Product Data: 38AUQ07 - 12 Heat Pump Outdoor Unit Split System With Puronr Refrigerant 60 HZ

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

38AUQ07 --- 12

Heat Pump Outdoor Unit


Split System with Puronr Refrigerant
60 Hz

Product Data

FEATURES/BENEFITS
System indoor and outdoor sections offer
outstanding performance in either the cooling
or heating mode
Heat pump system energy savings opportunity

C10108

Fig. 1 -- 38AUQ07--12

Electrical energy consumption is always a prime concern


when selecting an air-conditioning system for a
commercial application. An easy, effective way to save
energy is to install a heat pump. When building plans call
for a heat pump, consider a matched Carrier
38AUQ/40RUQ heat pump system. These systems not
only offer highly efficient cooling, they also provide a
clean, safe, efficient source of heat. In fact, they are
capable of delivering more than 3 units of heat energy for
each unit of electrical power consumed.

Heat pump uniqueness


The outstanding performance of these heat pump systems
is due to the heat pumps ability to absorb and transfer
heat from outdoors to indoors for heating, and from
indoors to outdoors for cooling. System indoor and
outdoor sections operate as evaporators or condensers,
depending on whether heating or cooling is required. The
heating cycle starts with the outdoor coil absorbing heat
from the surrounding air (even outside air at extremely
cold temperatures), and ends with the indoor coil releasing
or rejecting heat to the air around it.
the environmentally sound refrigerant

Gemini split system heat pump systems save energy and


provide outstanding heating and cooling all year with:
S All-season comfort in any climate
S High energy savings capability
S Suitability for new construction or replacement

38AUQ application versatility


Whether for a new application or replacement, these
Carrier split system heat pumps offer time-proven
performance for year-round comfort in any climate. With
matching 40RUQ air handler, the units standard cooling
operation ranges up to 125_F (52_C) and down to 35_F
(2_C) ambient temperatures. If lower ambient cooling
temperatures are required, Carriers Motor Master
controller will allow operation down to - 20_F (-- 29_C)
ambient temperatures.

FEATURES/BENEFITS (cont.)
Rugged long life compressor
The 38AUQ outdoor units are equipped with a scroll
compressor for superior efficiency and long life. Crank
case heaters are available where required and each circuit
is further protected by a suction line accumulator to
protect during the defrost cycles or unique applications.

38AUQ

Controls for performance efficiency


These units offer the building owner operating controls
and components designed for performance dependability.
The highly efficient hermetic scroll compressors are
engineered for long life and durability. The compressor
includes overload protection and compressor vibration
isolation for further enhancement of quiet operation. The
high-pressure switch protects the entire refrigeration
system from abnormally high operating pressures. A
loss-of-charge switch is also provided to protect the
system against low charge conditions.
Each unit utilizes the the Comfort Alertt diagnostic and
troubleshooting control system. This protects the units
operation and provides valuable diagnostic information
such as:
- System Go LED indicator
- Fault LED indicator
- Compressor fault LED indicator
- Phase loss protection
- Phase reversal protection
- Anti short cycle protection
The 24-v-- 75VA control circuit transformer permits quick,
easy wiring of standard and programmable 24-v
thermostats. The 24-- v-- 75VA control circuit transformer
also comes with a re-- settable circuit breaker for extra
protection.
Latest safety standards are assured through UL
(Underwriters Laboratories) and UL, Canada approval.
The 38AUQ units utilize a reliable defrost board with
field configurable timed defrost cycles. The defrost board
may be easily configured for defrost cycles of 30 to 90
minutes, depending upon the application.
Motor failure due to electrical overload is prevented by
temperature and current sensors. Coil quality and
performance are enhanced by copper tubes and aluminum
fins, which provide maximum heat transfer. The coil is
circuited for subcooling. A large heat transfer surface
offers additional efficiency.

Innovative Carrier 40RUQ indoor units are


custom matched to 38AUQ outdoor units for
superior system performance
The 40RUQ Heat Pump air handler has excellent fan
performance, efficient direct-expansion (DX) coils, easy
installation, and a unique combination of indoor air
quality features. Its versatility and state-of-the-art features
help to ensure that the heat pump system provides
economical performance now and in the future.

Easy installation and service The 40RUQ


multi-- position design and component layout helps to get
the unit installed and running quickly. The
direct-expansion (DX) coils have factory-installed
thermostatic expansion valves (TXVs) with matching
distributor nozzles. All 40RUQ units also include
factory-installed check valves and piping for heat pump
duty with matching 38AUQ units.
The 40RUQ units can be converted from horizontal to
vertical operation simply by repositioning the unit. Drain
pan connections are duplicated on both sides of the unit.
Fan motors and contactors are pre-- wired. For easier
service, the filters, motor, drive, TXVs, check valves, and
coil connections are accessible by removing a single side
panel.
Indoor-air quality (IAQ) features The unique
combination of IAQ features in the 40RUQ Series indoor
units helps to make sure that only clean, fresh,
conditioned air is delivered to the occupied space.
In the Cooling mode, direct-expansion (DX) cooling coils
prevent the build-up of humidity in the room, even during
part-load conditions.
Standard 2-in. disposable filters remove dust and airborne
particles from the occupied space.
Thermal
insulation
contains
an
immobilized
anti-microbial agent to inhibit the growth of bacteria and
fungi. The anti-microbial agent is registered with the U.S.
Environmental Protection Agency (EPA).
The pitched corrosion-free drain pan can be adjusted for a
right- or left-hand connection to provide positive drainage
and to prevent standing condensate.
The 40RUQ accessory economizer can provide ventilation
air to improve indoor air quality. When used in
conjunction with Carrier Comfort System thermostats and
CO2 sensors or PremierLink controller, the economizer
admits fresh outdoor air to replace stale, recirculated
indoor air.
Economy The 40RUQ Series air handlers have low
initial costs, and they continue to save money by
providing
reduced
installation
expense
and
energy-efficient performance.
Quick installation reduces installation costs, and TXVs,
check valves, and heat pump piping are factory-installed.
High-efficiency, precision-balanced fans minimize air
turbulence, surging, and unbalanced operation, cutting
operating expenses.
The economizer accessory precisely controls the blend of
outdoor air and room air to achieve comfort levels.
When the outside air enthalpy is suitable, outside air
dampers can fully open to provide free cooling.

FEATURES/BENEFITS (cont.)
TABLE OF CONTENTS
PAGE
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . 3
AHRI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Coil flexibility Model 40RUQ coils have galvanized


steel casings; inlet and outlet connections are on the same
end. The coils are designed for use with Puron (R-- 410A)
refrigerant and have 3/8-in. diameter copper tubes
mechanically bonded to aluminum sine-wave fins. The
coils include matched, factory-installed TXVs with
matching distributor nozzles. Check valves and heat pump
piping are also included in all 40RUQ units.

Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . 7


Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 9
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . 19
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . 20
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Duplicate piping access holes on both sides of the unit


eliminate drilling; condensate connections for both
vertical and horizontal installations are also provided on
both sides of the unit.

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 22

38AUQ

Rugged dependability The 40RUQ units are made to


last. The die-formed galvanized steel panels ensure
structural integrity under all operating conditions.
Galvanized steel fan housings are securely mounted to a
die-formed galvanized steel deck. Coil housings are
galvanized steel, and coils have aluminum fins
mechanically bonded to copper tubes. The condensate
drain pans provide corrosion-free performance.

MODEL NUMBER NOMENCLATURE


1

8 A U Q A 0

10 11 12 13 14 15 16 17 18

8 A 0 A 6 -- 0 A 0 A 0

Model
38AU = Commercial Split System
Puronr R--- 410A Refrigerant

Brand / Packaging
0 = Standard
1 = LTL

Type
Q = Heat Pump

Electrical Options
A = None
C = Non--- Fused Disconnect

38AUQ

Refrigerant Options
A = None
B = Low Ambient

Service Options
0 = None
1 = Un--- powered Convenience Outlet
2 = Powered Convenience Outlet

Nominal Tonnage
07 = 6 Tons
08 = 7.5 Tons
12 = 10 Tons

Factory Assigned
A = Default

Factory Assigned
A = Default

Base Unit Controls


0 = Standard Electrical Mechanical Controls

Factory Assigned
0 = Default

Design Rev
--- = Factory Assigned

Coil Options (Tube --- Fin --- Hail Guard)


A = Al/Cu Standard
B = Pre Coat Al/Cu
C = E--- Coat Al/Cu
M = Al/Cu Standard with louvered hail guard
N = Pre Coat Al/Cu with louvered hail guard
P = E--- Coat Al/Cu with louvered hail guard

Voltage
1 = 575/3/60
5 = 208/230/3/60
6 = 460/3/60

AHRI CAPACITY RATINGS


Cool
UNIT

COOLING
STAGES

NOM. CAPACITY
(TONS)

EER

IEER

38AUQ07 / 40RUQ07
38AUQ08 / 40RUQ08
38AUQ12 / 40RUQ12

1
1
1

6
7.5
10

11.0
11.0
11.0

11.8
11.8
11.8

NET COOLING
CAPACITY
(MBH)
70.0
89.0
112.0

TOTAL POWER
(kW)
6.4
8.1
10.2

High Heat at 47_F (8_C)


38AUQ07 / 40RUQ07
38AUQ08 / 40RUQ08
38AUQ12 / 40RUQ12

COOLING
STAGES
1
1
1

NOM. CAPACITY
(TONS)
6
7.5
10

NET HEATING CAPACITY


(MBH)
66.0
87.0
106.0

TOTAL POWER
(kW)
5.9
7.7
9.4

NOM. CAPACITY
(TONS)
6
7.5
10

NET HEATING CAPACITY


(MBH)
39.0
52.0
70.0

TOTAL POWER
(kW)
5.2
6.9
9.3

COP
3.30
3.30
3.30

Low Heat at 17_F ( -- 8_C)


UNIT
38AUQ07 / 40RUQ07
38AUQ08 / 40RUQ08
38AUQ12 / 40RUQ12

COOLING
STAGES
1
1
1

COP
2.20
2.20
2.20

LEGEND
AHRI
--- Air--- Conditioning, Heating and Refrigeration Institute
ASHRAE
--- American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER
--- Energy Efficiency Ratio
IEER
--- Integrated Energy Efficiency Ratio
NOTES
1. Rated in accordance with ARI Standard 340/360--- 07, as appropriate.
2. Ratings are based on:
Cooling Standard: 27_C (80_F) db, 19_C (67_F) wb indoor air temp and 35_C (95_F) db outdoor air temp.
IEER Standard: 27_C (80_F) db, 19_C (67_F) wb indoor air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.

SOUND POWER LEVELS, dB


UNIT

COOLING
STAGES

A ---Weighted
82
82
82

63
86.4
86.8
82.8

125
86.0
85.7
81.5

OUTDOOR SOUND (DB)


250
500
1000
79.2
80.2
77.6
80.3
80.3
77.7
79.2
79.4
76.2

38AUQ07
1
38AUQ08
1
38AUQ12
1
LEGEND
dB = Decibel
NOTE: Outdoor sound data is measure in accordance with ARI standard 270--- 2008.

2000
72.0
72.3
72.3

4000
67.9
70.2
69.4

8000
62.3
65.4
64.2

38AUQ

UNIT

38AUQ

PHYSICAL DATA
38AUQ07
38AUQ08
38AUQ12
Refrigeration System
# Circuits / # Comp. / Type
1 / 1 / Scroll
1 / 1 / Scroll
1 / 1 / Scroll
Shipping charge A/B (lbs)
10.0 Puron
13.0 Puron
15.0 Puron
System charge w/ fan coil * A/B (lbs)
18
21
27
High--- press. Trip / Reset (psig)
630 / 505
630 / 505
630 / 505
Low--- press. Trip / Reset (psig)
27 / 44
27 / 44
27 / 44
Outdoor Coil
Material --- Tube / Fin
Al/Cu
Al/Cu
Al/Cu
Round Tube Plate Fin Coil type
RTPF
RTPF
RTPF
Rows / FPI
2 / 17
2 / 17
2 / 17
total face area (ft2)
17.5
23.0
28.1
Outdoor fan / motor
Qty / Motor drive type
2 / direct
2 / direct
2 / direct
Motor HP / RPM
1/4 / 1100
1/4 / 1100
1/4 / 1100
Fan diameter (in)
22
22
22
Watts (total)
610
610
610
Piping Connections
Qty / Vapor (in. ODS)
1 / 1 1/8
1 / 1 1/8
2 / 1 3/8
Qty / Liquid (in. ODS)
1 / 3/8
1 / 1/2
1 / 1/2
* Approximate system charge with 25 ft. piping of sizes indicated with matched 40RUQ

OPTIONS AND ACCESSORIES


38AUQ
ITEM

OPTION*

Disconnect Switch (non-fused)

Enviro-Shield Coil Protection

Convenience Outlet (115-v) Powered

Convenience Outlet Non--- powered

Low Ambient Temperature Motormaster Control**

ACCESSORY

Outdoor Coil Grille

X
X

PremierLink Controls

Programmable Thermostats

* Factory--- installed option


Field --- installed accessory
** Available as an option or accessory

Enviro-- Shield outdoor coil options are available to


match coil protection to site conditions for optimum
durability. See the table below and refer to the Application
data for selection guidance. Consult a Carrier
representative for further information.

lockout capability to protect the service person. This


lockout switch saves time and effort as the service person
no longer needs to access a distant disconnect switch
while servicing the unit.
Outdoor coil louvered hail guard protects outdoor units
from hail and other flying debris.

Low ambient temperature Motormasterr head


pressure control operates in Cooling mode at outdoor
temperatures below 55 F. The Motormaster control varies
the speed of outdoor-- fan motors to maintain correct
condensing temperature down to 20 F.

Outdoor coil grille protects outdoor coil from large


objects and vandalism.
PremierLink controller is a field retrofit split system
control compatible with Carrier Comfort Networkr (CCN)
controls and other building automation systems (BAS).
This control is designed to allow users the access and
ability to change factory-- defined settings thus expanding
the function of the standard unit.

115-- v convenience outlet is available to provide power to


electric drills, lights, and refrigerant recovery machines.
This means that a separate 115-- v power supply is no
longer required.
Non-- powered convenience outlet requires the filed
installation of a general purpose 125-- volt 15-- A circuit
powered from a source elsewhere in the building.

Carrier commercial thermostats provide 7-- day


programmable capability for commercial application.

Non-- fused disconnect switch removes power locally at


the condensing unit. This switch also includes a power

Outdoor Coil Protection Applications


ENVIRONMENT
Enviro-Shield
DESCRIPTION
Alum Fin / Cu Tube

Standard
Non---Corrosive

Mild
Coastal

Moderate
Coastal

Severe
Coastal

Industrial

Combined
Coastal and
Industrial

Pre-Coated Al/Cu

E-Coated Al/Cu

38AUQ

Outdoor Coil Louvered Hail Guard

OPTIONS AND ACCESSORIES (cont.)

38AUQ

40RUQ
ITEM
Alternate Fan Motors
Alternate Drives
Prepainted Units
CO2 Sensors
Condensate Drain Trap
Discharge Plenum
Economizer
Electric Heat
Hot Water Heating Coils
Overhead Suspension Package
Programmable Thermostats
Return Air Grille
Steam Heating Coil
Subbase
UV--- C Germicidal Lamp**
* Factory--- installed option.
{ Field --- installed accessory
** Contact Application Engineer

OPTION*
X
X
X

ACCESSORY{

X
X
X
X
X
X
X
X
X
X
X
X

Factory--installed options
Alternate fan motors and drives are available to provide
the widest possible range of performance.
Prepainted steel units are available from the factory for
applications that require painted units. Units are painted
with American Sterling Gray color.

Field--installed accessories
CO2 sensors can be used in conjunction with the
economizer accessory to help meet indoor air quality
requirements. The sensor signals the economizer to open
when the CO2 level in the space exceeds the set point. A
Carrier Comfort System programmable thermostat can be
used to override the sensor if the outside-- air temperature
is too high or too low.
Condensate drain trap includes an overflow shutoff
switch that can be wired to turn off the unit if the trap
becomes plugged. Kit also includes a wire harness that
can be connected to an alarm if desired. The transparent
trap is designed for easy service and maintenance.
Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical
louvers enable redirection of airflow. Accessory is
available unpainted or painted. Field assembly is required
(only applicable for vertical application).

Economizer (enthalpy controlled) provides ventilation


air and free cooling if outside ambient temperature and
humidity are suitable. It can also be used with CO2
sensors to help meet indoor air quality requirements.
Electric resistance heat coils have an open-- wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
single-- point power connection is included.
Two-- row hot water coils have copper tubes mechanically
bonded to aluminum plate fins and non-- ferrous headers.
Overhead suspension package includes necessary
brackets to support units in horizontal ceiling installations.
Carriers line
of thermostats provide both
programmable and non-- programmable capability with the
new Debonairr line of commercial programmable
thermostats. The TEMP System controls offer
communication capability with staged heating and
cooling, and the Commercial Electronic thermostats
provide 7-- day programmable capability for economical
applications.
Return-- air grille provides a protective barrier over the
return-- air opening and gives a finished appearance to
units installed in the occupied space. Accessory is
available unpainted or painted.
One-- row steam coil has copper tubes and aluminum fins.
The Inner Distributing Tube (IDT) design provides
uniform temperatures across the coil face. The steam coil
has a broad operating pressure range; up to 20 psi (138
kPag) at 260_F (126_C). The IDT steam coils are
especially suited to applications where sub-- freezing air
enters the unit.
Subbase provides a stable, raised platform and room for
condensate drain trap connection for vertical
floor-- mounted units. Accessory is available unpainted or
painted.
UV-- C germicidal lamps inhibit the growth of mold and
fungus, which may grow on evaporator coil and
condensate pan surfaces. The use of UV-- C germicidal
lamps reduces the foul odors that may result from this
growth of mold and fungus. It also provides a
self-- cleaning function for the evaporator coil and drain
pan.

38AUQ

DIMENSIONS

C10109

Fig. 2 -- 38AUQ07--12

PERFORMANCE DATA
38AUQ07 -- 40RUQ07

COOLING COMBINATION RATINGS

38AUQ07 / 40RUQ07

58
62
1800
Cfm

EA
(wB)

67

38AUQ

72
76
58
62
2100
Cfm

EA
(wB)

67
72
76
58
62

2400
Cfm

EA
(wB)

67
72
76
58
62

2700
Cfm

EA
(wB)

67
72
76
58
62

3000
Cfm

EA
(wB)

67
72
76

THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC

75
63.5
55.7
66.4
50.6
72.8
41.6
79.7
32.4
----66.7
58.4
68.4
54.1
74.8
43.9
81.8
33.4
----69.3
60.7
70.1
57.2
76.4
46.1
83.5
34.3
----71.6
62.7
71.7
59.7
77.6
48.1
84.8
35.1
----73.6
64.4
73.6
61.2
78.6
50.0
85.9
35.9
-----

85
EA (DB)
80
63.5
63.5
66.4
59.5
72.8
50.5
79.7
41.4
85.5
34.2
66.7
66.7
68.4
64.2
74.8
54.2
81.8
43.8
87.7
35.5
69.3
69.3
70.1
68.3
76.4
57.6
83.5
45.9
89.4
36.7
71.6
71.6
71.7
71.7
77.6
60.9
84.8
48.0
90.7
37.8
73.6
73.6
73.6
73.6
78.6
64.0
85.9
49.9
91.8
38.8

85
71.3
71.3
68.3
68.3
72.8
59.4
79.7
50.5
85.5
44
74.9
74.9
74.3
74.3
74.8
64.4
81.8
54.1
87.7
46.4
78.0
78.0
79.5
79.5
76.4
69.1
83.5
57.6
89.4
48.8
80.6
80.6
83.7
83.7
77.6
73.6
84.8
60.8
90.7
51.1
82.8
82.8
86
86
78.6
77.9
85.9
64
91.8
53.2

75
61.2
53.7
63.5
49.2
69.6
40.2
76.2
31.0
----64.2
56.3
65.4
52.5
71.5
42.5
78.2
32.0
----66.7
58.4
66.9
55.7
72.9
44.6
79.6
32.9
----68.9
60.3
68.9
57.3
74.0
46.6
80.8
33.7
----70.7
61.9
70.7
58.8
74.9
48.5
81.8
34.4
-----

95
EA (DB)
80
61.2
61.2
63.5
58.0
69.6
49.1
76.2
40.1
81.7
32.8
64.2
64.2
65.4
62.6
71.5
52.7
78.2
42.3
83.7
34.1
66.7
66.7
66.9
66.8
72.9
56.1
79.6
44.5
85.2
35.2
68.9
68.9
68.9
68.9
74.0
59.4
80.8
46.5
86.4
36.3
70.7
70.7
70.7
70.7
74.9
62.4
81.8
48.4
87.4
37.3

AMBIENT TEMPERATURE
105
115
EA (DB)
EA (DB)
85
75
80
85
75
80
68.8 58.8 58.8 66.1 56.3 56.3
68.8 51.6 58.8 66.1 49.3 56.3
66.8 60.5 60.5 65.2 57.3 57.3
66.8 47.6 56.4 65.2 46.0 54.8
69.6 66.3 66.3 66.3 62.7 62.7
58
38.7 47.6 56.6 37.2 46.1
76.2 72.5 72.5 72.5 68.6 68.6
49.1 29.6 38.6 47.6 28.1 37.1
81.7
--77.7 77.7
--73.5
42.5
--31.4
41
--29.9
72.2 61.6 61.6 69.3 58.9 58.9
72.2 54.0 61.6 69.3 51.5 58.9
72.6 62.3 62.3 70.7 59.0 59.0
72.6 50.8 60.8 70.7 49.1 59.0
71.5 67.9 67.9 67.9 64.2 64.2
63
41.0 51.2 61.4 39.4 49.6
78.2 74.3 74.3 74.3 70.2 70.2
52.7 30.5 40.9 51.2 29.0 39.3
83.7
--79.5 79.5
--75.1
45
--32.6 43.4
--31.1
75.1 64.0 64.0 72.0 61.0 61.0
75.1 56.0 64.0 72.0 53.4 61.0
78.0 64.0 64.0 74.7 61.0 61.0
78.0 53.3 64.0 74.7 50.8 61.0
72.9 69.2 69.2 69.2 65.3 65.3
67.6 43.1 54.6 66.1 41.5 52.9
79.6 75.6 75.6 75.6 71.3 71.3
56.1 31.4 43.0 54.5 29.8 41.4
85.2
--80.8 80.8
--76.2
47.3
--33.7 45.7
--32.2
77.5 66.0 66.0 74.2 62.9 62.9
77.5 57.7 66.0 74.2 55.0 62.9
80.4 66.0 66.0 77.0 62.8 62.8
80.4 54.9 66.0 77.0 52.3 62.8
74.0 70.2 70.2 70.5 66.2 66.2
72.1 45.0 57.8 70.5 43.4 56.1
80.8 76.6 76.6 76.6 72.3 72.3
59.3 32.2 44.9 57.7 30.6 43.3
86.4
--81.9 81.9
--77.2
49.5
--34.8 47.9
--33.2
79.6 67.7 67.7 76.2 64.4 64.4
79.6 59.2 67.7 76.2 56.3 64.4
82.6 67.7 67.7 79.1 64.4 64.4
82.6 56.3 67.7 79.1 53.6 64.4
76.3 71.0 71.0 74.6 66.9 66.9
76.3 46.9 60.8 74.6 45.2 59.0
81.8 77.5 77.5 77.5 73.0 73.0
62.4 32.9 46.8 60.8 31.3 45.2
87.4
--82.8 82.8
----51.7
--35.7 50.0
-----

LEGEND:
THC --- Total Cooling Capacity, Gross (1000 Btu/h)
SHC --- Sensible Cooling Capacity, Gross (1000 Btu/h)

10

85
63.3
63.3
63.5
63.5
62.7
55
68.6
46.1
73.5
39.4
66.2
66.2
68.8
68.8
64.2
59.9
70.2
49.6
75.1
41.8
68.7
68.7
71.3
71.3
65.3
64.4
71.3
52.9
76.2
44.1
70.8
70.8
73.4
73.4
68.7
68.7
72.3
56
77.2
46.2
72.5
72.5
75.3
75.3
72.8
72.8
73.0
59.1
-----

75
53.5
46.9
54.0
44.2
59.0
35.6
64.5
26.5
----55.9
49.0
55.9
46.6
60.3
37.8
65.9
27.4
----57.9
50.6
57.9
48.2
61.2
39.8
66.9
28.2
----59.6
52.1
59.6
49.5
62.0
41.7
67.7
28.9
----61.0
53.3
61.0
50.7
62.7
43.4
68.3
29.6
-----

125
EA (DB)
80
53.5
53.5
54.0
52.9
59.0
44.5
64.5
35.5
69.1
28.4
55.9
55.9
55.9
55.9
60.3
48.0
65.9
37.7
70.4
29.5
57.9
57.9
57.9
57.9
61.2
51.2
66.9
39.7
71.5
30.5
59.6
59.6
59.6
59.6
62.0
54.3
67.7
41.6
----61.0
61.0
61.0
61.0
62.7
57.1
68.3
43.5
-----

85
60.2
60.2
61.5
61.5
59.0
53.4
64.5
44.5
69.1
37.8
62.9
62.9
65.3
65.3
60.3
58.2
65.9
47.9
70.4
40.1
65.2
65.2
67.6
67.6
62.7
62.7
66.9
51.2
71.5
42.4
67.1
67.1
69.6
69.6
66.9
66.9
67.7
54.3
----68.7
68.7
71.3
71.3
70.8
70.8
68.3
57.3
-----

PERFORMANCE DATA (cont.)

38AUQ08 / 40RUQ08

58
62
2250
Cfm

EA
(wB)

67
72
76
58
62

2625
Cfm

EA
(wB)

67
72
76
58
62

3000
Cfm

EA
(wB)

67
72
76
58
62

3375
Cfm

EA
(wB)

67
72
76
58
62

3750
Cfm

EA
(wB)

67
72
76

THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC

COOLING COMBINATION RATINGS


AMBIENT TEMPERATURE
85
95
105
115
EA (dB)
EA (dB)
EA (dB)
EA (dB)
75
80
85
75
80
85
75
80
85
75
80
78.7 78.7 87.1 76.0 76.0 84.1 73.1 73.1 80.9 70.0 70.0
70.4 78.7 87.1
68
76.0 84.1 65.4 73.1 80.9 62.6 70.0
83.6 83.6 83.6 80.1 80.1 80.1 76.3 76.3 77.5 72.3 72.3
63.1 72.0 80.9 61.5 70.4 79.3 59.7 68.6 77.5 57.9 66.7
91.4 91.4 91.4 87.6 87.6 87.6 83.5 83.5 83.5 79.1 79.1
51.8 60.8 69.7 50.3 59.2 68.2 48.6 57.5 66.5 46.8 55.8
99.9 99.9 99.9 95.7 95.7 95.7 91.3 91.3 91.3 86.4 86.4
40.2 49.3 58.4 38.7 47.7 56.8 37.0 46.1 55.1 35.3 44.4
--107.1 107.1
--102.6 102.6
--97.8 97.8
--92.6
--39.9 49.7
--38.4 48.1
--36.8 46.4
--35.1
82.8 82.8 91.6 79.9 79.9 88.4 76.8 76.8 84.9 73.4 73.4
74.0 82.8 91.6 71.4 79.9 88.4 68.6 76.8 84.9 65.6 73.4
86.1 86.1 88.2 82.4 82.4 86.3 78.5 78.5 84.3 74.3 74.3
67.8 78.0 88.2 66.1 76.2 86.3 64.2 74.3 84.3 62.1 72.1
94.0 94.0 94.0 90.0 90.0 90.0 85.6 85.6 85.6 81.0 81.0
55.0 65.3 75.6 53.4 63.7 73.9 51.7 62.0 72.2 49.9 60.2
102.6 102.6 102.6 98.2 98.2 98.2 93.5 93.5 93.5 88.4 88.4
41.8 52.1 62.5 40.2 50.6 60.9 38.5 48.9 59.2 36.8 47.1
--109.9 109.9
--105.2 105.2
--100.1 100.1
--94.6
--41.4 52.4
--39.9 50.8
--38.3 49.1
--36.5
86.2 86.2 95.4 83.1 83.1 91.9 79.8 79.8 88.2 76.2 76.2
77.1 86.2 95.4 74.3 83.1 91.9 71.3 79.8 88.2 68.1 76.2
88.1 88.1 94.7 84.4 84.4 92.6 80.4 80.4 90.2 76.3 76.3
72.1 83.4 94.7 70.2 81.4 92.6 68.1 79.2 90.2 65.5 76.3
96.0 96.0 96.0 91.8 91.8 91.8 87.3 87.3 87.3 82.4 82.4
58.1 69.6 81.1 56.4 68.0 79.5 54.7 66.2 77.7 52.9 64.4
104.7 104.7 104.7 100.1 100.1 100.1 95.2 95.2 95.2 89.9 89.9
43.2 54.9 66.5 41.6 53.3 64.9 40.0 51.6 63.2 38.2 49.8
--112.1 112.1
--107.1 107.1
--101.8 101.8
--96.2
--42.9 55.0
--41.3 53.4
--39.7 51.7
--37.9
89.1 89.1 98.5 85.8 85.8 94.9 82.3 82.3 91.0 78.5 78.5
79.7 89.1 98.5 76.7 85.8 94.9 73.6 82.3 91.0 70.2 78.5
90.0 90.0 100.4 86.1 86.1 98.3 82.4 82.4 94.0 78.5 78.5
75.9 88.1 100.4 73.9 86.1 98.3 70.7 82.4 94.0 67.4 78.5
97.6 97.6 97.6 93.2 93.2 93.2 88.6 88.6 88.6 83.6 83.6
61.0 73.7 86.5 59.3 72.1 84.8 57.6 70.3
83
55.7 68.4
106.4 106.4 106.4 101.6 101.6 101.6 96.6 96.6 96.6 91.1 91.1
44.6 57.5 70.3 43.0 55.8 68.7 41.3 54.1 66.9 39.5 52.3
--113.8 113.8
--108.7 108.7
--103.2 103.2
--97.4
--44.3 57.6
--42.7
56
--41.0 54.2
--39.2
91.6 91.6 101.3 88.1 88.1 97.5 84.5 84.5 93.4 80.5 80.5
81.9 91.6 101.3 78.8 88.1 97.5 75.5 84.5 93.4 71.9 80.5
91.7 91.7 104.7 88.2 88.2 100.7 84.5 84.5 96.5 80.5 80.5
78.7 91.7 104.7 75.7 88.2 100.7 72.6 84.5 96.5 69.1 80.5
98.9 98.9 98.9 94.4 94.4 94.4 89.6 89.6 89.6 84.5 84.5
63.8 77.8 91.7 62.1 76.1 90.0 60.3 74.2 88.1 58.3 72.2
107.8 107.8 107.8 102.8 102.8 102.8 97.7 97.7 97.7 92.1 92.1
45.9 60.0 74.0 44.3 58.3 72.4 42.6 56.6 70.6 40.7 54.7
--115.2 115.2
--110
110
--104.3 104.3
--98.4
--45.6 60.1
--44.0 58.4
--42.3 56.7
--40.5

LEGEND:
THC --- Total Cooling Capacity, Gross (1000 Btu/h)
SHC --- Sensible Cooling Capacity, Gross (1000 Btu/h)

11

85
77.4
77.4
75.5
75.5
79.1
64.7
86.4
53.4
92.6
44.6
81.1
81.1
82.1
82.1
81.0
70.4
88.4
57.4
94.6
47.3
84.2
84.2
87.1
87.1
82.4
75.9
89.9
61.3
96.2
49.9
86.8
86.8
89.7
89.7
83.6
81.1
91.1
65.1
97.4
52.4
89.0
89.0
91.9
91.9
86.1
86.1
92.1
68.7
98.4
54.9

75
66.6
59.5
68.0
55.8
74.3
45.0
81.2
33.5
----69.7
62.3
69.9
60.0
76.0
48.0
83.0
34.9
----72.2
64.6
72.3
62.1
77.3
50.9
84.3
36.3
----74.4
66.5
74.4
63.9
78.2
53.7
85.3
37.6
----76.1
68.1
76.2
65.4
79.1
56.2
86.1
38.8
-----

125
EA (dB)
80
66.6
66.6
68.0
64.6
74.3
53.9
81.2
42.5
87.0
33.3
69.7
69.7
69.9
69.9
76.0
58.2
83.0
45.2
88.7
34.7
72.2
72.2
72.3
72.3
77.3
62.4
84.3
47.9
90.1
36.1
74.4
74.4
74.4
74.4
78.2
66.3
85.3
50.4
91.1
37.4
76.1
76.1
76.2
76.2
79.1
70.0
86.1
52.8
92.0
38.6

85
73.7
73.7
73.4
73.4
74.3
62.8
81.2
51.5
87.0
42.7
77.1
77.1
79.8
79.8
76.0
68.5
83.0
55.5
88.7
45.4
79.9
79.9
82.5
82.5
77.3
73.9
84.3
59.4
90.1
48
82.2
82.2
84.9
84.9
79.0
79.0
85.3
63.1
91.1
50.5
84.2
84.2
87.0
87.0
83.8
83.8
86.1
66.8
92.0
52.9

38AUQ

38AUQ08 -- 40RUQ08

PERFORMANCE DATA (cont.)


38AUQ12 -- 40RUQ12
38AUQ12 / 40RUQ12

58
62
3000
Cfm

EA
(wB)

67

38AUQ

72
76
58
62
3500
Cfm

EA
(wB)

67
72
76
58
62

4000
Cfm

EA
(wB)

67
72
76
58
62

4500
Cfm

EA
(wB)

67
72
76
58
62

5000
Cfm

EA
(wB)

67
72
76

THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC

COOLING COMBINATION RATINGS


85
EA (dB)
75
80
85
103
103 116.2
89.9
103 116.2
108.7 108.7 110
81.2 95.6
110
118.8 118.8 118.8
66.9 81.4 95.9
129.4 129.4 129.4
52.1 66.8 81.5
--138.3 138.3
--54.9 70.8
108.2 108.2 122
94.3 108.2 122
111.8 111.8 119.4
86.7
103 119.4
122
122
122
70.6 87.2 103.7
132.6 132.6 132.6
53.7 70.5 87.2
--141.5 141.5
--56.9 74.6
112.3 112.3 126.7
98.0 112.3 126.7
114.4 114.4 127.8
91.7 109.7 127.8
124
124
124
74.1 92.6 111.2
135
135
135
55.2 73.9 92.7
--144
144
--58.8 78.3
115.9 115.9 130.7
101.1 115.9 130.7
116
116 136.3
96.6 116.4 136.3
126.1 126.1 126.1
77.4 97.9 118.4
137
137
137
56.6 77.2 97.9
--145.9 145.9
--60.5 82.0
118.9 118.9 134.1
103.7 118.9 134.1
119
119 139.2
98.7
119 139.2
127.6 127.6 127.6
80.6 102.9 125.3
138.5 138.5 138.5
57.9 80.4 102.9
--147.5 147.5
--62.2 85.5

AMBIENT TEMPERATURE
95
105
115
EA (dB)
EA (dB)
EA (dB)
75
80
85
75
80
85
75
80
85
99.5 99.5 112.2 95.6 95.6
108
91.2 91.2 102.9
86.8 99.5 112.2 83.4 95.6
108
79.6 91.2 102.9
104.1 104.1 107.7 99.1 99.1
105
93.6 93.6 102.2
78.9 93.3 107.7 76.5 90.8
105
73.8 88.0 102.2
113.6 113.6 113.6 108
108
108 101.9 101.9 101.9
64.7 79.2 93.7 62.4 76.8 91.3 59.8 74.2 88.7
123.7 123.7 123.7 117.5 117.5 117.5 110.7 110.7 110.7
49.9 64.6 79.3 47.6 62.2 76.8 45.0 59.6 74.2
--132.1 132.1
--125.3 125.3
--117.9 117.9
--52.7 68.4
--50.3 65.8
--47.7 63.1
104.3 104.3 117.6 100.1 100.1 112.8 95.3 95.3 107.5
91.0 104.3 117.6 87.3 100.1 112.8 83.1 95.3 107.5
107
107 116.8 101.8 101.8 113.9 96.1 96.1 110.3
84.3 100.6 116.8 81.7 97.8 113.9 78.6 94.5 110.3
116
116
116
111
111
111
104
104
104
68.4 84.9 101.4 65.9 82.4
99
63.3 79.8 96.3
126.6 126.6 126.6 120
120
120 112.8 112.8 112.8
51.5 68.2 84.9 49.0 65.7 82.4 46.4 63.1 79.7
--134.9 134.9
--127.7 127.7
--120
120
--54.6 72.2
--52.2 69.6
--49.5 66.9
108.2 108.2 122 103.7 103.7 116.9 98.6 98.6 111.2
94.4 108.2 122
90.4 103.7 116.9 86.0 98.6 111.2
109.4 109.4 124.7 104
104 121.7 98.7 98.7 115.5
89.0 106.9 124.7 86.3
104 121.7 81.9 98.7 115.5
118.6 118.6 118.6 112.4 112.4 112.4 105.6 105.6 105.6
71.8 90.3 108.8 69.3 87.8 106.3 66.6 85.1 103.5
128.7 128.7 128.7 121.8 121.8 121.8 114.4 114.4 114.4
52.9 71.6 90.3 50.4 69.1 87.7 47.8 66.4
85
--137.1 137.1
--129.6 129.6
--121.6 121.6
--56.4 75.9
--53.9 73.3
--51.3 70.5
111.5 111.5 125.7 106.7 106.7 120.3 101.3 101.3 114.2
97.3 111.5 125.7 93.0 106.7 120.3 88.4 101.3 114.2
111.7 111.7 130.7 106.7 106.7 124.9 101.4 101.4 118.6
92.7 111.7 130.7 88.6 106.7 124.9 84.1 101.4 118.6
120.2 120.2 120.2 113.8 113.8 113.8 106.8 106.8 110
75.0 95.5
116
72.5 92.9 113.3 69.7 90.1
110
130.4 130.4 130.4 123.3 123.3 123.3 115.7 115.7 115.7
54.2 74.8 95.5 51.7 72.3 92.9 49.0 69.5 90.1
--138.8 138.8
--131.1 131.1
--122.8 122.8
--58.1 79.5
--55.6 76.9
--52.9 74.1
114.3 114.3 128.9 109.2 109.2 123.1 103.6 103.6 117
99.7 114.3 128.9 95.3 109.2 123.1 90.4 103.6 117
114.4 114.4 133.8 109.3 109.3 127.9 103.6 103.6 121
94.9 114.4 133.8 90.7 109.3 127.9 86.0 103.6 121
121.6 121.6 122.8 115
115
120 107.8 107.8 116.8
78.1 100.5 122.8 75.5 97.7
120
72.6 94.7 116.8
131.8 131.8 131.8 124.5 124.5 124.5 116.7 116.7 116.7
55.5 78.0 100.5 52.9 75.4 97.8 50.2 72.6
95
--140.1 140.1
--132.3 132.3
--123.8 123.8
--59.8 83.0
--57.2 80.3
--54.5 77.5

LEGEND:
THC --- Total Cooling Capacity, Gross (1000 Btu/h)
SHC --- Sensible Cooling Capacity, Gross (1000 Btu/h)

12

125
EA (dB)
75
80
85
86.4 86.4 97.4
75.4 86.4 97.4
87.7 87.7 98.8
70.7 84.8 98.8
95.2 95.2 95.2
57.0 71.4 85.9
103.3 103.3 103.3
42.3 56.8 71.4
--110
110
--45.0 60.2
90.1 90.1 101.6
78.6 90.1 101.6
90.2 90.2 105.6
74.8 90.2 105.6
97.0 97.0 97.0
60.5 76.9 93.4
105
105
105
43.7 60.3 76.9
--111.7 111.7
--46.8 64.0
93.0 93.0 104.9
81.1 93.0 104.9
93.1 93.1
109
77.2 93.1
109
98.3 98.3 100.5
63.7 82.1 100.5
106.5 106.5 106.5
44.9 63.5 82.1
--113.1 113.1
--48.5 67.6
95.4 95.4 107.6
83.2 95.4 107.6
95.5 95.5
112
79.2 95.5
112
99.4 99.4 107.2
66.7 86.9 107.2
107.5 107.5 107.5
46.2 66.6 87.1
--114.2 114.2
--50.1 71.1
97.4 97.4 109.9
85
97.4 109.9
97.5 97.5 114.1
80.9 97.5 114.1
100.3 100.3 113.3
69.4 91.4 113.3
108.4 108.4 108.4
47.3 69.7 92.0
-------------

PERFORMANCE DATA (cont.)


38AUQ07 -- 40RUQ07

HEATING COMBINATION RATINGS

Return Air
CFM (Standard Air)
(F db)
1800

55

2400

3000

1800

65

2400

3000

1800

70

2400

3000

1800

80

2400

3000

TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW

---10
21.4
19.7
2.33
22.0
27.6
2.27
22.4
20.6
2.23
19.1
17.5
2.57
19.6
18.1
2.51
20.0
18.4
2.47
17.8
16.4
2.69
18.4
16.9
2.64
18.7
17.2
2.60
15.3
14.1
2.93
15.8
14.5
2.89
16.1
14.8
2.86

0
27.7
25.5
2.60
28.5
27.6
2.51
29.0
26.7
2.45
25.4
23.3
2.86
26.1
24.0
2.78
26.6
24.5
2.72
24.1
22.2
2.99
24.9
22.9
2.91
25.4
23.3
2.86
21.5
19.8
3.27
22.3
20.5
3.19
22.7
20.9
3.14

Temperature Air Entering Outdoor Coil (F db at 70% rh)


10
17
30
40
47
34.5
39.7
50.1
58.6
64.4
31.6
36.2
43.9
55.9
64.4
2.89
3.12
3.60
4.01
4.29
35.5
40.9
51.6
60.0
65.6
27.5
27.4
26.3
28.7
30.0
2.77
2.96
3.37
3.70
3.93
36.2
41.6
52.5
60.6
65.9
33.1
37.9
46.0
57.9
65.9
2.68
2.86
3.23
3.50
3.71
32.2
37.3
47.6
56.4
62.4
29.5
34.0
41.7
53.9
62.4
3.18
3.43
3.95
4.42
4.73
33.2
38.5
49.2
58.0
64.0
30.4
35.1
43.1
55.4
64.0
3.06
3.28
3.73
4.11
4.36
33.8
39.2
50.2
59.0
64.7
31.0
35.8
44.0
56.3
64.7
2.98
3.18
3.58
3.91
4.13
31.0
36.1
46.4
55.2
61.3
28.4
32.9
40.6
52.7
61.3
3.33
3.59
4.13
4.62
4.95
32.0
37.3
48.0
57.0
63.0
29.3
34.0
42.0
54.4
63.0
3.21
3.44
3.91
4.32
4.58
32.6
38.0
49.0
57.9
63.9
29.8
34.7
42.9
55.3
63.9
3.14
3.34
3.77
4.12
4.35
28.4
33.5
43.8
52.5
58.9
26.0
30.6
38.4
50.1
58.9
3.64
3.92
4.50
5.02
5.41
29.4
34.7
45.3
54.4
60.8
26.9
31.6
39.7
52.0
60.8
3.52
3.77
4.28
4.73
5.03
30.0
35.4
46.3
55.6
61.9
27.5
32.3
40.6
53.1
61.9
3.45
3.68
4.14
4.54
4.80

LEGEND:
TH --- Total Heating Capacity, Gross (1000 Btu/h)
THI --- Integrated Heating Capacity, Gross (1000 Btu/h)
kW --- Total Compressor Power Motor Input

13

50
67.0
67.0
4.43
68.0
30.0
4.04
68.3
68.3
3.80
65.1
65.1
4.87
66.5
66.5
4.48
67.1
67.1
4.24
64.0
64.0
5.09
65.6
65.6
4.70
66.4
66.4
4.46
61.5
61.5
5.56
63.5
63.5
5.16
64.6
64.6
4.92

60
75.6
75.6
4.91
76.3
30.0
4.41
76.2
76.2
4.11
73.8
73.8
5.39
75.0
75.0
4.90
75.4
75.4
4.59
72.8
72.8
5.63
74.2
74.2
5.14
74.7
74.7
4.83
70.6
70.6
6.13
72.4
72.4
5.65
73.2
73.2
5.34

38AUQ

38AUQ07 / 40RUQ07

PERFORMANCE DATA (cont.)


38AUQ08 -- 40RUQ08

HEATING COMBINATION RATINGS

38AUQ08 / 40RUQ08
Return Air
CFM (Standard Air)
(F db)
2250

55

3000

38AUQ

3750

2250

65

3000

3750

2250

70

3000

3750

2250

80

3000

3750

TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW

---10
31.6
29.1
3.83
32.2
29.7
3.70
32.6
30.0
3.62
29.5
27.1
4.24
30.2
27.7
4.12
30.6
28.1
4.04
28.3
26.0
4.45
28.9
26.6
4.33
29.4
27.0
4.26
25.6
23.6
4.89
26.3
24.2
4.78
26.7
24.5
4.71

0
39.6
36.4
4.14
40.5
37.2
3.96
40.9
37.6
3.86
37.4
34.4
4.56
38.3
35.2
4.40
38.8
35.7
4.29
36.2
33.3
4.79
37.1
34.1
4.62
37.6
34.6
4.52
33.6
30.9
5.26
34.5
31.7
5.10
35.0
32.2
5.00

Temperature Air Entering Outdoor Coil (F db at 70% rh)


10
17
30
40
47
47.8
53.8
66.9
78.2
86.1
43.8
49.0
58.6
74.7
86.1
4.45
4.67
5.18
5.65
5.96
48.8
55.0
69.4
80.1
88.0
44.7
50.2
60.8
76.5
88.0
4.22
4.42
4.87
5.23
5.44
49.4
55.8
70.3
81.2
88.8
45.3
50.9
61.6
77.5
88.8
4.09
4.26
4.67
4.97
5.15
45.6
51.4
63.7
75.8
83.8
41.8
46.9
55.8
72.4
83.8
4.90
5.14
5.65
6.19
6.55
46.7
52.7
65.8
77.8
85.8
42.8
48.1
57.7
74.3
85.8
4.68
4.88
5.32
5.75
6.00
47.3
53.5
67.3
78.9
86.7
43.4
48.8
59.0
75.4
86.7
4.54
4.72
5.12
5.50
5.68
44.4
50.3
62.3
73.7
82.5
40.6
45.9
54.6
70.3
82.5
5.14
5.39
5.91
6.43
6.87
45.5
51.4
64.2
76.6
84.6
41.7
46.9
56.2
73.1
84.6
4.92
5.12
5.57
6.03
6.29
46.2
52.2
65.5
77.8
85.6
42.3
47.6
57.4
74.3
85.6
4.78
4.97
5.37
5.77
5.97
41.8
47.7
59.5
70.2
79.4
38.3
43.5
52.1
67.0
79.4
5.64
5.92
6.47
6.99
7.49
42.9
49.0
61.2
72.7
82.1
39.3
44.7
53.6
69.5
82.1
5.42
5.65
6.12
6.57
6.93
43.6
49.8
62.3
74.7
83.3
39.9
45.4
54.6
71.3
83.3
5.29
5.50
5.90
6.33
6.59

LEGEND:
TH --- Total Heating Capacity, Gross (1000 Btu/h)
THI --- Integrated Heating Capacity, Gross (1000 Btu/h)
kW --- Total Compressor Power Motor Input

14

50
89.6
89.6
6.08
91.4
91.4
5.54
92.1
92.1
5.23
87.4
87.4
6.67
89.2
89.2
6.10
90.0
90.0
5.77
86.2
86.2
6.99
88.1
88.1
6.40
89.0
89.0
6.06
83.6
83.6
7.67
85.7
85.7
7.05
86.7
86.7
6.69

60
101
101
6.53
102
102
5.90
103
103
5.54
98.6
98.6
7.15
100
100
6.48
101
101
6.10
97.4
97.4
7.48
98.9
98.9
6.79
99.6
99.6
6.40
95.1
95.1
8.19
96.6
96.6
7.46
97.3
97.3
7.04

PERFORMANCE DATA (cont.)


38AUQ12 -- 40RUQ12

HEATING COMBINATION RATINGS

Return Air
CFM (Standard Air)
(F db)
3000

55

4000

5000

3000

65

4000

5000

3000

70

4000

5000

3000

80

4000

5000

TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW
TH
THI
kW

---10
35.9
33.1
4.46
36.8
33.8
4.34
37.2
34.2
4.26
32.5
29.9
4.94
33.3
30.7
4.83
33.8
31.1
4.76
30.7
28.3
5.20
31.5
29.0
5.09
32.0
29.4
5.02
26.9
24.8
5.75
27.6
25.4
5.65
28.0
25.8
5.59

0
46.0
42.3
4.83
46.8
43.0
4.66
47.4
43.5
4.55
43.0
39.5
5.36
44.0
40.4
5.19
44.6
41.0
5.09
41.4
38.0
5.64
42.3
38.9
5.47
42.9
39.4
5.37
37.8
34.8
6.23
38.7
35.6
6.08
39.3
36.1
5.98

Temperature Air Entering Outdoor Coil (F db at 70% rh)


10
17
30
40
47
56.1
64.2
81.1
96.6
106
51.4
58.5
71.0
92.3
106
5.18
5.45
6.03
6.59
6.83
57.2
65.4
83.0
97.9
107
52.4
59.7
72.7
93.5
107
4.96
5.19
5.67
6.08
6.28
57.9
66.2
84.8
98.3
107
53.0
60.3
74.3
93.9
107
4.82
5.03
5.50
5.79
5.96
53.3
61.2
77.9
92.9
104
48.8
55.9
68.2
88.7
104
5.75
6.05
6.66
7.24
7.58
54.4
62.5
79.5
95.7
105
49.8
57.0
69.7
91.3
105
5.52
5.78
6.29
6.79
6.99
55.0
63.3
80.7
96.3
105
50.4
57.7
70.7
92.0
105
5.39
5.61
6.07
6.47
6.65
51.9
59.7
76.3
90.9
102
47.5
54.4
66.8
86.8
102
6.06
6.36
7.00
7.57
7.98
52.9
61.0
78.0
93.5
104
48.5
55.6
68.3
89.3
104
5.83
6.09
6.62
7.14
7.38
53.5
61.8
79.0
95.2
104
49.1
56.3
69.2
90.9
104
5.69
5.93
6.39
6.85
7.03
49.0
56.6
73.0
86.9
98.3
44.9
51.6
63.9
83.0
98.3
6.72
7.04
7.73
8.32
8.85
50.1
57.8
74.7
89.4
101
45.9
52.7
65.4
85.3
101
6.49
6.76
7.35
7.84
8.21
50.6
58.5
75.7
90.8
102
46.3
53.4
66.3
86.8
102
6.35
6.60
7.11
7.57
7.84

LEGEND:
TH --- Total Heating Capacity, Gross (1000 Btu/h)
THI --- Integrated Heating Capacity, Gross (1000 Btu/h)
kW --- Total Compressor Power Motor Input

15

50
110
110
6.95
110
110
6.37
110
110
6.04
108
108
7.71
108
108
7.09
109
109
6.74
107
107
8.11
107
107
7.48
108
108
7.11
103
103
8.98
105
105
8.32
106
106
7.93

60
123
123
7.37
123
123
6.70
123
123
6.31
120
120
8.15
121
121
7.44
121
121
7.03
119
119
8.57
120
120
7.84
120
120
7.41
117
117
9.46
118
118
8.69
118
118
8.24

38AUQ

38AUQ12 / 40RUQ12

ELECTRICAL DATA
WITHOUT POWERED CONVENIENCE OUTLET
UNIT
SIZE

07

08

38AUQ

12

NOMINAL POWER
SUPPLY

VOLTAGE RANGE

COMPRESSOR

OFM

V ---Ph---Hz

Min

Max

RLA

LRA

Qty

208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60

187
414
518
187
414
518
187
414
518

253
506
633
253
506
633
253
506
633

19.0
9.7
7.4
25.0
12.2
9.0
30.1
16.7
12.2

123
62
50
164
100
78
225
114
80

2
2
2
2
2
2
2
2
2

POWER SUPPLY
FLA
(ea)
1.5
0.9
0.6
1.5
0.9
0.6
1.5
0.8
0.6

DISCONNECT
SIZE

MCA

MOCP

FLA

LRA

26.8/26.8
13.9
10.5
34.3/34.3
17.1
12.5
40.6/40.6
22.5
16.5

45/45
20
15
50/50
25
20
60/60
30
25

25/25
13
10
32/32
16
12
38/38
21
15

129/129
66
54
170/170
104
82
231/231
118
84

WITH POWERED CONVENIENCE OUTLET


UNIT
SIZE

07

08

12

NOMINAL POWER
SUPPLY

VOLTAGE RANGE

COMPRESSOR

OFM

V ---Ph---Hz

Min

Max

RLA

LRA

Qty

208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60
208/230--- 3--- 60
460--- 3--- 60
575--- 3--- 60

187
414
518
187
414
518
187
414
518

253
506
633
253
506
633
253
506
633

19.0
9.7
7.4
25.0
12.2
9.0
30.1
16.7
12.2

123
62
50
164
100
78
225
114
80

2
2
2
2
2
2
2
2
2

16

POWER SUPPLY
FLA
(ea)
1.5
0.9
0.6
1.5
0.9
0.6
1.5
0.8
0.6

DISCONNECT
SIZE

MCA

MOCP

FLA

LRA

31.6/31.6
16.1
12.2
39.1/39.1
19.3
14.2
45.4/45.4
24.7
18.2

50/50
25
15
60/60
30
20
60/60
30
30

31/31
16
12
38/38
19
14
44/44
24
17

134/134
68
56
175/175
106
84
236/236
120
86

ELECTRICAL DATA (cont.)

HEATER
PART NO.
CAELHEAT

SIZE

FAN MOTOR

V-PH-Hz

208-3-60
001A00
240-3-60

002A00

480-3-60

003A00

575-3-60

208-3-60
40RUQ
07--- 12

004A00

240-3-60

005A00

480-3-60

006A00

575-3-60

208-3-60
007A00
240-3-60

Hp

kW

FLA

1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7

0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76

7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2

Nominal
Capacity
(kW)
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15

LEGEND
FLA
Hp
MCA
MOCP

240

ACTUAL HEATER VOLTAGE


200

208

230

0.694 0.751 0.918

240

400

440

460

480

550

575

600

0.915

1.089

480

575

0.694 0.84 0.918

FLA
10.4
10.4
10.4
10.4
10.4
12.0
12.0
12.0
12.0
12.0
6.00
6.00
6.00
5.00
5.00
5.00
20.8
20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
24.1
12.0
12.0
12.0
10.0
10.0
10.0
31.3
31.3
31.3
31.3
31.3
36.1
36.1
36.1
36.1
36.1

MCA*

MOCP*

22.5
26.8
19.5
22.4
25.8
24.5
28.8
21.5
24.4
27.8
10.8
11.8
13.5
8.0
9.2
11.0
35.6
39.8
32.6
35.4
38.8
39.6
43.8
36.6
39.4
42.8
18.3
19.3
21.0
14.3
15.4
17.3
48.6
52.9
45.6
48.5
51.9
54.6
58.9
51.6
54.5
57.9

25
35
20
25
30
25
35
25
25
30
15
15
15
15
15
15
40
40
35
40
40
40
50
40
40
50
20
20
25
15
20
20
50
60
50
50
60
60
60
60
60
60

2. The following equation converts kW of heat energy to Btuh:


kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding
current.
4. Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00
is 55 lb (25 kg) each.

Full Load Amps


Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

* Values shown are for single-point connection of electric heat


accessory and air handler.
Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575
v. To determine heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor
shown in the table below for the unit voltage.
HEATER
RATING
VOLTAGE

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage
Stage
Total
1
2
3.8

3.8
3.8

3.8
3.8

3.8
3.8

3.8
3.8

3.8
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
7.5

7.5
7.5

7.5
7.5

7.5
7.5

7.5
7.5

7.5
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
11.3

11.3
11.3

11.3
11.3

11.3
11.3

11.3
11.3

11.3
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0

17

38AUQ

ELECTRIC HEATER DATA

ELECTRICAL DATA (cont.)


ELECTRIC HEATER DATA (cont.)
HEATER
PART NO.
CAELHEAT

SIZE

FAN MOTOR

V-PH-Hz

008A00

480-3-60

009A00

575-3-60

38AUQ

208-3-60
40RUQ
07--- 12

010A00

240-3-60

011A00

480-3-60

012A00

575-3-60

208-3-60
013A00
40RUQ
08,12

240-3-60

014A00

480-3-60

015A00

575-3-60

Hp

kW

FLA

2.4
2.9
3.7
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
2.4
2.4
2.9
3.7
2.4
2.4
2.9
3.7
2.4
2.9
3.7
2.0
3.0

1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
1.79
1.79
2.16
2.76
1.79
1.79
2.16
2.76
1.79
2.16
2.76
1.49
2.24

2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
11.0
5.2
7.5
10.2
11.0
5.2
7.5
10.2
2.6
3.4
4.8
2.3
3.8

Nominal
Capacity
(kW)
15
15
15
15
15
15
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
35
35
35
35
35
35
35
35
35
35
35
35
35

LEGEND
FLA
Hp
MCA
MOCP

240

ACTUAL HEATER VOLTAGE


200

208

230

0.694 0.751 0.918

240

400

440

460

480

550

575

600

0.915

1.089

480

575

0.694 0.84 0.918

FLA
18.0
18.0
18.0
15.1
15.1
15.1
52.1
52.1
52.1
52.1
52.1
60.1
60.1
60.1
60.1
60.1
30.1
30.1
30.1
25.1
25.1
25.1
73.0
73.0
73.0
73.0
84.2
84.2
84.2
84.2
42.1
42.1
42.1
35.1
35.1

MCA*

MOCP*

25.8
26.8
28.6
20.6
21.7
23.6
74.7
78.9
71.7
74.5
77.9
84.7
88.9
81.7
84.6
87.9
40.8
41.8
43.6
33.1
34.3
36.1
105.0
97.7
100.6
104.0
119.0
111.7
114.6
118.0
55.9
56.9
58.6
46.8
48.7

30
30
30
25
25
25
80
80
80
80
80
90
90
90
90
90
50
50
50
35
35
40
110
100
110
110
125
125
125
125
60
60
60
50
50

2. The following equation converts kW of heat energy to Btuh:


kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding
current.
4. Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00
is 55 lb (25 kg) each.

Full Load Amps


Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

* Values shown are for single-point connection of electric heat


accessory and air handler.
Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575
v. To determine heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor
shown in the table below for the unit voltage.
HEATER
RATING
VOLTAGE

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage
Stage
Total
1
2
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0

18

TYPICAL PIPING AND WIRING

HORIZONTAL INSTALLATION

WEATHERPROOF
FUSED DISCONNECT*
PER NEC
OUTDOOR
UNIT

MOISTURE
INDICATOR
SIGHT GLASS*

38AUQ

FIELDSUPPLIED
POWER

ELECTRIC
HEATER
ACCESSORY

POWER WIRES
LLSV*

INSULATED
VAPOR
LINE
CONTROL
WIRES

FILTER LIQUID
DRIER* LINE

INDOOR
UNIT

CONDENSATE DRAIN
POWER WIRES

INDOOR
THERMOSTAT
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN

C09054

19

TYPICAL WIRING SCHEMATIC


SCHEMATIC
208/230V 6,7.5,10T SNGL HP
115V
FIELD
SUPPLY

FIOP
NON-POWERED
CONVENIENCE
OUTLET

GR

BLK
BLK

BLK
FIOP CONVENIENCE OUTLET 115V
NOTES:
1. CONNECT PER
LOCAL CODE
2. FOR 240V SUPPLY
CONNECT BLU TO GRA
AND RED TO YEL

RED
YEL
BLU
240V
TRAN4
YEL
BLU

RED

GRA
GRA

POWER
SUPPLY

GFI-CO

BLK

DISCONNECT

FIELD

L1

T1

BLK

L2

T2

BLU

L3

T3

YEL

BLK
BLK
YEL
YEL

MOTORMASTER
FIOP/ACCESSORY

BLK

RED

BLK

WHT

COIL TEMP
SENSOR

SPEED CONTROL

11

21

BLK

13

23

YEL

BLU

TB1

CADM
T1

BLK

T2
T3

BLU

CCH1

T1

BLU

T2

YEL

T3

COMP

GRN-YEL
H3

H1

X4

H2

SECONDARY
120V

EQUIP GR

GRN-YEL
BLK

X1

X3

X2

BLK

H4

RESET

WHT

BLK

WHT
SWITCH

FUSE

BLK

SCB
FIOP/ACCESSORY

BLK

BLK

SEE
NOTE 5

BLK

TRAN1
230

DEFROST WILL TERMINATE NORMALLY IF


DFT IS CLOSED.

24V

24V

IFM
BLU

OF
OF

K5

K1

K1

Y1

Y2

W1

W1

Y2

Y1

W2

W2

LLSV

P2

Y1

P3
3

BRN

CONN
BOARD

CONN
BOARD

L
P

CADM

BRN

ACCESSORY

BLU

BLK BLU

BLK

HPS

LPS

FPT

HPS

LPS

FPT

TB2

CIRCUIT

BLK

SVR

BLU

1
2

RVS

BRN

LOC

BRN

FIOP/
ACCESSORY
ORN

SCB

BRN

BLU

OFR

BRN

CONN
BOARD

BRN

HR

4
3
2

BRN

YEL

YEL

DFT

RED

Y2

HPS
10

BRN

BRN

BLK

BRN

RED

BRN

OFR

BLU

10

ORN

YEL
YEL

ORN

RED

BRN

BRN

HR

VIO

PNK

CONN
BOARD

Y2

W2

GRN/YEL

RED

YEL

W1

24V

24V

RED
RED

BRN

208

CB

RED

A1
10
A2

A1
10
A2

YEL

RED

L1
24VAC

ORN

CONN
BOARD

5
4

P1

TRAN2
230

VIO

YEL

BLK

E-HEAT

BRN

GRN/YEL

DEFROST BOARD

208

CB
RED

THERMOSTAT

OFM 2

YEL
BRN

YEL

DEFROST WILL TERMINATE IN 30 SEC. IF


DFT IS OPEN.

OUTDOOR
CONNECTION
BOARD(TB)

BRN

CAP 1

RED

INDOOR
CONNECTION
BOARD (TB)

OFM 1

YEL

YEL

BLK

PERMANENT SHORT WILL BE IGNORED.

ON

ON

BLK

SHORT FOR > 5 SEC. AND RELEASE FOR


FORCED DEFROST.

OR

ON

ON

OR

OFF

ON

ON

OR

ON

ON

OFF

OFF

OFF

38AUQ

BLK

RED

FIELD SELECTABLE OPTIONS FOR TIME


PERIOD BETWEEN DEFROST CYCLES (MINUTES).
SHORT TEST WIRES (USE
SPEED
SHORT METAL OBJECT) FIELD
UP
SPEED-UP CYCLE

120 MINUTES

90 MINUTES

BLK

DEFROST BOARD
DIP SWITCH SETTINGS
(DEFAULT)
60 MINUTES

BLK

BUSSMAN T-15
125V 15A

30 MINUTES

OFR

BLK

TEST

SVR
RED

WHT

DFT1

DFT2

WHT

DFT1

DFT2

RED

WHT

ACCESSORY
HR
RED

PNK

BRN
PNK

WHT

WHT
BRN
BRN
BRN
BRN
BRN

5
6

10

T1
DATA
T2 PORT

24V

T3

Y2
W1
W2

CAP

13

23

230

BRN

SCB

BRN

OFR

BRN

24V

TRAN2

24V

208

DEFROST BOARD
(DFB)

24V

DFT1

TB

TRAN1

TRAN1

DFT2

C
F

OF

8
9

230

OFR

CADM

L1

24V

208

11

EHEAT

3
4

R
Y1

21

24V

BRN

P
1

CONNECTION BOARD(TB)

CADM

P
2

TRAN2

P
3

CONTROL BOX
COMPONENT ARRANGEMENT

BRN

X
A1
A2

SVR

TB2

HR

SCB

FIELD

FIELD CONTROL WIRING

WIRING

LEGEND
FIELD SPLICE
X

MARKED WIRE

TERMINAL(MARKED)
TERMINAL(UNMARKED)

TERMINAL BLOCK
SPLICE
FACTORY WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
ACCESSORY OR OPTIONAL WIRING
TO INDICATE COMMON
POTENTIAL ONLY, NOT
TO REPRESENT WIRING

C CONTACTOR, COMPRESSOR
CAP CAPACITOR
CH CRANKCASE HEATER
CADM COMFORT ALERT - DIAGNOSTICS MODULE
COMP COMPRESSOR MOTOR
DFB DEFROST BOARD
DFT DEFROST THERMOSTAT
EQUIP EQUIPMENT
FPT FREEZE PROTECTION THERMOSTAT
FU FUSE
GR GROUND
HPS HIGH PRESSURE SWITCH
HR HEATER RELAY
LLSV LIQUID LINE SOLENOID VALVE
LOC LOSS OF CHARGE SWITCH
OFM OUTDOOR FAN MOTOR
OFR OUTDOOR FAN RELAY
RVS REVERSING VALVE SOLENOID
SCB SPEED CONTROL BYPASS
SVR SOLENOID VALVE RELAY
TB TERMINAL BLOCK
TRAN TRANSFORMER

DISCONNECT PER NEC

NOTES:
1. IF ANY OF THE ORIGINAL WIRE FURNISHED
MUST BE REPLACED, IT MUST BE REPLACED
WITH TYPE 90 C WIRE OR ITS EQUIVALENT.
2. USE COPPER CONDUCTORS ONLY.
3. COMPRESSORS AND FAN MOTORS ARE
THERMALLY PROTECTED. THREE PHASE
MOTORS ARE PROTECTED AGAINST PRIMARY
SINGLE PHASING CONDITIONS.
4. TRANSFORMER IS WIRED FOR 230V UNIT. IF
UNIT IS TO BE RUN WITH 208V POWER SUPPLY,
DISCONNECT BLK WIRE FROM 230V TAP AND
CONNECT TO 208V TAP.
5. ON UNITS WITH SPEED CONTROL, REMOVE
BLACK WIRE BETWEEN CONTACTOR TERMINAL 11
AND OFR TERMINAL 4 AT CONTACTOR TERMINAL
11 AND CONNECT TO SCB TERMINAL 2.

38AU500363

C
C10132

Fig. 3 -- 38AUQ07--12 UNITS 230--3--60


20

APPLICATION DATA
REFRIGERANT LINE SIZING Consider the length
of the piping required between the outdoor and indoor
units. The maximum allowable line length is 100 ft (30.5
m). See Maximum Vertical Separation Table below.
Refrigerant vapor piping should be insulated

placed in the main liquid line (see Figs. 4 & 5) between


the outdoor unit and the indoor coil. Locate the solenoid
valve at the end of the liquid line, near the outdoor unit
connections, with flow direction arrow pointed at the
outdoor unit. Refer to Refrigerant Specialties Part
Numbers Table below. (A liquid line solenoid valve is
required when the liquid line length exceeds 75 ft [23 m].)
This valve prevents refrigerant migration (which causes
oil dilution) to the compressor during the off cycle, at low
outdoor ambient temperatures. Wire the solenoid
according to the unit label

Maximum Vertical Separation*


DISTANCE FT (M)
Unit 38AUQ
Above Unit 40RuQ
07
07
50 (15.2)
08
08
60 (18.3)
12
12
60 (18.3)
* Vertical distance between indoor and outdoor units.
UNIT
38AUQ

UNIT
40RUQ

AIRFLOW

INSTALL FILTER DRIER(S) AND MOISTURE


INDICATOR(S) Every unit MUST have a
bi-- directional filter drier in the liquid line. Locate the
filter drier at the indoor unit, close to the evaporator coil
thermal expansion valve (TXV) inlets.

Liquid
Line OD

Part
Number Ref

38AUQ*07

3/

8-in

8 cu. in.

KH43LG091

38AUQ*08

1/

2-in

16 cu. in.

KH43LG085

38AUQ*12

1/

2-in

16 cu. in.

KH43LG085

10
DIAMS

8 DIAMS
MIN

FLO
W
LIQUID
LINE
SOLENOID
VALVE

C10133

INDOOR
COIL CKT 2

Desiccant
Volume

FILTER DRIER
A LOCATION

TXV

Fig. 4 -- Location of Sight Glass(es) and Filter Driers


(typical 38AUQ/40RUQ size 07 & 08 system)

Puron--duty Filter Drier(s)


Qty

15 DIAMS
MIN

SIGHT GLASS
A LOCATION

LEGEND
TXV Thermostatic Expansion Valve

38AUQ units include one Puron-- duty filter drier, shipped


in cartons attached to the unit base pan. Remove the filter
drier and prepare to install in the liquid line at the
evaporator coil. Do not remove connection fitting plugs
until ready to connect and braze the filter drier into the
liquid line position.

Model-Size

EQUALIZER LINE

TXV
SENSING
BULB

INDOOR
COIL CKT

38AUQ

IMPORTANT: A refrigerant receiver is not provided with


the unit. Do not install a receiver.

AIRFLOW

INDOOR
COIL CKT 1

Installation of liquid line moisture indicating sight glass in


each circuit is recommended. Locate the sight glass(es)
between the outlet of the filter drier and the TXV inlet.

AIRFLOW

EQUALIZER LINE

TXV
SENSING
BULB

15 DIAMS
MIN

10
DIAMS

TXV
CKT 2

SIGHT GLASS
LOCATION

FILTER DRIER
LOCATION

8 DIAMS
MIN
FLO
W

TXV
SENSING
BULB

15 DIAMS
MIN

LIQUID
LINE
SOLENOID
VALVE

10
DIAMS

TXV
CKT 1
8 DIAMS
MIN

Refer to Refrigerant Specialties Part Numbers Table for


recommendations on refrigeration specialties.

LEGEND
TXV Thermostatic Expansion Valve

Select the filter drier for maximum unit capacity and


minimum pressure drop. Complete the refrigerant piping
from the indoor unit to the outdoor unit before opening
the liquid and suction lines at the outdoor unit.

A10134

Fig. 5 -- Location of Sight Glass(es) and Filter Driers


(typical 38AUQ/40RUQ size 12 system)

INSTALL LIQUID LINE SOLENOID VALVE It is


recommended that a bi-- directional solenoid valve be

Refrigerant Specialties Part Numbers


LIQUID LINE
SOLENOID VALVE
(LLSV)

LLSV
COIL

SIGHT
GLASS

ALC-066208

AMG-24/50-60

HMI-1TT3

ALC-066209

AMG-24/50-60

HMI-1TT4

ALC-066212

AMG-24/50-60

HMI-1TT5

LIQUID LINE
SIZE (in.)
3/
1/
5/

21

FILTER
DRIER
Provided with unit.

GUIDE SPECIFICATIONS -- 38AUQ07--12


Split System Heat Pump Outdoor Unit with PURON Refrigerant
HVAC Guide Specifications Section 15678
Size Range:

66,000 to 106,000 Btuh Heating


6 to 10 Nominal Tons Cooling

Carrier Model Numbers: 38AUQ07 thru 12


Part 1 General
1.01

SYSTEM DESCRIPTION

38AUQ

A. Outdoor-- mounted, electrically controlled, air-- cooled split system heat pump suitable for on-- the-- ground or
rooftop installation. Unit shall consist of a scroll air-- conditioning compressor assembly, an air-- cooled coil,
propeller-- type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract
drawings. Unit shall function as the outdoor component of an air to air electric heat pump system.
B. Unit must be designed with a Puron (R-- 410A) refrigerant circuit to match Packaged Heat Pump Air Handling Unit(s), 40RUQ for matched systems approved by the manufacturer.
1.02

QUALITY ASSURANCE
A.
B.
C.
D.

Unit shall be rated in accordance with ARI Standard 340/360.


Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
Unit cabinet shall be capable of withstanding 500-- hour salt spray exposure per ASTM B117 (scribed specimen).
E. Air-- cooled outdoor coils shall be leak tested at 150 psig and pressure tested at 650 psig and qualified to UL
burst test at 1980 psig.
F. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.

1.03

DELIVERY, STORAGE AND HANDLING


Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers recommendations.

1.04

WARRANTY (FOR INCLUSION BY SPECIFYING ENGINEER)

Part 2 Products
2.01

EQUIPMENT
A. General:
Factory-- assembled, single piece, air-- cooled split system heat pump. Contained within the unit enclosure shall
be all factory wiring, piping, controls, compressor, holding charge Puron (R-- 410A), and special features
required prior to field start-- up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a pre-- painted baked
enamel finish.
2. A heavy-- gauge roll-- formed perimeter base rail with forklift slots and lifting holes shall be provided to
facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion resistant.
D. Compressor:
1. Compressor shall be of the hermetic scroll type.
2. Compressor shall be mounted on rubber grommets.
3. Compressor shall include overload protection.
4. Compressors shall be equipped with a crankcase heater.
5. Compressor shall be equipped with internal high discharge temperature protection.
22

23

38AUQ

E. Coil:
1. Coil shall be air-- cooled and circuited for sub cooling during cooling mode of operation.
2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then cleaned, dehydrated, and sealed.
F. Refrigeration Components and Operation:
1. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full
charge of compressor oil, and a holding charge of refrigerant.
2. Unit shall be capable of starting and running up to 125 F (52 C) and down to 35 F (2 C) ambient outdoor
temperature.
3. Unit shall operate at +/-- 10% from rated voltage
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-- reset safety until reset from thermostat.
c. Each unit shall utilize the Comfort Alert Diagnostic Board that provides:
(1.) System Pressure Trip fault code indication
(2.) Short Cycling fault code indication
(3.) Locked Rotor fault code indication
(4.) Open Circuit fault code indication
(5.) Reverse Phase 3 fault code indication
(6.) Welded Contactor fault code indication
(7.) Low Voltage fault code indication
(8.) Anti-- short cycle protection
(9.) Phase reversal protection
2. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall
include:
a. High discharge pressure protection switch.
b. Loss-- of-- charge protection switch.
H. Electrical Requirements:
1. Unit electrical power shall be single-- point connection.
2. Unit control circuit shall contain a 75VA - 24-- v transformer for unit control.
I. Special Features:
1. Unit-- Mounted, Non-- Fused Disconnect Switch:
Switch shall be factory-- installed and internally mounted. NEC and UL-- approved non-- fused switch shall
provide unit power shutoff. Switch shall be accessible from outside the unit and shall provide power off
lockout capability.
2. Convenience Outlet:
a. Powered convenience outlet.
(1.) Outlet shall be powered from main line power to the rooftop unit.
(2.) Outlet shall be powered from line side or load side of disconnect by installing contractor, as required by code. If outlet is powered from load side of disconnect, unit electrical ratings shall be
UL certified and rated for additional outlet amperage.
(3.) Outlet shall be factory-- installed and internally mounted with easily accessible 115-- v female
receptacle.
(4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.
(5.) Voltage required to operate convenience outlet shall be provided by a factory-- installed step-down transformer.
(6.) Outlet shall be accessible from outside the unit.
(7.) Outlet shall include a field-- installed Wet in Use cover.
b. Non-- Powered convenience outlet.
(1.) Outlet shall be powered from a separate 115/120v power source.
(2.) A transformer shall not be included.
(3.) Outlet shall be factory-- installed and internally mounted with easily accessible 115-- v female
receptacle.
(4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.

3.

38AUQ

4.

5.

6.
7.

(5.) Outlet shall be accessible from outside the unit.


(6.) Outlet shall include a field-- installed Wet in Use cover.
Low-- Ambient Temperature Control:
A low-- ambient temperature control shall be available as a factory-- installed option or as a field-- installed
accessory. This low-- ambient control shall regulate speed of the condenser-- fan motors in response to the
saturated condensing temperature of the unit. The control shall maintain correct condensing pressure at
outdoor temperatures down to 20 F (-- 29 C).
Optional Outdoor Coil Materials:
a. Pre-- Coated Aluminum-- Fin Coils:
Coils shall have a durable epoxy-- phenolic coating to provide protection in mildly corrosive coastal
environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin and copper tube. Epoxy-- phenolic barrier shall minimize galvanic action between dissimilar metals.
b. E-- Coated Aluminum-- Fin Coils:
Coils shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without
material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall
be high gloss black with gloss requirements of 60_ of 65 to 90% per ASTM D523-- 89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-- 92A and cross hatch adhesion of 4B-- 5B per ASTM D3359-- 93. Impact
resistance shall be up to 160 in./lb (ASTM D2794-- 93). Humidity and water immersion resistance shall
be up to a minimum of 1000 and 250 hours respectively (ASTM D2247-- 92 and ASTM D870-- 92).
Corrosion durability shall be confirmed through testing to no less than 1000 hours salt spray per ASTM
B117-- 90. Coil construction shall be aluminum fins mechanically bonded to copper tubes.
Thermostat Controls:
a. Programmable multi-- stage thermostat with 7-- day clock, holiday scheduling, large backlit display, remote sensor capability, and Title 24 compliance.
b. Commercial electronic thermostat with 7-- day time clock, auto-- changeover, multistage capability, and
large LCD temperature display.
c. Carrier PremierLink Controller Field Installed:
This control will function with CCN and ComfortVIEW software. It shall also be compatible with
ComfortLink controllers. It shall be ASHRAE 62-- 99 compliant. It shall accept a CO2 sensor in the
conditioned space and be Demand Control Ventilation (DCV) ready. The communication rate must be
38.4K or faster.
Louvered hail Guard Package:
Louvered hail guard package shall protect coils against damage from hail and other flying debris.
Outdoor Coil Grille:
Grille shall add decorative appearance to unit and protect outdoor coil from large objects and vandalism.

Edition Date: 02/10

Catalog No: 38AUQ---01PD

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Replaces: NEW

Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231

Printed in U.S.A.

24

You might also like