Saes T 903

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Engineering Standard

SAES-T-903
Outside Plant Electrical
Protection and Grounding
Communications Standards Committee Members

31 March, 2004

Al-Dabal, J.K., Chairman


Al-Ghamdi, K.S., Vice Chairman
Al-Hashel, M.H.
AliKhan, M.S.
Almadi, S.M.
Al-Nufaii, A.S.
Al-Shammary, D.M.
Dabliz, Z.E.
Daraiseh, A.A.
Elsayed, M.
Gotsis, S.D.
Ismail, A.I.
Jabr, A.A.
Kahtani, W.H.
Karr, S.K.
Mckew, M.P.
Qatari, S.A.
Tageldin, T.G.

Saudi Aramco DeskTop Standards


Table of Contents

1
2
3
4
5
6

Scope............................................................. 2
Conflicts and Deviations................................. 2
References..................................................... 2
Design............................................................ 3
Installation.................................................... 13
Testing and Inspection................................. 13

Figure 1 - Bonding and Grounding


at Cable Entrance................................ 14

Previous Issue: 30 September, 2003

Next Planned Update: 1 April, 2009


Page 1 of 14

Primary contact: Tag Tageldin on 872-9019

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

Scope
This standard prescribes mandatory requirements governing systems planning,
designing and engineering of electrical protection for telecommunications outside plant.
This includes upgrading existing facility when a new cable is being placed.

Conflicts and Deviations


Any deviations, providing less than the mandatory requirements of this standard require
written waiver approval as per Saudi Aramco Engineering Procedure SAEP-302.

References
All referenced Specifications, Standards and Codes, Forms, Drawings and similar
material shall be of the latest issue (including all revisions, addenda and supplements)
unless stated otherwise. Listed below are applicable standards.
3.1

Saudi Aramco References


Saudi Aramco Engineering Procedure
SAEP-302

Instructions for Obtaining a Waiver of a


Mandatory Saudi Aramco Engineering
Requirement

Saudi Aramco Engineering Standards


SAES-T-243

Telecommunications: Protection Equipment in


Communication Buildings

SAES-T-435

Telecommunications Station Protection

SAES-T-604

Communications Plant - Clearances/Separations Aerial

SAES-T-624

Telecommunications Outside Plant - Fiber Optics

SAES-T-629

Telecommunications Buried Cable and Wire

SAES-T-634

Telecommunications - Cable Testing and


Acceptance

SAES-T-887

Telecommunications: Electrical CoordinationProtection at Power Plants and Radio Stations

SAES-T-903

Telecommunications: Outside Plant Electrical


Protection and Grounding

SAES-T-916

Communications Building Cable

SAES-T-928

Telecommunications - OSP Buried Plant


Page 2 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

3.2

SAES-T-903
Outside Plant Electrical
Protection and Grounding

Industry Codes and Standards


GTE

General Telephone and Electronics

NEC

National Electrical Code

NESC

National Electrical Safety Code

UL

Underwriter's Laboratories

Design
The GTE 903 series on "Protection - Outside Plant" and GTE 605 series on "Protection
and Bonding" are hereby recognized as Saudi Aramco Engineering Standard SAES-T903. Mandatory items and modifications are listed herein.
4.1

Protection General Considerations

4.1.1

Definitions
Approved Ground: A ground is suitable for connection to the building
entrance facility protector, the entrance cable shield, or the PBX equipment
single point ground. The NEC stresses the importance of bonding together
all available electrodes into a system.
The first choice for grounding of protectors is to the nearest available location
on the system, whichever results in the shortest run (maximum allowable
distance shall be 6.1 m of grounding conductor. Refer to SAES-T-916.
Exposed Facilities: Any outside plant facilities that are subject to the
effects of lightning, power crosses, power induction, or differences in
ground potential. All Saudi Aramco cable and facilities are considered to be
exposed.
Fuse Cable: A length of protective cable of # 24 AWG or # 26 AWG
copper conductors that is inserted in the plant and intended to fuse open on
foreign power currents before damage occurs to the cable, customer terminal
wiring, or apparatus that it protects. It does not protect against lightning
currents and associated voltages.
Protector (Cable): A protector that limits the voltage between the
conductors and shields of the cable. Standard cable protectors are equipped
with 6-mil (blue) carbon blocks.
Protector (User Terminal or Switching Center): A device that limits
voltage between conductors and ground. It is equipped with fail safe solid
state arresters.

Page 3 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

Single Point Terminal: It is the only acceptable point ground for


connection from the equipment to the external protection grounding system.
It shall consist of copper bus bar to which the main ground conductor,
permanently attached to the power ground or building steel (which has been
bonded to power ground), has been securely attached.
Sneak Current: A foreign current flowing to the ground through terminal
wiring and equipment that is driven by a voltage that is too low to cause a
protector to arc over or ground.
Common Grounding: Common grounding is the use of the same ground
electrode by all services. Underwriter's Laboratories listed (UL-listed) or
equivalent ground or bond connectors shall be used.
Common Bonding: Common bonding is the interconnecting of separate
ground electrodes and is necessary at locations where common grounding
cannot or has not been used. UL-listed or equivalent ground or bond
connectors shall be used.
4.1.2

General

4.1.2.1

Protection for telecommunication facilities at crossings and parallels of


power lines of over 20 kV phase-to-ground, or serving or passing within a
GPR zone of influence of power substations, shall be coordinated as
specified by SAES-T-887 and with the Saudi Aramco Communications
Standards Committee Chairman (Information Technology Planning
Division) representative.

4.1.2.2

All metallic loops in Saudi Aramco are considered exposed to lightning,


except any on premises extensions that are:
a)

Not exposed to 300 volts or more and

b)

Not extended to a separate building located more than 43 m (140 ft.)


away.

Commentary Note:
The 43 m (140 ft.) is the zone of protection and it is the physical wall-to-wall
distance between buildings.

4.1.2.3

All exposed telecommunication cable conductors that enter buildings shall


be protected with UL-listed protectors.

4.1.2.4

Never share a vault, pull box, or manhole with a power system of any
voltage.

Page 4 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

4.1.2.5

Telecommunication facilities shall not be grounded to a non-grounded


power system.

4.1.2.6

Never share a trench with a power cable having a phase-to-ground voltage of


more than 20 kV.

4.1.3

Electrical Code Requirements

4.1.3.1

Common grounding shall be provided as required by the National Electrical


Code (NEC) Article 800, Section D - Grounding Method.

4.1.3.2

All telecommunications engineering design and construction shall comply


with the National Electrical Code (NEC) Article 800, as well as applicable
sections in the NESC.

4.1.4

Grounding Electrodes

4.1.4.1

Power ground shall be the preferred ground electrode. If the power service
(first choice ground source) is not located within 6 m (20 ft.) of the
telephone station protector, relocate the telecommunication protector, or use
one of the following electrodes:
a)

Ground ring of # 2 AWG (35 mm) minimum copper conductor,


encircling the building at a minimum depth of 0.76 m (2.5 ft.)

b)

Grounded metal frame of the building

c)

A 25-ohm or less ground electrode bonded to power service ground


Note:

All the above grounds present on the premises shall be bonded


together, regardless of the distance between electrodes or ground
systems.

4.1.4.2

Ground rods are only allowed to be used when no other ground medium is
available.

4.1.4.3

If more than one ground rod is required to achieve 25 ohms, they must be
greater than 1.8 m (6 ft.) apart, and shall be bonded together with a
minimum of # 6 AWG (16 mm) bare tinned-copper ground wire. Refer to
NEC Article 800-40.

4.1.4.4

Chemical treatments of the earth around ground electrodes shall not be used.
Marl or concrete could be used to assist in maintaining moisture content
around ground electrodes.

4.1.4.5

To provide an electrode that will not readily dry-out, main electrodes shall
consist of a minimum of 2.44 m (8 ft.) ground rod(s). If more than one is
used, they shall be bonded together with a minimum of # 6 AWG (16 mm)
Page 5 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

bare tinned-copper ground wire. A ground resistance of 25 ohms or less


shall be established.
4.1.4.6

Telecommunication ground rods shall be bonded to foreign ground rods


when they are located within 2 m (6 ft.) of each other.

4.1.4.7

Locate distribution cable terminals or pedestals so that the drop or service


wire can be run to the same side of the premises as the power service or to
an adjacent side. The protector shall be located so that the total length of the
ground and bond wire from the protector to the power service or building
ground does not exceed 6.1 m (20 ft.). In all circumstances, the
telecommunications ground shall be bonded to the power ground.

4.1.4.8

All ground conductors placed inside or on buildings shall be insulated


according to NEC, Article 800.40 (a)(1).

4.2

Cables Entering Communication Buildings

4.2.1

Termination of Outside plant cables on distribution frames shall be fail safe


solid state protectors. Refer to SAES-T-243.

4.2.2

Cables entering communication buildings, either directly or in vaults, shall


have fuse cables installed according to Table 1.
Table 1
Gauge of
Entrance Cable
19 or 22
19 or 22
24
24
26

4.2.3

Gauge of
Fuse Cable
24
26
None
26
None

Gauge of
Tip Cable
22
24 or 22
22
24
24 or 22

Bonding and Grounding at Cable Entrances


All cables entering communication buildings and containing a metallic
shield, armor and/or strength members shall be grounded and bonded:
a)

To each other

b)

Not more than 15 m (50 ft.) from the point of entrance

4.3

Cables Entering User Buildings

4.3.1

Station Terminal Equipment

Page 6 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

4.3.1.1

Station terminal equipment is represented by such items as telephones,


answering sets, PBX's, data and alarm circuits, modems, computers,
computer terminals, or other electronic type installations. All of these items
shall be served from a protected building entrance terminal.

4.3.1.2

Telephone service, power service, and CATV shall be provided with a


common ground system to protect against differences in ground potential
between the systems.

4.3.2

Bonding and Grounding at Cable Entrance

4.3.2.1

All cables entering buildings and containing a metallic shield and/or strength
member shall be grounded and bonded:
a)

To each other

b)

Not more than 15 m (50 ft.) from the point of entrance (refer to Figure 1)

4.3.2.2

A metallic splice case must be used at the first splice point inside the
building for cables of 400 pairs or less.

4.3.3

Metallic Conduits
All metallic conduits (entrance, riser, tie and station), shall be electrically
bonded together and grounded to the main or floor ground bus bar.

4.3.4

Entrance Terminal Grounding

4.3.4.1

The ground lug of protected building terminals shall be connected to an


approved and permanent ground (master ground bar) with a minimum of 6
AWG (16 mm) insulated solid copper ground wire with no cut, splices or
sharp bends. The minimum acceptable bending radius shall be 15 cm (6 in.)
for sizes up to # 6 AWG (16 mm). The maximum length of ground wire
shall not exceed 6.1 m (20 ft.).

4.3.4.2

The design engineer shall illustrate the exact grounding arrangements on the
construction drawings, from the ground lug of the protector to the power or
building ground.

4.3.4.3

The actual grounding path shall be recorded on the "as-built" drawings.

4.4

Outside Plant Cable Bonding and Grounding

4.4.1

General

4.4.1.1

The design engineer shall review the existing distribution plant where
construction activity is to take place (in pedestals and manholes where
Page 7 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

splicing, transfers, removal or placement of cable occurs) to ensure that the


cable electrical protection devices and the bonding and grounding of cable
sheaths meet current Saudi Aramco Standards. This review shall include the
physical inspection and testing of made ground electrodes. All noncomplying situations must be corrected. This shall include electrical
protection devices, grounding, and bonding systems inside existing
buildings. The requirements of this paragraph apply to all projects and work
orders.
Commentary Note:
The intent of this standard is to insure that the electrical protection system is
maintained and safety hazards are highlighted and corrected. When an
existing electrical protection device (bond and grounding connection and
conductor, station protector) is found to be missing, defective or damaged, a
report identifying (manhole, pedestal, terminal no. and location) each item is
to be issued promptly. The report is to be forwarded to the responsible
maintenance and operations agency so that immediate action can be taken to
make repairs of the electrical protection system.
Exception:
The exception to this is when a project job order specifically calls for the
repair of the electrical protection system in the scope of work and
construction drawing.

4.4.1.2

The metallic shields (including any armors) of all cables through splices (in
pedestals, direct buried or in manholes/handholes) splice cases, terminals,
apparatus cabinets, etc., shall be continuous throughout the length of the
cable, except where it is purposely broken by an insulating joint (within zone
of influence of electric power stations). All metallic shields and armors, if
present, of all cables shall be made continuous with #6 AWG (16 mm) or
larger bonding wire. All bonds are to be connected to a common ground to
ensure that all cables are at the same potential.

4.4.1.3

At junctions of cable and distribution and service wire, bond the support
wire or armor of the service wire to the cable strand or shield.

4.4.1.4

When aerial telecommunication cables and CATV cables are jointly


exposed, bond their separate strands:

4.4.1.5

a)

At the beginning and the end of the exposure

b)

Four times per 1.6 km (1 mile)

Cabinets and repeater housings shall be grounded using a grounding


electrode with a resistance of 25 ohms or less according to the National
Electrical Safety Code (NESC).

Page 8 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

4.4.1.6

In sections that are not jointly used, the cable must be grounded using a
grounding electrode with a resistance of 25 ohms or less at 610 m (2000 ft.)
intervals.

4.4.2

Aerial Strand

4.4.2.1

Aerial strands shall be continuous and bonded together.

4.4.2.2

When power lines with voltages in excess of 300 volts (but not over 20 kV
phase to phase) cross over telecommunication cables on a common pole and
a power ground is present, bond the cable strand to the power ground. If
separate poles are used, bond the cable strand to the power ground or a 25ohm maximum man made ground electrode at the first pole on each side of
the crossing.

4.4.2.3

If a power ground is not present, bond the cable strand to a ground electrode
with a resistance of 25 ohms or less on each side of the crossing.

4.4.2.4

Cable shields and armors, if present, shall be bonded to the vertical power
ground conductor within the communication space on joint-use poles.

4.4.2.5

Where two cables from different communication buildings terminate on the


same pole at the exchange boundary from different directions, and are not
electrically connected any where in their routes, their support strands shall
be continuous or bonded together.

4.4.2.6

Separate telecommunication cables on the same supporting structures shall


be bonded together at least every 610 m (2000 ft.). Where two cables are
supported on the same cable suspension bolt, the bolt does not function as
the necessary bond.

4.4.3

Aerial Polyethylene Sheath Cable

4.4.3.1

Where splice cases and splice case-type terminals are used, the metal of the
sheath shall be bonded to the strand through the sheath clamps that are
fastened to the splice case.

4.4.3.2

Telecommunication cables shall not be placed on power lines carrying


voltages of 20 kV phase-to-phase or higher. Joint use shall not be permitted
with delta-wired power distribution systems. Refer to SAES-T-604, "Plant Clearances/ Separations - Aerial", for establishing the minimum acceptable
clearances when constructing telecommunications plant on joint pole lines.

4.4.3.3

Bond down guys to support strands and vertical ground conductors. Any
existing strain insulators shall be omitted or bonded across with a minimum

Page 9 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

of # 6 AWG (16 mm) copper ground wire unless they have been
specifically placed for isolation in places such as at power substations.
4.4.3.4

Aerial cable shields and strands shall be continuous, bonded together and
grounded to the power ground at intervals not exceeding 305 m (1000 ft.).

4.4.4

Fuse Cable Protection


Fuse cable shall be placed at the junction of aerial cable with buried or
underground cable according to the matrix as shown in Table 2.
Table 2 Fuse Cable Requirement at Aerial-Buried
or Underground Cable Junctions

Aerial
Cable Gauge
26
24
24
22
22
19
19
Note: (1)

Buried or Underground
Cable Gauge
Any
26
24, 22,19
26, 24
22, 19
26, 24
22, 19

Fusing Required
Yes
No
x
x
(1)
x
x
x
x
x

Fuse Cable Gauge

24
24

If 24 or heavier gauge cable extends to the central office, not fusing at this junction will require fusing
at the central office unless 22 gauge tip cable is used.

4.4.5

Underground Polyethylene Sheath Cable

4.4.5.1

The manhole/handhole/pullbox ground electrode shall be:


a)

Minimum of one 16 mm (5/8 in.) diameter by 2.44 m (8 ft.) long


ground rod. If required to obtain required resistance, additional rods
must be placed.

b)

Tested and measured for resistance to meet requirements as stated in


4.1.4.

4.4.5.2

Bonding and grounding of polyethylene sheath cable at intermediate


manholes or pull-throughs where no opening is made in the polyethylene
jacket is not required. However, ensure that the distance to a bonded and
grounded point is not more than 305 m (1000 ft.).

4.4.5.3

When cables run through metallic conduits, bond the cable metallic shield
(and armor if present) to each end of the conduit. Refer to SAES-T-629 for
additional details.

4.4.5.4

The steel armor in wire /or tape-armored cables shall be bonded to its
underlying metallic shield(s) on each side of all splices (in pedestals, direct
Page 10 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

buried or in manholes/handholes, etc.), junctions and terminations. If wire


or tape-armored cable is spliced to a standard underground polyethyleneinsulated cable (PIC) or to a submarine cable, both ends of the tapes or wires
shall be bonded to the cable shields on both sides of the splice. Armor wires
shall be bonded to the cable shield(s) at the end of the submarine cable. All
bonds shall then be grounded to a common approved ground (refer to
paragraph 4.1.4.1) with a minimum of #6 AWG (16 mm) copper ground
wire. This shall apply to all types of cable including standard feeder and
distribution outside plant copper conductor cables, fiber optic cables (with or
without interstitial copper pairs) and pulse code modulation (PCM) cables.
4.4.6

Buried Polyethylene Sheath Cable

4.4.6.1

Buried cable shields and armors shall be grounded at points not more than
610 m (2000 ft.) from a ground of 25 ohms or less.

4.4.6.2

When a telephone cable is buried beside or beneath aerial grounded power


lines, bond the telephone cable shield to the power ground at the beginning
of the exposure, at the end of the exposure, and at points not more than 305
m (1000 ft.) from a ground point.

4.4.6.3

When a telephone cable is buried besides or beneath aerial ungrounded


(delta) power lines, establish 25-ohm or less man made grounds. Bond the
telephone cable shield to the man made grounds at the beginning of the
exposure, at the end of the exposure and at points not more than 305 m
(1000 ft.) from a ground point.

4.4.6.4

Where a terminal housing/pedestal is located within 3 m (10 ft.) of an


electrical supply terminal or transformer housing (grounded system), a # 6
AWG (16 mm) copper wire shall be used to bond the telecommunication
terminal housing to the electrical supply terminal or secondary section of the
transformer.

4.4.6.5

When telecommunication cables are buried parallel to buried power facilities


(in a joint or separate trench) with fixed separation (one meter or less) and,
where there is no requirement for a telecommunications pedestal/terminal, a
telecommunication cable may be buried past distribution power
transformers/terminals etc., without placing a telecommunications
pedestal/terminal solely for the purpose of bonding the cable shield to the
power ground. However, ensure that no point on the cable is more than 150
m (500 ft.) from a bond to the power ground. Refer to GTE 887-000-050,
Paragraph 8.14.

4.4.6.6

In areas where a terminal housing/pedestal is subject to disturbance/damage


from vehicles, etc., it shall be protected with a pedestal guard. These have
Page 11 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

typically been constructed of steel pipe. Where pedestal guards are


constructed of steel pipe or other metallic materials, they shall be bonded to
the pedestal with a # 6 AWG (16 mm) copper wire. The copper ground
wire shall be attached to a metallic post of the pedestal guard (using cadweld
method or an approved mechanical connector) at a point 50-75 mm above
the concrete encasement of the metallic post base.
4.4.7

Joint Burial of Power and Telecommunications Cables


Separations between buried power facilities (power cable, power pedestals,
etc.) and telecommunication cables (when crossing) shall not be less than
300 mm (12 in.) of well-tamped earth. In areas where this is not possible, 75
mm (3 in.) of concrete or 100 mm (4 in.) of masonry is permitted. Where
the power exposure is greater than 15 kV phase to phase, buried
telecommunication cables shall be placed inside PVC or similar
characteristic conduit at the crossing. Refer to SAES-T-928.

4.4.8

Fiber Optic Cable

4.4.8.1

All metallic members of a fiber optic cable, shall be bonded together and
grounded at all splice locations. The ground shall meet these requirements:

4.4.8.2

1.

Be of 25 ohms or less resistance.

2.

Be bonded to the power ground, when available within 3 m (10 ft.).


Where there is no requirement for a pedestal/terminal, a fiber optic cable
may be buried past distribution power transformers/terminals, etc.,
without placing a pedestal/terminal solely for the purpose of bonding the
cable metallic members to the power ground. However, ensure that, no
point on the cable is more than 150 m (500 ft.) from a bond to the power
ground. Refer to GTE-887-000-050, Paragraph 8.14.

When a fiber optic cable containing metallic members is placed on a pole


line (and the inductive effects of nearby power lines are not calculated),
bond the metallic members to the support strand at all splice points and at
intervals not to exceed 2 km (1.25 miles). Where it is not practical to place
bonds every 2 km, or where there are complicated power exposures, the
bonding and grounding design must be reviewed and approved in writing by
the Saudi Aramco Communications Standards Committee Chairman
(Information Technology Planning Division). In any case, the separation
between bonds will not be permitted to exceed 4.8 km (3 miles). Each bond
point shall be grounded to the power ground, where available. In other
areas, a ground electrode of 25 ohms resistance or less shall be provided.
Joint use with delta power systems is not permitted. Refer to SAES-T-624.

Page 12 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

4.4.8.3

SAES-T-903
Outside Plant Electrical
Protection and Grounding

Bond the support strand to the power ground at intervals of 610 m (2000 ft.)
or less.

Installation
Electrical protection of all types of communication facilities including, but not limited to,
copper conductor cables used for feed and distribution, pulse code modulation (PCM)
cables used for carrier and local distribution, and metallic fiber optic cables (with or
without interstitial copper pairs) is mandatory and shall be according to SAES-T-435,
SAES-T-887, SAES-T-903, SAES-T-916, and other applicable standards as referenced in
this standard.

Testing and Inspection


Electrical protection equipment shall be tested with the cable according to SAES-T-634.
Inspection of installations shall be carried out by the Saudi Aramco Inspection
Department during all phases of construction.

31 March, 2004

Revision Summary
Revised the "Next Planned Update". Reaffirmed the contents of the document, and reissued
with no other changes.

Page 13 of 14

Document Responsibility: Communications


Issue Date: 31 March, 2004
Next Planned Update: 1 April, 2009

SAES-T-903
Outside Plant Electrical
Protection and Grounding

Building Cable Conduit


(metallic conduit shall
be bonded to the cabinet)

Cabinet

189B1 Unit

GRD Connector

Entrance Cable
Protector
Unit

66-Type
Connector
Block

Cable Splice
GRD Connector

# 6 AWG Insulated
Outside Plant Cable

Ground Wire
Cabinet Ground

To Grounding Electrode

Figure 1 - Bonding and Grounding at Cable Entrance

Page 14 of 14

You might also like