08 Protection
08 Protection
08 Protection
6.1 Introduction
300
301
6.2.1 Introduction
301
302
6.2.3 Applications
321
331
340
6.3.1 Introduction
340
340
346
351
352
360
6.4.1 Introduction
360
366
370
6.4.5 SIPROTEC7KE85
FaultRecorder, Measurement and Phasor
Measurement Unit (PMU)
374
378
381
385
385
389
393
396
399
400
400
401
408
411
414
423
299
300
301
302
303
304
Fig.6.2-3: SIPROTECCompact
Fig.6.2-4: SIPROTECCompact
rear view
Infeed
7SJ80
SIEMENS
7RW80
Backup transformer
protection
Busbar protection via
reverse interlocking
Voltage/frequency
protection
Load shedding
Load restoration
SIEMENS
MV-Substation
7SD80
SIEMENS
7SJ80
SIEMENS
7SJ80
7SD80
SIEMENS
Cable
7RW80
7SC80
7SK80
SIEMENS
7SJ80
SIEMENS
SIEMENS
7SK80
SIEMENS
SIEMENS
Generation
Transformer
Feeder
Motor
Bus Coupler
305
The Feeder Automation device 7SC80 is designed for decentralized as well as for centralized feeder automation applications.
This solution allows various flexible high speed applications like
FLISR (Fault Location, Isolation, and Service Restoration)
Detect and locate a fault in the feeder, isolate the faulty section
and set the healthy portions of the feeder back into service
Source transfer
Detect and isolate a faulty source and set the de-energised
sections of the feeder back into service
Load Balancing
Balance the load within a feeder by moving the disconnection.
Activation of individual line sections
Isolate a dedicated section of a feeder for maintenance without
affecting other sections. Fig. 6.2-7 shows an example of a
typical ring main application with overhead lines and 5 sections.
Every section is protected and automated by the SIPROTEC
7SC80 Feeder Protection.
Substation
Substation
50/50N
50/50N
1
Communication network
50/50N
50/50N
1
50/50N
Current jump detection
306
2 operation LEDs
In an illuminated 6-line LC display, process
and device information can be indicated as
text in different lists.
4 navigation keys
8 freely programmable LEDs serve for
indication of process or device information.
The LEDs can be labeled user-specifically. The
LED reset key resets the LEDs.
Fig.6.2-8a:
with open cover
Fig.6.2-8b:
with closed cover
and open battery
compartment
307
Fig.6.2-10a:
Voltage terminal block
All binary inputs are independent and the pick-up thresholds are
settable using software settings (3 stages). The relay current
transformer taps (1 A/5 A) are new software settings. Up to 9
function keys can be programmed for predefi ned menu entries,
switching sequences, etc. The assigned function of the function
keys can be shown in the display of the relay.
With overcurrent protection SIPROTEC 7SJ81 there is also a
device for low-power current transformer applications.
Fig.6.2-10b:
Current terminal block
Wmax = 9.5mm
d1 = 5.0mm
Wire cross-section
Stripping length
(when used without conductor sleeve)
Stripping length
(when used without conductor sleeve)
308
d1
Wire cross-section
Fig.6.2-13b:
Ring cable lug
Fig.6.2-13a:
Front view, surface-mounted housing
309
Innovation highlights
With SIPROTEC5, we have combined a functionality that has
been proven and refined over years with a high-performance
and flexible new platform, extended with trendsetting innovations for present and future demands.
Holistic workflow
The tools for end-to-end engineering from system design to operation will make your work easier throughout the entire process.
The highlight of SIPROTEC5 is the greater-than-ever emphasis
on daily ease of operation. SIPROTEC5 provides support along
all the steps in the engineering workflow, allowing for system
view management and configuration down to the details of
individual devices, saving time and cost without compromising
quality (fig.6.2-17).
Holistic workflow in SIPROTEC5 means:
Integrated, consistent system and device engineeringfrom
the single-line diagram of the unit all the way to device
parameterization
Simple, intuitive graphical linking of primary and secondary
equipment
Easily adaptable library of application templates for the most
frequently used applications
Manufacturer-independent tool for easy system engineering
Libraries for your own configurations and system parts
Multiuser concept for parallel engineering
Open interfaces for seamless integration into your process
environment
A user interface developed and tested jointly with many users
that pays dividends in daily use
Integrated tools for testing during engineering,
commissioning, and for simulating operational scenarios, e.g.,
grid disruptions or switching operations.
Operation
Documentation
Testing
Maintenance
Design
Application
Specication
Holistic
Workflow
Commissioning
Test
Documentation
Implementation
Device selection
Planning
Engineering
Settings
310
SIPROTEC 5
Protection
Control
52
Automation
Monitoring
Data acquisition and
recording
Communication
Cyber Security
Test
311
Equipment
The monitoring of equipment (condition monitoring) is an
important tool in asset management and operational support
from which both the environment and the company can benefit.
Functional integration Data acquisition and recording
The recorded and logged field data is comprehensive. It represents the image and history of the field. It is also used by the
functions in the SIPROTEC 5 device for monitoring, interbay and
substation automation tasks. It therefore provides the basis for
these functions now and in the future.
Functional integration Communication
SIPROTEC5 devices are equipped with high-performance
communication interfaces. These are integrated interfaces or
interfaces that are extendable with plug-in modules to provide a
high level of security and flexibility. There are various communication modules available. At the same time, the module is
independent of the protocol used. This can be loaded according
to the application. Particular importance was given to the
realization of full communication redundancy:
Multiple redundant communication interfaces
Redundant, independent protocols with control center possible
(e.g. IEC60870-5-103 and IEC61850 or double
IEC60870-5-103 or DNP3 and DNP IP)
Full availability of the communication ring when the switching
cell is enabled for servicing operations
Redundant time synchronization (e.g. IRIG-B and SNTP).
312
your application, or you build a device yourself from the extensive SIPROTEC 5 hardware building blocks to exactly fit your
application. Pre-configured devices can be extended or adapted
as needed.
With the devices SIPROTEC 7xx85, 7xx86 and 7xx87 you can also
combine different base and expansion modules, add communication modules and select an installation variant that fits the
space you have available. The devices SIPROTEC 7xx82 and
7xx84 can not be extended with expansion modules.
With this modular principle you can realize any quantity structures you desire. In this way, hardware that is tailored to the
application can be selected. Fig.6.2-19 shows a modular device
consisting of a base module and 4 expansion modules.
The advantage of modular building blocks
The SIPROTEC 5 hardware module building blocks provides the
cumulative experience of Siemens in digital protection devices
and bay controllers. In addition, specific innovations were
realized that make the application easier for you, e.g. recorder
and PQ functionalities.
The SIPROTEC5 hardware building blocks offer:
Durability and robustness
Tailored hardware extension
Robust housings
Excellent EMC shielding in compliance with the most recent
standards and IEC61000-4
Extended temperature range
25 C to + 70 C/13 F to + 158 F.
Modular principle
Freely configurable and extendable devices
Large process data range (up to 24 current and voltage
transformers for protection applications and up to 40 for
central busbar protection as well as more than 200 inputs
and outputs for recording applications possible)
Operation panel that is freely selectable for all device types
(e.g. large or small display, with or without key switches,
detached operation panel)
Identical wiring of flush-mounting and surface-mounting
housings.
User-friendly operation panel
Eight freely assignable function keys for frequently required
operator control actions
Separate control keys for switching commands
Context-sensitive keys with labeling in the display
Complete numeric keypad for simple entry of setting values
and easy navigation in the menu
Up to 80 LEDs for signaling, 16 of which are in two colors.
Application-friendly design
No opening of device necessary for installation and servicing
Easy battery replacement on the back of the device
Simple exchange of communication modules with plug-in
technology
Electronically settable (no jumpers) threshold for binary
inputs
Rated current (1A/5A) of current transformer inputs
configurable electronically (no jumpers)
Removable terminal blocks
Pre-wiring of terminals is possible
Simple replacement of current transformers, e.g. with
sensitive ground current transformers if neutral grounding
method is changed.
Increased safety, since open current transformer circuits are
no longer possible (safety CT plug).
313
Fig.6.2-21: Operation panels with (from left) large and small display, and operation panel without display
314
need to navigate conveniently and quickly through all information that is shown in the display. 2LEDs on the upper border of
the operation panel inform you about the current device operating state.
1
2
1
2
16 LEDs (red)
Key switch S5
Remote/Local
Key
switch S1
Interlocking Off/Normal
3
4
315
Large
graphical display
16 LEDs (red)
LED reset
USB interfaces
Control/command keys
10
Context-sensitive keys
11
Cursor keys
12
13
10
11
10
316
12
13
317
318
Protection-class
current transformers
Instrument
transformers
Measuring range
5A
500 A
5A
100 A
1A
100 A
1A
20 A
5A
40 A
1A
8A
1A
1.6 A
5A
8A
1A
1.6 A
Plug-in modules
Plug-in modules are available for communication or analog
inputs. The communication modules are described in the Communication section.
Fig.6.2-30: Measuring-transducer input module ANAI-CA-4EL
319
Available in the
base module
Power supply
Implemented in
device row
PS203
CB202
IO101
IO102
IO110
IO201
IO202
IO203
IO204
10
IO205
12
IO206
IO207
IO208
IO209
IO211
Description
It is a typical module for protective
applications. In contrast to the IO202, it is
equipped with more relay outputs
12
1,2
1,2
1,2
1,2
16
1,2
1,2
16
1,2
1,2
1,2
1,2
1,2
1,2
1,2
1,2
IO215
IO230
41)
320
Availabe in the
expansion module
2 2)
BO power relay
measuring trans
ducer 20 mA/10 V
BO change-over
contacts type F
BO change-over
contacts
PS201
BO normally-open
contacts type HS
2 2)
BO normally-open
contacts type F
BO normally-open
contacts
1
BI (isolated)
I-input
U-input
PS101
Designation
BI (connected to
common potential)
48
*) In preparation
1) 10 V voltage input for high-resistance RC-splitter
2) of which 1 life contact
The connection diagrams of the individual modules are included in the appendix.
6.2.3 Applications
Fig.6.2-31 provides an overview of the application of
SIPROTEC5 devices in the grid. This is a simplified illustration.
Particularly with the advent of regenerative suppliers, energy is
being injected into the grid at all voltage levels.
7 XX
YY
Device types
Now that you have been introduced to the innovation highlights
of the SIPROTEC 5 devices, the following text will describe the
devices. They are easily identified with the aid of a five-digit
abbreviation code.
The first digit (6 or 7) stands for the digital equipment. The two
letters describe the functionality, and the last two digits identify
typical properties. Fig. 6.2-32 shows the definition of device
types based on designation.
Application templates
Application templates allow you to fast track your solution. A
library of application templates is available that can be tailored
to the specific functional scope for typical applications.
Generation
Transmission
Distribution
7SJ85
7KE85
6MD8
7SL87
7SA87
7SS8
7KE85
7SD87
7KE85
6MD8
7SJ86
7VK87
7UT8
7SK85
7SA82
7SA82
7SJ82
6MD8
7SA86
7SD82
7SJ82
7SJ85
7SS8
7SJ85
7SD86
7SJ85
7SD82
7SK82
7UT8
7KE85
7SJ86
7SL86
7UT8
7SD86
7SK85
7SA86
7SJ85
M
G
M
321
52 A-QA
FG Transformer side 1
MP
I-3ph 1
I-3ph
I-3ph
49
50BF
Ctrl
87N
Measured values
CB
BI
BO
FG Transformer 1
I-1ph
50N 51N
87
Measured values
FG Transformer side 2
MP
I-3ph 2
I-3ph
I-3ph
50
52 B-QA
51
FG
Function group
MP
Measuring point
BI
Binary input
BO
Binary output
QA/CB
Circuit breaker
Ctrl
Control
49
Overload protection
50BF
Circuit-breaker
failure protection
Overcurrent protection
50/51
50BF
Ctrl
Measured values
CB
BI
BO
87
Differential protection
87N
Ground-fault
differential protection
Protection functions
Device types
Overcurrent protection
Overcurrent protection with PMU and
control
ANSI
Function
Abbr.
3-pole
1-pole
21
Distance protection
Z<
7SJ82, 7SJ85
Line protection
Distance protection with PMU and control
FL
Fault locator
FL
25
Sync
27
Undervoltage protection
V<
7SL86, 7SL87
32
P>, P<
7VK87
37
Undercurrent, underpower
I<, P<
46
Unbalanced-load protection
I2>
49
, I2t
50/50N
I>
50Ns
INs>
7SJ86
Motor protection
Motor protection with PMU and control
7SK82, 7SK85
Busbar protection
Busbar protection
7SS85
Bay controller
Bay controllers for control/interlocking tasks
with PMU and monitoring, optionally with
protection function
6MD85, 6MD86
7KE85
*) In preparation
322
50L
Load-jam protection
I>L
50BF
CBFP
51/51N
IP, INp
51V
t=f(I)+V<
67
I>, IP (V, I)
67N
67Ns
IN>, (V, I)
79
Automatic reclosing
AR
87
Differential protection
PMU
Synchrophasor measurement
PMU
Application examples
Medium-voltage applications for all system grounding types
52
7SJ82/85
7SJ82/85
52
FG Voltage/current
50/51 50N/51N
7SJ82/85
52
QA1
52
FG Voltage/current
52
QA2
50/51
67N
67
79
FL
50/51 50N/51N
79
67N
Ctrl
Protection communication
PI
Ctrl
67
FG Circuit breaker
Ctrl
Protection communication
79
67N
FG Circuit breaker
50N/51N
67Ns
FG Voltage/current
67
PI
Properties
Reliable detection of transients and static ground faults
Cost saving due to integrated transient function
Directional and non-directional protection and control
functions
Acquisition and transmission of PMU variables possible.
Properties
Directional DMT/IDMTL protection without grading times
Fast fault clearance
Low-cost due to integrated protection interface
Monitored data exchange
Adaptable to different communication infrastructures.
QA1
52
QA1
52
QA2
52
QA3
52
7SJ85
FG Voltage/current 3-phase 1
50/51
50N/51N
FG Voltage/current 3-phase 2
50/51
50N/51N
FG Voltage/current 3-phase 3
50/51
50N/51N
QA2
52
QA3
52
79
Ctrl
Ctrl
Ctrl
79
Ctrl
Ctrl
79
Ctrl
FG Voltage/current
50/51
50/51
Ctrl
FG Voltage/current
Ctrl
FG Motor
25 46
50/51 27 59
Ctrl
Properties
Reduced investment because 1 device for multiple feeders
Simple parameterization
Shorter commissioning times
Cost savings because up to 7 feeders possible with 1 device.
Properties
Protection for each bay
Central control for multiple feeders
High availability because backup protection functions can be
activated in the controllers.
323
Autotransformer bank
Two-winding transformer
52
QA1
FG Transformer side 1
49
49H
50BF
49
59
50BF
81
FG Transformer 1
87
50/51
87T
87TNode
Auto transformer
FG compensation side
FG Transformer side 2
50/51
50BF
Ctrl
Ctrl
Ctrl
50/51
Ctrl
50BF
50BF
Ctrl
50BF
Ctrl
52
QA2
Properties
Clear assignment of the functions to the primary element
Reduced investment
Simple parameterization
Reduced wiring and faster commissioning.
Properties
Reduced investment due to integration of the differential and
node protection function in one unit (87 and 87 Node)
High sensitivity with single line to ground faults.
52
52
QA2
QA1
52
FG Transformer side 1
49
87N
50BF
7SA86
21
Ctrl
59N
50N/51N
FG Transformer 1
87
51
50BF
7UT86
Ctrl
51
FG Transformer side 2
FG Line
51
7SA86
21
21
87T
7SJ85
50/51
52
QA3
87T
50BF
59N
Ctrl
52
52
324
Properties
Separate acquisition, monitoring and control of all circuit
breakers
High sensitivity with single line to ground-fault differential
protection
Cost savings due to 87T and 87T N in one unit.
Properties
Free design of the protection and backup protection concept
Inclusion of line protection devices
Increased availability.
52
QA1
52
QA1
FG Motor
27
32
38
50/51 59
46
48
49S
59N 67Ns
FG Motor 1
27
49R
32
38
50/51 59
66
46
48
59N 66
49S
49R
67Ns
FG Motor 2
FG Analog units
87M
RTD
FG Analog units
RTD
Ctrl
RTD
Ctrl
RTD
Properties
Reduced investment because protection and control in one
device
Thermal motor protection functions for reliable motor
monitoring
Thermal motor protection functions with direct connection of
temperature sensors.
Properties
High sensitivity and short tripping times due to differential
protection function
Cost saving due to integration of the differential protection
function in a separate function group.
52
QA1
52
QA
FG Motor 1
27
32
38
50/51 59
46
48
59N 66
49S
51
67Ns
FG
Motor diff
87M
F G Motor side
FG Motor 2
52
QA1
87M
52
QA2
FG Analog units
7UT86
F G Motor (stator)
49R
F G Motor side
F G C ircuit breaker
C trl
RTD
Ctrl
52
QA3
Properties
Autonomous differential protection functions
High sensitivity and short tripping times due to differential
protection function
Separate acquisition and monitoring of the current
transformers.
Properties
Acquisition, monitoring and control of all circuit breakers
Differential protection function also available during starting.
325
52
52
QA1
21
52
QA1
FG Line 1
QA2
FG Line 1
87
50BF
87L
Ctrl
79
FG Line 2
50BF
Ctrl
21
79
50BF
Ctrl
FG Voltage/current
50/51
50N/51N
Line 1
Line 2
25
50BF
Ctrl
Properties
Clear assignment of protection and control in separate devices
Less external components by detection and selection of busbar
voltage in the device
High reliability due to backup protection functions in the 6MD8
bay controller
High availability due to emergency control in the 7SL8
protection device.
Properties
Low-cost due to protection of both lines in one device
Stable due to consideration of the influences of the parallel
line for the distance protection function.
52
QA1
52
87L
FG Line 2
21
FG Line 2
87L
FG Line 1
21
326
7SD8
87L
87L
QA2
FG Line 1
Line 1
7SD8
87L
FG Circuit breaker QA1
79
50BF
Ctrl
Protection interface
PI
52
Ctrl
52
PI
Ctrl
52
PI
Ctrl
PI
79
50BF
Ctrl
79
50BF
Ctrl
Protection interface
PI
7SD8
52
79
50BF
Ctrl
Line 2
Protection interface
Ctrl
7SD8
52
Ctrl
7SD8
52
Ctrl
87L
87L
87L
PI
PI
PI
Properties
High availability due to protection and device redundancy
Low-cost because only 2 devices required for 2 lines
Reliable because of parallel processing of the protection
functions in the devices.
Properties
High availability because differential protection is also active
when a communication link fails
Self-restoring due to automatic switchover from ring to chain
topology
High ease of maintenance because single line ends can be
taken out of the differential protection configuration for
commissioning and servicing.
BB 1
FG Line 1
21
87L
FG Line 1
87
50BF
52
QA1
79
Ctrl
FG Line 2
21
50BF
79
Ctrl
QA1 52
FG
Ctrl
FG
Line 1
Ctrl
Ctrl
Ctrl
Line 1
52
QA2
FG
25
Ctrl
QA2 52
25
Ctrl
Line 2
25
Line 2
FG Line 1
21
FG Line 2
21
52
QA3
87
50BF
79
Ctrl
Ctrl
FG Line 2
87L
FG
FG
52 QA3
Ctrl
FG
Ctrl
50BF
79
Ctrl
BB 2
Properties
Clarity due to clear assignment of protection and control
High availability due to protection redundancy (Main 1 and
Main 2)
Simple reliable central control of the entire diameter
Reliable due to emergency control in every line in the
protection device
Reduced wiring due to integrated voltage selection
System-wide diameter bus based on IEC 61850
electrically isolated data exchange,
reduced wiring
easy expansion.
Properties
Clear assignment of the primary protection function (line
differential protection 87) to a line in one device (Main 1)
The distance protection function (21) is implemented in the
protection device of the other line by a 2nd line function
group
High availability and reliability due to device and protection
redundancy
Low cost.
327
BB1
BB2
BB1
52
QA1
QB1 QB2
7SJ85
7SJ85
52
QA1
FG Capacitor bank
50N
37
49
59C
FG Capacitor bank
60C
50N/51N
59C
59N
37
60C
49
67N
Capacitor bank
50BF
50/51
50BF
Ctrl
Filter section
Capacitor bank
50
328
Properties
Precisely adapted due to dedicated function group and
application-specific protection function, such as peak
overvoltage protection (ANSI 59C) and sensitive currentunbalance protection (ANSI 60C)
L ow cost due to integration of all required functions into
one device.
Properties
Optimum protection of complex banks and filter circuits by
flexible hardware and flexible function design
Low cost due to integration of all necessary functions into one
device with up to 7 3-phase measuring points.
Bay 1
QB1
QB1
...
Bay 2
QB2
52
QB2
BB1
BB2
QB1
QA1
QB2
BI1
7SS85
52
QA1
FG Disconnector QB2
FG Disconnector QB1
BI1
50BF
50EF
Ctrl
FG Disconnector QB2
FG Disconnector QB2
FG Disconnector QB1
FG Disconnector QB1
50BF
50EF
Ctrl
52
QA1
50BF
50EF
BI1
Ctrl
FG Busbar
87B
Inherent CBFP
Check zone
Bus zone 1
Bus zone 2
Supervision
Properties
Central busbar protection
Grouping of all primary components of a bay in the
bay image
Configurable busbar function group
One device for up to 15 measuring points
Flexible adaptation to the topology
(up to 4 busbar sections and 4 couplings can be configured)
Integrated disconnector image
Convenient graphical configuration with DIGSI 5.
329
SIGUARD PDP
52
Node device A
SIPROTEC 5
PMU
52
52
Node device B
Node device C
SIPROTEC 5
SIPROTEC 5
PMU
PMU
Properties
Each SIPROTEC 5 device can be equipped or retrofitted with the
PMU function
Online and offline evaluation of the PMU data in the
monitoring system, SIGUARD PDP.
330
12.0
11.0
Rush
N
10.0
9.0
8.0
7.0
6.0
5.0
Sensitivity
Protection should be as sensitive as possible in order to detect
faults at the lowest possible current level. At the same time,
however, it should remain stable under all permissible load,
overload and through-fault conditions. For more information:
www.siemens.com/systemplanning. The Siemens engineering
programs SINCAL and SIGRADE are especially designed for
selective protection grading of protection relay systems. They
provide short-circuit calculations, international standard characteristics of relays, fuses and circuit-breakers for easy protection
grading with respect to motor starting, inrush phenomena, and
equipment damage curves.
Phase-fault overcurrent relays
The pickup values of phase overcurrent relays are normally set
30% above the maximum load current, provided that sufficient
short-circuit current is available. This practice is recommended
particularly for mechanical relays with reset ratios of 0.8 to 0.85.
Numerical relays have high reset ratios near 0.95 and allow,
therefore, about a10% lower setting. Feeders with high transformer and/or motor load require special consideration.
Transformer feeders
The energizing of transformers causes inrush currents that may
last for seconds, depending on their size (fig.6.2-56). Selection
of the pickup current and assigned time delay have to be coordinated so that the inrush current decreases below the relay
overcurrent reset value before the set operating time has
elapsed. The inrush current typically contains only about a 50%
fundamental frequency component. Numerical relays that filter
out harmonics and the DC component of the inrush current can
therefore be set to be more sensitive. The inrush current peak
values of fig.6.2-56 will be reduced to more than one half in
this case. Some digital relay types have an inrush detection
function that may block the trip of the overcurrent protection
resulting from inrush currents.
Ground-fault protection relays
Earth-current relays enable a much more sensitive setting,
because load currents do not have to be considered (except
4-wire circuits with 1-phase load). In solidly and low-resistance
earthed systems, a setting of 10 to 20% rated load current can
generally be applied. High-resistance earthing requires a much
more sensitive setting, on the order of some amperes primary.
The earth-fault current of motors and generators, for example,
should be limited to values below 10 A in order to avoid iron
burning. In this case, residual-current relays in the start point
4.0
3.0
2.0
1.0
10
100
400
0.5 1.0
1.0 10
> 10
0.16 0.2
0.2 1.2
1.2 720
331
Motor feeders
The energization of motors causes a starting current of initially
5to 6 times the rated current (locked rotor current).
A typical time-current curve for an induction motor is shown in
fig.6.2-57.
In the first 100ms, a fast-decaying asymmetrical inrush current
also appears. With conventional relays, it was common practice
to set the instantaneous overcurrent stage of the short-circuit
protection 20 to 30% above the locked rotor current with a
short-time delay of 50 to 100ms to override the asymmetrical
inrush period.
Numerical relays are able to filter out the asymmetrical current
component very rapidly so that the setting of an additional time
delay is no longer applicable.
The overload protection characteristic should follow the thermal
motor characteristic as closely as possible. The adaptation is
made by setting the pickup value and the thermal time constant,
using the data supplied by the motor manufacturer. Furthermore, the locked-rotor protection timer has to be set according
to the characteristic motor value.
Time grading of overcurrent relays (51)
The selectivity of overcurrent protection is based on time
grading of the relay operating characteristics. The relay closer to
the infeed (upstream relay) is time-delayed against the relay
further away from the infeed (downstream relay). The calculation of necessary grading times is shown in fig.6.2-57 by an
example for definite-time overcurrent relays.
Inverse-time relays
For the time grading of inverse-time relays, in principle the same
rules apply as for the definite-time relays. The time grading is
first calculated for the maximum fault level and then checked for
lower current levels (fig.6.2-58).
10,000
1,000
Time in
seconds
100
10
1
0.1
0.01
0.001
10
Locked-rotor current
Overload protection
characteristic
Time
51
51
51
0.2-0.4 seconds
Main
Feeder
Maximum feeder fault level
Current
332
Calculation example
The feeder configuration of fig.6.2-60 and the associated load
and short-circuit currents are given. Numerical overcurrent
relays 7SJ80 with normal inverse-time characteristics are
applied.
Operating time
52M
51M
52F
52F
51F
51F
0.2-0.4
Time grading
Fault
Fault
inception detection
Interruption of
fault current
t 51F
t 52F
Circuit-breaker
interruption time
This current setting should be lowest for the relay farthest downstream. The relays further upstream should each have equal or
higher current settings.
Overshoot*
t OS
Margin tM
t 51M
Oil circuit-breaker
t52F = 0.10 s
Mechanical relays
tOS = 0.15 s
tM = 0.15 s
Example 2
Vacuum circuit-breaker
t52F = 0.08 s
Numerical relays
tOS = 0.02 s
Safety margin
tM = 0.10 s
Station B:
The relay in B has a primary protection function for line B-C and
a backup function for the relay in C. The maximum through-fault
current of 1.395A becomes effective for a fault in location F2.
For the relay in C, an operating time time of 0.11s (I/Ip = 19.93)
is obtained.
It is assumed that no special requirements for short operating
times exist and therefore an average time grading interval of
0.3s can be chosen. The operating time of the relay in B can
then be calculated.
F3 C
F4 B
F2
13.8 kV
Station
51
51
51
7SJ80
7SJ80
7SJ80
Max.
load
A
ISCC. max*
CT
ratio
13.8 kV/
0.4 kV
Fuse: D
160 A
625 kVA
5.0 %
L.V. 75
Load
F1
Load
Load
300
4,500
400/5
1.0
400
11.25
170
2,690
200/5
1.1
220
12.23
50
1,395
100/5
0.7
70
19.93
1,395A
Value of Ip/IN = = 6.34 (fig.6.2-60)
220A
523
*)
ISCC. max = Maximum short-circuit current
= Relay current multiplier setting
**) Ip/IN
= Primary setting current corresponding to Ip/IN
***) Iprim
333
100
50
40
30
20
Tp [s]
10
334
3.2
5
4
1.6
3
2
0.8
0.4
0.50
0.4
0.2
0.3
0.1
0.2
0.05
0.1
0.05
2
6 8 10
20
p
[A]
Normalinverse
0.14
t = Tp(s)
(I/Ip)0.02 1
Strong inverse characteristics may be used with expulsion-type
fuses (fuse cutouts), while extremely inverse versions adapt
better to current limiting fuses.
In any case, the final decision should be made by plotting the
curves in the log-log coordination diagram.
Electronic trip devices of LV breakers have long-delay, shortdelay and instantaneous zones. Numerical overcurrent relays
with one inverse-time and two definite-time zones can closely
be adapted to this (fig.6.2-63b).
Ip = 0.104.00 IN
Tp = 0.053.2 s
I>> = 0.125 IN
400/5 A
52
Ip = 1.0 IN
Tp = 0.11 s
I>> =
7SJ80
Bus-B
Ip = 0.104.00 IN
Tp = 0.053.2 s
I>> = 0.125 IN
200/5 A
52
7SJ80
Ip = 0.7 IN
Tp = 0.05 s
I>> =
Bus-C
100/5 A
52
Ip = 1.0 IN
Tp = 0.17 s
I>> =
Ip = 0.104.00 IN
Tp = 0.053.2 s
I>> = 0.125 IN
7SJ80
TR
13.8/0.4 kV
625 kVA
5.0%
fuse
VDE 160
MV bus
Inverse-time relay
Time
51
Other
consumers
50/51
Fuse
n
a
LV bus
Fuse
a)
MV bus
n
a
LV bus
0.2 s
Current
Maximum fault available at HV bus
Fig.6.2-63 a + b: Coordination of an overcurrent relay with an MV fuse and low-voltage breaker trip device
335
Z3A
Opet
rating 3
time t 2
Z2A
Z1A
t1
ZL A-B
Z2B
Z1C
Z1B
ZL B-C
B
Load
ZLC-D
C
Load
D
Load
X
X 3A
X 2A
B
X1A
VTratio
XPrim Min = XRelay Min
CTratio
R1A
XPrim Min
lmin =
XLine
The shortest setting of the numerical Siemens relays is 0.05
for 1 A relays, corresponding to 0.01 for 5A relays. This allows
distance protection of distribution cables down to the range of
some 500 meters.
Breaker failure protection setting
Most numerical relays in this guide provide breaker failure (BF)
protection as an integral function. The initiation of the BF protection by the internal protection functions then takes place via
software logic. However, the BF protection function may also be
initiated externally via binary inputs by an alternate protection.
In this case, the operating time of intermediate relays (BFI time)
may have to be considered. Finally, the tripping of the infeeding
breakers requires auxiliary relays, which add a small time delay
(BFI) to the overall fault clearing time. This is particularly the
case with one-breaker-and-a-half or ring bus arrangements
where a separate breaker failure relay (7VK8) is used per
breaker.
The decisive criterion of BF protection time coordination is the
reset time of the current detector (50BF), which must not be
exceeded under any condition during normal current interruption. The reset times specified in the Siemens numerical relay
manuals are valid for the worst-case condition: interruption of a
fully offset short-circuit current and low current pickup setting
(0.1 to 0.2 times rated CT current).
336
R 2A
R 3A
R
50BF
50BF
P1
P1: primary
protection
P 2: alternate
protection
P2
O
R
A
N
D
The reset time is 1 cycle for EHV relays (7SA8, 7VK8) and 1.5 to
2 cycles for distribution type relays (7SJ**).
Fig.6.2-66 shows the time chart for a typical breaker failure
protection scheme. The stated times in parentheses apply for
transmission system protection and the times in square brackets
for distribution system protection.
Fault incidence
BFI =
breaker failure
initiation time
(intermediate
relays, if any)
Protect.
Breaker inter.
Current
detector
(50 BF)
reset time
Margin
time
(2~)
[4~]
(1~)
[2~]
(2,5~)
[2,5~]
time
(1~)
[2~]
0,5~
BFI
BFT =
breaker failure
tripping time
(auxilary relays,
if any)
(5~)
[8~]
0,5~
BFT
(2~)
[4~]
Adjacent
breaker
int. time
(9~) [15~]
The requirements for protective current transformers for transient performance are specified in IEC60044-6. In many practical cases, iron-core CTs cannot be designed to avoid saturation
under all circumstances because of cost and space reasons,
particularly with metal-enclosed switchgear.
The Siemens relays are therefore designed to tolerate CT saturation to a large extent. The numerical relays proposed in this
guide are particularly stable in this case due to their integrated
saturation detection function. As an example you find the
current transformer requirements for SIPROTEC 7UT8 transformer protection devices. This example should give you an
overview how to handle CT requirements during you protection
calculation.
For all SIPROTEC 5 devices you find detailed requirement tables
in the device manuals. Please refer to the latest manual version
for your CT requirement calculation.
More accurate dimensioning can be done by more intensive
calculation with Siemens CTDIM (www.siemens.com/ctdim)
program. Results of CTDIM are released by the relay manufacturer.
337
338
339
During the last years, the influences on the business of the power
supply companies have changed a lot. The approach to power
grid operation has changed from a static quasi-stable interpretation to a dynamic operational management of the electric power
grid. Enhanced requirements regarding the economy of lifetime
for all assets in the grid are gaining importance.
As a result, the significance of automation systems has increased
a lot, and the requirements for control, protection and remote
control have undergone severe changes of paradigm:
340
Control centers
IEC -101 or -104
Ax-Bus
SICAM 230
SICAM AK
Ethernet TCP/IP
IEC 61850
SIPROTEC
Protection relais
PE elements
Alternative interface
(substitution of terminal blocks)
Parallel data
(from marshalling rack)
Control centers
IEC - 101 or IEC - 104
SICAM 230 or
SICAM SCC
SICAM RTUs
SICAM PAS
Ethernet TCP/IP
IEC 61850
IEC - 104
SIPROTEC
High-voltage
n x bays
SICAM CMIC
Medium-voltage
m relais
Station data
Fig.6.33: Basic principle of a SICAMstation automation solution with alternative station controllers
341
SICAM TOOLBOX II
SICAM TM Zentralgert
Local input / output
Central processing
NTP
IEC 60870-5-104
SICAM TM
Data node
Front end
Gateway
IEC 60870-5-104
SICAM TM-FW-Unterstation
Local processing
Decentralized acquisition
IEC 60870-5-103
IEC 61850
IEC 60870-5-104
IEC 60870-5-101
SICAM RTUs
SICAM TM
Turbine controller
Power plant management
Automation & control
SICAM RTUs
SIPROTEC / IEDs
342
343
344
NOR
USA
GBR
BEL
CH
USA
ITL
MEX
KOL
BRA
GER
OES
TRK
Training
Configuration
Installation and
commissioning
RUS
IND
Lifecycleservices
CHN
SIN
IDS
Incl. refurbishment of
old systems and
old equipment
Our solutions are not only compatible with older devices, they
are also very innovative. The Frost&Sullivan Technology Leadership Award 2006 was presented to Siemens for pioneering in the
development of an innovative technology, the IEC61850.
With Siemens energy automation solutions, every user is on the
safe side: The combination of long-term experience and the
newest innovation supplies safety for many years to come.
Bay 1 ... n
TCP/IP
IEC61850
Fiber-optic
connections
ILSA protocol
Switchgear
Bay 1 ... n
Switchgear
Fig.6.37: Migration from LSA to PAS
345
6.3.3 SICAMPAS
SICAMPAS (Power Automation System) meets all the demands
placed on a distributed substation control system both now
and in the future. Amongst many other standardized communication protocols, SICAMPAS particularly supports the IEC61850
standard for communication between substations and IEDs.
SICAMPAS is an open system and in addition to standardized
data transfer processes it features user interfaces for the
integration of system-specific tasks and offers multiple automation options. SICAMPAS can thus be easily included in existing
systems and used for system integration, too. With modern
diagnostics, it optimally supports commissioning and maintenance. SICAMPAS is clearly structured and reliable, thanks to its
open, fully documented and tested system (fig.6.3-8).
System overview, application and functionality of SICAMPAS
SICAMPAS is an energy automation solution; its system
architecture makes it scalable.
SICAMPAS is suitable for operating a substation not only from
one single station level computer, but also in combination with
further SICAMPAS or other station control units. Communication in this network is based on a powerful Ethernet LAN.
With its features and its modular expandability, SICAMPAS
covers a broad range of applications and supports distributed
system configurations. A distributed SICAMPAS system
operates simultaneously on several computers.
SICAMPAS can use existing hardware components and
communication standards as well as their connections.
SICAMPAS controls and registers the process data for all
devices of a substation, within the scope of the data transfer
protocols supported.
SICAMPAS is a communication gateway. This is why only one
single data connection to a higher-level system control center
is required.
Control center
Station unit
full server
Corporate
network TCP/IP
IEC 60870-5-101
DNP3
IEC 60870-5-104
DNPi
HMI
Station bus
Ethernet TCP/IP
Serial hub
IEC 61850
Fig.6.38: Typical SICAMPAS configuration; IEDs are connected to the station unit with IEC61850 and various other protocols
(IEC60870-5-103, DNP3, etc.). The station unit communicates with the higher-level system control center by means
of IEC60870-5-101 and/or 104
346
the devices at the feeder and station control levels on the basis
of Ethernet. IEC61850 supports the direct exchange of data
between IEDs, thus enabling switching interlocks across
feeders independently of the station control unit, for example.
IEC60870-5-103 (Master):
Protection relays, IEDs, bay control units, measured value
recorders and transformer controllers from many
manufacturers support the IEC60870-5-103 protocol and can
therefore be connected directly to SICAMPAS.
IEC60870-5-101 (Master):
The IEC60870-5-101 protocol is generally used to connect
telecontrol units. The balanced and unbalanced traffic
modes are supported.
Automatic dialing is also supported for the connection of
substations with this protocol. SICAMPAS can establish the
dial-up connection to the substation either cyclically or as
required (e.g., for command output). By contrast, the
substation can also establish a connection cyclically or in
event-triggered mode.
IEC60870-5-104 (Master):
Furthermore, connection of substations is also supported by
the TCP/IP-based IEC60870-5-104 protocol.
DNP3 (Master) Level 3:
Apart from the IECprotocols -101 and -104, DNP3 is another
standardized telecontrol protocol used by many IEDs and RTUs
and applied worldwide. The units can be connected both
serially and with TCP/IP (DNPi). TCP/IP-based communication
can operate with an asymmetrical encryption procedure, thus
meeting security requirements.
PROFIBUS DP (Master):
PROFIBUS DP is a highly powerful field bus protocol. For
example, it is used for industrial automation and for
automating the supply of electricity and gas. PROFIBUS DP
serves to interface multifunctional measuring instruments
such as SICAMP (I, V, P, Q, p.f. (cos) or, for example, to
connect ET200 components for gathering messages and for
simple commands. Messages, for example, can be derived
from the signaling contacts of fuse switch-disconnectors.
Mobus (Master)
Besides PROFIBUS DP, the Mobus protocol is also well-known in
industrial applications. SICAMPAS allows to connect IEDs und
RTUs with this protocol, both via serial and TCP/IPbased
connections.
Protocols
SICAMPAS supports the following communication
protocols (optionally available):
Control center connection IEC60870-5-101,
IEC60870-5-104, DNP3, Modbus, TG 8979, CDT
Open data exchange OPC server, OPC XML DA server,
OPC client
IED and substation connection IEC61850,
IEC60870-5-101, IEC60870-5-103, IEC60870-5-104,
DNP3, PROFIBUS FMS (SIPROTEC 4), PROFIBUS DP,
Modbus, SINAUT LSA-ILSA
Fig.6.39: Versatile communication with SICAMPAS
347
Automation tasks
can be configured in SICAMPAS with the CFC (Continuous
Function Chart), which conforms to IEC61131. In this editor,
tasks are configured graphically by wiring function blocks.
SICAMPAS comes with an extensive library of CFC function
blocks, developed and system-tested specially for energy automation.
Applications range from generation of simple group indications
through switching interlocks to complex operating sequences.
Creation of operating sequences is supported by the SFC Editor
(Sequential Function Chart).
In this context, additionally pre-configured and system-tested
applications such as frequency-based load shedding, transformer
monitoring and SF6 gas monitoring can be optionally licensed.
Besides special functional components and CFCs, the scope of
supply also covers operating images for SICAMSCC.
348
Redundancy
SICAMPAS features comprehensive redundancy functions to
boost the availability of the station automation system:
The substation control unit can be used in a duplicate
configuration (system redundancy)
The communication to IEDs and RTUs can be redundant
(interface redundancy)
Subordinate units can be duplicated (redundancy at the bay
control level)
Subunits that are only designed for communication with one
master (e.g., with only one serial interface) can be supported.
The individual applications (communication protocols) operate
independently of each other in a hot/standby connection, i.e. a
changeover, e.g., of the IEC61850 client from one station
control unit to the other due to a disturbance has no effects on
the communication connection to the control center, which
remains on the first station control unit without interruption.
Apart from a higher stability in unaffected communication
connections, the redundancy changeover of affected components takes place within a very short time (depending on application and configuration, between 250 ms and max. 3 sec).
Adjustments during operation such as bay/telecontrol blocking,
switching authority, but also marking commands to the SoftPLC
for operational control of the automation functions, are kept
synchronous in both station control units during redundancy
operation. The current adjustments are also valid after a redundancy changeover. SICAMSCC communicates simultaneously
with both redundant station control units. A redundant structure
is also possible for process visualization with SICAMSCC and
fault-record archiving with SICAMPQ Analyzer as shown in
fig.6.3-10.
Scope of information
The amount of information to be processed by SICAMPAS is
essentially determined by the following factors:
Computer network concept (multiple-computer network or
single-station system)
Performance data of the hardware used
Performance data of the network
Size of the database (RDBMS)
Rate of change of values
With a distributed PAS system using a full server and up to 6
DIPs, a maximum of 350 IEDs and 20,000 data points can be
supported.
Process visualization with SICAMSCC
In the operation of a substation, SICAMPAS is used for configuration purposes and as a powerful data concentrator.
SICAMSCC serves as the process visualization system. Several
independent SICAMSCC servers can be connected to one
SICAMPAS. Connection of redundant servers is also possible.
SICAMSCC supports the connection of several SICAMPAS systems. In the signal lists, the original time stamps are logged in
ms resolution as they occur in the devices. With every signal, a
series of additional data is also presented to provide information
about causes (spontaneous, command), event sources (close
Corporate
network TCP/IP
HMI
clients
Station unit
Full Server
Station unit
Full Server
Station bus
Ethernet TCP/IP
IEC 61850
Fig.6.310: Typical redundant configuration: The station unit and the HMI server are based on a redundant structure to boost availiability
= D01
= D02
= D03
BBI
= D04 = D05
= D06
220 kV
= D07
= D08
= D09
0.0 kV
BBII
0A
600 A
600 A
0A
600 A
T01
TP 0
10.1 kV
0A
T02
T03
TP 0
= K12/13
TP 0
10.1 kV
= K17
= K22
= K19/20
600 A
T04
TP 0
10.1 kV
= K08
600 A
10.1 kV
= K33
= K26/27
= K01/02
Fig.6.311: Process visualization with SICAMSCC
are supported, but also the display of various device and communication states (e.g., up-to-date/not up-to-date, feeder and
telecontrol blocking, etc.). Measured values and switching
device states that are not continuously updated due to, e.g.,
device or communication failure or feeder blocking, may be
updated directly via the operation panel with SICAMSCC
(fig.6.311).
349
SICAM SCC
IEC 61850
IEC 60870-5-104
SICAM PAS
Distributed process connection
with IEDs
Integrated engineering tool
Integrated configuration and
test function (online)
350
IEDs
Direct connection of IEDs
with IEC 61850
Engineering with DIGSI 4
Further information
www.siemens.com/substationautomation
SICAM PAS
Field devices
Protection devices
SICAM PQS
Power-quality equipment
351
All components of the ACP family are using the same communication modules, and therefore they can use all available protocols. In addition to standards like IEC60870-5-101/103/104
and IEC61850 (client and/or server), also DNP3 and Modbus are
available in addition to a lot of legacy and third-party protocols
for connecting third-party devices.
Another joint feature of all components is the integrated flash
memory card, where all parameters and firmwares are stored. A
simple exchange of a component is now possible, just by
changing the memory card.
352
Besides the standard protocols there are also a variety of thirdparty protocols available (DNP3, Modbus etc.).
Simple process interfacing
In addition to the central acquisition and output of process
signals within an SICAMAK mounting rack, it is possible to use
SICAMRTUs peripheral elements (fig.6.314).
An essential feature of the SICAMRTUs peripheral elements is
the efficient and simple interfacing possibility of the process
signals. This takes place on so-called I/O modules, which are
distinguished through a robust casing, a secure contact as well
as solid electronics. The I/O modules are lined up in rows. The
contact takes place during the process of latching together,
without any further manipulation. Thereby each module remains
individually exchangeable.
A clearly arranged connection front with LEDs for the status
display ensures clarity locally. The structure of the terminals
enables a direct sensor/actuator wiring without using intermediate terminal blocks with wire cross-sections up to 2.5mm2.
Modules for binary inputs and outputs up to DC220V open
further saving potentials at the interface level.
Depending on the requirements, the I/O modules can be fitted
with either an electrical bus or an optical bus, through which the
peripheral signals can be acquired as close as possible to the point
of origin. In this way, broad cabling can be reduced to a minimum.
353
Easy engineering
An essential aspect in the overall economical consideration are
the costs that occur for the creation, maintenance and service.
For this, the reliable SICAMTOOLBOXII is used.
Object orientation:
The object orientation makes it possible to also utilize the
same characteristics of same-type primary-technology units
and operational equipment (e.g., disconnectors, circuitbreakers, feeders etc.) for the configuration. The close
coupling with the design tool ensures the consistent, uniform
documentation of the entire plant through to circuit diagram.
Through this, considerable rationalization results with
engineering.
Open-loop and closed-loop control according to IEC61131-3:
Open-loop and closed-loop control application programs are
created by means of CAEx plus according to IEC61131-3, a
standard that is generally accepted and recognized in the
market. As a result, the training periods are reduced
considerably.
All engineering tasks can also be carried out remotely:
All engineering tasks, from the system diagnostic through to
the online test, can also be performed remotely with the
SICAMTOOLBOXII. For this, a separate communication link
between SICAMTOOLBOXII and SICAMAK is not necessary:
Every available communication interface can be used. Using
further automation units of SICAMTM, AK or BC, the
SICAMTOOLBOXII can be remotely positioned over an
arbitrary number of hierarchies.
354
SICAM TOOLBOX II
SICAM TM Zentralgert
Local input / output
Central processing
NTP
IEC 60870-5-104
SICAM TM
Data node
Front end
Gateway
IEC 60870-5-104
IEC 60870-5-103
IEC 61850
IEC 60870-5-104
IEC 60870-5-101
SICAM TM-FW-Unterstation
Local processing
Decentralized acquisition
SICAM RTUs
SICAM TM
Turbine controller
Power plant management
Automation & control
SICAM RTUs
SIPROTEC / IEDs
Fig.6.315: SICAMTM system architecture: connection of up to 16 peripheral elements via bus interface (electrical)
355
356
Peripherals
A peripheral element is constituted of
1 power supply module,
1 peripheral control module, and
up to 8 I/O modules (fig.6.317)
The respective data sheets document how many I/O modules
may actually be used per peripheral element and in what order
they can be used.
A key feature of SICAMTM is that it provides for the efficient and
simple connection of the process signals. This is done at the I/O
modules standing out for a robust housing, reliable contacting,
and sound electronics.
The I/O modules are added side by side to the peripheral control
module. Contact is established as soon as they engage with one
another, without requiring any further manual intervention.
Even so, every single I/O module can still be exchanged separately and mounted on a DIN rail. It may be installed horizontally
or vertically.
Removable terminals (I/O connectors) are used for the simple
handling of modules when they are to be mounted or
exchanged. Since the terminals carry the wiring, no connections
need to be disconnected when devices are exchanged.
To interface peripheral elements to the master control element,
a bus interface module must be fitted on the side of the master
control element. Using simple, standardized USB cables, the
peripheral control modules are connected to the bus interface
module, thereby reducing the assembly effort required for their
connection to a minimum.
The Ax1703 peripheral bus permits the secured, serial, insystem communication between the master control element and
the peripheral elements. Serial communication also renders it
possible to detach individual or all peripheral elements via
optical links up to 200m from the master, with full system
functionality remaining intact.
357
Device characteristics
Communication interfaces and protocols
2 x Ethernet LAN TCP/IP10/100BASE-TX for communication and
engineering
1 x RS-232, 1 x RS-485 (galvanically isolated)
IEC 60870-5-101/-103/-104, Modbus
IEC 61850 client & server
SNMP V3
Further protocols on request
Operation and display
Local operation with 4 function keys and display (128x96
pixels)
Power, ready and error LED, status LEDs of communication
interfaces
Real time clock
+/- 2 ppm, maintenance-free, buffered, time synchronization
via SNTP (Network Time Protocol), automatic adjustment to
daylight saving time
Electromagnetic compatibility
IEC 60870-2-1, IEC 61010, IEC 60255-5, IEC 61000-4, EN
55022, CE marking
Auxiliary voltage
DC 18 - 72 V
Applications
All the options offered by the SICAMCMIC device can be roughly
subdivided into the following three applications:
Monitoring: The first stage focuses on the monitoring of
stations to enable rapid fault localization and high availability.
Telecontrol: The second stage involves switchgear telecontrol
in addition to monitoring, thus minimizing downtime. Thanks
to this application, fault isolation and power supply restoration
of de-energized network sections are no longer difficult tasks
for power supply utilities.
Load flow control: In the third stage, the effects of
decentralized power feed-ins are managed via automation.
Network losses can be in this way significantly reduced.
The SICAMCMIC device is designed for harsh environmental
conditions and can be used in unheated, small local network
stations, as it has a high degree of electromagnetic compatibility
and is intended for the temperature range from -40 C to +70 C.
If the number of integrated I/O is not sufficient, SICAMCMIC can
be expanded with up to six proven SICAMI/O modules.
Communication
The communication to the control center is possible in several
ways and a multitude of protocols. It doesnt make any difference whether via Multi-Point Traffic, Dial-Up Traffic or LAN/WAN/
GPRS/UMTS.
Fig.6.319: SICAMCMIC
358
Inputs/outputs
12 galvanically isolated digital inputs (24-60 VDC)
8 digital outputs
Temperature range:
From -40C to +70C (basic unit)
From -25C to + 70C (SICAMI/O module)
Housing specification (basic unit)
Plastic housing for DIN rail mounting
Dimensions: 128 x 124 x 123 mm (W / H / D)
Protection class: IP20, IP40 front
Special features
Integrated web server for configuration and diagnostics
Data storage via SD memory card (storage of parameters and
device firmware)
Freely programmable user programs according to
IEC 61131-3
Future security standard (BDEW white paper conformity and
integrated crypto chip)
For further information:
www.siemens.com/sicam
Control system
NTP
IEC 60870-5-104
6
SICAM
FCM
MS
NS
SICAM
CMIC
SICAM P850/855
Sample configuration:
SECONDARY SUBSTATION
359
Voltage quality
Voltage quality, also termed power quality (PQ), covers a variety
of characteristics in a power system. Chief among these is the
quality of the voltage waveform. There are several technical
standards defining voltage quality criteria, but ultimately quality
is determined by the ability of customers equipment to perform
properly. The relevant technical phenomena are: variations in
frequency, fluctuations in voltage magnitude, short-duration
voltage variations (dips, swells, and short interruptions), longduration voltage variations (overvoltages or undervoltages),
transients (temporarily transient overvoltages), waveform
distortion, etc. In many countries voltage quality is regulated to
some extent, often using industry-wide accepted standards or
practices to provide indicative levels of performance.
Supply quality
Quality is generally recognized as an important aspect of any
electricity supply service. Customers care about high quality just
as much as low prices. Price and quality are complementary.
Together, they define the value that customers derive from the
electrical supply service.
Vo
lt
Cu
rre
nt
dis
tu
rb
an
ce
ag
ed
ist
ur
ba
nc
es
Fig.6.4-1: Power quality monitoring provides value to everyone to the local utility, to the consumer, to the local economy and to the
environment
360
Who is responsible?
An interesting problem arises when the market fails to offer
products that meet the customers power quality needs. If a
customer cannot find equipment that is designed to tolerate
momentary power interruptions, the customer may, for
example, pressure the power supplier and the regulator to
increase the power quality of the overall distribution system. It
may be in the suppliers interest to help the customer address
the power quality and reliability problem locally.
The electrical supply system can be considered a sort of openaccess resource: In practice, almost everybody is connected to it
and can freely feed into it. This freedom is now limited by
standards, and/or agreements. In European countries, the
EN50160 European standard is generally used as a basis for the
supply quality, often also termed the voltage or power quality.
There is currently no standard for the current quality at the point
of common coupling (PCC), but only for equipment. The interaction between the voltage and current makes it hard to draw a
line between the customer as receiving and the network
company as supplying a certain level of power quality. The
voltage quality (for which the network is often considered
responsible) and the current quality (for which the customer is
often considered responsible) affect each other in mutual interaction.
Harmonic
Reactive power
Flicker
Unbalance
Harmonic
predistortion
Voltage dips/swells
Voltage variations
Interruption
Fig.6.4-2: Utility and industries, both are responsible for voltage quality
361
Problem
Voltage signal
f1
f2
0.1
f1
time (s)
0.2
Description
Cause
Effect
Frequency distortions:
A frequency variation involves
variation in frequency above or
below the normally stable utility
frequency of 50 or 60Hz
M
isoperation, data loss, system
crashes and damage to
equipment and motor
F
or certain kinds of motor load,
such as in textile mills, tight
control of frequency is essential
Supply interruption:
Planned or accidental total loss of
power in a specific area
Momentary interruptions lasting
from a half second to 3 seconds
Temporary interruptions lasting
from 3 seconds to 1 minute
Long-term interruptions lasting
longer than 1 minute
S
ensible processes and system
shutdown or damages
L oss of computer/controller
memory
P
roduction losses or damage
M
emory loss, data errors, dim or
bright lights, shrinking display
screens, equipment shutdown
M
otors stalling or stopping and
decreased motor life
Voltage signal
f1 > f2
interruption
time up to
three minutes
0
0.1
0.2
time (s)
0.4
0.5
Voltage signal
0.1
0.2
time (s)
0.4
0.5
Voltage signal
0.1
0.2
Voltage signal
0.1
0.2
time (s)
0.4
0.5
with repetition
time (s)
0.4
0.5
Voltage signal
Transients
0.02
0.04
time (s)
0.08
0.1
E
quipment shutdown by tripping
due to undervoltage or even
overheating and/or damage to
equipment due to overvoltage
R
educed efficiency or life of
electrical equipment
Flicker:
Impression of unsteadiness of
visual sensation induced by a light
stimulus, the luminance or spectral
distribution of which fluctuates
with time
Intermittent loads
Motor starting
Arc furnaces
Welding plants
C
hanges in the luminance of
lamps can result in the visual
phenomenon called flicker on
people, disturbing concentration,
causing headaches, etc.
Transient:
A transient is a sudden change in
voltage up to several thousand
volts. It may be of the impulsive or
oscillatory type (also termed
impulse, surge, or spike)
Notch:
This is a disturbance of opposite
polarity from the waveform
P
rocessing errors
D
ata loss
L ock-up of sensitive equipment
B
urned circuit boards
Noise:
Noise is caused by
This is an unwanted electrical signal
electromagnetic interference
of high frequency from other
from appliances, e.g. microwave,
equipment
radio and TV broadcasts, arc
Harmonic:
welding, heaters, laser printers,
Distortion is alteration of the pure
thermostats, loose wiring, or
sine wave due to non-linear loads
improper grounding
on the power supply
Harmonic distortion is caused by
non-linear loads
362
N
oise interferes with sensitive
electronic equipment
It can cause processing errors and
data loss
H
armonic distortion causes
motors, transformers, and wiring
to overheat
Improper operation of breakers,
relays, or fuses
PQ
application
Regulatory
power
quality:
Explanatory
power
quality:
Description
Hardware
Measurements
Power Quality
Recorders
(mainly
ClassA)
PQ recorders
Class A, S or B
and fault
recorder/PMU
Project
phases
Planning
activities
SICAM
Q80
support
System
installation
and
configuration
Defining PQ
objectives
Define PQ
measurement
objectives (regulative,
explanatory, or both)
and define the targets
Start
measuring
Evaluation
System
improvement
and/or
countermeasures
Define measuring
points and install
devices and systems
Automatic
notification or
systemic system
check-up for events or
standards violations
Power quality
compliance
Reporting and/or
event evaluation
Analysis of information,
controlling, action plan,
adaptation to standards,
comparison with
defined targets
Easy configuration
with SICAM Q80
Manager
Reliable
measurement
of defined quantities
Automatic report
generator in case
of limit valutation
Standards
The purpose of power quality indexes and measurement objectives is to characterize power system disturbance levels. Such
indexes may be defined as voltage characteristics and may be
stipulated in a Grid Code that applies to electrical system interfaces. Power quality Grid Codes make use of existing standards
or guidelines defining voltage and current indexes to be applied
to interfaces in low, medium, or high-voltage systems, for
example, EN50160. This standard defines and describes the
main characteristics of the voltage at the system operators
supply terminals in public LV and MV power distribution systems.
Indexes for HV-EHV will also be described in the new edition of
EN50160. Since electrical systems among regions and countries
363
EN 50160
VA
1.1 VA
0.9 VA
1.1 Vn (rms)
Vn (rms)
0.9 Vn (rms)
V(rms)
IEC 61000-4-30
Measurement of voltage quality
IEC 61000-4-7
Harmonics
IEC 61000-4-15
Flickermeter
Parameter
Power frequency
Voltage magnitude
variations
Relative
voltage
(%)
Even harmonics
Multiples of 3
Order h
Relative
voltage
(%)
Order h
Relative
voltage
(%)
1.5
11
3.5
15
0.5
6 24
0.5
13
21
0.5
17
19
1.5
23
1.5
Short interruptions of
supply voltage
25
1.5
Long interruption of
supply voltage
Temporary, power
frequency
overvoltages
Transient overvoltages
Supply voltage
unbalance
Harmonic
voltage/THD
Interharmonic voltage
Table6.4-3: R
equirements according to EN50160
364
Short supply
interruption
t < 3 min
Transmission
1
2
IEC61000-4-15:1997 + A1:2003:
Flickermeter, Functional and Design Specifications: This section
of IEC61000 provides a functional and design specification for
flicker measuring apparatus intended to indicate the correct
flicker perception level for all practical voltage fluctuation waveforms.
IEC61000-4-7, Ed. 2, 2002-08:
General Guide on Harmonics and Interharmonics: This is a
general guide on harmonics and interharmonics measurements
and instrumentation, for power supply systems and equipment
connected thereto.
Subtransmission
Generation/
Distributed
generation
4
7
5
Distribution
LOAD
(industrial)
6
8
Low voltage
9
LOAD
No.
Measurement points
Location
Possibly busbar
Generation
station/distributed
generation
Subtransmission, line
supply
Subtransmission feeder
(line or transformer)
Step-down transformers
Distribution load
LV supply
LV load
365
Function overview
Measurement of voltage, current, active & reactive power,
frequency, active and reactive energy, power factor, symmetry
factor, voltage and current harmonics up to the 21st, total
harmonic distortion
Single-phase, three-phase balanced or unbalanced connection,
four-wire connection
Communications: PROFIBUS-DP, MODBUS RTU/ASCII or
IEC60870-5-103, MODBUS RTU/ASCII (only SICAMP50 Series)
communication protocol
Simple parameterization via front key or RS485 communication
port using SICAMP PAR software
Graphic display with background illumination with up to 20
programmable screens
Real-time clock: Measured values and states will be recorded
with time stamps
1 MB memory management: The allocation of the nonvolatile
measurement memory is programmable
Recording and display of limit value violations and log entries.
Battery: Recordings like limit value violations or energy counter
values stay safely in the memory up to 3 months in case of a
blackout.
Applications
Power monitoring systems with SICAMP, a permanently installed
system, enables continuous logging of energyrelated data and
provides information on operational characteristics of electrical
systems. SICAMP helps identify sources of energy consumption
and time of peak consumption. This knowledge allows to allocate and reduce energy costs.
SICAM P 7KG775x
Option
Voltage
L1
L2
Binary
outputs
Auxiliary
power
Measuring inputs
Inputs/
outputs
Communication via
RS485
Terminal A
Current
L3
L1
L2
L3
W
N/-
Terminal F
Terminal E
B2
B1
N/+
Terminal H
Terminal G
DC: 24-250 V
AC:100-230 V
k
L1
l
k
L2
l
k
L3
RS485
N
PE
RS232
Parameterization
366
Master
station
Analog inputs
from transducers 020 mA
Analog outputs
Water
Flow rate, pressure, PH, etc.
Gas
Flow rate, pressure, etc.
Energy metering
Binary outputs
Oil
Flow rate, pressure, etc.
Messages, limit-value
violations
Long-distance heading
Relay contacts
Electrical quantities
of other breakouts
Switch at limit-value
violations
Communication
Digital inputs
Time synchronization
Mean features
Use in the IT, TT and TN power systems
Ethernet communication via the Modbus TCP or IEC61850
Edition 2 protocol; serial communication via Modbus RTU and
IEC60870-5-103 via the RS485 interface is optional
External time synchronization via the Network Time
Protocol (NTP).
SICAMP850 system view
SICAMP850 can communicate flexibly with automation systems
and evaluation stations via open protocols such as IEC61850
and Modbus TCP.
They are available directly from the device in the form of HTML
pages on a connected PC.
Fig.6.4-9: SICAMP850
Time synchronization
via NTP server
Ethernet:
Modbus TCP
or IEC 61850
Serial:
Modbus RTU or
IEC 60870-5-103
367
4 x voltage
terminal
Terminal
block F
Terminal
block E
Terminal
block H
Communication
Ethernet: IEC61850 or MODBUS TCP communication protocol
Optional serial RS485 interface that enables the device to
communicate via the MODBUS RTU or the IEC60870-5-103
communication protocol.
4 x analog outputs
Current:
0 mA to 20 mA
4 mA to 20 mA and
20 mA to 20 mA
Max. AC 690 V
(phase-phase)
Max. AC 400 V
(phase-neutral)
Signalization LEDs
Automatically monitor the functions of the hardware, software
and firmware components.
Field level
4 x LEDs
Terminal
block K
Voltage:
0 V to 10 V and
-10 V to 10 V
3 x current
terminals
2 x binary outputs
AC 1 A
AC 5 A
AC 230 V or
DC 250 V
Power supply
DC 24-250 V
AC 100-230 V
IP addr button
Terminal
block G
RS 485 Serial
Modbus RTU / IEC
60870-5-103
Terminal
block J
Ethernet
Modbus TCP
10/100 Mbit/s
Terminal
block Z
1. RTU
2. 4 analog outputs
3. 4 analog outputs
4. Binary outputs
V, I
Control center
V, I
V, I
V, I
Alarms, measurements
and indications
Ethernet/MODBUS TCP or
IEC 61850 (7KG9662)
368
Parameterization/
value display
Measurands
The following measurands can be recorded or calculated from
the measured quantities:
TRMS (True RMS) for alternating voltage and current
Active, reactive and apparent power
Active, reactive and apparent energy
Power frequency
Phase angle
Power factor and active power factor
Voltage and current unbalance
Mean value of the 3 phase voltages: Vavg
Mean value of the 3 phase currents: Iavg
Time synchronization
For a common time basis when communicating with peripheral
devices and time stamping of the process data.
External time synchronization via Ethernet NTP
External time synchronization via field bus using the RTU or
the IEC60870-5-103 communication protocol
Internal time synchronization via RTC (if external time
synchronization is not available).
Response time for analog and binary outputs
The faster response time of the analog and binary output is a
very important feature of SICAMT that enables a reliable reaction of the controlling applications. The response time of the
device is 120ms at 50Hz and 100ms at 60Hz.
Applications
Conversion and integration of measurands into substation
automation, protection or SCADA process via RTU and/or via
protocols IEC61850 (for KG9662 variant), MODBUS TCP,
IEC60870-5-103 for further control and/or monitoring tasks
Monitoring of lower voltage levels and heavy load control, e.g.
air conditioning and motors
Depending on the device type, the input circuits for voltage
measurement are either designed as voltage dividers or they
are galvanically isolated. Devices with galvanic isolation can be
used without voltage transformers in the power systems IT, TT
and TN. Devices with a voltage divider can also be used in
these power systems; for IT power systems, however, an
upstream voltage transformer is required.
369
Benefits
Customer satisfaction: Companies with a suitable power
quality monitoring system are proven to be more reliable
suppliers and users of energy.
Asset protection: Early identification of disturbances and active
response to them. Comprehensive information for enhancing
the visibility and control of assets at the edge of the grid.
In case of negotiations or disputes, power quality monitoring
provides evidences to align interests and to support
agreements between parts.
Quality of supply is in the interests of power utilities,
regulators, consumers and the environment.
Function overview
Measurement of continuous phenomena and disturbances
according to the necessary accuracy requirements, as stipulated
in IEC61000-4-15, IEC61000-4-7 and IEC61000-4-30 (Class A).
370
Features
Suitable for monitoring single-phase, 3- and 4-wire power
systems (up to 1,000 Vrms)
4 voltage, 4 current, or 8 voltage measuring channels
Standard: 4 binary inputs, 4 binary outputs
Sampling rate 10 kHz for network analysis
Measurement accuracy 0.1 % of the range
High local storage capability: removable compact flash
(standard delivery 2 GB)
Enhanced data compression process (power quality data)
Automatic data transfer
Automatic comparison and reporting of the power quality
profile according to EN50160 or your local standards
Automatic notification in case of a fault or violations by e-mail,
SMS, and fax
Export functions
Ethernet and modem communication interfaces for
parameterization, remote monitoring and polling
GPS/DCF-77/IRIG-B and NTP for synchronization
Network trigger system
Simple operation, compact and robust design.
SICAMQ100
The SICAMQ100 multifunctional measuring device is used for
acquisition, visualization, evaluation and transmission of electrical measured variables such as alternating cur-rent, alternating voltage, frequency, power, harmonics etc. The acquisition, processing and accuracy of measured variables and events
are performed according to the IEC61000-4-30 Class A power
quality measurement standard. The measured variables can be
output to a PC or system control via communication interfaces
or shown on a display. In addition to the monitoring function,
the SICAMQ100 all-in-one device provides a combined recording and evaluating function: measured values can be recorded in
parameterizable time intervals with various recorders such as
power quality and fault recorders. Long-time data and events are
evaluated directly in the device and displayed as a report
according to the power quality standards (e.g., EN50160).
Application
The SICAMQ100 device is used in single-phase as well as in
three-wire and four-wire systems (with neutral conductor). The
device is applied wherever comprehensive meas-urement of
supply quality is necessary at power utilities as well as in
industry and trade sectors.
Central 1
Central 2
NTP synchronization
Ethernet
Substation 1
Substation 2
Ethernet
Ethernet
GPS synchronization
GPS synchronization
Benefits
Comprehensive acquisition of relevant network parame-ters
for early identification of supply quality problems.
Manufacturer-independent, comparable measured values
obtained by using the IEC61000-4-30 Class A standard
measurement methods.
PQ reporting according to EN50160 direct in web server.
Easy operation via integrated web server for parameterization,
diagnosis, evaluation and reporting.
Interoperability is guaranteed by using standard inter-faces
and standard protocols (IEC61850, MODBUS TCP) and data
formats (PQDIF, Comtrade and CSV).
371
Time synchronization
Via Ethernet: NTP client (Network Time Protocol)
Auxiliary voltage
DC 24 250 V and
AC 110 230 V, 50/60Hz
Housing specification
Compact dimensions: 96 x 96 x 100 mm (W/H/D)
Special features
PQ reporting according to EN50160 and CBEMA direct over
HTML web server
Evaluation of events directly in HTML via COMTRADE
Viewer/SIGRA Plugin
Flexible data export in the PQDIF, COMTRADE and CSV format
Memory capacity of 2 GB for storage of the recorder data for
years of power quality data
MODBUS Master and Gateway function
372
SICAMP855
The SICAMP855 multifunctional device is used to collect, display
and transmit measured electrical variables such as AC current,
AC voltage, power types, harmonics, etc. The measurands and
events are collected and processed according to the Power
Quality Standard IEC61000-4-30. The communications interfaces can be used to output the measurands to a PC and the
control center or display them on a display.
In addition to the monitoring function, the SICAMP855 all-inone device also provides a combined recording and evaluation
function. It can record measurands at programmable time
intervals, using a wide range of recorders, such as power quality
and fault recorders. Long-term data and events are evaluated
directly in the device according to the power quality standards
(such as EN50160) and output as reports.
Applications
SICAMP855 device is used in single-phase systems, threephase
systems and four-phase systems (with neutral conductors). They
are used primarily in power utilities but also in other industrial
and commercial applications.
The web server integrated into the device is used to configure
the parameters and output measured values via HTML pages on
a connected PC/laptop. In devices with displays, the parameters
can also be configured with the function keys on the front of the
device, and the measured values can be output to the display.
The output variables can also be transmitted to control or other
systems such as SICAMPQS V8.01 (planned) via the communications interfaces (Ethernet, e.g., IEC61850) in the form of digital
data.
Feautres
Robust and compact design according to IEC62586-1, Class S
(leading standard)
Use of SICAMP850/P855 in the IT, TT and TN power systems
Ethernet communication via the Modbus TCP or IEC61850
Edition 2 protocol; serial communication via Modbus RTU and
IEC60870-5-103 via the RS485 interface is optional
External time synchronization via the Network Time Protocol
(NTP)
The measurands and events are detected according to the
Power Quality Standard IEC61000-4-30. The measurement
system corresponds to Class A. In terms of functional scope,
measuring ranges and accuracy, SICAMP850/P855 are Class S
devices.
Additional measurands: Minimum/mean/maximum values,
flicker, event detection, voltage dips (Udip), voltage
interruptions and overvoltages (swells)
Events are evaluated directly in HTML via the integrated web
server
2-GB memory for recording recorder data
Evaluations: Power quality reports and online viewer output
directly on the HTML page
Data export: PQDIF and COMTRADE data.
Device characteristics
Input measuring circuits
4x alternating voltage, 3x alternating current (max. 10A)
Measured variables
True RMS alternating voltage and alternating current up to the
100th harmonic
Power frequency, active, reactive and apparent power, power
factor and active power factor, phase angle
Alternating voltage and alternating current unbalance
Alternating voltage and alternating current harmonic up to
the 40th order
THD (total harmonic distortion) of alternating voltage and
alternating current
Communication interfaces and protocols
Ethernet: MODBUS TCP, IEC61850 Edition 2
Serial: Modbus RTU, IEC60870-5-103
Operation and display
Full graphic display including operation via 4 function keys
4 LEDs for state and system messages
Integrated web server to interact with PC via HTML pages
Time synchronization
Via Ethernet: SNTP client (Simple Network Time Protocol)
Via fieldbus
Internal Real Rime Clock (RTC)
Auxiliary voltage
DC 24 250 V
AC 110 230 V, 50/60Hz
Housing specification
Plastic housing for DIN rail mounting, optional panel
mounting, protection class max. IP51
Dimensions: 96 x 96 x 100 mm (W/H/D)
Special features
Measured value acquisition according to the IEC61000-4-30
power quality measurement standard including flicker
Automatic PQ reporting according to EN50160
Mean value, event and fault recorder functionality
Data export in the PQDIF and COMTRADE format
Memory capacity of 2 GB for storage of the recorder data
Evaluation of events directly in HTML via the integrated web
server
373
6.4.5 SIPROTEC7KE85
FaultRecorder, Measurement and
Phasor Measurement Unit (PMU)
SIPROTEC7KE85 fault recorder is designed to suit present and
future requirements in a changing energy sector. Powerful and
reliable monitoring combined with flexible engineering and
communication features provide the basis for maximum supply
reliability.
Commissioning and maintenance work can be completed safely,
quickly and thus cost-effectively with high-performance test
functions. Due to a modular design, the SIPROTEC5 fault
recorder can always be flexibly adapted to specific requirements.
Application
Stand-alone stationary recorder for extra-high, high and
medium-voltage systems
Component of secondary equipment of power plants and
substations or industrial plants
Function overview
Integration to SIPROTEC5 family
Consistent HW concept
Variety of extension modules
DIGSI as configuration tool
Choice of functionality via functional points
Disturbance recorder class S for applications in substations at
MV/HV/EHV level and in power plants
1 FastScan recorder
2 SlowScan recorder
5 Continuous recorder
Power quality recorder class S according to EN50160 for
analysis and recording/archiving of power quality problems of
all power applications
Event recorder for binary signals for observation of the status
of various primary components like circuit-breakers,
disconnectors, etc.
PMU according to IEEE C37.118.
Communication with IEC61850
Sampling frequencies programmable between 1kHz and 16KHz
Time synchronization via IRIG B/DCF77/SNTP
Internal mass storage:
12 GByte ring buffer
Health monitoring/Lossless data compression
Flexible routing
Any assignment of a measured value to each recorder
Free combination of measuring groups for power calculation
Recorded quality bits
Quality statement for each recorded value + monitoring of
channel quality in SIGRA or SIC AM PQ Analyzer
Recording of and triggering on GOOSE values
Creating of flexible trigger conditions with CFC (Continuous
Function Chart)
Auxiliary functions for simple tests and comissioning
Test recorder for commissioning and system test
*in preparation
374
V1
1
Substation 1
V2
2
Substation 4
Substation 2
Substation 3
V3
3
Region 2
User interface 2
PDC 2
PDC 1
IEEE C37.118
PMU 1
PMU 2
PMU 3
Fig.6.4-21: Connection of 3 Phasor Measurement Units with two Phasor Data Concentrators (PDCs) SIGUARD PDP
375
QB1
QB2
QA1 52
V4
MP
V-1ph 1
FG PMU
QB9
I1
I2
I3
V-1ph
MP
V-3ph
I-3ph 1
I-3ph
I4
V1
V2
V3
MP
Comm.
IEEE C37.118
V-3ph 1
Line
FG
MP
PMU
Function group
Measuring point
Phasor Measurement Unit
376
Solution 2:
Solution 1:
Evaluated with:
Evaluated with:
SICAM PQS
PQ Analyzer
SICAM PQS
PQ Analyzer
SIPROTEC
7SK85
SIPROTEC
7SK85
220 kV
Solution:
SIPROTEC
7KE85
Evaluated with:
SICAM PQS
PQ Analyzer
110 kV
SIPROTEC
7KE85
20 kV
SICAM Q80
Industrial enterprise
SICAM Q80
SICAM Q100
Wind energy
Solution:
20 kV
SIPROTEC
7KE85
Evaluated with:
SICAM PQS
PQ Analyzer
400 V
SICAM Q80
Welding shop
SICAM Q80
Press shop
SICAM Q100
Paint shop
377
Substation level
(Validation)
Process level
(Recording)
IEC61850
IEC 60870-5-103
Profibus FM8
SIPROTEC
Others
Protection devices
SICAM R
7KE85 Others
Fault recorder
378
SIGRA (opt.)
Complete documentation
Modbus
Profibus DP
PQ recorder
Snapshot
of violated
operational data
via SoftPLC&PDR
SICAM P/P850
Office level
(Analysis)
Fault records
Power quality data
PDR records
Extended
fault record analysis
SICAM PQ Analyzer
One Cockpit forthe whole SICAM PQS archive
SICAM T
Power meter
Others
PQ explorer
PQ explorer makes detailed analyses possible based on comparing the measured power quality data directly with the Grid
Codes. This comparison and the large number of different
diagrams available for displaying power quality data make it
possible to understand the nature and extent of a power quality
violation very quickly and to initiate adequate (fig. 6.4-29).
Report browser
Reports are created automatically at weekly, monthly, and
annual intervals and in the event of a violation of the Grid Code.
The report browser shows an overview of these automatically
generated reports in selected time ranges and the assessment of
the results. The individual reports can be opened directly in the
report browser (fig. 6.4-30).
PQ inspector
The PQ inspector is a supplementary module that shows at a
glance the power quality condition of the entire network for a
selected period. This allows for quick identification of the origin
and type of violation. Another feature of PQ inspector is the
option of generating power quality reports through step-by-step
user prompting and on the basis (fig. 6.4-31).
Fig.6.4-31: PQ inspector
Fig.6.4-29: PQ explorer
379
Station 1
Segment A1
Segment A2
Field 21
Field 12
Segment B1
Segment C1
Field 22
Field 11
Ca
Voltage levels
bl
bl
Station 2
Cable A
Ca
Segment B2
Segment C2
Field 31
Field 32
Station 3
6
SICAM Diamond Server
& SICAM PQS Fullserver/SICAM PQ Analyzer
SDS
Internet / Intranet
SIPROTEC
SIMEAS R
SICAM Q80
Others
380
NbgH/400/MlhM/U1
MlhM/400/NbgH/U1
kV 400
300
200
100
0
-100
-200
-300
-400
Fig. 6.4-34: Voltage vector of two measurement points in the
network
Applications
Analysis of the power ows in the system
SIGUARD PDP can display a clear and up-to-date image of the
current power ows in the system with just a few measured
values from widely distributed phasor measurement units
(PMU). This requires no knowledge of the network topology.
The power ows are shown by means of phase angle
differences.
Monitoring of power swings
All measured values from PMUs can be displayed and
monitored with easy-to-configure phasor diagrams and time
charts (see fig. 6.4-35). Any power swings that occur are
detected quickly and reliably. The monitored zone can be
flexibly adjusted to the current situation in terms of time,
geography, and content.
Evaluation of the damping of power swings
Using the function Power Swing Recognition an incipient
power swing is detected and the appropriate damping is
determined. Detection of a power swing and, if applicable, its
insufficient or non-existing damping is signaled (alarm list).
There are two ways of detecting a power swing: Based on
angle differences between two voltages (two PMUs necessary)
or based on power swing recognition of the active power (one
PMU for current and voltage measured values is adequate).
Monitoring of the load on transmission corridors
The voltage-stability curve is especially suitable for displaying
the instantaneous load on a transmission corridor. The
currently measured operating point is shown on the work
curve of the line (voltage as a function of the transmitted
power). In this way, the remaining reserve can be shown at
any time. This requires PMUs at both ends of the line.
381
Fig. 6.4-35: M
onitoring diagrams from the application "power sing recognition"
MlhM to NbgH
11:09:52....
2010-...
Island
detection
ISD potential
network
subsplit
appearing
11:09:52....
2010-...
Island
detection
ISD network
subsplit
appearing
11:09:52....
2010-...
Island
detection
ISD potential
network
subsplit
disappearing
kV 500
400
300
200
100
0
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
GW
382
383
6
f
[Hz]
50.04
50.02
Trigger
event
50.00
49.98
49.96
49.94
49.92
Lead
time
Follow-up time
t [s]
384
385
SICAM
Station unit
Ethernet cable
Switch
Switch
Switch
max. 6 relays
per switch
386
Serial Ethernet
E converter
serial hub
IEC 60870-103
protocol
Control center
IEC 60870-5-101 or -104
SICAM
Switch
Switch
Converter
RS 485/232
IEC 60870-5-103 (RS 485)
SIPROTEC
Fig.6.5-2: Serial bus wiring in accordance with RS 485
Control center
SICAM
SICAM
Starcoupler
Switch
Switch
Switch
Switch
IEC 60870-5-103
SIPROTEC
Fig.6.5-3: Star wiring in accordance with RS 232 or
per fiber-optic cable
387
SICAM
Several rings can also be combined on the basis of this fundamental structure, e.g., one per voltage level. Usually these
ringsare combined to form a higher level ring which then
communicates with redundant station devices. This version
offers the highest availability for station-internal communication (fig.6.5-7).
Switch
Switch
Switch
Switch
EHV
Switch
Switch
Switch
Switch
HV
Switch
388
Switch
Switch
MV
6
Fig.6.5-9: CB202: expansion
modules with
communication
modules and analog
input module
389
Ethernet protocols
The Ethernet module can be plugged in once or multiple times
in the device. This enables running identical or different protocol
applications in multiple instances. Multiple networks are possible for IEC61850 or DNP3 TCP, but they can also be operated
in a common Ethernet network. A module implements the
IEC61850 protocol application, e.g., the data exchange between
devices using GOOSE messages. The other module is responsible
for the client-server communication over the DNP TCP protocol.
The client-server architecture of IEC61850 enables one server
(device) to send reports to up to 6 clients simultaneously. In this
case, only one network is used.
390
Examples
Redundancies to substation automation systems
2 redundant substation automation systems
2 different substation automation systems.
Example 1: Two redundant substation automation systems
Fig.6.5-12 show shows a serial optical network which connects
the serial protocol interfaces of the device to one master, respectively. Transmission is accomplished in multipoint-star configuration and with interference-free isolation via optical fiber.
For the IEC60870-5-103 protocol, the device supports special
redundancy procedures. For instance, a primary master can be
configured that is preferred to the second master in control
direction. The current process image is transmitted to both
masters.
The fig.6.5-13 describes a fully redundant solution based on
IEC61850. 2 Ethernet communication modules are plugged into
each SIPROTEC5 device. 2 redundant fiber-optic rings are set up
by means of the switches integrated in the module and connected to the redundant clients (substation automation systems). Alternatively, the redundant IEC61850 communication
could also be accomplished via a common optical ring.
IEC 60870-5-103/
DNP3
Master
IEC 60870-5-103/
DNP3
Master
Serial connections
Star coupler
Star coupler
SIPROTEC 5
Device 1
Device 2
Device n
IEC 61850,
DNP3 TCP
Client
Switch
IEC 61850,
DNP3 TCP
Client
Switch
Switch
Switch
SIPROTEC 5
Device 1
Device 2
Device n
391
Substation controller
IEC 61850 Client
Switch
DIGSI 5
DIGSI
Ethernet
switch
Star coupler
Serial optical
USART
module
Client-Server communication
via the integrated Ethernet
interface
Fig.6.5-14: Communication to IEC61850 client and serial connection
to an IEC61870-5-103 master
Substation controller
DNP3 TCP Slave
Switch
DIGSI 5
DIGSI
Ethernet
switch
Switch
Redundant substation control connection
Switch
Reporting/control
Switch
Substation controller
IEC 60870-5-103 Master
Substation controller
DNP3 Master
Star coupler
Serial optical
USART
module
Client-Server communication
via the integrated Ethernet
interface
Ethernet ring
Fig.6.5-15: Communication to DNP3 TCP slave and serial connection
to an DNP3 master
SIPROTEC 5
GOOSE
Fig.6.5-16: Separate buses for reporting and GOOSE communication
392
Switch
Switch
Switch
SIPROTEC 5
SIPROTEC 5
SIPROTEC 5
SIPROTEC 5
Switch
Redundant substation control connection
Switch
Switch
Ethernet ring
SIPROTEC 5
Fig.6.5-18: Operation with integrated switch and ring redundancy
Ring structure
Switch 1
Switch 2
Optical ring
FastEthernet
RSTP
FastEthernet
RSTP
RSTPSwitch
Non
RSTP IED
393
394
Switch
PRP-B
Switch
Switch
Switch
Switch
Switch
PRP-B
Switch
Switch
Switch
Switch
Switch
Switch
Switch
Switch
Switch
Switch
Switch
Switch
PRP-A
Switch
PRP-B
Switch
B
up to 50 devices on the ring
Switch
Switch
395
Single-mode FO 9/125 mm
Module 3: 24 km LC connectors
Module 4: 60 km LC connectors
Module 4: 100 km LC connectors
7SD610
7SA6
7SD610
7SA6
396
820 nm
max.
1.5 km
7SD610
7SA6
X21
G703.1
Communication
converter
Digital
communication
network
Communication
converter
7SD610
7SA6
Protection topology
52
PI 1
PI 2
PI 1
52
PI 2
52
PI
SIPROTEC 5
SIPROTEC 5
C37.94
SIPROTEC 5
52
PI 1
PI 1
4
SIPROTEC 5
PI
X21
G703.1
Communication
network
Module type:
USART-AD-1FO
USART-AE-2FO
Communication converter
2 Mbits/s
PI
SIPROTEC 5
52
52
5 kV fix
52
9 m/125 m
single-mode
optical fiber
up to 170 km
PI
SIPROTEC 5
Module type:
USART-AD-1FO/ST
USART-AE-2FO/ST
52
SIPROTEC 5
Communication converter
PI
PI
USART-AD-1FO
USART-AE-2FO
SIPROTEC 5
SIPROTEC 5
Repeater
52
PI
2 Mbits/s
52
C37.94
SIPROTEC 5
SIPROTEC 5
Communication
network
Module type:
USART-AD-1FO/ST
USART-AE-2FO/ST
52
Multiplexer
PI
SIPROTEC 5
Module type:
USART-AD-1FO/ST
USART-AE-2FO/ST
52
SIPROTEC 5
FO direct connection
PI
SIPROTEC 5
Module type:
Single module USART-AF-1LDFO/4 km/duplex LC
Double module USART-AW-2LDFO/4 km/2 x duplex LC
Single module USART-AG-1LDFO/60 km/duplex LC
Double module USART-AU-2LDFO/60 km/2 x duplex LC
Single module USART-AK-1LDFO/100 km/duplex LC
Double module USART-AV-2LDFO/100 km/2 x duplex LC
397
52
PI
FO direct connection
SIPROTEC 5
52
PI
SIPROTEC 5
398
399
There may be chances during the lifecycle of the energy automation system that are not known today. This future demand can
be addressed already today by scalable systems that are easy to
expand, updated and retrofitted.
A main value of an automation system is the data model. The
data model still remains the same even if the automation system
is changed, because it is based on the process level (e.g., switchgear). The value of the data model can be preserved on a longterm basis through systematic data transfer and an evolutionary
development of existing systems.
To benefit from technological advances on a continuing base,
while remaining flexible, it is necessary to work with standardized communications based on open interfaces.
For system integration without any problems, the right system
architecture (redundancies, communication, system functions)
and all interfaces have to be clearly defined and optimized.
ENEAS
(Efficient Network and Energy Automation Systems)
Solutions
for substation
automation and
protection
Digital substation
automation systems
Telecontrol systems
Protection systems
Solutions
for distribution
automation
Medium voltage
automation
Feeder automation
Applications
Solutions
for monitoring
Disturbance and
fault record analysis
Condition
monitoring
Power quality
systems
Solutions
for control center
400
Solutions
for life cycle
management
Consulting
Training
Support
Maintenance
Retrot
Financing
401
402
Telecontrol systems
Telecontrol systems designed as ENEAS solutions provide multihierarchical monitoring and remote control as well as automation functions at all levels. The modular system can be adapted
to any primary processes and their spatial distribution. System
solutions are available for both energy transmission and distribution to optimally perform telecontrol tasks for all aspects of data
acquisition and process interfacing, communication, data concentration, and automation. From small substations using
terminal block technology to large telecontrol stations with high
signal density and numerous interfaces, ENEAS covers the entire
spectrum. Its modular structure ensures long-term expandability.
All components are based on a shared system architecture and
technology, so that entire systems can be parameterized with a
common tool throughout all project phases. Data point entry on
individual devices is a thing of the past, and multiple entries are
effectively prevented, even in mixed systems. All components
deployed in ENEAS telecontrol systems utilize the same communication functions, so that the available protocols are usable in
all telecontrol components. Along with the IEC60870-5 series
and IEC61850 standard protocols, DNP 3.0 and Modbus are also
available for all applications. In addition to these standards,
numerous proprietary protocols for components by other manufacturers are also supported. The modular concept, distributed
architecture, and evolutionary development principle ensure
that these systems have long life expectancy and are open for
future developments, thus providing a high degree of investment safety and enabling the creation of Smart Grids (fig.6.7-3).
Protection systems
Reliable, efficient, adaptable substation protection systems are
crucial for high- and medium-voltage power supply operations.
They must react to faults in milliseconds in order to prevent
damage to costly equipment such as switchgear, transformers
and cables, ensure a high level of safety, and avoid failures of
supply. ENEAS solutions for protection systems ensure a reliable,
efficient power supply. They are designed to allow selective
procedures for different network structures and changes in
operational processes, and they provide much more than just
the dependable fulfillment of the basic functions of protection,
control and monitoring. ENEAS solutions incorporate innovative
approaches such as harmonized interfaces and interoperability,
multi-layered safety mechanisms, and efficient engineering.
Intelligent functions form one of the key prerequisites for Smart
Grids. ENEAS protection systems support network operation
during fault tracking or power quality analysis, adding useful
features to the proven benefits of older protection systems.
ENEAS solutions for protection systems allow individual protection devices to work together perfectly using the powerful
communication technologies available today. Examples are,
among others, the complex protection requirements of 1.5 CB
schemes or automatic load shedding between power plants in
industrial networks (fig.6.7-4).
403
Speed
Faster project delivery
Reduced effort in the definition of requirement and detail
clarifications
Faster project documentation
Faster service and support-based on known project design
(fig.6.7-5).
Benefits
Quality
Multiple tested applications and templates provide improved
quality to projects
Increased quality of proposals
More transparency of proposed services
Improved quality of project documentation
Improved quality of hotline and after-sales services.
Security
Easier to adapt and enhance the system even after
commissioning
Safe operation from the user interface to the command output
Secure maintenance: standardized documentation
Secure lifetime support: longterm maintenance because of
large installed base
Security of investment: migration strategies thanks to a wide
installed base.
MV GIS DBB
MV GIS SBB
BE5
-QC91
BE5
BE2
Plant type
MV AIS SBB
Incoming cable/
trafo-feeder
Incoming-feeder
Over-Head Line
(CHL)
QB1
QC9
BE2
BE1
QC1
BE1
Bus section
coupler
QA1
BA1
QA2
QA1
QB22
QC23
QB12
QC13
QB1
QC9
QB2
QC22
BA1
BC1
QC9
QB1
QB1
QC9
QB1
QC9
QB2
QA1
QA1
QA1
BC1
BC1
BC1
BC2
BC2
BC2
BA1
BA1
BA1
-QC92
-QB1
-QB1
-QB1
-QB1
-QB1
-QA1
-QA1
-QA1
-QA1
-QA1
QA1
QB21
QB11
QC13
QB2
QB1
QC9
QB1
QC2
QB10
QA1
BA1
QA1
QB1
QC9
BC2
Bus section
coupler
BA1
QA1
-BC1
-BC1
-BC1
-BC2
-BC2
-BC2
-BA1
-QC9
BC1
-BA1
-QC9
-BC1
-BC2
-BA1
-BA1
-QC9
-QC9
BC2
BA1
Incoming-feeder
Over-Head Line
Outgoing
feeder
Outgoing
cable-feeder
Outgoing cable/
trafo-feeder
Incoming-feeder
Over-Head Line
(CHL)
Incoming cable/
trafo-feeder
Outgoing-feeder
Bay level
Outgoing cable/
trafo-feeder
12 bay types
11 bay types
404
11 bay types
Bus section
coupler
Outgoing-cable
feeder
No.
Type
1.0
Incoming feeder
1.1
1.2
1.3
2.0
Outgoing feeder
2.1
2.2
2.3
2.4
Incoming feeder
Outgoing feeder
Coupler
3.1
Bus coupler
3.2
Bus sectionalizer
Central
4.1
Station overview
To control centers
Station level
Communication
Interface station data
Station-wide function
Station operation
Station communication
Connecting all devices
IEC-compliant
Station
operation
HMI
IEC 61850
Bay level
Combined control and protection
Bay functions
Bay operation
n x bay units
405
HV HIS
Compact grid connection
Bay x
Plant type
-QO2
-QZ1
-QA1
Bay x
Bay x
-QA1
-BC1
-QO2
-BA5
-QZ1
-QZ1
-QA1
-T
1 bay types
-QO2
-BA5
3 bay types
Turbine strings
(no of strings/turbines
per string is indicative only)
Offshore Substation
Single undersea cable
(no diverse path)
Switch/Router
IEC 60870-5-104
to TNO
red. Option
Fig.6.7-10: Example Automation of the power collection grid with ENEAS generic solutions for wind power
-QA1
-BC1
406
-BC1
-QZ1
Offshore Substation
HMI Server
SICAM 230
-QO3
-QZ2
-BC1
-QA1
WEB UI Provided
by Others
Onshore Substation
-BA5
-QO3
-QZ2
-QZ1
WTG Transition
Piece (Option
Cost)
SIPROTEC Relay
Bay x
-BA5
-BA5
Turbine strings
(no of strings/turbines
per string isindicative only)
MV AIS SBB
Bay level
The set of the three base modules has been specially designed
toprovide SIPROTEC 5 devices for off-the-shelf solutions for
high-voltage switchgear.
SIEMENS
SIEMENS
SIEMENS
-QB2
-QB1
-QA1
SIEMENS
SIEMENS
-QB1
-BC1
-BC2
-QA1
-BC1
-BC2
SIEMENS
-QB2
Double-busbar
transformer feeder
SIEMENS
SIEMENS
SIEMENS
-QB2
-BA12
-QB1
SIEMENS
Double-busbar
bus coupler
-BA11
Double-busbar
line feeder
-QA1
-BC1
-BC2
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
-QB9
SIEMENS
SIEMENS
-BC3
-BC4
-QC9
-QA2
-BA1
-BA1
6
Fig.6.7-12: ENEAS migration: different life and investment cycles for
primary and secondary equipment
Product availability
Product phase-out
Phase-out
declaration
~ 2 years
Product
cancellation
~ 10 years
407
408
types of primary equipment: circuit-breakers, reclosers, disconnectors, sectionalizers and load breakers.
Portfolio:
Medium- and low-voltage automation
Self-healing applications and wide area monitoring
Monitoring, remote control, and self-healing application
High supply reliability for the customer a major requirement
for electricity supply systems is mainly determined by the
distribution networks, which typically feature a low degree of
automation only. Even the automation of a smaller part of the
network with Monitoring, remote control, and self-healing
application can realize significant improvements. Intelligent
automation equipment in primary and secondary substations
allows for effective monitoring and decision-making without
human intervention. Reliability of energy supply primarily
depends on the distribution network, and its importance is
growing. It is generally quantified by two indicators: SAIDI
(non-availability) and SAIFI (interruption frequency).
Scalable distribution automation solutions start with simple
monitoring and control of distribution substations, and end
withclosed-loop self-healing (Fault Location Isolation and
Service Restoration). In cable networks, mainly RTUs and shortcircuit detectors are used for the automation of ring-main units.
For overhead line networks, IEDs and protection relays ensure
control and monitoring of reclosers and sectionalizers. Selfhealing automation can provide secure and reliable operation
ofoverhead lines and cable networks, and can be used for all
Decentral
Intelligence Provided
by RMU and Feeders
Semi-Decentral
Automation systems
at substation level
Central
Automation
implemented
at Control Center
409
410
411
412
Generation control
Industry grids are often supported by several generators to
support island mode in case of a fault of the intertie to the
external utility. Beyond that, these generators are used to
reduceenergy production costs and improve the security of
supply. In industry grids there are mainly gas turbines, steam
turbines, and diesel engines to drive the generators. They
allaretypically equipped with their own primary controllers:
thegovernor and the excitation with voltage control.
If several generators operate jointly in an islanded industry grid,
they need to be coordinated to maintain nominal frequency and
voltage. This is the task of a secondary control, which is the
main part of generation control (fig.6.7-20).
ENEAS generation control supports the grid operator in all
modes:
In connected mode it keeps power import and phase angle
within contractual limits by controlling own production
In island mode it stabilizes frequency and voltage in the grid.
Set 1
Turbine
Set n
Generator
Governor
Turbine
Excitation Primary
controller
AVR
Governor
Generator
Excitation Primary
controller
AVR
Secondary
controller
Generation control
Load/frequency
control
Automatic voltage
control
Spinning reserve
calculation
Load
sharing
Workstation 1
Workstation n
SICAM 230
control center
Redundant server
for SCADA and
generation
control
Plant level
Ethernet
Substation level:
SICAM SCU
and HMI
Feeder level:
SIPROTEC
protection
and control
6
Redundant
controller for
load shedding
Substation operation
Remote maintenance
Station n
Router
Station bus:
Ethernet and
IEC 61850
Interface to the primary controller
413
Introduction
Flexibility, modularity and scalability ENEAS solutions for
monitoring and control center
The borders between substation automation, control center and
branch systems like wind power, airport and industry are fluent
because of the increased performance of modern host systems
and the software architecture behind them. Also, customer
demands require a highly flexible, scalable and reliable control
center system that support the workflows of today and make
them prepared for the requirements of the future.
ENEAS monitoring and control center solutions cover a large
range of application fields. With the engineering experience of
thousands of systems for:
Substation automation
Control center for utilities incl. electricity, gas, water and
district heating
Wind power application
HVDC platform
Condition monitoring
Industry
Airports
Buildings and hospitals
Data centers
Smart Grid applications.
Virtualized
Hardware
Electricity
Region I
Gas
Region II
Renewable
Management
Server
Service
Region III
Workstation
Terminal
Region I WorkServer
station
Terminal
Region II
Server
Editor
414
Emergency workstation
All-in-one, server-client
Redundancy
Web server integration
Power distribution calculation
Message control (SMS, mail, etc.)
Communication protocols
Multi-touch applications
Report generator.
With a powerful basis of functionalities it is possible to ensure the
main workflows. But as a functional shaping, a lot of expansion
modules that support the operator are needed. A flexible control
center system also has to provide extension functions like:
Topological coloring
Fault localization out of protection data
Switching sequence management
EMS energy management system for electricity and gas
Power distribution calculation
Simulation
Switching procedure management
SQL outsourcing/Database connectivity
Report generator
Energy management for renewables
Distribution automation functionalities.
Modularity
Our control system software has always proven effective for
traditional applications in substation automation and in power
grids with electricity, gas, water, and district heating. It also
serves as the basis for wind farm, industry, and airport technology. More importantly, we use the same platform for implementing application-specific solution packages, for example,
condition monitoring, load shedding, network monitoring, meter
integration, and power quality monitoring. These modules can
be used in any combination, depending on the application.
Virtualization
Virtualization enabled the number of physical servers to be
reduced substantially, with a commensurate decrease in maintenance costs. Hardware can be shared and jointly monitored. Only
four physical servers are used for all of the virtual servers, with
data stored on a RAID system that is shared by all of the systems.
http://w3.siemens.com/smartgrid/global/en/productssystems-solutions/control-center-solutions/small/Pages/
Solutions-for-Small-Control-Center.aspx
415
416
Asset monitoring
SCADA workstation ( onshore and offshore )
Energy management (e.g. German EEG)
Remote operation center for renewables
Communication to wind power controller
Communication to TSO grid operator (fig.6.7-25)
Maintenance and remote operation
Maintenance and remote operation are becoming increasingly
important for wind power systems. Two drivers for remote
control centers are:
Distributed wind turbines
Operation and maintenance crews observe turbines that are
installed across larger regions, up to a country or a continent.
That kind of installations are not easy to reach. With a remote
system, the fault diagnosis is much faster and crews are
coordinated much more effectively.
Large wind power plants onshore and offshore
Especially in offshore installations, the platforms and
windturbines are hard to access. Thus, on-site work must
beplanned very carefully, and is very expensive. A wellimplemented operation and maintenance system supports
onshore and offshore crews in order to reduce working time
on site, maintenance efforts, and downtimes of the plant
(fig.6.7-26).
SCADA System
(Offshore)
SCADA System
(Offshore)
SICAM 1703
Data Concentrator
& Auxillary Park Signals
REMOTE
Access
132 kV
Connection to:
Grid Operator
Platform / Wind Farm Owner
Service and Support Provider
IEC 61850
Switch
32 kV
Switch
SIPROTEC (Turbines)
Onshore
Offhore
417
Transformer
Hot-spot temperature (ANSI/IEEE)
Ageing/loss of lifetime
Energy efficency/cooling efficiency
Gas-in-oil analysis
Bushing monitoring.
GIS (HV/MV)
Gas density monitoring
Partial discharge monitoring.
Circuit-breaker monitoring
CT/VT monitoring
Performance monitoring (tripping and reaction time)
Spring or hydraulic system monitoring
Maintenance counter and alarms.
Overhead line monitoring
Voltage and sag monitoring
Icing monitoring
Ampacity monitoring (fig.6.7-28)
ISCM can be integrated into any existing switchgear. As a complete, integrated solution, this innovative condition monitoring
system delivers comprehensive information on the systemss
condition in a standardized data format.
418
Grid diagnostics
SIMEAS SAFIR efficiency in grid analysis and monitoring
Changing market conditions, more and diverse tasks, and
increasingly small windows of time for an adequate reaction to
grid disturbances pose new challenges to power grid operators.
The detailed real-time overview of a power systems performance is of the utmost importance today due to increased
bidirectional power flow and a need for real time system awareness. This supports the grid operators in having a clearer picture
of the network supporting blackout prevention, having clearer
information of assets and infrastructure being used. The electrical markets are in the deregulation process and cost minimizing programs are put in place. In addition, more and more
tasks must be fulfilled by the same crew (or by a reduced crew)
at the system operator's site. Users require fast fault identification and fault clearance.
SIMEAS SAFIR
Is a web-based system giving real-time grid information for
better situation awareness
Is a software platform that provides the basis for optimal data
integration of various devices within a power system
Collects fault records, substation automation events, power
quality measurements, and synchrophasors
Enables manufacturer independent, system-wide access to
measurements
Fig.6.7-29: SIMEAS SAFIR analysis cores: fault analysis, power quality and wide area monitoring
419
Business data
Data warehouses
Supervisory control and data acquisition
Geographic information systems.
Data processing with SIMEAS SAFIR provides a number of
tangible advantages for all departments that have to work with
system monitoring data:
Control and protection staff benefit from the automatic
reading and processing of all available data, and a unified
report standard. This makes cumbersome and time-consuming
manual reporting a thing of the past.
The asset management benefits from consistent fault analysis
and the drawn conclusions about faults related to assets. In
this way, manual fault and power quality reports handling
becomes obsolete, and maloperation or defects can be
prevented beforehand.
The management can act on the basis of more and more
transparent data, which makes maintenance faster and more
calculable.
Control center operators benefit from automated data
collection and processing that makes possible timely and
well-informed decisions on the basis of full access to all
relevant data.
420
Fault analysis
Collecting data and putting the pieces of the event analysis
puzzle together does not need to be a tedious, time-consuming
matter. SIMEAS SAFIR utilizes data from all sources for time- and
cost-efficient grid control and maintenance. Line faults due to
environmental influences cannot be prevented. SIMEAS SAFIR
makes handling such faults faster, easier, and more efficient.
SIMEAS SAFIR collects fault records from all data sources like
protection relay or digital fault recorder automatically usually
in COMTRADE format. In this process, time synchronization is
verified and optimized, so the records can be grouped in event
folders. These records are pre-processed to facilitate further
analysis. The software detects analog signal changes, and
provides numerous measurements, such as phasors and loop
impedances, for each electrical state of the power system. User
can also flag fault records and hide them, which occur during
commissioning or protection testing. SIMEAS SAFIR enables for
the control and protection staff a time-efficient analysis and
reporting. This reduces costs and contributes to a better
system reliability through measures derived from
comprehensive data (fig.6.7-30).
SIMEAS SAFIR also can collect the events at the source by using
RTUs or dedicated IEC61850 gateways, for instance.
Alternatively, SCADA databases or exports from substation
automation systems can be used. This way, SIMEAS SAFIR
becomes a system-wide sequence of events (SOE) recorder,
which is the optimum solution (fig.6.7-33).
SIMEAS SAFIR groups all data that are related to a power
system event into a single folder, which considerably facilitates
the analysis: fault records, slow-scan records, voltage dips,
andothers. The application can then determine critical event
patterns. Users browse the list of events which draws the
attention on the spots and patterns of interest for each event.
Events are tagged as important based on several criteria, and
users can register to receive notifications based on their own
preferences.
Power quality
Addressing the new challenges power system operators have to
master Power Quality (PQ) monitoring. Traditionally focused on
the quality of supply at the lower voltage levels, PQ monitoring
plays an increasing role on all voltage levels today. The reasons
include the obligation to know the quality of supply to distribution systems or major customers, and to quickly assess the
impact of voltage events. But the flow of harmonic currents or
unbalanced currents often also needs to be understood, from
421
6
Fig.6.7-32: Phasor diagram
422
ENEAS Secure Substation is integral part of the energy automation solutions for Smart Grid, see section 8.5 (IT-Security).
423