure 6-3) appears.
4.
Select all of the BESTCOMS files for installation by clicking the Select all button. Click the Next> button
to proceed to the Select a User screen of Figure 6-4.
5.
Click the check box next to the desired user or click the Select all button to make BESTCOMS available
to all users. Click the Next> button to complete the installation. The Installation Complete screen (Figure
6-5) appears and confirms that BESTCOMS was installed successfully. Click the Quit button to exit the
setup utility.
Connect your handheld and PC using a HotSync cable or cradle and perform a HotSync operation
to load BESTCOMS on your handheld.
STARTING BESTCOMS
BESTCOMS is started by tapping the BESTCOMS icon on the main menu (Figure 6-6) of your handheld. The
screen of Figure 6-7 appears and prompts you to enter the password. The DECS-100 is delivered with a
password of decs. If an incorrect password is entered or the Cancel button is tapped, a message will appear
and notify you that an invalid password was selected. Tapping the Ok button exits BESTCOMS and returns
you to the main menu (Figure 6-6). Entering the correct password and tapping OK displays the BESTCOMS
startup screen (Figure 6-8) followed by a screen (Figure 6-9) asking you to select the desired operating mode.
CAUTION
When applying operating power to the DECS-100 for programming purposes,
observe the precautions called out in Section 4, Installation, Preliminary Setup.
6-3
NOTE
The Save to DECS button of the main screen (Figure 6-13) is not always present.
It is displayed only in On-Line mode when settings have been changed but not
saved to the DECS-100. If BESTCOMS is exited (either by turning off the
handheld or switching to another application) without tapping the Save to DECS
button, setting changes are not saved in the DECS-100 and may be erased if the
DECS-100 loses operating power.
The Save to DECS button does not appear when using BESTCOMS in Off-Line
mode.
C
C
C
C
C
C
C
Configuration
Settings
Control
Limiter
AVR/FCR Gain
Protection
Var/PF Gain
A group of settings is accessed by tapping the group name listed on the main screen. A summary of the
individual settings available at each screen is provided in Table 6-1.
6-5
Settings Screen
Voltage Setpoint (AVR)
Field Current Setpoint (FCR)
Var Setpoint
PF Setpoint
Control Screen
Soft Start Time
Underfrequency Kneepoint
Volts/Hertz Slope
Voltage Matching Speed
Droop Setpoint
Limiter Screen
Overexcitation Limiter
OEL Ki
OEL Kg
Protection Screen
Overexcitation Voltage Enabled
OEL Shutdown Enabled
LOS Transfer to FCR Enabled
OEL Shutdown Time Delay
Generator OV Shutdown Enabled
LOS Shutdown Enabled
Field OV Shutdown Enabled
Generator Overvoltage Level
Field Overvoltage Level
LOS Time Delay
LOS Balance Level
LOS Imbalance Level
Generator Short-Circuit Level
Var/PF Screen
Var Ki
Var Kg
PF Ki
PF Kg
Changing Settings
When a setting screen is selected and displayed, the description for each setting is listed in the Item column,
the value for each setting is listed in the Value column, and the range for the highlighted setting is listed in the
Settings Range box.
To change a setting, highlight the desired setting by tapping it. Ensure that the cursor is on the Change to: line
and enter the new value in the Graffiti writing area of your handheld. In the example of Figure 6-14, the
Control screen Soft Start Time setting of 20 seconds is being replaced with a new setting of 50 seconds. Once
the new value is entered in the Change to: line, the Update button is tapped to send the setting to the DECS100. When the handheld confirms the DECS-100 setting change, the handheld emits a two-tone beep, the
new setting is displayed in the Value column, and the Save to DECS button appears in the lower, right-hand
corner of the screen. (Figure 6-15).
6-6
Multiple changes can be made before saving the DECS-100 settings. Settings are saved by tapping the Save
to DECS button on any of the screens that display the button.
Alarm and Contact Input Status
The Alarm/Contact Status screen (Figure 6-16) is accessed from the BESTCOMS main screen (Figure 6-13).
Tap the arrow () on the Other Pages: line and then select Front Panel Alarms from the drop-down menu.
The Alarms portion of this screen displays the status of the DECS-100 front panel LEDs. An alarm condition
is indicated by a checked box (:). The Contact Status section indicates whether the DECS-100 52LM, 52JK,
and Voltage Matching contact inputs are open or closed. To refresh the status of the Alarm/Contact Status
screen indicators, tap the Update button. To return to the main screen, tap the Back icon ( ).
System Status
The System Status screen shown in Figure 6-17 is accessed from the main screen (Figure 6-12) by tapping
the arrow on the Other Pages: line and then tapping System Status. The System Status screen displays the
current mode setting beside or below each Mode button. Note that the voltage matching and var/power factor
mode settings will not appear on the System Status screen if your DECS-100 does not have those optional
features.
6-7
C
C
C
C
C
6-8
On the BESTCOMS main screen, tap the arrow () on the Other Pages: line.
2.
Select File Operations from the drop-down menu and then tap the Open button in the Which
Settings? dialog box to access the File Operations screen.
3.
Tap the arrow () on the File Actions: line of the File Operations screen.
4.
5.
Use the handheld Graffiti writing area to enter a name for the file. Up to 50 alphanumeric characters
can be used. Note that no more than approximately 13 characters are shown in the Save As: field when
entering a file name.
On the BESTCOMS main screen, tap the arrow () on the Other Pages line.
2.
Select File Operations from the drop-down menu and then tap the
Settings? dialog box to access the File Operations screen.
3.
Select the desired settings file from the list on the File Operations screen to load the settings into
BESTCOMS.
4.
5.
6-9
6.
Tap the arrow () on the File Actions: line and select SEND to DECS from the drop-down menu.
7.
Ensure that the proper data cable is connected between the DECS-100 and your handheld.
8.
Tap the Ok button in the Connect Cable dialog box to send the file.
9.
Tap the Ok button to acknowledge that the settings were sent to the DECS-100.
10.
To save the settings in DECS-100 memory, tap the Save to DECS button which is accessible from any
of the BESTCOMS screens.
11.
On the BESTCOMS main screen, tap the arrow () on the Other Pages: line.
2.
Select File Operations from the drop-down menu and then tap the
Settings? dialog box to access the File Operations screen.
3.
Tap the arrow () on the File Actions: line and then select SEND to DECS from the drop-down menu.
4.
Ensure that the proper data cable is connected between the DECS-100 and your handheld.
5.
Tap the Ok button in the Connect Cable dialog box to read the DECS-100 settings into BESTCOMS.
6.
Once the settings are read, tap the Ok button to acknowledge that the DECS-100 settings were read
into BESTCOMS.
On the BESTCOMS main screen, tap the arrow () on the Other Pages: line.
2.
Select File Operations from the drop-down menu and then tap the Open button in the Which
Settings? dialog box to access the File Operations screen.
3.
Tap the arrow () on the File Actions line and then select DELETE saved file.
4.
Tap the name of the settings file that you want to delete.
5.
Tap the Delete button to remove the selected settings file from your handheld.
PASSWORD PROTECTION
Password protection guards against unauthorized changing or viewing of DECS-100 settings. A single
password protects all settings. The DECS-100 is delivered with a default password of
decs. Once the
password is changed, it should be stored in a secure location. If the user-defined password is lost or forgotten,
BESTCOMS must be reloaded to restore the default password.
Changing the Password
A new password can be programmed by performing the following steps.
1.
Access the Main drop-down menu (Figure 6-20) by tapping the title bar of the main screen. Older
versions of BESTCOMS may require that you tap the Menu icon on your handheld screen to access
the Main drop-down menu.
2.
3.
When prompted, enter the desired password and tap OK. The BESTCOMS password is not casesensitive; either lower-case or upper-case alphanumeric characters are acceptable. When OK is
tapped, the new password is activated and BESTCOMS displays the new password. In the example
of Figure 6-21, a password of 123 was entered.
4.
6-10
6-11
7-1
7-1
7-1
7-1
7-2
7-3
7-3
7-4
7-4
7-4
7-5
7-5
7-5
7-6
TROUBLESHOOTING
If you do not get the results that you expect from the DECS-100, first check the programmable settings for the
appropriate function. Use the following troubleshooting procedures when difficulties are encountered in the
operation of your excitation system.
Generator Voltage Does Not Build
Step 1.
Verify that all wiring is properly connected. Refer to Figures 4-6 through 4-10.
If wiring is improperly connected or loose, reconnect wiring properly.
If wiring connections are correct, proceed to Step 2.
Step 2.
Step 3.
For PMG power, check for correct input power to the DECS-100. Refer to Section 1,
Information, Specifications for input power requirements.
General
If voltage is not present, refer to the generator manual for repair procedures (PMG system only).
If voltage is present, proceed to Step 4.
Step 3a. If the DECS-100 is being shunt powered (non-PMG) mode, verify that the residual voltage applied
to the power input is at least 6 Vac.
If the applied voltage is less than 6 Vac, refer to the generator manual and flash the generator field.
If the applied voltage is 6 Vac or greater, proceed to Step 4.
Step 4.
Step 5.
Verify that the front panel OVEREXCITATION SHUTDOWN indicator is not lit.
If the front panel OVEREXCITATION SHUTDOWN indicator (field voltage) is lit, check the
generator and/or load conditions. Interrupt input power or shut down the generator for a minimum
of one minute.
If the front panel OVEREXCITATION SHUTDOWN indicator is not lit, proceed to Step 6.
Step 6.
Verify that the front panel OVEREXCITATION LIMITING indicator is not lit.
If the front panel OVEREXCITATION LIMITING indicator is lit, check the generator and load
conditions. Also check the field current limit setpoint for the correct level. Interrupt input power or
shut down the generator for a minimum of 1 minute.
7-1
If the front panel OVEREXCITATION LIMITING indicator is not lit, proceed to Step 7.
Step 7.
Verify that the DECS-100 soft start settings are correct. Too long of a soft start setting may give the
appearance of no buildup.
If the soft start settings are incorrect, adjust the settings.
If the soft start settings have no effect, proceed to Step 8.
Step 8.
Step 2.
Verify that the underfrequency knee setpoint is not greater than the generator frequency.
If the underfrequency setpoint is too high, adjust the setpoint below the rated generator frequency.
If the underfrequency setpoint is correct, proceed to Step 3.
Step 3.
Step 4.
For PMG power, check for correct input power to the DECS-100. Refer to Section 1,
Information, Specifications for input power requirements.
General
If the DECS-100 input voltage is low, refer to the PMG manual for PMG repair (PMG system only).
If the voltage is at the required level, proceed to Step 5.
Step 4a. If the DECS-100 is being shunt powered (non-PMG), verify that the power potential transformer (if
used) has the correct turns ratio, is sized properly, and is supplying the correct voltage level to the
power input.
If the turns ratio of the power potential transformer is incorrect, is sized too small, or is not supplying
the correct input power, replace the power potential transformer.
If the power potential transformer is correct, proceed to Step 5.
Step 5.
Verify that the sensing potential transformer (if used) has the correct turns ratio and is operating
correctly.
If the turns ratio of the sensing potential transformer is incorrect, replace the sensing potential
transformer.
If the sensing potential transformer is operating correctly, proceed to Step 6.
Step 6.
Verify that the front panel OVEREXCITATION LIMITING indicator is not lit.
If the front panel OVEREXCITATION LIMITING indicator is lit, check the generator and/or load
conditions. Also check the field-current limit setpoint for the correct level. Interrupt input power or
shut down the generator for a minimum of one minute.
If the front panel OVEREXCITATION LIMITING indicator is not lit, proceed to Step 7.
Step 7.
7-2
Low generator output voltage may occur when operating in droop mode with an inductive load.
DECS-100 Maintenance and Troubleshooting
If the low voltage condition is not caused by the droop function, proceed to Step 8.
Step 8.
Verify that the voltage setpoint is not being modified by application of voltage to the optional
Accessory Input.
If the low voltage condition is not caused by voltage applied to the Accessory Input, proceed to Step
9.
Step 9.
Step 2.
Verify that the sensing potential transformer (if used) has the correct turns ratio.
If the turns ratio of the sensing potential transformer is incorrect, replace the sensing potential
transformer with the correct one.
If the sensing potential transformer is correct, proceed to Step 3.
Step 3.
High generator output voltage may occur when operating in droop mode with a capacitive load.
If the high voltage condition is not caused by the droop function, proceed to Step 4.
Step 4.
Verify that the voltage setpoint is not being modified by application of voltage to the optional
Accessory Input.
If the high voltage condition is not caused by voltage applied to the Accessory Input, proceed to
Step 5.
Step 5.
Step 2.
Step 3.
If the DECS-100 is powered from a PMG, check for grounded PMG leads.
If the PMG leads are grounded, isolate them from ground.
If the PMG leads are not grounded, proceed to Step 4.
Step 4.
Verify that the generator frequency is not dropping below the DECS-100 underfrequency setpoint
when load is applied to the generator.
If the generator frequency is dropping below the underfrequency setpoint, reduce the setpoint if
possible. Also check the prime mover and generator for proper sizing in relation to the applied load.
If poor regulation is not related to DECS-100 underfrequency operation, proceed to Step 5.
7-3
Step 5.
Step 6.
Verify that the governor for the prime mover is operating properly.
If the governor is not operating properly, troubleshoot using the manufacturer's suggested
procedures.
If the governor is operating properly, proceed to Step 2.
Step 2.
Verify that the sensing and input power leads are connected securely.
If the sensing or input power leads are not connected securely, tighten the connections.
If the sensing or input power lead connections are secure, proceed to Step 3.
Step 3.
Verify that the DECS-100 Stability Range is set to the proper range.
If the Stability Range setting is incorrect, reset the Stability Range.
If the Stability Range setting is correct, proceed to Step 4.
Step 4.
Step 2.
Verify that the generator exciter field voltage requirements are compatible with the DECS-100.
If the exciter field voltage requirements are not compatible with the DECS-100, contact Basler
Electric Customer Service for recommendations.
If the exciter field voltage requirements are compatible with the DECS-100, proceed to Step 3.
Step 3.
Step 4.
Step 2.
Step 3.
7-4
Verify that the sensing potential transformer (if used) has the correct turns ratio and is functioning
properly.
DECS-100 Maintenance and Troubleshooting
If the sensing potential transformer has the wrong turns ratio or is malfunctioning, replace it.
If the sensing potential transformer is correct and functioning properly, proceed to Step 4.
Step 4.
Step 5
Step 2.
Verify that the DECS-100 output (field) current limit is not set too low.
If the output current limit setpoint is too low, adjust for the proper setting.
If the output current limit is set properly, proceed to Step 3.
Step 3.
Verify that the generator exciter field current requirements are compatible with the DECS-100.
If the generator exciter field current requirements are not compatible with the DECS-100, contact
Basler Electric Customer Service for recommendations.
If the generator exciter field current requirements are compatible with the DECS-100, proceed to
Step 4.
Step 4.
Step 5.
Step 2.
No Droop
Step 1.
Step 2.
Verify that the DECS-100 52J/K contact input (if present) is closed or the Var/PF function is
disabled via BESTCOMS. Var/PF operation must be disabled for droop operation. If var/PF
operation is disabled, proceed to Step 3.
Step 3.
Step 4.
Check for an open in the circuit connected to DECS-100 CT1 and CT2.
7-5
Verify that all connections are correct according to Figures 4-6 through 4-9.
If connections are incorrect, correct the problem.
If connections are correct, proceed to Step 6.
Step 6.
Verify that the load being applied to the generator for droop testing is not purely resistive.
If only a resistive load is being applied to the generator, apply an inductive load and retest.
If the load being applied to the generator is inductive, proceed to Step 7.
Step 7.
Verify that your DECS-100 is compatible with the current sensing transformer (1 A or 5 A
secondary) being used. For example, a current sensing transformer with a 1 ampere output rating
would produce very little droop if your DECS-100 has a 5 ampere current transformer input. Refer
to Figure 1-1 of Section 1, General Information to check the current transformer input of your
DECS-100.
If the current transformer input is incorrect, replace the current sensing transformer or the
DECS-100 for compatibility.
If the current transformer input is correct, proceed to Step 8.
Step 8.
If the above steps fail to correct the malfunction, replace the DECS-100 unit.
No Voltage Matching
Step 1.
Verify that the Voltage Matching option was purchased and is enabled in the software.
If not enabled, use the BESTCOMS software to turn on voltage matching.
If voltage matching is enabled, proceed to Step 2.
Step 2.
Verify that all connections are correct according to Figures 4-6 through 4-9 as required for the
Voltage Matching option of the DECS-100.
If the interconnection is incorrect, reconnect according to the appropriate interconnect diagram.
If the interconnection is correct, proceed to Step 3.
Step 3.
Step 4.
Check for correct utility reference voltage on DECS-100 terminals B1 and B3.
If the interconnection is incorrect, reconnect according to the appropriate interconnect diagram.
If the interconnection is correct, check for open system fuses.
Verify that the potential sensing transformer, if used, is connected to DECS-100 terminals B1 and
B3.
If potential sensing transformer connections are correct, proceed to Step 5.
Step 5.
Verify that the generator output voltage setpoint is within 10 percent of the measured utility bus
voltage.
If the setpoint is too low or too high, adjust the setpoint to the appropriate level.
If the setpoint is correct, proceed to Step 6.
Step 6.
7-6
If the above steps fail to correct the Voltage Matching malfunction, replace the DECS-100.
DECS-100 Maintenance and Troubleshooting